24811r8 LMCP UM
24811r8 LMCP UM
                                                                                      INTRODUCTION
The LMCP series panels are available for Dimming (LMCPx-10V) or
                                                                                                                                 INTERIOR                                ENCLOSURES
Switching (LMCPx) control of lighting and plug loads. The panels can be
networked together to enable automation throughout an entire facility.
With LMCP panels, you can maintain code-compliant control of building exterior
lighting as well as larger interior areas. Recommended applications include office
building lobbies, corridors, loading docks, school gymnasiums, commons areas
and hallways. LMCP panels are also ideal for retrofit scenarios where mounting
control equipment near existing branch circuit breakers is beneficial, and digital
switches, sensor devices, and load parameter configuration are required to meet
complex operational sequences.
The HDR panel relays respond to inputs from Digital Lighting Management
(DLM) switches, occupancy sensors, daylight sensors, input modules and
0-10V outputs on dimming panel models.
Multiple panels may be networked together for global control operation
without the use of a Network Controller or BAS. The LMCP panel also
provides a native-BACnet integration solution via BACnet MS/TP, or with
optional NB-ROUTER, BACnet/IP. Relay, group, and control device status,
including occupancy sensor status, are available as BACnet objects. When a                                                          Figure 1: Panel interior and enclosures
Wattstopper Network Controller is used, it will automatically recognize LMCP
panels and map them to the browser-based user interface so that they can be
configured with minimal additional setup.
CONTENTS
                                                                                                        2
                                          FEATURES AND BASIC TERMINOLOGY
A group allows you to control one or more relays in one or more panels.
Groups provide an easy way to assign parameters quickly to multiple loads.
Each group has seven parameters that will determine the behavior of the
relay. In a typical application each relay in a group will be set to the same
parameters, so that lighting in multiple areas, controlled by different panels
can all be set to follow the same schedules and behavior. However, it is also
possible to program a relay in a group to different behavior, if needed. So, for
example, if a relay controls a hallway or corridor that needs a different time
delay before turning off, you can change the value for that relay while still
having it follow all of the other behaviors of other relays in the group. A panel
can store information for up to 99 groups, but when panels are networked
together more groups are available. Each relay can belong to one or more of
those groups. Groups are discussed in detail in the section “Groups, Scenes,
Schedules, and Macros” on page 8.
NOTE: If a relay in a group has been programmed to different behavior, it is
         possible for the group settings to override the individual relay settings.
                                                                                      Figure 1: Panel interior and enclosures
         See “Group Settings vs. Individual Relay Settings” on page 9 for
         details.
NOTE: If using the LMCP in conjunction with a Segment Manager (LMJA, LMSM), it is important to understand that groups in the LMCP
         are separate from Segment Manager groups, which can only be accessed by the Segment Manager itself.
Channels
A channel is a label for a BACnet data object. A BAS integrator sends messages to a channel to schedule After Hours (AH) and Normal
Hours (NH). Channel is a binary value. Note that a value of “Active” sets the channel to AH while a value of “Inactive” sets it to NH.
Part of what a group does is to respond to scheduled events that determine when Normal Hours and After Hours begin. Because a
channel message also determines Normal Hours and After Hours, it is important to understand the difference between groups and
channels. As mentioned above, a panel has 99 memory locations for groups. But since panels can be connected, the total number of
groups is much larger. Therefore a group number can be higher than 99, but it is still stored in one of the 99 slots. The channel number
will correspond to the slot number where the group number is stored.
Groups 1-8 will always correspond to Channels 1-8. Above number 8, the group numbers are stored into the slots in the order they are
created. So, for example, if group 52 is the first group that you program on a panel, it will be stored in memory location 9 and therefore,
you would send a message on channel 9 to affect Normal Hours or After Hours for group 52.
NOTE: Assigning group numbers above 99 requires LMCS-100 software, and in the software, you will view the groups in the order they
         were created, so are able to determine the channel number.
Smartwire
Smartwire provides a quick and easy way to assign loads (relays) to groups, using the buttons on the panel. When programming directly
on the panel, Smartwire applies only to groups 1–8. However, if using the LMCT-100-2 to program the panel, you can use Smartwire
with groups 1–99. See “Load Binding to Groups 1–8 (Smartwire)” on page 15 for details.
Push n’ Learn
Push n’ Learn (PnL) is the method used to bind loads to sensors and switches, via button pushes. See “Push n’ Learn” on page 15 for details.
Schedules
Schedules allow you to turn loads on or off at specific times. There are 254 schedules available per panel. A group can also respond to
schedules sent from a Segment Manager (LMJA, LMSM) or BACnet-enabled BAS. See “Schedules” on page 10 for details.
Dark/Light
Dark/Light settings allow you to specify turning a group on or off based the amount of outside light. This can be done either with an
astronomical schedule that calculates sunrise and sunset based on your latitude and longitude, or else based on an LMIO-301 photocell
input module or LMIN-104 set to it’s photocell function. Up to 32 dark/light settings can be stored per panel. For details, see “Dark/Light
Events” on page 11.
                                                                      3
The LMRD boards connect to the LMPI board other with DB9 cables. They must be connected as follows:
  • LMCP 8 – Use the top left(#1) DB9 jack.
  • LMCP 24 – Use the top left (#1) DB9 jack for the left LMRD board and the top right (#2) jack for the right LMRD board.
  • LMCP 48 – Use the top left (#1) DB9 jack for the top left LMRD board, the top right (#2) jack for the top right LMRD board, the
    bottom left (#3) jack for the bottom left LMRD board, and the bottom right (#4) jack for the bottom right LMRD board.
Power to the relays comes from the transformers through the LMPI and into the LMRD boards.
    Relay Connection Header                                               Relay Status LEDs – The LED will be ON when the relay
                                                                          turns on, and OFF when the relay turns off. It will blink during
                                                                          the transition between Normal Hours and After Hours, for the
                                                                          amount of time specified with the Blink parameter. (If blink time
                                                                          is set to 0, it will not blink.)
                                                                          In Smartwire mode, the LED will BLINK on and off when relay
                                                                          is included in Group, and OFF when relay is excluded from
                                                                          Group.
                                                                          In PnL mode, the LED will be ON when relay is selected for
                                                                          binding with buttons, and OFF when not selected.
