Specification
Specification
2.1 GENERAL
***END OF SECTION***
A. Furnish all materials specified herein or indicated on the
SECTION 16150 – LIGHTING FIXTURES drawings.
B. All lightings fixtures, ballast, and lighting controls shall be
PART 1 – GENERAL
UL listed and bear UL label or IEC equivalent.
1.1 DESCRIPTION C. Fixtures shall be selected from the fixture schedule from
the description of the fixture with consideration to
A. The work required under this section consists of the mounting, number and types of lamps, and reference
supply, installation, testing, and commissioning of the notes contained in the fixture schedule and in accordance
lighting fixtures and associated equipment and materials. with these specifications. The fixtures catalogue number is
provided for easy reference only.
1.2 QUALITY ASSURANCE
D. Ballast and transformers shall be suitably rated for
A. Industry Referenced Standards: The following operation on electrical system voltage to which they are
specifications and standards are incorporated into and to be connected.
become part of this specification aby reference. Except
2.2 PRODUCT/MATERIAL DESCRIPTION
where a specific date is given, the issue in effect (including
amendments, addenda, revisions, supplements, and A. Lighting Fixtures
errata) on the date of invitation for bids, shall apply. In
text, such specifications and standards and referenced to 1. Where fixtures are provided with plastic prismatic
be basic designation only. lenses, lens shall be UV stabilized virgin acrylic.
2. HID fixtures with metal halide lamps shall have a
1. NFPA 70 – National Electrical Code protective borosilicate glass lens.
2. Underwriter’s Laboratories, Inc. 3. Fixtures shall be prewired.
57 Electrical Lighting Fixtures 4. External luminaries to be weatherproof made from
3. American National Standards Institute (ANSI) Copper, stainless steel or approved non-corrodible
C82.1, .2, .3: Ballast material.
4. The Philippine Electrical Code 5. All production are fittings to be dust sealed to IP54
5. International Electrical Commission and suitable for harsh environment areas.
IEC 347 Lamp Control Gear
IEC 662 High Pressure Sodium Lamps B. Ballast
IEC 598 Luminaries General
IEC 921 Ballast for Fluorescent Lamps 1. Ballast for high intensity discharge fixtures shall be
IEC 911 Ballast for Discharge Lamps – General high power factor, regulating type, with voltage
regulation of ±10%, and crest factor of not more than
B. Acceptable Manufacturers: Products of the following 1.8. Primary starting current shall not exceed
manufacturers, which comply with these specifications, operating current.
are acceptable. 2. Ballast for fluorescent lighting fixtures will be
electronic.
3. Battery Ballast: 6. Have reversed battery polarity protection.
a. All exit lights and emergency lights shall be 7. Have lamp removal protection.
operable from either normal, generator power or 8. LED indication of charging mode.
self-contained battery back-up ballast.
4. ELV Transformers B. Emergency Luminaries
a. Fully enclosed.
All emergency luminaries shall:
b. Maximum power loss within ELV transformers
shall not exceed 20% of its rated power output. Contain visual indicator lights
c. Maximum transformer voltage regulation Include local light switches
variance: 5%. Contain inverter protection against damage in
the event of lamp failure removal.
C. Lamps: Contain battery packs to operate the luminaries
1. Lamps shall be supplied with each lighting fixture. for a period of 3 hours.
2. Metal halide lamps shall have a minimum CRI of 70 Standard luminaries specified with battery back-
with a colour temperature in the range of 3200oK to up shall be delivered to site complete with all
4000oK and a colour shift during lamp life of less than inverters, change over system and battery.
500oK.
3. Fluorescent lamps shall be tri-phosphor coated lamps PART 3 – EXECUTION
with a CRI of 85 and 3,000 maintained lumens for
3.1 FIXTURES SUPPORTS AND MOUNTING
36W fittings.
4. Auxiliary Quartz halogen lamps to be provided for HID A. Lighting fixtures will be installed in accordance with the
luminaries which switch off when the luminaries manufacturer’s recommended mounting methods.
reaches maximum illumination. Provide complete details regarding the required mounting
D. Power Factor Connection methods for each of the fittings in the location they are to
1. Correct each luminaries to a minimum power factor be installed. All lighting shall be supported from the
of 0.9 lagging. building structure.
2. Self-healing, hermitically sealed type to be used with B. Surface mounted fixtures mounted on concrete structure,
a built in protective device. sheet rock or plaster ceiling or low density acoustical tile
ceilings shall be mounted with two 6mm x 40mm x
2.3 EXIT SIGNS
100mm metal spaces between the fixture and the ceiling,
A. Emergency Exit luminaries shall: if required. HID fittings shall be provided complete with
1. Be of the 2x10 watt (minimum) fluorescent lamp, “quick mount” base for ease of maintenance.
with one lamp for battery operated emergency C. Propose complete dimensioned, fixing details for all
operation and the other lamp for 220V operations. fittings recessed in the walk-on ceiling to enable the
Under mains failure the battery will operate the ceiling to be prepared for their mounting.
luminaries for 3 hours.
3.2 INSTALLATION
2. Incorporate “EXIT” lettering directional arrows as
detailed in the Schedule or as determined on site. A. Verify focusing, orientation and mounting details of all
3. Contains a main failure relay. fittings prior to installing.
4. Be adequate ventilated. B. Labels shall be positioned on fixtures so that they will not
5. Contained sealed nickel cadmium cells with the be visible under normal operating conditions of the
following features: fixtures.
Securely fastened in position with purpose C. Install all recessed or semi-recessed luminaries in a means
made clamps separately housed in a battery enabling adequate cooling.
pack. D. Install lamps in all lighting fixtures.
Located clear in any source. E. Do not install luminaries or transformers in thermal
Positioned to permit removal and insulation.
replacement without removing other F. Allow for repositioning of all production area fittings to
components, and the luminaries mounted in ensure full coordination with process or building services
position. pieces of equipment.
Minimum installed life of five (5) years and a G. Luminaries are not be suspended off sprinkler, water, or
guaranteed life of 3 years when operated in mechanical services. Use steel pipe suspension rods or
accordance with the manufacturer’s electroplated welded link chain as appropriate.
directions in the proposed exit luminaries.
H. Provide unswitched active supply to each emergency D. Driven electrodes, earth pits, connection to building
luminaries, exit signs. structured elements, Copper, strapping etc. as
I. All lighting fixtures shall be free of light leaks, wraps, appropriate to be included.
dents, and other irregularities.
