MG-120
2-port RS232/422/485 Modbus Gateway
                                                                                                                                    Serial Interface
                                                                                                                                    • Two DB9 interfaces support RS232, 2-wire RS485, 4-wire
                                                                                                                                      RS485 and RS422 standards
                                                                                                                                    • Asynchronous serial data rates up to 921600bps
                                                                                                                                    Ethernet Interface
                                                                                                                                    • 1-port 10/100BASE-TX RJ45 with auto MDI/MDI-X function
Standard Modbus TCP/RTU/ASCII Network Integration
PLANET MG-120 2-port RS232/422/485 Modbus Gateway supports the standard
Modbus Protocol, which makes it possible for converting any Modbus Protocols
                                                                                                                                    Management Function
between Modbus TCP, Modbus RTU, and Modbus ASCII for all supported
                                                                                                                                    • Built-in IP-based Web interface and telnet interface for
hardware interfaces. Its serial protocol can be used for industrial automation where
                                                                                                                                      remote management
SCADA or HMI system is in place.
                                                                                                                                    • Software Protocol supports Modbus TCP, Modbus RTU,
Moreover, its network integration can be upgraded from the SNMP network to the
                                                                                                                                      Modbus ASCII, IP, ARP, DHCP and DNS
automated Modbus TCP network, which brings interconnection over Ethernet longer
                                                                                                                                    • Supports RTU Master, RTU Slave, ASCII Master, and
distances, thus making a network infrastructure more flexible.
                                                                                                                                      ASCII Slave four serial operation modes via management
                                                                                                                                      interface
                                                                                                                                    • Master mode supports 32 TCP slave connection requests
                                                                                                                                    • Slave mode supports 32 TCP master connections
                                                                                                                                    • PLANET Modbus Gateway utility for finding client device
                                                                                                                                      on the network
                                                                                                                                    • PLANET Smart Discovery utility automatically finds the
                                                                                                                                      client devices on the network
A Conversion Bridge for Flexible Network Deployment                                                                                 • Firmware upgrade/configuration backup and restore via
The MG-120 can be a conversion bridge between the equipment with the Modbus                                                           HTTP protocol
RTU/ASCII Protocol and the administrator workstations that run the Modbus TCP/IP
Protocol. The RS232/422/485 serial interface of the MG-120 provides the Modbus
                                                                                                                                    Case and Installation
RTU/ASCII operation mode and various baud rate options to meet the demand
                                                                                                                                    • -10 to 60 degrees C operating temperature
of integration between the Modbus TCP/IP Protocol, Modbus RTU Master/Slave
Protocol and Modbus ASCII Master/Slave Protocol.                                                                                    • Reset button for resetting to factory default
                                                                    RJ45
                                                                    LNK/ACT   100
                                        5V   , 2A max.
 Modbus TCP/IP Ethernet                                     Reset
                                                                                                      RS232/RS422/RS485
                Modbus TCP/IP                                                       Serial Cable                Modbus
                                                                                     RS232/422/485
                10/100TX UTP                                                                                   Equipment
  Workstation
  with SCADA                                             MG-120
                                RTU          ASCII                   RTU              ASCII
                                Slave        Slave                  Master            Master
                                32 TCP Masters                           32 TCP Slaves
                                                                                                                100BASE-TX UTP
                                                                                               RS232/422/485
                                                                                                    RS485       RS232/RS422/RS485
                                                                                                                                                                                               1
                                                                                                                                                        MG-120
The advantage of having the MG-120 is to assist users to build an environment between the Modbus TCP Protocol and the Modbus RTU/ASCII Protocol
easily, thus offering an application solution to the control equipment without Ethernet ports, and the control equipment can only control through a PC
workstation or control panel.
In addition, the effective integration solution of Modbus Ethernet devices, Modbus serial equipment or multi Modbus master / slave in a hybrid network brings
the following:
 ■ Master mode supports up to 32 TCP slave connection requests
 ■ Slave mode supports up to 32 TCP master connections
                                Differences between Serial Devices and Modbus Gateway
                         Serial Devices Server
                          VCOM Utility +
                                                                                                1:1
                             Serial         Virtual
                           Application     COM port
                                                                                               Serial Port
                                                           RJ45 UTP                         (RS232/422/485)
                                                                        ICS-110
                                                                                                             Serial Device
                         Modbus Gateway
                                                                                               1 : 32
                          Modbus TCP
                          Application/
                            SCADA                                                              Serial Port
                                                           RJ45 UTP                         (RS232/422/485)
                                                                        MG-110
                                                                                                                                               ID1~32
                                                                                                        Modbus RTU/ASCII
                                                                                                          Serial Devices
Remote Management
The MG-120 makes the connected Modbus RTU/ASCII equipment become IP-based facilities and is able to connect to the Modbus TCP/IP network via
its R232/422/485 serial interface and 10/100BASE-TX RJ45 Ethernet port. It provides a remote web management and telnet Interface for efficient remote
network management. The MG-120 also provides PLANET Modbus Gateway utility tool and supports PLANET Smart Discovery utility to help network
administrator to easily get the current IP subnet address information or change the IP subnet address setting of the MG-120.