                                                                    4
                                    Figure 2b: LMCPx-10V – Dimming Panel
                                                 LMRD Board
                                                                            0-10V Connections
                                     Override Buttons and Status LEDs       Connect purple wire on “+” terminal,
Relay Connection Header
                                                                            and pink wire on “-” terminal on the
                                                                            removable connector
                                                                                 +
                                                                                 –
                                                            5
                                       The photo below shows the current version of the LMPI board.
                                       An older version of the board is shown on the following page.
Transformer
Power
Connector
Aux Power
Jumper
Selection
Aux Power
Connector
              SW2 – 511 ohm
                                                                                   Group LEDs – Indicates the      Group Buttons – Toggles Group 1 to 8
              Bias Up
                                                                                   status for Group 1 to 8 for     when pressed and released. Also used to
              SW3 – 511 ohm
                                                                                   loads in this panel only, where enter and exit Smartwire mode.
              Pull down
                                                                                   any member load ON indicates
              (behind MS/TP Connector)            SW4 – 120 ohm                    ON, and all member loads
                                                  Termination Resistor             OFF indicates OFF. Blinks
          LMRD Communication                      (behind MS/TP Connector)
          Activity LEDs – Light when                                               during Smartwire mode.
          communication occurs              MS/TP Connector –
          between one of the four           For connection to other
          LMRD cards.                       panels - 3 connections       Panel Config Button and LED
                                            available
Dip Switches
The default for all dip switches is OFF.
                                   P: Pilot Signal
                                                                                                                   Pilot Light
                                                                                                                   24VDC (max 5mA)
                                   C: Pilot common
                                   S: Override Signal
                                                                                                                   Momentary
            PC SC                  C: Override common
                                                                                                                   Push Button
NOTE: These connectors are only found on LMCPX switching panels, and not on the LMCPx-10V dimming panels.
Load Numbering
Load IDs are assigned on the panel based on the LMRD cards. Loads are numbered on a single card from top to bottom. With multiple
cards, numbering continues from left to right, top, then bottom. So on an LMCP-48, loads are numbered as follows:
  • Top Left Card – Loads 1–12                           • Top Right Card – Loads 13–24
  • Bottom Left Card – Loads 25–36                       • Bottom Right Card – Loads 37–48
                                                                      7
                                 GROUPS, SCENES, SCHEDULES, AND MACROS
A group allows you to control one or more relays in one or more panels. Each group has seven parameters that will determine the
normal hours/after hours behavior of the relay(s):
         Parameter                                                         Definition
 Blink                   Amount of minutes load stays ON, when a scheduled event occurs that switches the load OFF when
                         transitioning from Normal Hours to After Hours. The relay will turn off and on once, then the Override LED for
                         that relay will blink continuously for the time period. The LEDs for all switches bound to that group will also
                         blink continuously. Pressing the button will keep the load ON and the time delay countdown will start. When
                         the countdown reaches 0, the blink function re-occurs.
                         NOTE: Blink does not apply when transitioning from After Hours to Normal Hours.
                         Possible values are:
                            • None
                            • 1–240 minutes
                            • Use Load – If set to this value , each individual load will use the value of the same parameter found
                              under the Load Settings menu.
                            • Reset to Load – This value is identical to “Use Load”.
 Time Delay NH           If a load is commanded to turn ON when the schedule switches to Normal Hours, the load will automatically
                         turn OFF after the time delay expires. If the load is turned on manually by a switch after the schedule
                         switches to Normal Hours, the load will again automatically turn OFF after the time delay expires.
                         Possible values are the same as Blink. Default is “None”
 Time Delay AH           Identical to Time Delay NH, but the behavior occurs when the schedule switches to After Hours. Works in
                         conjunction with Blink.
                         Possible values are the same as Blink. Default is “120 minutes”.
 Transition AH > NH      Behavior of the relay when Normal Hours begins.
                         Possible values:
                           • 0–100%
                           • LNZ – Returns to load to the last value that was not 0 (completely off)
                           • Do Nothing – No change occur
                           • LNZ Occupied – Returns to load to the last value that was not 0 (completely off) if the room has an
                             occupancy sensor and the sensor indicates the room is occupied. If the room is unoccupied or if there
                             no sensor in the room, there is no change to the load.
                           • Use Load – This uses the value for each individual load instead of a group value. Setting this value for
                             individual loads is only possible if using LMCS-100 software.
                           • Turn Off – Turns the load Off
 Transition NH > AH      Behavior of the relay when After Hours begins.
                         Possible values are the same as AH–>NH.
 Sensor NH               Determines how the relay responds to sensor input during Normal Hours. Possible values are:
                           • Nothing – Load does not respond to occupancy sensor
                           • Off Only – Responds to sensor input when vacancy is detected but not when occupancy is detected
                           • On Only – Responds to sensor input when occupancy is detected but not when vacancy is detected
                           • On/Off – Responds to sensor input for both occupancy and vacancy detection
                           • Off Only Internal – Responds to vacancy commands only. Instead of using the default value of one
                             minute for the blink warn feature, the sensor will use the amount of time entered in the Blink parameter.
                           • On Only Internal – The load responds only to Occupancy commands and once the load is on, it will
                             not shut off for the length of time entered in the Time Delay NH parameter. Instead of using the default
                             value of one minute for the blink warn feature, the sensor will use the amount of time entered in the
                             Blink parameter.
                           • On/Off Internal – Responds to both occupancy and vacancy commands. Instead of using the default
                             value of one minute for the blink warn feature, the sensor will use the amount of time entered in the
                             Blink parameter.
                           • Use Load – This uses the value for each individual load instead of a group value. Setting this value for
                             individual loads is only possible if using LMCS-100 software.
                         NOTE: Keep in mind that this parameter determines whether the loads assigned to the group will respond
                                 to sensor input. It does not determine whether the loads will turn on or off. That is set within the
                                 sensor programming (either on the sensor itself, or by using the LMCT-100-2 remote or LMCS-100
                                 software).
 Sensor AH               Determines how the relay responds to sensor input during After Hours. Possible values same as above
NOTE: The start times for normal hours and after hours are determined by a Schedule. For details on Schedules, see “Schedules” on
      page 10.
                                                                 8
A group can be set to one of six macros, which contain pre-defined values for each of the seven parameters. Or, you can customize the
setting for your own specific needs. For details, see “Macros” on page 11.