E. Building grounding shall be provided a shown.
3.3 CLEANING AND ADJUSTMENT
Soft Drawn
3.4 EMERGENCY LIGHTING 2.3 BRASS CONNETORS
A. Mains Supply Bolt type, Burndy, T & B or exothermic weld.
Before commissioning, ensure mains supply has been
continuously connected for at least 24 hours. PART 3 EXECUTION
3.11 Grounding conductor for branch circuits are not shown on 3.20 Inspect wiring system junctions for proper grounding.
the drawings, however, grounding conductors shall be Verify connections of grounds either mechanical,
installed with all branch circuit raceways and cables. hydraulic or exothermic. Verify proper connections to all
Grounding conductor shall be as noted otherwise on the components of the grounding system. Note all system
plan. components which are interconnected and the type of
connection.
3.12 Grounding conductors for feeders will be installed. Where
the grounding conductor size in not indicated in the
drawings, the conductor shall be sized in accordance with
the equipment grounding conductor table of the
Philippine Electrical Code. ***END OF SECTION***
3.13 A grounding conductor will be installed in all flexible SECTION 16195 – ELECTRICAL IDENTIFICATION
conduit installations. For branch circuits the grounding
PART 1 GENERAL
shall be sized to match branch circuit conductors.
1.1 DESCRIPTION OF WORK
3.14 The equipment grounding conductor shall be attached to
equipment with a bolt or sheet metal screw used for no A. Provide nameplates on the following types of equipment:
other purpose. Where the grounding conductor is 1. Panelboards
stranded, attachment shall be made utilizing a lug 2. Safety Switches or Circuit Breakers
attachment to the grounding conductor with a crimping 3. Control Panels
tool. 4. Control Devices
5. Cabinets and Pull Boxes
3.15 Ground all motors by drilling and tapping the bottom of
6. Receptacle
the motor junction box and attaching the equipment
7. Switchgear/Switchboard
grounding conductor to the box with a round head bolt
8. Automatic Transfer Switch
used for no other purpose. Conductor attachment shall be
9. Transformer and related Electrical Equipment
through the use of a lug attached to the conductor with
10. Switchgear/Switchboard, Panelboard and related
crimping tool.
equipment directories.
3.16 Equipment grounding conductors shall terminate on the
panelboard or switchboard ground bus only. Provide a B. Provide color coding of branch circuit and feeder
separate termination lug for each conductor originate. Do conductors for phase and voltage identification.
not terminate neutral conductor on the ground bus.
C. Provide wire makers for:
3.17 Effectively earth all metal work in the vicinity of
1. Branch Circuit Identification
switchboard. Do not earth equipment via a neutral bus or
2. Control Wire Identification
the earth connection.
1.3 MANUFACTURER
3.18 Ground Resistance: This Contractor shall furnish
instruments for and measure ground resistance of entire A. Wire Markers: Panduit or approved equal.
main grounding system and each rod. Measured
PART 2 PRODUCTS
resistance of entire system for building and substations
shall not exceed 5 Ohms. 2.1 NAMEPLATES
3.19 Resistance test of each ground rod and of entire system, A. Equipment nameplates shall be engraved laminated
where specified, shall be determined by “fall-of- phenolic, with white surface and black core. Use 3 mm
potential” method using either a ground Ohmer or
thick material for plates of to 50 mm x 100 mm. Larger A. Color coding or wire markers of control wiring for
size, use 4 mm thick material. equipment furnished by owner or other trades shall be
the same as the equipment marking or color coding.
B. Edges of nameplates shall be chamfered 1 mm x 45 mm
approximately. Lettering shall be gothic or normal block
style. Space between lines shall be equal to width of the ***END OF SECTION***
letters. Use 6 mm minimum height letters which occupy
four per 25 mm. Increases size to 20 mm on largest plates.
Lettering shall include name of equipment specific unit
SECTION 16204 – GENERATOR SETS
number and references to ‘on-off’ or other instructions
applicable lettering on receptacle shall indicate branch PART 1 – GENERAL
circuit number and panel identification.
1.1 SCOPE
2.2 WIRE MARKERS A. The stand-by generating set to be furnished under this
Section of the Specification shall be complete with engine
Shall be oil-resistant, adhesive backed vinyl film with drive, generator, exciter, generator switchboard, battery
legends etched into surface, markers shall be brandy B- charger, batteries, day tank and accessories.
700 or approved equal.
B. All labor, tools, testing equipment, instructions, drawing,
PART 3 EXECUTION
and technical information necessary for the installation
3.1 CONDUCTOR COLOR CODE and testing of the complete equipment shall be provided
including maintenance for a period of one (1) year.
A. Branch circuit and feeder conductors shall be color coded
by furnishing conductors with colored insulation or by
wrapping insulation with colored tape where exposed in 1.2 APPLICABLE STANDARDS
junction boxes and cabinets. Color coding shall be as
1.2.1 BS
follows:
1.2.2 DIN
B. 230 Volts, 3 Phase, 3 Wire
1. Phase Conductors - Black (A), Red 1.2.3 IEC
(b), Blue (C) 1.2.4 NEMA
2. Grounding - Green
1.3 RECOMMENDED BRAND
C. 460 volts, 3 phase, 3 wire
1.3.1 Caterpillar
1. Phase Conductors - Brown (A),
Orange (b), Yellow (C) 1.3.2 Cummins
2. Grounding - Green
PART 2 – PRODUCT
D. 230 Volts, 1 Phase, 2 Wire 2.1 CAPACITY
1. Phase Conductors - Black (A), Red
(b), Blue (C) 2.1.1 The Stand-by generating set shall be rated as:
2. Grounding - Green
A. Rating - As specified
3.2 CONDUCTOR LABELING in the plan
B. System Voltage - As specified
A. Except branch circuit conductor shall be labeled with wire in the plan
markers to identify circuit number. C. Winding Pitch - 2/3 Pitch
3.3 NAMEPLATE ATTACHMENT D. Stand-by duty at 0.80 power factor, 3 phase,
3 wire, 60Hz, 1800RPM.
A. Except where adhesive is specified, other nameplates
shall be securely attached using corrosion resistant metal 2.1.2 The ratings of both engine and generator must be
screws. substantiated with manufacturer’s standard published
curves.
3.4 WIRING COLOR CODING FOR AUXILLARY SYSTEMS
2.1.3 Rating must reflect the net power available after 2.3 SHOP DRAWING AND INSTRUCTION MANUAL
deducting all engine or motor driven accessories.
2.3.1 Complete installation drawings and technical catalogs
2.1.4 The stand-by generating set shall have the following shall be submitted for approval before manufacturing,
general features: two (2) copies to the Architect/Engineer and one (1) copy
to the Owner. Record drawings and instruction manual in
A. Designed for emergency power, stationary
triplicate shall be furnished to the Owner on delivery or
services, with an over-all efficiency of at
equipment.
least 90% at full load.
B. Engine rating based upon a plant elevation 2.3.2 Construction shop drawings showing the equipment
of 305 meters above mean sea level, at 30oC layout, foundation plan details, exhaust pipe line, fuel
and 717.5 mmHg. line, switchboard, and accessories shall be submitted for
C. Equipped with solid-state static or brush less approval prior to the construction of basement slab on
rotating exciter. installation.