                          Remote Management
                                                                                                                                     RJ45
                                                                                                                                     LNK/ACT   100
                                                                                                        5V   , 2A max.
                                                                                                                             Reset
                       MB VCOM Utility
                                                                                            TCP/IP
                                                  Telnet
                                                                                                                         MG-120
                                                                                                         Modbus Gateway Series
                        Web Browser
Modbus Serial Port State Monitoring
The MG-120 shows the details of the total bytes transmitted and received on the RS232/422/485 serial interface, and the detailed total number of frames
transmitted and received on the remote web/telnet management interface. This function allows network administrator to check the status and statistics of the
MG-120 via the single RS232/422/485 serial interface.
                                                                                                                                                                 2
                                                                                                                                   MG-120
Applications
RTU/ASCII Master to Multi Modbus TCP/IP Slaves
The MG-120 can act as a bridge between the RTU/ASCII master equipment and the multi-TCP/IP slave equipment in a Modbus TCP/IP networking
environment to control multi-TCP/IP slave equipment via the RTU/ASCII master equipment..
                RTU/ASCII Master to Multi Modbus TCP/IP Slaves
                                                                                                       MG-120
                                                             RS485                                     Modbus Gateway
                                 HMI
                           RTU/ASCII Master
                                                                                                                 Modbus TCP/IP
                                                                                                                 Slave Devices
                                       DCS                                                       DCS
                                                                                                                 100BASE-TX UTP
                                                                                                RS485            RS485
Multi Modbus TCP/IP Master to RTU/ASCII Slaves
The MG-120 can operate as a bridge between the multi-TCP/IP master equipment and the RTU/ASCII slave equipment in a Modbus TCP/IP networking
environment to control the RTU/ASCII slave equipment via the multi-TCP/IP master equipment.
                 Multi Modbus TCP/IP Master to RTU/ASCII Slaves
                               Host Computer                                                   Modbus TCP
                                                                                              Master Devices
                                       Modbus TCP Master                                                   PLC
                                                              MG-120                                         MG-115A
                                                              Modbus Gateway                                 Modbus Gateway
                               RS485            RS485                                          RS485
        Flow Meters (Drive)                             Flow Meters (Drive)                   Modbus/RTU Modbus/ASCII
                                                                                                   Slave Devices
                                                                                                                         100BASE-TX UTP
                                                                                                              RS485      RS485
                                                                                                                                               3
                                                                                        MG-120
Product Specifications
Product                  MG-120
Serial Interface
Serial Ports             2 x DB9 male
                         RS232
                         RS422
Serial Standards
                         4-wire RS485
                         2-wire RS485
Baud Rate (Data Rate)    50bps to 921Kbps
Data Bits                5, 6, 7, 8
Stop Bit                 1, 1.5, 2
Parity Type              Odd, Even, None, Space, Mark
                         RTS/CTS and DTR/DSR (RS232 only)
Flow Control
                         XON/XOFF
                         RS232: TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
                         RS422: Tx+, Tx-, Rx+, Rx-, GND
Signals
                         4-wire RS485: Tx+, Tx-, Rx+, Rx-, GND
                         2-wire RS485: Data A (+), Data B (-), GND
Pin Assignment
                         RTU Master/RTU Slave/ASCII Master/ASCII Slave
Operation Mode           Master mode: Supports up to 32 TCP slave connection requests
                         Slave mode: Supports up to 32 TCP master connection requests
Ethernet Interface
Ethernet Ports           1 x RJ45
Standard                 10/100BASE-TX
Distance                 100m
ESD Protection           6KV
Hardware
Installation             DIN-rail kit and wall-mount ear
Dimensions (W x D x H)   97 x 70 x 26mm
Weight                   189 g
                         System: Link
LED Indicators           TP Port: Link/Active
                         Serial Port: Active
Power Requirements       External Power Adaptor 5V DC, 2A max.