                                                                    9
Occupancy Sensor Events for Groups
An occupancy sensor event determines how loads assigned to a group will respond, based on input from an occupancy sensor. You can
program up to 99 events. A single event will be assigned to a group.
NOTE: If using multiple occupancy sensors, when programming with the LMCT-100, you should only assign ONE sensor input to a
       group. Assigning more than one sensor to a group will lead to inconsistent response (but you can assign different sensors to
       different groups). If you need to assign multiple sensors to a group, use the LMCS-100 software to program the actions. The
       LMCS software has additional capabilities for programming input from multiple sensors.
NOTE: Occupancy sensor events can be assigned to either a group or a scene. For details on scenes, see below.
For each group, there is an Occupancy parameter (triggered when the sensor detects occupancy) and a Vacant parameter (triggered
when it detects vacancy). For group events, the available values for both occupancy and vacancy are:
  • 0–100% – Load goes to the specific value selected
  • LNZ – Set the load to the last non-zero level.
  • Turn Off – This relinquishes the load—it doesn’t actually “turn off” the load. The loads will still wait for the sensor delay timers to
    expire before turning off. If the Partial Off parameter on the Load Settings menu is a value other than 0, the load will go to that
    level.
  • Do Nothing – No change to the load.
  • NH Ovrride – Set the load to Normal Hours. The value of the AH–>NH parameter for the group will be applied.
  • AH Ovrride – Set the load to After Hours. The value of the NH–>AH parameter for the group will be applied.
  • Normal Hrs – Set the load to Normal Hours. All settings found on the Normal Hours tab within LMCS-100 for loads and sensors will
    be applied. (These settings are only available if you are using LMCS-100 software.)
  • After Hrs – Set the load to After Hours. All settings found on the After Hours tab within LMCS-100 for loads and sensors will be
    applied. (These settings are only available if you are using LMCS-100 software.)
Scenes
The LMCP also has the ability to control Scenes (but only on the panel’s Cat 5e local network). Scenes are similar to Groups in that they
control group of loads but also provide the ability to fade between one value and another when the scene is changed. For a switching
LMCP, if assigning relays within the LMCP to a scene, it will switch relays on or off, since no dimming is possible.
There are sixteen possible scenes per “room” (or in this case a panel). When a scene is activated (typically by assigning it to a switch),
all loads assigned to that scene will respond. You can select which loads are included in the scene.
Scenes are normally assigned to a button switch (the LMSW-105 5-Button Switch is commonly used for this but any button can be set
as a scene button).
Scenes can also be triggered by Occupancy Sensors and Dark/Light events. The load control is similar to that of Occupancy Sensors
and Dark/Light events for groups, but for scene events, you determine whether to turn the scene On or Off.
NOTE: Even though Scene events are separate from Group events, in the LMCT-100-2, you access these events from the Group Occ
         Sensors and Group Dark/Light screens within the Group Setup menu
Schedules
You can schedule up to 254 date and time based events per panel. Each event is assigned to a group, and determines one action for
the group. For each event, you specify the time the event occurs. You also specify the days of the week in which the event will occur.
Additionally, you specify whether the event will occur on any day designated as a holiday.
The possible actions sent to the group include:
If panels are networked and multiple panels use the same group number to control relays in those panels, then any events scheduled
in one panel will affect the other panels (since events are always assigned to a group number). By using different group numbers in
different panels, you can limit which panels will respond to those scheduled events.
Assigning a Panel to be the Master Clock
Every LMCP has a clock in it, which allows you to set time and date for controlling schedule events and calculating sunrise and sunset for
Dark/Light events. To set the clock, use the LMCT-100-2 hand held remote, LMCS-100 software, or BACnet Time Synchronization via a BAS.
Additionally, if you have more than one panel networked together, any panel can be set to be the master clock. It will periodically send
out clock information to the other panels so that they remain synchronized. You can set how often the master sends the clock message.
The advantage of having any panel act as a master is that if the master panel is taken off-line for any reason, any other panel can be
easily set to be master and all panels will still remain in sync. (Note that if the original panel is put back on-line you will want to revert the
replacement master or the original panel to back to being a slave, so that you don’t have two master clocks on the network.)
To assign a panel as the master, you need LMCS-100 software. For more information on LMCS-100, see “Programming the LMCP” on
page 14.
                                                                       10
Macros
A macro is a set of pre-defined values for the seven parameters that are part of a group. Each group can be set to a specific macro,
or to use no macro and instead use a customized set of values. There are six macros in the LMCP. Following is a description of the
intended use for each macro, followed by a list of all parameter values:
NOTE: If you want to set up custom parameters that are similar to one of the macros, select that macro first, then go into Custom mode
         and change only the value that different from the macro default.
   • Manual – This macro should be used when there are no occupancy sensors or switches associated with the Group and only on/off
     actions from schedules or dark/light are intended. Since On/Off changes are based only on schedules and dark/light sensors, the
     only parameter in the macro that has any effect is Blink, which will provide a warning to occupants by momentarily shutting the load
     off and then back on.
   • Override Time AH – This macro is designed for situations where only switches are used (no occupancy sensors). An override time
     delay is set so that if a switch is used to keep the light on during after hours, the load turns off after two hours. The load is set to
     turn ON when entering Normal Hours. If you instead want to require that the load be manually turned on, start with this macro when
     creating the group, select CUSTOM, and modify the Transition AH > NH action to a value of “Do Nothing.” Additionally, adjust Time
     Delay AH if you want a different amount of time before the load turns off.
       NOTE: The settings in this macro are used for Groups 1–8, when you use Smartwire to assign relays to a group.
   • Sensor Day Disable – For use with occupancy sensors, this macro turns all loads ON during Normal Hours; they can be turned off
     or back on manually, with no override time delay. When After Hours begins, loads are turned OFF and sensor functionality is set to
     Auto On/Off. A two hour time delay is set for cases in which some loads in the group are not bound to sensors, but only to switches.
   • Sensor Man-On NH – In this macro, relays are left OFF when Normal Hours begins. Occupancy sensors trigger loads on occupant
     arrival, but do not time out until after hours. When After Hours begins, loads turn OFF and sensors switch to Auto On/Off. As with
     the Sensor Day Disable macro, a two hour time delay is set for cases in which some loads in the group are not bound to sensors,
     but only to switches.