D. Engine-generator shall be capable of carrying
2.4 ENGINE
variable loads with an average power factor
of 80% of the stand-by rating for continuous 2.4.1 The engine shall be four- (4) cycle, solid injection type of
operations. either vertical in-line or V-type construction and adapted
for burning Diesel Oil #2.
2.4.2 The normal full load speed of the engine shall now exceed
2.2 GENERATOR
1800 RPM. A full hydraulic governor shall regulate the
2.2.1 The generator shall be built-in accordance with NEMA gen-set engine to within ±0.50% of rated speed.
standard for temperature rise with Class F insulation.
2.4.3 Fuel consumption shall not exceed 0.29 liter/KWH at any
2.2.2 The general construction shall be with dynamically load between 50% to 100% of rated load.
balanced rotor, cast iron main frame, ventilating fan.
2.4.4 The engine shall be provided with the following standard
Continuous amortisseur windings and single row bearing.
equipment:
2.2.3 Provide an automatic voltage regulator to maintain a
A. Turbocharger
regulation of 0.50% for steady state and ±2.0% from no-
B. The engine shall be water-cooled with unit
load to full load. Terminal voltage shall be adjustable
mounted radiator complete with fan, core
within ±5% of rated voltage.
guard, fan guard, with flexible pipe
2.2.4 Output voltage complete recovery time after sudden connection at engine and radiator.
application or rejection of rated load shall be within 0.50 C. Dry type exhaust manifold.
seconds. D. Lubricating oil-cooler and filter with
replaceable element.
2.2.5 The generator shall have a transient voltage drop of less
E. Fuel oil filter.
than 15% on sudden application of 100% rated load and
a. Each engine shall have a lube oil cooler
sustained short circuit capacity 400% rated current.
and shall be provided with a full flow
2.2.6 The generator switchboard shall contain the following paper element type oil filter with
equipment: replaceable elements. Provide a by-pass
valve to ensure oil circulation around a
A. The main circuit breaker suitable for the gen- clogged filter element.
set. b. Each engine shall be equipped with an
B. Ammeter and voltmeter with transfer electronic speed and load-sensing
switch. governor.
C. Frequency meter. 1. Type: Electronic Woodward
D. Gauges, alarm and pilot lights for engine 2301A
accessories. 2. Stability: ± ¼% maximum
E. Manual/Automatic solid state battery frequency variation at any
charger, with high-low rate charger, voltage constant load from no load to
regulator, voltmeter and ammeter. full load, without reference to
F. All necessary accessories for the satisfactory the supply authority normal
operation of the generator shall be provided. supply.
3. Regulation: 2% maximum J. Engine Starting System
frequency deviation between a. The engine shall be provided with a 24V
no-load steady state and full DC (or as required) electric starting
load steady state. system.
4. Electric actuator and magnetic b. The starting system shall include a DC
speed sensor. starting motor, starting relay and an
5. Suitable for multiple parallel auto reset breaker to protect against
sets and parallel operation with butt engagement.
the supply authority. c. Starting batteries shall be low
F. Coupling maintenance of the manufacture’s
Directly couple the engine and generator standard offer, mounted in close
shaft using a self-aligning type of coupling, proximity to the starting motor.
capable of transmitting the engine maximum
output torque under operating conditions, K. Air supply/exhaust system shall include
including starting and overload. a. A dry-type air intake filter of sufficient
G. Skid base, lifting brackets spring type capacity to permits 200 hours of
vibration isolators and all accessories continuous operator before filter
necessary for the complete operation of the servicing is necessary.
engine. b. An exhaust system shall connect the
H. Engine Cooling System exhaust outlet of the engine to a
a. The engines shall incorporate a unit silencer. The silencer shall be critical
mounted radiator air with flow through rated.
ventilation from the generator plant c. A flexible stainless steel connection shall
room. be mounted at the engine exhaust
b. Size radiator at 15% greater than the outlet(s). Piping and silencer shall be
engines maximum full load heat lagged throughout its entire length with
rejection to allow for overload not less than 50mm of rock wool or
conditions failures. other approved insulating material, and
c. Ensure the system is suitable for the sheathed overall with a galvanized steel
specified ambient temperature, altitude sheet covering. The type of insulation
and location. and cladding material shall be for
d. The radiator fan shall be the high static approval.
type to allow for connection for
discharge attenuator. The exhaust stack shall extend a
e. Coordinate the required discharge minimum of 1.5m above the roof or 1m
attenuator with the generator radiator clear of the building wall and be
size. complete with all necessary mechanical
supports vibration isolation, roof over-
I. Battery Operating System flashing and rain cap to approval.
A current limiting battery shall be provided
for the generator set to automatically All components of the exhaust system
recharge accessory batteries. Each of the shall be stainless steel.
charges shall have a high rate and low rate
charging feature with automatic changeover The exhaust system shall include
and shall include overload protection, silicon expansion joints and sliding suspension
diode full wave rectifiers, voltage surge bracket to allow for expansion and
suppressors, DC ammeters, DC voltmeter, 24 contraction of the system. Support the
hour automatic equalizer timer, low/high DC system independently of the engines.
voltage alarm relay. AC pilot light and fused L. Vibration Suppression
AC input and DC output. The chargers shall
be capable of recharging discharged Minimize the transmission of vibration and
batteries in twelve (12) hours while carrying noise from rotating or reciprocating
normal load. equipment to other building elements.
a. General: Use inertia bases where
nominated with mass at least that of the
M. Equipment Requiring Vibration Isolation
equipment supported.
Mountings
b. Construction: Steel, or steel-framed
reinforced concrete. Position foundation
Except for external equipment which is not
bolts for equipment before pouring
connected to the structure of any building,
concrete.
support rotating or reciprocating equipment
c. Supports: Support on vibration isolation
on mounting as follows.
mountings using height saving support
a. For static deflection < 15mm: Single or
brackets.
double deflection neoprene in-shear
R. Signs
mountings incorporating steel top and
a. Warning: Provide the following on each
base plates and a tapped hole for
side of each generating set:
botling to equipment.
b. For static deflection > 15mm: Spring
“WARNING: This set may start at any
mountings.
time without notice.”