Power Consumption        5.5 watts (max)
Enclosure                Metal
                         < 5 sec: System reboot
Reset Button
                         > 5 sec: Factory default
Management
                         Web management
                         Telnet Console management
                         Windows-based MB VCOM Utility management
Management Interfaces
                         SNMPv1, v2c / SNMP Trap
                         UNI-NMS monitoring
                         PLANET Smart Discovery Utility
IP Version               IPv4
                         RTU Master
                         RTU Slave
Operation Mode
                         ASCII Master
                         ASCII Slave
                                                                                                 4
                                                                                                            MG-120
                                        Windows-based Only:
                                         Windows XP
                                         Windows Server 2003
                                         Windows 7
Virtual COM Utility Platform Supports
                                         Windows Server 2008
                                         Windows 8 (Must install the latest version of WinPcap)
                                         Windows Server 2012 (Must install the latest version of WinPcap)
                                         Windows 10
Fault Alarm                             Record: System log / SNMP trap
Time                                    NTP
Security                                Accessible IP (white list)
SNMP                                    SNMP v1 and v2c
Standards Conformances
                                        FCC Part 15 Class A,
Regulatory Compliance
                                        CE Certification Class A
                                        IEEE 802.3 10BASE-T
                                        IEEE 802.3u 100BASE-TX
                                        RFC 768 UDP
                                        RFC 793 TFTP
                                        RFC 791 IP
                                        RFC 792 ICMP
Standards
                                        RFC 854 Telnet
                                        RFC 958 NTP
                                        RFC 1908 SNMPv2c
                                        RFC 2068 HTTP
                                        RFC 2131 DHCP Client
                                        EIA/TIA RS232/422/485
Regulatory Approval                     RoHS
Environment
Operating Temperature                   -10 ~ 60 degrees C
Storage Temperature                     -10 ~ 70 degrees C
Humidity                                5 ~ 95% (non-condensing)
                                                                                                                     5
                                                                                                                                                   MG-120
Dimensions
• MG-120
                                          26.20
           RS232/422/485 Modbus Gateway
           MG-120
                                                                                                                         100
                                                                                                                         LNK/ACT
                                                  P1
                                                                                                                                           Reset
                                                                                                                70.30
                                                                  RS232/422/485 Modbus Gateway
                                                                                           x    x
                                                                                         /R x/R PWR
                                                  P2
                                                                                                                               , 2A max.
                                                                                       Tx     T
                                                                                  P1       P2
                                                                                                                               5V
                                                                                  94.00
                                                                                                  46.70
                                                                          �
                                                                           7.0
                                                                              0
                                                                                                                        Unit: mm
Ordering Information
MG-120                                                 2-port RS232/422/485 Modbus Gateway (-10~60 degrees C)
                                                                                                                                                            6
                                                                                                                                                                          MG-120
Related Products
MG-110                                         1-port RS232/422/485 Modbus Gateway (-10~60 degrees C)
MG-115A                                        1-port RS232/422/485 Modbus Gateway with 1-port 100BASE-FX SFP (-10~60 degrees C)
IMG-2100T                                      IP30 Industrial 1-Port RS232/RS422/RS485 Modbus Gateway (1 x 10/100TX, -40~75 degrees C)
IMG-2105AT                                     IP30 Industrial 1-Port RS232/RS422/RS485 Modbus Gateway (1 x 100FX, -40~75 degrees C)
IMG-2200T                                      IP30 Industrial 2-Port RS232/RS422/RS485 Modbus Gateway (2 x 10/100TX, -40~75 degrees C, 2KV isolation)
                                               IP30 Industrial 4-Port RS232/RS422/RS485 Modbus Gateway (2 x 10/100TX, -40~75 degrees C, 2KV isolation,
IMG-2400T
                                               2 x DI + 2 x DO)
  PLANET Technology Corporation
  11F., No.96, Minquan Rd., Xindian Dist., New Taipei City 231,                                                                                                                MG-120
  Taiwan (R.O.C.)
                                                                        PLANET reserves the right to change specifications without prior notice. All brand names and trademarks are property of
  Tel: 886-2-2219-9518              Fax: 886-2-2219-9528                their respective owners. Copyright © 2020 PLANET Technology Corp. All rights reserved.
  Email: sales@planet.com.tw        www.planet.com.tw
                                                                                                                                                                                                  7