   • Sensor Auto – This macro sets sensors to Auto On/Off for both Normal Hours and After Hours operation, so loads turn ON only
     based on sensor or switch input. A 120 minute override time delay is used during the After Hours period. This allows for consistent
     functionality in response to sensors at all times, while accommodating the inclusion of relays not bound to sensors that share the
     same operational time window.
   • Auto Switch-1xx – This macro is designed to work with the AS-100 Automatic Control Switch. The AS-100 is a switch that controls
     the line voltage (instead of sending a low voltage control message to the panel or other room controller). Instead, the AS-100
     responds to timed power interrupt signals coming from a relay in the panel, providing automatic shutoff with a blink warning when
     transitioning between normal hours and after hours. Other timed interrupt signals can turn the power on or off. You assign a relay
     to “AS-100” mode using LMCS-100 software or on the Load Config (PnL) menu in the LMCT-100-2. All relays in “AS-100 mode”
     remain closed except for the timed interrupts. If this macro is assigned to a group, you should only assign relays in “AS-100” mode
     to that group. When using this Macro, none of the seven group parameters apply. (Although Blink is set to 5 minutes, the blink time
     is actually controlled by the AS-100, not the LMCP.)
       NOTE: Since selecting this mode puts all relay in the associated group into “AS-100” mode, you should not assign those relays to
               another group set to a different macro.
NOTE: Keep in mind that Macros only affect the behavior during the transitions to Normal Hours and After Hours, plus the response to
         occupancy sensors. Any scheduled events and input from photocell sensors will still affect the loads.
NOTE: The values for the seven parameters are only applied to the Group when the Macro (or custom) information is sent to the LMCP
         from the LMCT-100-2 remote or LMCS-100 software. If a subsequent message is sent to the LMCP with a different value for
         a parameter, the original value is overwritten, and will only change back to the original value if the Macro is sent again to the
         group. So for example, if a relay is assigned to two different groups, and each group has been assigned a different Macro, the
         last macro sent to the LMCP will determine the behavior of that relay.
                                                                          Macro Values
                                         General Settings                          Transition Settings             Sensor Behavior
         Macro              Blink      Time Delay NH       Time Delay AH         NH>AH           AH>NH             NH             AH
  Manual                    5 min            None                None           Do nothing      Do nothing      Off Only       Off Only
  Override Time AH          5 min            None              120 min           Turn off         Turn on       Off Only       Off Only
  Sensor Disable Day        5 min            None              120 min           Turn off         Turn on      Follow On         Auto
                                                                                                                 Only
  Sensor Man-On NH          None             None              120 min           Turn off       Do nothing      Off Only         Auto
  Sensor Auto               5 min            None              120 min          Do nothing      Do nothing        Auto           Auto
  Auto Switch-1xx           5 min            None                None           Do nothing      Do nothing     Do nothing     Do nothing
                                                      DARK/LIGHT EVENTS
The LMCP can be programmed to turn relays on or off based on when it becomes dark outside (night) or light (day). You can program
up to 32 separate dark/light events, and each event is assigned to a group or a scene. For each event, you can select whether to base
the change from dark to light and light to dark on either an astronomical calculation of sunrise and sunset, or from a photocell connected
to an LMIN-104 or LMIO-301. You can have multiple LMIN-104s/LMIO-301s connected to the network and assign different groups to
different LMIN-104 or LMIO-301s, or you can have a single LMIN-104 or LMIO-301 but assign different light thresholds to different
groups.
NOTE: You can only select a single LMIN-104 or LMIO-301 if programming with the LMCT-100-2. To use multiple LMIN-104s/LMIO-
         301s, you must program with the LMCS-100 software.
                                                                     11
Each Dark/Light event has a Dark parameter and Light parameter.
If the event is assigned to a group, then for each parameter you can choose the following:
    • 0-100% – Load goes to the specific value selected
    • LNZ – Set the load to the last non-zero level.
    • Turn Off – This relinquishes the load—it doesn’t actually “turn off” the load. The loads will still wait for the sensor delay timers to
      expire before turning off. If the Partial Off parameter on the Load Settings menu is a value other than 0, the load will go to that
      level.
    • Do Nothing – No change to the load.
    • NH Override – Set the load to Normal Hours. The value of the AH–>NH parameter for the group will be applied.
    • AH Override – Set the load to After Hours. The value of the NH–>AH parameter for the group will be applied.
    • Normal Hrs – Set the load to Normal Hours. All settings found on the Normal Hours tab within LMCS-100 for loads and sensors will
      be applied. (These settings are only available if you are using LMCS-100 software.)
    • After Hrs – Set the load to After Hours. All settings found on the After Hours tab within LMCS-100 for loads and sensors will be
      applied. (These settings are only available if you are using LMCS-100 software.)
If the event is assigned to a Scene, then for each parameter you choose whether to turn the Scene On or Off.
                                                          Dark                                                                 Light
                                                      aka Sunset                                                            aka Sunrise
                                                       aka Dusk                                                              aka Dawn
                                                                                               12
  CONNECTING SWITCHES, SENSORS, PHOTOCELLS, AND OTHER DLM ACCESSORY DEVICES
Switches
The panel’s local DLM network supports all models of DLM switches. Switch buttons may be bound to an individual relay (load), scene,
or network group in the panel. If a switch is bound to a group and any load assigned to that group is ON, the LED on that switch will
indicate ON.
There are several advantages to binding a switch to a group:
  • If you add a load to a group, that switch will immediately control that load without having to re-program the switch.
  • You can assign a switch to the same set of loads controlled by a schedule or dark/light event
  • If you have multiple panels connected, and the same group number assigned to loads in those panels, the switch will control the
     loads from those other panels in addition to the panel in its local network. This allows you to program a single switch that can be
     used as a master, to turn all lights on or off in the case of an emergency or other special circumstance.
Occupancy Sensors
The panel’s local network supports all models of DLM occupancy sensors. Using Push n’ Learn, any number of occupancy sensors can
control the same relay(s) in the local panel. In this case, all sensors must be in the unoccupied state before the relay(s) turn off.
A maximum of 32 sensors can control an individual load. (The total number of sensors controlling various loads is limited only by the
network limitations described above.)
Daylight Sensors
The LMLS-400 and LMLS-500 daylight sensors are capable of controlling relays in the panel as switching loads, or dimming loads if a
dimming capable room controller is connected to the local DLM network.