2.5.2 The alternator shall be rated for maximum temperature 2.7 GENERATOR CONTROL STATION
rise or 130oC over 40oC ambient. Class of insulation shall
be NEMA class F. The station shall contain the auxiliary devices associated
with its engine generator set and shall include the
2.5.3 The alternator shall be equipped with a digital, LCD following:
readout, true RMS sensing volts-per-hertz type voltage
regulator to maintain voltage within limits specified 2.7.1 Engine Starting Control:
below: A. The engine starting control logic shall be
A. Stability: ½ % maximum voltage variation at any microprocessor (PLC) based and shall
constant load from no load to full load. automatically start, protect and monitor
B. Regulation: ½ % maximum voltage deviation between each engine generator set. Electro-
no load steady state and full load steady state. Mechanical controls are unacceptable. The
C. Transient: 22% voltage dip or overshoot on one-step PLC shall be GE series 9030 or equivalent.
application or removal of 0.8 power factor 75% load. The engine starting control shall be capable
D. Transient: 10 seconds maximum voltage recovery of controlling engines furnished with the
time with application or removal of 0.8 power factor following:
75% load. a. Starting motor magnetic switch.
b. Electrically operated fuel control.
c. Normally open protective switches returned to the automatic position, the
that close for abnormal conditions engine shall shut down after the cool
or pressure, temperature, speed down period.
and liquid level when required. e. Test On-Line: When placed in this
position, the engine shall start, run and
B. The engine starting control logic shall connect to the bus as if a start signal
provide electrically isolated contacts for were received.
electronic governor control, electric fuel f. When returned to the “Automatic”
control, and battery charger disconnect position, the circuit breaker shall open
during cranking and common shutdown and the engine shall run for the cool
alarm annunciation. down period and then shut down.
All pilot lights shall be oil-tight LED type. Bushing CT’s HV/LV Relay Class HV =
50:5A
2.9 WARRANTY
LV =
2.9.1 Complete stand-by Generating Set shall have a warranty 5000:5A
for a period of one (1) year by the supplier from the date
smooth surface at the edges. Both sides of each
sheet shall be insulated with a durable; heat
Guaranteed with tolerance according to standards.
resistance baked enamel or vanish. The
Hot dip galvanized radiators. overlapping joint core shall be rigidly clamped
with positive locking devices to insure adequate
Radiators and conservator are detached for transport and mechanical strength to support the winding,
delivered separately packed. prevent shifting of laminations during shipment
and to reduce vibration to minimize noise level
during operation.
Conservator type vacuum proof tank with detachable
2.1.3 Winding
radiators, radiator shut-off valves, loop circuit tap
changer, lifting hooks, jacking lags, pulling eyes, drain
The design construction, and treatment of the
valve with sampling plug, earthing terminals, rating and
winding shall be given properly, consideration to
plate diagrams.
all service factor such as dielectric strength and
mechanical strength of insulation, coil
characteristics, uniform electrostatics, uniform
Surface treatment: painted tank RAL6013 rush green, 180 electrostatic flux distribution, prevention of
um according to standard SFS 5225 corona formation and restriction to free oil
PART 2 – PRODUCTS circulation.
2.1.4 Bushing
2.1 Transformer Construction
The bushing shall conform to the requirements
2.1.1 Tank
of the reference standard. All porcelain used in
Each transformer shall be provided with steel be bushing shall be wet process, homogeneous, and
provided with steel case of substantial free from cavities and other flaws. The glazing
construction, which shall be oil tight. The tank shall be uniform and color and free from blisters,
shall be an effective cooling and Ventilation burns or other defects. The color of all porcelain
construction to release internal heat produced insulators shall be chocolate brown and all
during service. Each of the four sides shall be porcelain parts be one piece.
produced from a single sheet of metal which is
fabricated of a rigid bottom with an oil drainage
outlet, corrugated side walls with a thickness 2.1.5 Transformer Oil
greater than 1.2mm. That tank shall be capable
of withstanding, without leakage or permanent The transformer oil shall be well filtered. The
deformation, the oil pressure at a maximum over dielectric strength shall not less than 69KV.
pressure of 1.0kg/cm2 and a vacuum of 755mm. Before filling in the transformer tank shall, as
Hg and have sufficient strength to withstand tested by ADTM D 877 or equal. The dielectric
internal and external faults. The tank cover shall strength of the sample on insulation oil taken
be provided with sufficient slope on all sides so from the new transformer shall not less than
as to avoid collection of rainwater or other 69KV, when measured in accordance with ANSI
moisture. Standard method of testing electrical insulation
oil C59.12-1966 or equivalent.
2.1.2 Core
PART 3 – EXECUTION
The core shall be constructed entirely of high
quality, cold rolled grain oriented, non-aging; 3.1 INSTALLATION
high permeability silicon steel and designed to
accessible 100% rated voltage without making ANSI C2, NFPA 70, and the requirements
any damage to the transformer core. The steel specified herein.
shall be in thin amination thus allowing a good 3.2 FIELD TEST AND INSPECTION
lamination factor, annealed after cutting by
highly precise machines and rolled to insure
3.2.1 Acceptance Checks, Settings, and Tests: Perform i. Check all low voltage circuit breakers in
in accordance with the manufacturer’s accordance with manufacturer’s instruction.
recommendation and the latest IEEE standards. Set all trip devices in accordance with
Perform work in a careful and safe manner so as government provided settings and check
not to endanger personnel or equipment. time-current characteristics with a test kit,
Perform tests in such a way as to obtain which has been approved by the breaker
information about the performance of the manufacturer.
breaker, relay, meters, wiring, and instrument
transformers together as a unit, as well as j. Verify minimum resistance to ground of all
separately. Testing and calibration of power grounding systems.
relays shall be performed by a certified relay
technician. k. Transformer Test: Test transformer
secondary voltages and adjust the voltage at
3.2.2 Acceptance Checks and Tests: Shall include, but
the transformer to provide the required
not be limited to the following:
secondary voltage.
a. Compare actual connection with wiring
diagrams. If differences are found,
3.3 FIELD TEST
determined if error is in diagram or in actual
wiring and correct as necessary. 3.3.1 After installation, before energized, the
transformer shall be tested as follows:
b. Inspect all devices, equipment, etc. for
a. Visual and dimension check
damage or maladjustment caused by
b. Measurement of insulation
shipment or installation.
resistance
c. Measurement of voltage ratio
c. Assure that tightness of bolted bus joints are
d. Check of vector group symbol
in accordance with manufacturer’s
e. Check of insulation oil
recommendations (use calibrated torque
f. Functional test for protective
wrench).
devices
d. Perform all mechanical operators and The instrument for above tests and the
contact alignment tests on breakers and cost of test and report shall be provided
operating mechanism in accordance with and borned by the supplier.
manufacturer’s recommendations. Make
adjustment as necessary. ***END OF SECTION***
2.1 Switchboard shall be floor standing, with components 3.1 Contractor shall install and connect switchboard at the
removable from front and shall be NEMA Class 1 (IP20), location as shown on the approved drawings. Provide
unless otherwise shown. necessary supports, framework, etc. as required for
proper rigid installation.
2.2 Screwed-on front covers shall be fabricated from code
gauge sheet, and shall be sectionalized to permit removal
of section during construction and for maintenance. Top
***END OF SECTION***
and side enclosing sheet plates shall be removable.
Assembly shall be provided with proper ventilation.