Analog Photocells
As described in the previous section on Dark/Light Events, the panel’s local network supports the LMIO-301 Analog Photocell Module or
LMIN-104. This module supplies the “light” and “dark” trigger. The panel has user settings for foot candle levels and time delay. The time
delay is used before triggering “light” and “dark” events to establish a dead band and prevent nuisance switching. Only one LMIO-301
per panel can be programmed via the LMCT-100; more can be connected if using LMCS-100 software.
Two types of photocell sensor heads can be used. The LMPO-200 is intended for outdoor use, while the LMPS-6000 is intended
for indoor use where there is direct exposure to high light levels, as would be present adjacent to the glass in an atrium, skylight, or
clearstory.
                                                                     13
            USING AN LMCP WITH ROOM CONTROLLERS AND PLUG LOAD CONTROLLERS
By connecting room controllers and plug load controllers to the DLM local network, you can increase the number of loads in the network.
The maximum number of loads, including all the loads within the panel, is 64. Since the maximum number of devices on a single
network is 48, the total number of additional controllers possible will also be dependent on the number of other DLM devices on that
network. The same cable length requirements apply as with other DLM devices.
Connecting additional controllers to the panel provides several advantages:
  • The loads connected to those controllers can be assigned to groups, the same as the relays in the panel. This allows for scheduling
    of those loads and all other group features.
  • Dimming loads can be added to the network, provided you have a room controller with dimming capability.
  • Current monitoring of plug loads and dimming loads is possible as part of the network control. (Note that current monitoring of
    dimming loads within the panel is not available.)
NOTE: There is a maximum of 4 LMRC-10x room controllers, LMPL-101 plug load controllers, and/or LMPB-100 power boosters
        allowed per network (A or B), for a maximum total of 8. This applies only to the 10x series and not the 2xx series.
                                                Connecting Room and Plug Load Controllers
                   Network A                                                                                      LMPL-
                                     213              102            211            213            212             101
                                                                     15
   3. To exit PnL, hold the Config button for 3 seconds, until the LED stops blinking. Or if using the LMCT-100-2, select EXIT.
If you have one or more DLM Room controllers connected to the LMCP, then as when you cycle through the loads by pressing the
Config button, once the last relay is reached on the LMCP, the sequence advances to the Room Controller with the highest serial
number and cycles through the loads on that controller in order.
A primary difference in operation of the LMCP compared to a DLM Room Controller is that by default, while in load configuration mode,
the panel relays do not turn on and off in sequence as the Config button is pressed. Only the LED associated with the relay turns on On
a DLM Room Controller, the load itself will turn on and off.
NOTE: It is possible to change the LMCP so that the relays turn on and off in PnL, just like a room controller. This is done by setting Dip
        switch #7 on the LMPI board to the ON position.
LMCT-100-2 Basics
The LMCT-100-2 provides an easy to read display and a simple user interface that makes it easy to navigate through programmable
features It both send information to and receives information from the LMCP and other DLM devices.
It is important to understand that all information is stored in the LMCP or accessory devices, and not the
LMCT-100-2. Therefore, if you change any values on the LMCT-100-2, you must select the Send option in order to save your changes.
If you press the Home button, Back button, or select Done without first sending the data to the LMCP, that data is not saved.
User Interface Navigation
You navigate from one field to another using  (up) or  (down) arrow keys. The active field flashes between yellow text on black
background and black text on yellow background. Navigation “wraps” around, so if the active field is the top field and you need to get to
the field at the bottom of the screen, pressing  will bring you to the bottom in a single key press.
NOTE: The up and down arrow keys are always used to move between fields. So even when fields are placed on the same horizontal
         line, which is often found with the Action options at the bottom of the screen, you still use the Up/Down arrows to move left/right
         between fields.
Once a menu field is active, press the Select        button to open that menu.
Value fields are used to adjust parameter settings. They are shown within “less than/greater than” symbols: <value>. Change the value
using  and  arrow keys. In general the  key increments and the  key decrements a value. Selections wrap-around if you
continue to press the key beyond maximum or minimum values. Move between value fields using  or  arrow keys.
The       button takes you to the main menu.
The        (Back) button can be thought of as an undo function. It takes you back one screen. Changes that were in process prior to
pressing the       key are lost.
At the bottom of any screen that includes programmable fields, you will see Send and Done (and sometimes additional choices). As
mentioned previously, you must press Send to save your data to the LMCP before pressing Done, if you want to save the values you
set on that screen.
On some screens, one of the options at the bottom of the screen will take you to a secondary, related screen. For example, at the
bottom of the Program Schedules screen is an Active Days option, where you choose which days the schedule will be active. In the
case, the Schedule Active On screen has only a Done option at the bottom—you must return to the Program Schedules screen
before you can send the schedule information to the LMCP.
  Up or Down                     Select
    Button                       Button
                                                                     16
Display                                   Description                                              Press
                  B AT =
   Adjust Light Level
   Global Network                                                                                               then
   Utilities                              Scroll to Global Network. Press Select.                               Select
   Panel Setup
   Group Setup
             More
Network - Panel
                                                                    17
Viewing the Network Status
The Network Status shows the communication “health” of the network and the number of devices currently found on the network.
Display                                   Description                                            Press
Network - Panel
                   B AT =
    Adjust Light Level
    Global Network                        Scroll Down or Up to Highlight Panel Select, then
                                          press Select.                                                     or            then
    Utilities                                                                                                             Select
    Panel Setup
    Group Setup
              More
Panel Setup
    Location Settings                     This screen is the starting point for all following
    Date and Time                         instructions.
    Panel Programming
    Panel Status
                                                                     18
Display                                     Description                                            Press
Panel Setup
    Location Settings                       When you first enter the Panel Setup screen,
    Date and Time                           Location Settings is already highlighted.                 Select
    Panel Programming                       Press Select.
    Panel Status
Panel Setup
    Location Settings                       From Panel Setup, scroll to Date and Time. Press                     then
    Date and Time                           Select.                                                              Select
    Panel Programming
    Panel Status
       Date and Time Set                    Scroll to each field and set the value. An illegal                       to move to each
                                                                                                           or
 Ye a r :            <2014>                 date (for example, February 30) cannot be entered.                       parameter
 Month:            <August>                 After selecting all values, scroll to DSTSTD and                         to change the value
 Date:                 <14>                 press Select.                                                  or
                                                                                                                     of the parameter
 Hour (24 Hour):       <16>
 Minute:               <37>                 NOTE: There is no clock in the LMCT-100-2,                               then choose
                                                     so the time values will not change if you                       DSTSTD and
      SEND       DSTSTD        DONE                  remain on this screen longer than a minute.                     press Select
                                            This screen determines if the panel will follow                           to move to each
       D S T C o n fi g u r a t i o n       Daylight Savings Time. If you set Follows DST                  or
                                                                                                                      parameter
                                            to “Yes”, you can choose a value of “Auto” or
 F o l l o w s D S T:            < Ye s >   “Manual” for Method. Select BEGINS.                                       to change the value
 Method:                        <Auto>                                                                     or
                                            NOTE: If you set Follows DST to “No”, the                                 of the parameter
                                                    Method field disappears. Highlight DONE                           then choose
                                                    and press Select, or press      to return to                      BEGINS and
      BEGINS        ENDS       DONE                                                                                   press Select
                                                    the Date and Time Set screen
                                                                      19
Display                                   Description                                            Press
Panel Programming
Panel Programming functions include:
  • Schedules – Allows you to specify an event and assign it to a group
  • Holidays – Allows you to specify a specific date as a holiday. Used in conjunction with schedules.
Display                                   Description                                            Press
Panel Setup
      Panel Programming
       603981210
To avoid repeating the same steps for every function described in the following pages, the Panel Programming Sections assume you
have already navigated to the Panel Programming screen.
Schedules
On this set of screens, you assign and event to a group, and set one action for that event. For each event, you specify the time the
event occurs. You also specify whether the event will occur on a per day basis. Additionally, you specify whether the event will occur on
any day designated as a holiday.
Display                                   Description                                            Press
      Panel Programming
       603981210
                                          From the Panel Programming screen, highlight              Select
 Schedules
 Holidays                                 Schedules and press Select
                                                                    20
Display                                   Description                                              Press
       Schedule Active On                 For each day of the week, select whether the                               to move to each
                                                                                                           or
                                          event will be active (Yes or No). Additionally, select                     parameter
  Mon:     <Y>         Tu e :   <Y>       whether the event will be active on holidays. (You
  We d :   <Y>         Thu:     <Y>                                                                                  to change the value
                                          determine which days are holidays in the Holidays                or
  Fri:     <Y>         Sat:     <N>                                                                                  of the parameter
  Sun:     <N>     Holiday:     <N>       screen.)
                                                                                                                     then choose
                                          Highlight DONE and press Select to return to the                           DONE and
                 DONE                     Program Schedule screen.                                                   press Select
Holidays
On this screen, you determine which days are designated as holidays.
Display                                   Description                                              Press
      Panel Programming
       603981210
                                          From the Panel Programming screen, highlight                          then
 Schedules
 Holidays                                 Holidays and press Select                                             Select
      Point to the desired                Point the LMCT-100-2 at the infrared sensor on the
      Panel IR Sensor and
         press ‘Select’                   LMRD board and press Select to open the Holiday            Select
                                          Setup screen.
Panel Status
This screen displays the date and time,based on the panel settings, sunrise/sunset times based on date and location settings, whether
the current date is a holiday, and the current settings of the dip switches. Additionally, it will display an error message for certain
problems.
                                                                    21
Display                                  Description                                             Press
Panel Setup
      Point to the desired               Point the LMCT-100-2 at the infrared sensor on the
      Panel IR Sensor and                LMRD board and press Select.
         press ‘Select’
                                                                                                   Select
                                         One of the following screens will display,
                                         depending on the Status option you selected.
                   B AT =
    Adjust Light Level
    Global Network                       Navigate to the Group Setup option on the second                   then
    Utilities                            main menu screen and press Select.                                 Select
    Panel Setup
    Group Setup
              More
          WARNING:
      LMBC or Panel must
        be connected                     A warning appears, explaining that a bridge or
          To a c c e s s                 panel is needed for this functionality. Press Select,     Select
         Group Setup                     then point the LMCT-100-2 at any IR enabled
                                         device and press Select again..
          Press ‘Select’
           to proceed
                                                                   22
Display                                  Description                                             Press
DONE
Group Loads
On this set of screens, you assign loads to groups and customize the behavior of those groups.
Display                                  Description                                             Press
DONE
            Group Setup
                                                                                                              to choose the
 Group:                    <1+>                                                                          or
 Ty p e :             <Custom+>          Choose the Group number. Press Select to open                        Group number
                                         the Group x Loads screen.                                            then press
                                                                                                              Select
      DONE     DELETE     SEND
                                                                                                              to move to each
                                                                                                         or
          Group 1 Loads                  To assign various loads to the group, scroll through                 parameter
                                         each Load number and select whether that load                        to change the value
                                         is a Member of that group. When complete, select                or
 Load:                         <1>                                                                            of the parameter
                                         DONE to return to the Group Setup screen.                            then choose
 Member:                    < Ye s >                                                                          DONE and
                                         You also select have the option of using the
                                         Smartwire function instead of manually scrolling                     press Select
       DONE      SMARTWIRE               through the loads. To do this, select SMARTWIRE.                             OR
                                                                                                              Select SMARTWIRE
         P oint to any IR
       enabled devic e and
         press Selec t to                Point the LMCT-100-2 at the infrared sensor on the        Select
       begin Smartwiring                 LMRD board and press Select
        loads within the
              P anel
                                                                  23
Display                                   Description                                            Press
DONE
                                                                   24
Display                                    Description                                           Press
Group Dark/Light
On this set of screens, you assign individual dark/light events.
Display                                    Description                                           Press
DONE
      Point to the desired                 Point the LMCT-100-2 at the infrared sensor on the
      Panel IR Sensor and
         press ‘Select’                    LMRD board and press Select to open the Dark/           Select
                                           Light Events screen.
                                                                    25
Display                                Description                                              Press
      Dark/Light Events
 Event:                        <1>                                                                              to change the value
                                                                                                        or
                                       Select the Event number in which to store the                            of the parameter
                                       dark/light event. Then highlight NEXT and press                          then choose
                                       Select to open the Dark/Light Event x screen.                            NEXT and
                                                                                                                press Select
  NEXT    DONE    DELETE     SEND
                                                                 26
Display                                   Description                                             Press
Utilities
The LMCT-100-2 contain a number of different Utilities. This section covers the Status utilities provide status information on loads and
groups, photosensors, and sensors connected to the panel.