2.3 Main buses shall be Copper and braced for short circuit SECTION 16470 – PANELBOARDS
stresses. Buses shall be sufficient size to limit temperature
rise to 55oC above ambient. Adjacent vertical sections PART 1 GENERAL
shall be connected with horizontal bus.
1.1 SECTION INCLUDES
2.4 All bus bars shall be electrical grade Copper. Sizing shall be
A. Distribution panelboards.
based on the highest ampere frame rating (1.55 amperes
B. Branch circuit panelboards.
pes sq. mm). All joints and contract surfaces shall be
C. Load centers.
silver-plated.
D. Meter centers.
2.5 Steel housing parts, inside and out, shall be given rust
1.2 RELATED SECTIONS
inhibiting phosphatizing treatment and finished in blue-
gray powder coated enamel. A. Section 16170 – Grounding and Bonding.
B. Section 16195 – Electrical Identification.
2.6 Circuit breaker units shall be insulated case with stored
energy quick-make, quick-break operating mechanism. 1.3 REFERENCES
The breaker shall be provided with electronic trip units,
with long, short, and instantaneous trips. A. NECA Standards of Installation (published by the NECA).
B. NEMA AB1 – Molded Case Circuit Breakers.
2.7 Each circuit breaker shall be mounted in sheet steel C. NEMA ICS 2 – Industrial Control Devices, Controllers, and
enclosure with external operating handle that can be Assemblies.
locked in open or closed position. Circuit breaker should D. NEMA KS1 – Enclosed and Miscellaneous Distribution
be square be Square ‘D’ brand. Equipment Switches (600 Volts Maximum).
E. NEMA PB 1 – Panelboards.
2.8 Switchboard shall be for service indicated above with
F. NEMA PB 1.1 – Instructions for Safe Installation,
main bus and grounding bus. Bus ratings shall be as
Operation and Maintenance of Panelboards Rated 600
shown on drawings.
Volts or Less.
2.9 Metering Components (Main Bus) G. NETA ATS – Acceptance Testing Specifications for
Electrical Power Distribution
1. Voltmeter and 3-phase selector switch with off H. NFPA 70 – National Electrical Code.
position. I. PEC – Philippine Electrical Code.
2. Ammeter and 3-phase selector switch with off 1.4 SUBMITTALS FOR REVIEW
position.
A. Shop Drawings: Indicate outline and support point
3. Current Transformer, suitable ratio. dimensions, voltage, main bus ampacity, integrated short
circuit ampere rating, circuit breaker and fusible switch
4. Potential transformer, suitable ratio.
arrangement and sizes.
5. Demand Meter
1.5 SUBMITTALS FOR INFORMATION
2.10 Terminal Lugs
A. Submit manufacturer’s installations. Indicate application
conditions and limitation of use stipulated by Product
testing agency specified under Regulatory Requirements. H. Circuit Breaker Accessories: Trip units and auxiliary
Include instructions for storage, handling, protection, switches as indicated.
examination, preparation, and installation of Product. I. Enclosure: As indicated, size as required.
J. Cabinet Front: Surface type, fastened with concealed trim
1.6 SUBMITTALS FOR CLOSEOUT
clamp or screws, concealed hinged door with flush lock,
A. Record actual locations of panelboards and record actual metal directory frame, finished in manufacturer’s
circuiting arrangements in project documents. standards gray enamel, powder coated.
B. Maintenance Data: Include spare parts listing; source and
2.2 BRANCH CIRCUIT PANELBOARDS
current prices of replacement parts and supplies; and
recommended maintenance procedures and intervals. A. Manufacturers:
1. Square – D or approved equal.
1.7 QUALIFICATIONS
B. Description: NEMA PB1, circuit breaker type, lighting and
appliance branch circuit panelboard.
A. Manufacturer: Company specializing in manufacturing the
Products specified in this section woth minimum three (3) C. Panelboard Bus: Copper, ratings as indicated. Provide
years documented experience. Copper ground bus in each panelboard; provide insulated
ground bus where scheduled.
1.8 REGULATORY REQUIREMENTS
A. Conform to requirements of NFPA 70 or PEC. D. Minimum Integrated Short Circuit Rating: 10,000 amperes
B. Products: Listed and classified by Underwriters RMS symmetrical for 240 volt panelboards; or as indicated
Laboratories, Inc. or testing firm acceptable to the in the plans.
authority having jurisdiction as suitable for the purpose
specified and indicated. E. Molded Case Circuit Breakers: NEMA AB 1, bolt-on type
thermal magnetic trip circuit breakers, with common trip
1.9 MAINTENANCE MATERIALS handle for all poles, listed as Type SWD fir lighting circuits,
A. Furnish two (2) of each panelboard key. Type HACR for air conditioning equipment circuits, Class A
ground fault interrupter circuit breakers where scheduled.
PART 2 PRODUCT Do not use tandem circuit breakers.
2.1 DISTRIBUTION PANELBOARDS
F. Enclosure: NEMA PB 1, Type 1/Type 3R.
A. Manufacturers:
1. Square – D or approved equal. G. Cabinet Box: As required.
B. Description: NEMA PB 1, circuit breaker type.
C. Service Conditions: H. Cabinet Front: Flush / Surface cabinet front with
1. Temperature concealed trim clamps, concealed hinge, metal directory
2. Altitude frame, and flush lock all keyed alike. Finish in
D. Panelboard Bus: Copper, rating as indicated. Provide manufacturer’s standard gray enamel, powder coated.
Copper ground bus in each panelboard.
E. Minimum integrated short circuit rating: As indicated.
PART 3 EXECUTION
F. Molded Case Circuit Breakers: NEMA AB 1, circuit
breakers with integral thermal and instantaneous 3.1 INSTALLATION
magnetic trip in each pole. Provide circuit breakers UL
listed as Type HACR for air conditioning equipment branch A. Install panelboards in accordance with NEMA PB 1.1 and
circuits. the NECA “Standard of Installation.”
G. Controllers: NEMA ICS 2, AC general-purposes Class A
magnetic controller for induction motor rated in B. Height: 6 feet (1800 mm) to top of panelboard; install
horsepower, with bimetal overload relay. Coil operating panelboards taller than 6 feet (1800 mm) with bottom no
voltage: 120 volts, 60 Hertz. Size as shown on Drawings. more than 4 inches (100 mm) above floor.
Provide unit mounted control power transformer and
HAND-OFF-AUTO selector switch or STOP-START C. Provide filler plates for unused spaces in panelboards.
pushbutton station and RED, GREEN indicating light in
front cover.
D. Provide typed or neatly handwritten circuit directory for 1. All substitute equipment proposed as equal to the
each branch circuit panelboard. Revise directory to reflect equipment specified herein, shall meet or exceed the
circuiting changes required to balance phase loads. following standards.
2. For equipment other than that specified, the
E. Provide engraved plastic nameplates under the provisions contactor shall supply proof that such substitute
of Section 16195. equipment does in fact equal or exceed the features,
functions, performance, and quality of the specified
F. Provide spare conduits out of each recessed panelboard equipment.
to an accessible location above ceiling/below floor. 3. Two copies of all submittals shall be submitted to the
Minimum spare conduits: As indicated identify each as Architect/Engineer for review.
SPARE. 4. The contractor shall submit at least three (3) installed
and fully functional project references. The reference
G. Ground and bond panelboard enclosure according to projects shall be using similar brand and system
Section 16170. configuration proposed for this project.
B. Shop Drawings:
3.2 FIELD QUALITY CONTROL
1. Sufficient information, clearly presented, shall be
A. Field inspection, testing, and adjusting shall be performed. included to determine compliance with drawings and
specifications.
B. Inspect and test accordance with NETA ATS, except 2. Include manufacturer’s name(s), model numbers,
Section 4. ratings, power requirements, equipment layout,
device arrangement, complete wiring point-to-point
C. Perform inspections and test listed in NETA ATS, Section diagrams, and conduit layouts.
7.4 for switches, Section 7.5 for circuit breakers. 3. Show panel module layout, configurations, and
terminations.
3.3 ADJUSTING C. Manuals:
1. Submit simultaneously with the shop drawings,
A. Adjust installed work.
complete operating and maintenance manuals listing
the manufacturer’s name(s) including technical data
B. Measure steady state load current at each panelboard
sheets.
feeder; rearrange circuits in the panelboard to balance
2. Wiring diagrams shall indicate internal wiring for each
the phase loads to within 20 percent of each other.
item of equipment and the interconnections between
Maintain proper phasing for multi-wire branch circuits.
the items of equipment.
3. Provide a clear and concise description of operation
that gives the information required to properly
operate the equipment and system.
***END OF SECTION*** 4. Approvals will be based on complete submissions of
SECTION 16770 – BACKGROUND MUSIC (SPEAKER) SYSTEM manuals together with shop drawings.
D. Modifications:
PART 1 GENERAL 1. Provide the services of a factory trained and
authorized technician to perform all system
1.1 SCOPE
modifications, upgrades or changes. Response time of
A. New background music (speaker) system shall be installed the technician to the site shall not exceed forty-eight
in accordance with the specifications and drawings. (48) hours except during legal holidays, calamity and
war.
1. Speaker circuits shall be capable of one speaker 2. Provide all hardware, software, programming tools
circuit per zone or floor or as shown on the plans. and documentation necessary to modify the system
2. Speaker circuits and control equipment shall be on site.
arranged such that loss of any one (1) speaker circuit 3. Modification includes addition and deletion of
will cause will not loss of any other speaker circuit in devices and changes to system operation and custom
the system. label changes for devices.
E. Certifications:
1.2 SUBMITTALS 1. Together with the shop drawing submittal, submit a
A. General: certification from the major equipment manufacturer
indicating that the proposed supervisor of installation 1. Conduit shall be in accordance with the Philippine
and the proposed performer of contract maintenance Electrical Code (PEC), local and national
is an authorized representative of the major requirements.
equipment manufacturer and trained on network 2. Where possible, all wiring shall be installed in conduit
applications. or raceway. Conduit fill shall not exceed 40 percent of
2. Include names and addresses in the certification. interior cross sectional area where three or more
3. The contractor shall also submit photocopies of the cables are contained within a single conduit.
licenses of the Electronics and Communications 3. Cable must be separated from any open conductors
Engineer(s) that will be involved in the said project. of power, or Class 1 circuits, and shall not be placed
in any conduit, junction box or raceway containing
1.4 GUARANTY:
these conductors, per NEC Article 760-29 or
A. All work performed and all materials and equipment equivalent PEC article.
furnished under this contract shall be free from defects 4. Wiring for low voltage audio, control and alarm input
and shall remain so for a period of at least (1) year from communication and similar power-limited auxiliary
the date of acceptance. functions might be run in the same conduit as
B. The full cost of maintenance, labor and materials required speaker line circuits.
to correct and defect during this one-year period shall be 5. Conduit shall net enter any BGM. Or any other
included in the submittal bid. remotely mounted control panel equipment or
backbones, except where conduit entry is specified by
1.5 APPLICABLE PUBLICATIONS: the BGM manufacturer.
6. Minimum conduit size shall be ½ inch (15mm).
A. The publications listed below from a part of this
7. The contractor shall submit cut samples or sample
specification. The publications are referenced in text by
board for approval.
the basic designation only.
1. Acoustic and sound system publications.
B. Wire:
1.6 APPROVALS:
1. All BGM system wiring must be new, unless specified
A. The system must have proper listing and/or approval herein.
from the following mationally recognized agencies. 2. Wiring shall be in accordance with local and national
codes (e.g., NEC Article 760 or PEC equivalent) and as
UL Underwriters Laboratories Inc recommended by the manufacturer of the BGM
JIS Japanese Industry Standards system.
PS Philippines Standards 3. Number and size of conductors shall be as
recommended by the manufacturer of the BGM
system manufacturer, but not less than 1.25 mm.
PART 2 – PRODUCTS (#16 AWG) twisted TF for speaker circuits, control
circuits and 0.9 mm. (#18 AWG) shielded cable for
2.1 EQUIPMENT AND MATERIAL. GENERAL:
low level audio signals.
A. All equipment and components shall be new, and the 4. All wire and cable shall be listed and/or approved by
manufacturer’s current model. a recognized testing agency for use with a signaling
B. Consult the manufacturer’s installation manuals for all system.
wiring diagrams. Schematic, physical equipment sizes, etc. 5. Wiring used for the audio/control circuit and
before beginning system installation. communication shall be shielded cable and installed
C. Refer to the riser/connection diagram for all specific in conduit unless specifically accepted by the BGM
system installation/termination/wiring data. equipment manufacturer.
D. All equipment shall be attached to walls and ceiling/floor 6. Wiring for audio/control circuit shall support a
assemblies and shall be held firmly in place. (e.g., devices minimum wiring distance of 500 feet 0r 150 meters.
shall not be adequate to support the required load. 7. All speaker circuit shall use twisted pair 16 AWG (1.25
mm.) minimum.
2.2 CONDUIT AND WIRE: 8. Wires and cables shall be West Penn Wires, Nishi
A. Conduit: Nippon or approved equal.
9. The contractor shall submit cut samples or sample
board for approval.
C. Terminal Boxes, Junction Boxes, and Cabinets:
***END OF SECTION***
1. All boxes and cabinets shall be UL listed for their
intended purpose.
D. Speaker circuit shall be arranged to serve like categories. SECTION 16741 – TELEPHONE SERVICE, PATHWAYS AND WIRING
Mixed category circuitry shall not be permitted except as
PART 1 GENERAL
noted by the BGM manufacturer.