An additional screen containing status information specific to panels is also available from the Panel Setup screen. See “Panel Status”
on page 21.
Display                                   Description                                             Press
                   B AT =
    Adjust Light Level
    Global Network                        Navigate to the Utilities option on the second main                     then
    Utilities                             menu screen and press Select.                                           Select
    Panel Setup
    Group Setup
              More
         Utilities Menu
    SmartWire
    Identify Devices
    Force System into PnG
                                          Navigate to the Status option and press Select.
                                                                                                                  then
    Room Mode                                                                                                     Select
    Load Shed
    Status
              Done
Status – Panel
    Load Status
    Group Status
    Light Level                           Press Select to choose the Load Status option.                       Select
    Occupancy Sensors
Done
                                                                    27
Load Status
This set of screens displays details about each load in the panel, as well as any loads in connected room controllers.
Display                                   Description                                               Press
   Load 1 Online
                                          This screen displays the BACnet priority of the load
   1   2  3    4  5    6
    .  .   .    .  .   .                  DLM devices will typically have a priority of 8.                       Select
   7   8  9 10 11 12                      Highlight PROPERTIES and press Select.
   .   1    .   .  .    .
  13 14 15 16
   .   .   .   .
    PROPERTIES      DONE
   Load     2     Properties      3
                                          This screen displays the sensor behavior for this
          Sensor Behavior
 AH:          Man On/Auto Off             load.
                                                                                                             Select DONE
 NH:              Auto On/Off             Highlight DONE and press Select to return to the
                                          Status screen.
          PRIOR          DONE
                                                                    28
Group Status
This set of screens displays the loads that are assigned to the group, along with their current on/off state. Additionally, you can view the
settings for the group. Finally, in cases where the setting of an individual load are different from the group settings, you can view the
differences. This can be extremely helpful when trying to diagnose a situation in which a load is not responding as expected. Keep in
mind that individual loads can be programmed with different values from the group but still be a member of the group.
Display                                    Description                                               Press
Status – Panel
    Load Status
    Group Status                           From the Status Menu, highlight the Group Status                          then
    Light Level                            option and press Select.                                                  Select
    Occupancy Sensors
Done
          Group Status
                                                                                                                     to change the value
    Group:                       <1>                                                                         or
                                           Select the Group number that you want to display,                         of the parameter
                                           highlight NEXT, and press Select.                                         then choose
                                                                                                                     NEXT and
                                                                                                                     press Select
         NEXT             DONE
          Press
          Select                           Point the LMCT-100-2 at the infrared sensor on the
      Point to the desired
      Panel IR Sensor and                  LMRD board and press Select.
         press ‘Select’
                                                                                                                  Select
                                           One of the following screens will display,
                                           depending on the Status option you selected.
                                                                     29
Display                                   Description                                            Press
Light Level
This screen displays the current light level, in foot candles, registered by an LMIO-301 with an attached photosensor.
Status – Panel
    Load Status
    Group Status                          From the Status Menu, highlight the Light Level                          then
    Light Level                           option and press Select.                                                 Select
    Occupancy Sensors
Done
Status – Panel
    Load Status
    Group Status                          From the Status Menu, highlight the Occupancy                            then
    Light Level                           Sensors option and press Select.                                         Select
    Occupancy Sensors
Done
                                                                   30
Display                                    Description                                              Press
BACnet Settings
The following parameter settings and concepts are important to understand when configuring the LMCP for BACnet communication:
  • Device ID – The device ID is a unique number, between 0 and 4194302, that identifies a device in a BACnet network. Every device
    in the network must have a different number. By default, the LMCP uses the last 6 digits of the serial number (plus a leading 0 to
    complete the seven digit number). This number can be changed if needed, for example, when required by an integrator, as part of a
    BAS. Once set, the LMCP will remember the ID number even if other parameters are reset to their default values.
  • Device Name – This is a label for the panel, useful when working with LMCS in a situation where multiple panels are used, to help
    more easily distinguish between the panels. Any numerals or letters can be used in naming the panel. By default, the name is the
    same as the serial number. The name can be programmed using either LMCS, the LMCT-100-2, or a BAS application.
  • MS/TP MAC Address – The MS/TP MAC address is an additional identifier, used by the devices on the network to communicate
    with each other. It is a number between 0 and 127. It is important to understand the difference between the device ID and the MS/
    TP MAC Address. The Device ID is, in essence, a number that identifies “who” the devices is, while the MS/TP MAC address
    identifies its “location”.
      In a BACnet network, all the devices pass a token to each other to determine which device has control of communication over
      the network. The MS/TP MAC address is used to “locate” other devices. When a device receives the token, it will take control of
      the communication and send messages to other devices as needed. It then passes the token to the device with the next highest
      MS/TP MAC address. In order to do this, it sends an “Are you there?” message on the MAC address one higher than its own. If it
      receives a response, it passes the token. If it does not receive a response, it tries again on the next highest number, continuing in
      this manner until it receives a response. This “Are you there?” message is referred to as a Poll For Master.
      NOTE: In order to send and respond to this Poll For Master message, a device must be designated as a master device. Other
               devices (slave devices) on the network will not respond, and cannot take control of the communication.
      While the Device ID is fixed and should not change, the MS/TP MAC address can change as devices come on or drop off the
      network. By default, the LMCP will automatically assign an MS/TP MAC address. When the LMCP is powered up, it will check
      the network for other devices to determine if its current MAC address is being used by another device. If, not it will keep the same
      address, but if it is, and will assign an unused number between 32 and 127.
      You can manually assign an MS/TP MAC address instead of having the LMCP automatically assign the number. This can be
      useful, especially in larger networks where response time is important. Since the Poll For Master message checks the next highest
      address number and then increments that number until it finds a device, having devices with gaps between numbers can increase
      latency. If you have 10 devices, numbered 0–9, you will have optimal performance since no time is wasted sending the Poll For
      Master message to an unused number.
                                                                    31
  • Max Master – The Max Master parameter is another parameter that will cut down on latency. The value you set for this parameter
    is the highest number the LMCP will check when sending a Poll For Master message, before returning to 0. So, in the previous
    example, where there are 10 devices numbered 0–9, if you set the Max Master to 9, it will never check addresses 10–127.
      NOTE: If using the LMCP with a global controller such as a router, BAS or Segment Manager, the global controller will always
              default to a MAC address of 0.
NOTE: You should be aware that devices connected over the DLM Local Network also have MAC addresses for communication
        purposes, but that MAC address is entirely separate from the MS/TP MAC address.
Further details on Device IDs and MAC addresses can be found in WattStopper’s Technical Bulletin #180 at http://www.wattstopper.com/
resources/download-center/tech-bulletins-whitepapers.aspx.
                                                                      32
                                                        BACnet Connectivity Scenarios
                                                                                             Optional connection
Addressing shown using optimized
                                                                                             to LMCS-100
Device IDs and Mac addresses.
                                                                                             software.
Default IDs and Auto MAC addressing
can be used as desired, but sequential
                                                                                             Must match UDP
addresses can optimize performance
                                                                                             port# of any
if needed.
                                                                                             routers
                                                        LMCP Panels
         ID: 86004               ID: 86005                ID: 86006         ID: 86007               ID: 86008
         MAC: 04                 MAC: 01                  MAC: 06           MAC: 07                 MAC: 08
The Device ID’s of this BACnet Segment Network are unique so that it could be combined
with the top network if desired. Combining Segment Networks is done using NB-ROUTERs
that must then assign a network number to each Segment Network.
                                                                      33
                                                             APPENDIX A
BACnet Objects
NOTE: While there are 96 object instances available for many of the objects listed below, keep in mind that the LMCP panel supports
      only 48 devices per network (A & B), and the panel itself is one of the devices in each network. Therefore, there is never a case
      where you would use all 48 instances of an object in a single network.
                                                                  34
Object Instance                   Object Alias                                         Object Function
BI101–BI9608       Button state                            Read button state for 1 to 8 buttons per switch for 1 to 96 switches.
BI1–BI96           Detection state                         Occupancy sensor detection state. Active = occupied.
BV101–196          Switch lock status                      Read switch status (locked or unlocked).
                                                           Active = locked.
BV201-299          Group Normal Hours/After Hours          Normal Hours/After Hours selection for a group.
                                                           Active = after hours.
MV4001–MV4096 Daylight sensor 1–96, operating mode         For LMLS-400 daylight sensor 1–96, operation mode:
                                                           1 = ON/OFF, 2 = bi-level, 3 = tri-level, 4 = dimming.
MV4101–MV4196 Daylight sensor 1–96, setpoint multiplier For LMLS-400, off setpoint multiplier: 1=1.25x, 2=1.50x, 3=1.75x, 4=2x.
                                                 Room Level Control Objects
BV1                Schedule state                          Normal hours/after hours selection. Active = after hours.
                                                           NOTE: This changes the status for the entire panel, and therefore can
                                                                  conflict with BV201-299, if not used carefully.
BV2                Switch lock control                     Lock or unlock enabled switches. Active = lock.
                                                           NOTE: This changes the switch lock status for every switch connected
                                                                   to the panel, and therefore can conflict with BV101-196, if not
                                                                   used carefully.
BV3                Room occupancy status                   Read occupancy status (occupied or unoccupied).
                                                           Active = occupied.
                                                           NOTE: This is the logical OR of the states of ALL sensors connected
                                                                   to the panel regardless of their local control scheme. In other
                                                                   words, if any sensor has a status of occupied, this value will
                                                                   read occupied.
BV4                Force all loads ON                      Active = all loads ON at priority 1. Inactive = relinquish at 1 and ON at
                                                           priority 8.
                                                           NOTE: This will force all loads connected to the panel ON.
BV5                Force all loads OFF                     Active = all loads OFF at priority 2. Inactive = relinquish.
                                                           NOTE: This will force all loads connected to the panel OFF.
MV1                Scene control                           Write scene selection. Range = 1 to 16.
MV2                Demand response (shed) control          Activate room level DR mode: 1 = no shed, 2 = shed mode, permit
                                                           switch override, 3 = shed mode, prohibit switch override.
                                                           NOTE: This will affect all loads connected to the panel.
AV901              MS/TP MAC address                       Default is 255 for automatic, writable in the range of 0 to 127.
AV902              MS/TP network speed                     Baud rate: 9600, 19200, 38400, 57600, 78600, 115200.
AV903              Input room size                         Allows user to write area in square feet from 0 to 65,534, default is 0.
AV904              Room lighting watts                     Read total lighting wattage for room.
                                                           Total of baseline watts for active relays, or if no baseline wattage for
                                                           the relays are used, then this is calculated as AV401 * AV501 + any
                                                           usage from LMRC/LMFC connected via CAT5 to the panel.
                                                           NOTE: This does not include used from LMPLs. Use AV906 for plug
                                                                    load controllers.
AV905              Room watts/sq.ft.                       Read total room lighting W/ft2.
                                                           If the input room size for the entire application area is used and the
                                                           baseline watts method or AV401 * AV501 method is used, then this
                                                           object will calculate the aggregate watts per square foot of the whole
                                                           panel’s application area.
                                                           Use of this object is not recommended for use in applications where
                                                           panels cover mixed areas.
AV906              Room plug load watts                    Read total plug load wattage for LMPLs connected to the panel.
                                                              35
            WARRANTY INFORMATION                          INFORMATIONS RELATIVES À LA GARANTIE                     INFORMACIÓN DE LA GARANTÍA
Wattstopper warranties its products to be free            Wattstopper garantit que ses produits sont           Wattstopper garantiza que sus productos
of defects in materials and workmanship for a             exempts de défauts de matériaux et de fabrication    están libres de defectos en materiales y mano
period of five (5) years. There are no obligations        pour une période de cinq (5) ans. Wattstopper        de obra por un período de cinco (5) años. No
or liabilities on the part of Wattstopper for             ne peut être tenu responsable de tout dommage        existen obligaciones ni responsabilidades por
consequential damages arising out of, or in               consécutif causé par ou lié à l’utilisation ou       parte de Wattstopper por daños consecuentes
connection with, the use or performance of this           à la performance de ce produit ou tout autre         que se deriven o estén relacionados con el
product or other indirect damages with respect            dommage indirect lié à la perte de propriété, de     uso o el rendimiento de este producto u otros
to loss of property, revenue or profit, or cost of        revenus, ou de profits, ou aux coûts d’enlèvement,   daños indirectos con respecto a la pérdida
removal, installation or reinstallation.                  d’installation ou de réinstallation.                 de propiedad, renta o ganancias, o al costo
                                                                                                               de extracción, instalación o reinstalación.