A. Installation shall be in accordance with the PEC, local and 1.2 RELATED SECTIONS
national codes, as shown on the drawings and as
A. Section 16112 – Surface Raceways.
recommended by the major equipment manufacturer.
B. All conduit, junction boxes, conduit supports and hangers 1.3 REFERENCES
shall be concealed in finished areas and may be exposed
in unfinished areas. A. EIA/TIA-568 – Commercial Building Wiring Standard.
C. If construction in ongoing during this period, measures B. EIA/TIA-569 – Commercial Building Standard for
shall be taken to protect the cameras from contamination Telecommunication Pathways and Spaces.
and physics damage. C. NFPA 70 – National Electrical Code.
A. The service of a competent, factory-trained engineer to A. Telephone Service Entrance Pathway: PVC conduit from
technician authorized by the manufacturer and/or point of telephone utility connection at property line to
distributor of the system shall be provided to technically building service termination cabinet.
supervise and participate during all of the adjustment and B. Backbone Pathway: Conform to EIA/TIA 569 using conduit
test for the system. and sleeve as indicated.
1. Before energizing the cables and wires, check for C. Horizontal Pathway: Conform to EIA/TIA 569, using
correct connections and test for short circuits, ground raceway, backboards, and cabinets as indicated.
faults, continuity, and insulation. D. Premises Wiring: By Owner. Completer from telephone
2. Check installation, supervision, and operation of all equipment to each outlet, using wire and cable as
devices. specified.
3. All conditions that the system could encounter should 1.5 PROJECT RECORD DOCUMENTS
be introduced on the system.
4. Verify the proper receipt and the proper processing A. Record actual locations and sizes of pathways and outlets.
of the signal at the BGM and the correct activation of
1.6 QUALITY ASSURANCE
the control points.
5. When the system is equipped with optional features, A. Telephone Utility:
the manufacturer’s manual should be consulted to B. Perform work in accordance with telephone utility’s rules
determine the proper testing produces. and regulations.
6. This is intended to address or grouped devices,
sensitivity monitoring, verification functionality and 1.7 ACCEPTABLE MANUFACTURER
similar. A. Lucent technologies
3.4 FINAL INSPECTION: B. Krone
C. Or approved equal
A. At the final inspection, the factory-trained engineer or
technician authorized by the manufacturer and/or 1.8 QUALIFICATIONS
distributor of the system shall demonstrate that the
system functions properly respect.
A. Installer: Company specializing in installing telephone A. A 110 cross connect shall be provided at each backboards
premises wiring with minimum three years documented for every 25-pair or part thereof, cable serving the
experience. telephone distribution backboards. Individual cross
connects shall have D-rings mounted above for proper
1.9 REGULATORY REQUIREMENTS
routing of cables.
A. Conform to requirements of NFPA 70. B. D-rings shall be provide from the feeder and station cable
B. Furnish Products listed and classified by Underwriter’s conduits to be the backboards cross connects on each
Laboratories, Inc., as suitable for purpose specified and floor.
indicated. C. Provide a minimum of at least 25% spare termination
capacity.
1.10 MAINTENANCE SERVICE
2.5 PATCH/JUMPER CORDS
A. Furnish service and maintenance of premises wiring for
one year from Date of Substantial Completion. A. Category 5 – Six pin modular plug to eight pin modular
plug on each end. Provide 2 Pair connectors also. Patch
cord shall be pre-assembled and factory tested with
category 5 cable, snag less modular plugs.
PART 2 PRODUCTS
2.6 TELEPHONE OUTLET
B. Instruction of Personnel
B. Test Instruments
1. The Sub-Contractor shall provide an operator skilled
1. All instruments and appliance required for testing
in all aspects of the operation and Telephone
shall be furnished by the Sub-Contractor for the
Installation to thoroughly instruct the building
duration of the tests. Other instruments specified as a
Maintenance Staff in the operation, maintenance
permanent part of the installation may be used for
Staff in the operation, maintenance and
testing purposes. Test instruments shall be tested for
troubleshooting techniques associated with the
accuracy by an approved laboratory and recent test
installation. Alternatively, the Sub-Contractor may
certificates shall be made available to the Owner
provide more than one operator, each skilled in a
prior to site testing.
particular aspect of the installation.
2. The operator or (operators) shall be required to be
C. Test Reports Forms.
available on site for a total of forty (40) man hours
1. The results of all testing and balancing as required
per week not necessarily during normal working
under this section of the Specification shall be
hours, for a period of two (2) weeks from the date of
submitted to the Owner in a net and legible manner.
handover of the installation. Reimbursement rates for
2. Typical test report forms will be made availability by
properly authorized hours in excess of this figure will
the Owner indicating the format in which tests results
be subject to agreement with the Employer.
should be submitted should this be necessary. The
3. The operator shall also carry out any testing,
Sub-Contractor shall be submitted should this be
adjustment or recording of pressure voltage or like
necessary. The Sub-Contractor shall also forward
data as requested by the Architect during the two
manufacturer’s performance curves or data for all
week period.
items of equipment.
4. All instruments and appliances and required for
testing or recording of data shall be furnished by the
D. Testing and Commissioning
Sub-Contractor for the duration of the tests. The
1. On completion of the hydrostatic pressure test, the
results of all testing and recording of data shall be
Sub-Contractor shall notify the Owner and proceed to
submitted to the Owner in a neat and legible manner.
operate, test and adjust the equipment. All
components shall be systematically tested for correct
C. Operational Maintenance
operation to ensure an approved installation.
1. The Sub-Contractor shall allow for and carry out
2. When the Sub-Contractor is satisfied the installation
comprehensive maintenance and service of all
is complete, fully operational and meeting the
equipment and machinery installed under this Sub-
requirements of the code, he shall notify the Owner
Contract during the Defects Liability Period.
in writing and an appointment made to inspect the
2. The cost of maintenance of the installation shall be
installation to ensure all works and tests have been
stated as a separate sum as required in the tender
satisfactory completed. The Sub-Contractor shall
form. This cost shall be inclusive of all spare parts and
allow for attendance during inspection with necessary
other items necessary.
equipment and skilled labor to test the equipment in
3. The maintenance period shall commence from the
the presence of the Owner.
date of issue of a certificate of Practical Completion
of the installation and shall include, but not be limited
to the requirements set out in this section.
4. Maintenance of services and equipment shall be recommendation for each item and
carried out during visits to the site at regular monthly equipment.
intervals. vii. Removable Control Panel Wiring diagrams
5. Prior to Practical Completion, the Sub-Contractor held in rigid plastic folders with folders
shall prepare a detailed operation service and securely fixed in the Manuals.
maintenance schedule setting out the extent of and viii. All descriptions on drawings and description
frequency of service to each item of equipment and shall be in the English Language with test
machinery. expressed in clear consistent, readily
6. The Sub-Contractor shall submit the draft schedule to understandable terms.
the Owner for approval. The approved schedule shall
be used as the basis for all maintenance and service E. Service Contract
inspections. 1. At the conclusion of the contract maintenance period
7. At the completion of each inspection, the service the Owner shall have the option to enter into an
schedule and complete service report shall be annual maintenance contract for servicing and the
endorsed by the building Supervising Engineer within Sub-Contractor shall set out the price for this work on
seven (7) days. the “FORM OF OFFER”. This service contract shall
8. Regular service shall include the inspection of all exclude the cost of spare parts etc. which shall be
items and equipment including both fixed and moving charged at ruling prices.
parts, contacting parts, contacting surfaces and
securing mediums. F. Training – 40 man hours.
D. Maintenance Manual
1. On completion of the work and prior to making ***END OF SECTION***
application for Practical Completion, the Sub-
Contractor shall supply to the Owner three (3)
bounds copies of Operating and Maintenance
SECTION 16467 – ENCLOSED CIRCUIT BREAKERS
Instruction Manuals covering all plant installed under
or associated under or associated with this PART 1 GENERAL
specification.
2. The Manuals shall be complied with section tabs and 1.1 SECTION INCLUDES
section indexes and shall be bound using rigid plastic- A. Molded case enclosed circuit breakers.
coated covers held together using screws or equal
approved method. 1.2 RELATED SECTIONS
3. The Manuals shall clearly indicate in correct
A. Section 16195 – Electrical Identification: Engraved
sequence, the operation and function of all plant and
nameplates.
equipment under both automatic and manual control
and shall include complete information in 1.3 REFERENCES
maintenance required for each item of equipment.
4. The information shall be supplemented by all A. NECA Standard of Installation (National Electrical
necessary plan layout drawings of reasonable scale, Contractors Association).
diagrammatic layout and circuit wiring diagrams. B. NEMA AB 1 – Molded Case Circuit Breakers.
5. The Manuals shall include in particular, the following C. NFPA 70 – National Electrical Code.
information. D. PEC – Philippine Electrical Code.
i. General System Description 1.4 SUBMITTALS FOR REVIEW
ii. System Technical Description and Schematic
iii. System Software Description A. Product Data: Provide catalog sheets showing rating, trip
iv. Maintenance and Operation Instructions units, time current curves, dimensions, and enclosure
v. Operating instructions for the operator’s details.
positions and telephone stations.
1.5 SUBMITTALS FOR INFORMATION
vi. A schedule of maintenance programmed in a
logical format indicating weekly, monthly, A. Manufacturer’s Instructions: Indicate application
quarterly, half-yearly, and yearly conditions and limitations of use stipulated by Products
maintenance requirements and/or testing agency specified under Regulatory Requirements.
Include instructions for storage, handling, protection, C. Finish using manufacturer’s standard enamel finish gray
examination, preparation, and installation of Product. color.
PART 2 PRODUCTS
2.1 MANUFACTURERS
***END OF SECTION***
A. Square – D or approved equal.
A. Enclosure: NEMA AB 1, Type as required. 1.5 The manufacturer must furnish proof that the penetration
B. Fabricated enclosure from steel, seal was tested with at least 3 cable trays penetrating
with trays being at least 40% by volume filled with cables.
1.6 Where Copper cable trays are penetrating the opening, PART 1 – GENERAL
the penetration seal must have been tested with an
1.01 SCOPE
Copper tray.
This section covers the requirements for supply, delivery
2.0 REQUIREMENTS
and installation of fire alarm and detection system,
2.1 The penetration seal must be unaffected by direct water complete and ready to use.
exposure, moisture or prolonged exposure to humidity.
1.02 REFERENCE STANDARDS
2.2 Where a wet coating material, a putty or mastic are being
A. National Fire Protection Association (NFPA) Publications:
used for the installation of the penetration seal, said
B. Factory Mutual System (FM) Publication:
materials must not contain components or substances
C. Underwriter’s Laboratories, Inc. (UL) Publication:
which are hazardous to human health, i.e. toxic,
carcinogenic or skin irritating. 1.03 GENERAL REQUIREMENTS:
2.3 The penetration seal must be unaffected and not lose its Materials and installation shall conform to Section 16001
protective effectiveness by aging. “GENERAL PROVISIONS”, Section 16050 “BASIC
MATERIALS AND METHOD FOR ELECTRICAL WORKS”, and
2.4 The ease of retrofitting, such as the addition of cables or
Section 16123. “WIRES AND CABLE FOR 0-600V CIRCUIT”,
other utilities is a mandatory requirements. Wherever
with the additions and modifications specified herein. The
retrofitting is expected to be frequent, a “fire pillow” type
work including to the installation of a complete and
is preferable.
usable standard system conforming to the applicable
2.5 Where a pillow type of fire seal is required or specified, requirements of NFPA 72A, 72D, and 72E, except as
the fire pillows must be meet the following requirements. modified herein. Materials and equipment to be furnished
under this contract shall be essentially the current design
a. A fire pillow type seal must meet the same fire protection
products on one manufacturer regularly engaged in the
requirements as listed above under “Requirements for
production of such equipment and shall be listed by the
Penetration Seals” as per PEC, NEC, NFPA requirements.
Underwriter’s Laboratories, Inc. (UL) or approved by
b. A fire pillow type seal must have been tested in an
Associated Factory Mutual Laboratories (FM).
opening no less than 800 x 800 mm, unsupported by cable
trays utilities, withstanding the horse stream test as per 1.04 QUALIFICATION OF INTALLER
UL 1479 or ASTM E-814.
Prior to installation, the Contractor shall submit data for
c. A single fire pillow, when held over as open flame (Bunsen
the approval of the Project Manager which will show that
burner) for 5 minutes with the tip of the flame impinging
he has successfully installed fire alarm system of the same
on the bottom of the pillow, must not allow the filling
type and design as specified herein, or that he has a firm
material to run out.
contractual agreement with a subcontractor having such
d. Since it is expected that fire pillows, over prolonged
required experience. The data shall include the names and
periods of time and possibly aided by vibration, will
locations of at least two installation where the Contractor
“settle”, i.e. compact, whereby in wall penetrations
shall indicate the type and design of these systems and
openings on the top side could develop, the fire pillows
certify that these systems have performed satisfactorily in
should counteract this by expanding during heat
the manner intended for a period of not less than 18
exposure.
months.
e. Where required, the pillow – type penetration seal should
be protected against theft or damaged by a metal screen A. Manufacturer’s Representative: The service of a
with gauge of no less than 4mm. qualified manufacturer’s representative or technician,
experienced in the installation and operation of the
type of system being provided shall be furnished to
supervise the testing, including final testing,
adjustment of the system and instruction to Owner.
***END OF SECTION***
1.05 SUBMITTAL
PART 3 – EXECUTION
***END OF SECTION***
3.01 TESTS DURING INSTALLATION: