1336frest 5.14

This document provides installation instructions for connecting a Dynamic Brake or Chopper to G or H Frame Drives, including programming information and typical schematics. It includes details on frame ratings, connection point locations, control power schemes, and parameter programming. Safety precautions are emphasized, particularly regarding power disconnection and DC bus discharge before installation.

Uploaded by

Edgar Bonetto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
29 views8 pages

1336frest 5.14

This document provides installation instructions for connecting a Dynamic Brake or Chopper to G or H Frame Drives, including programming information and typical schematics. It includes details on frame ratings, connection point locations, control power schemes, and parameter programming. Safety precautions are emphasized, particularly regarding power disconnection and DC bus discharge before installation.

Uploaded by

Edgar Bonetto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Installation Instructions

Dynamic Brake or Chopper Connection


(1336 PLUS, PLUS II, FORCE, IMPACT G & H Frame Drives)

This publication will provide connection and drive programming


information for a Dynamic Brake or Chopper connection to a G or H Frame
Drive. Refer to Frame Ratings to match your drive nameplate data with a
frame letter.

Contents Typical Power Schematic Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Inductor/Connection Point Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Typical Control Power Scheme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Typical Control Logic Scheme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Typical Parameter Programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Frame Ratings Table A Three-Phase Drive Rating(1)


Frame Reference 380 – 480V 500 – 600V
G 187 – 448 kW 224 – 448 kW
250 – 600 HP 300 – 600 HP
Frame Reference 380 – 480V 575 – 600V
H 293 – 384 kW 489 – 590 kW
700 – 800 HP 700 – 800 HP

(1) kW and HP are constant torque (CT) ratings.


2 Dynamic Brake or Chopper Connection

Typical Power Schematic Figure 1


TO
Diagram 3-1

MCP1
L1 1071

L2 1081

L3 1091

LINE
PE

TE PE F1 F2 F3
BUS BUS
CHASSIS

TE PE R S T

TERMINAL BLOCK TB1

TERMINAL BLOCK TB2


(INTERFACE CONTROL BOARD) See Figures 2
through 5 for
TERMINAL BLOCK TB3
details about
(INTERFACE BOARD) making these
connections
AC DRIVE
inside the drive.

OPTION PORTS
ADAPTER ADAPTER
TERMINAL BLOCK TB1
1 2
+DC -DC PE U V W

HUMAN INTERFACE E9 E10


BRAKE CHOPPER MODULE
MODULE
ESC SEL TB1
1 2 3 4 5 6 E12 E11
JOG R

(T2)
(T1) (T3)
(G) AC
MOTOR

ab1002a
Dynamic Brake or Chopper Connection 3

Inductor/Connection Point During power up, there can be a racing condition between the time the drive
Locations control board comes alive and verifies all input status and the time the
Chopper control board comes alive and closes its AUX contact. To correct
this condition, Rockwell recommends connecting a programmable CR4 NC
contact at TB2-16 and TB2-17 across the Brake Chopper AUX Contact to
shunt the contact until the BUS is fully charged and the logic inputs are
satisfied. See Table B for recommended programming to provide enough
time for the Chopper AUX contact to close, thus preventing AUX fault in
the drive at power up.

ATTENTION: To avoid a shock hazard, assure that all


! power to the drive has been removed before proceeding. In
addition, verify that the DC bus has discharged by
measuring across the “+DC” and “–DC” terminals of TB1
with a voltmeter. The voltage should be 0.0VDC.

Important: Two different inductors were used — use appropriate drawing


for inductor style in drive to have DB added.
Figure 2
G Frame Drives

The inductor terminals to connect DC


braking or DC Chopper braking onto the
DC Bus are located in this area. Refer to
additional details on following pages.

ab1003a
4 Dynamic Brake or Chopper Connection

Figure 3
H Frame Drives

The inductor terminals to connect DC


braking or DC Chopper braking onto the
DC Bus are located in this area. Refer to
additional details on following pages.

ab1081
Dynamic Brake or Chopper Connection 5

Figure 4 DC Bus Inductor Style A Connection Points for Dynamic Brakes


(G Frame Drive shown, H Frame Drive similar)
To (–) DC To (+) DC
Brake/Chopper Brake/Chopper
Terminals Terminals
Wires Are Not Part Of Drive.
These Wires Added By Customer
When DB Is Used. Shown Here
For Added Clarity. (Stud Is M10 Thread)
Upper Inductor
Stud is (+) DC Bus
(M10 Thread)

Lower Inductor Stud


is (–) DC Bus ab1001a
(M10 Thread)

Figure 5 DC Bus Inductor Style B Connection Points for Dynamic Brakes


(G Frame Drive shown, H Frame Drive similar)
Upper Inductor Stud
is (+) DC Bus
Lower Inductor Stud (M10 Thread)
is (–) DC Bus To (+) DC
(M10 Thread) Brake/Chopper
Terminals

To (–) DC
Brake/Chopper
Terminals

Wires Are Not Part Of Drive.


These Wires Added By Customer
When DB Is Used. Shown Here
For Added Clarity. (Stud Is M10 Thread) ab1000a
6 Dynamic Brake or Chopper Connection

Typical Control Power


Scheme
From
1-5
PT1 1071 1091
1100 VA L1 L2
F4 F5
KLDR-6 460V KLDR-6
600V (H3) (H2) 600V
(H1) (H4)
W1
3062 F6
3061 X1 X2
(X1) 115V (X2) (21-24)
(2) (1) FNM-9 ENCL FAN1
250V
3065
ENCL FAN2

PE

(3)

(4)

3061 3065
To To
2-18 2-18
Dynamic Brake or Chopper Connection 7

Typical Control Logic


Scheme

TB2 FROM
CONTROL BOARD
1 2021 2-39
POT HIGH 10
CR1
(9) 3065
2 POT LOW 2031
COMMON 11
(10)
3 2041
CR2 12
POT/SIGNAL COMMON (11)

4
TERMINAL BLOCK TB2 2061
CR3 13
5 0-10V INPUT (12)
2081 2071
COMMON 14
(35) 2091 (13)
6 4-20mA INPUT 2082
(36) CR3 15
SHD (14)
(37)
7 PULSE INPUT (–)

2111
CR4 16
8 PULSE INPUT (+) (15)
2081 2121
COMMON 17
(38) (16)
2131 2131
9 METER OUTPUT CR4
(39) 18
SHD JUMPER J5 PROGRAMMABLE
IMPORTANT:
(40) TE 1-2 (4-20mA) CONTACTS
PARA 176 = 11
3-4 (0-10VDC) PAR 158,174-176
"DRIVE READY"
(25)
TE A1
LOGIC EARTH GND AUXILIARY OUTPUT
TE A2
FROM
3-41
(5) 3061
W5 FROM
(6) 3-41
OFF CUSTOMER 3065
HAND AUTO (19)
INTERLOCK TB3
2201 INTERFACE BOARD
2203 W8 2204
19 START
X00 (12) (13)
CUSTOMER
2223 R1 INTERLOCK
W9 2225
20 STOP
00X (15) (14) (13) (16)
2-26

R1
2261
TERMINAL BLOCK TB3
2-26

AUTO START AUTO STOP R1


2262
21 COMMON
(9) (10) (11) 2-22
2-24 22 REVERSE

BRAKE CHOPPER 23 2ND ACCEL INPUT MODE 14


AUX CONTACT
2291
1 2 24 AUXILIARY (PAR 21 = 14)
(7) (17)

RESISTOR 25 COMMON
CAGE THERMOSTAT
26 2ND DECEL
2321
27 SPD SEL 2
(00X) (28) TO
2331 PLC
(29)

2342
28 SPD SEL 1
(00X) SS2
CUSTOMER
INTERLOCK
W7 (20) 29 COMMON
2361
30 ENABLE
2201 (8) (18) 3065
ab1004a
TO 2-01
Typical Parameter Table B
Programming Parameter Description Standard Default Shipped setting Installed Setting
9 Control Select Full Custom
21 Input Mode 1 14
49 Break Frequency 0 Default 0%
176 CR4 Out Select Alarm Drive Ready

www.rockwellautomation.com

Corporate Headquarters
Rockwell Automation, 777 East Wisconsin Avenue, Suite 1400, Milwaukee, WI, 53202-5302 USA, Tel: (1) 414.212.5200, Fax: (1) 414.212.5201

Headquarters for Allen-Bradley Products, Rockwell Software Products and Global Manufacturing Solutions
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe: Rockwell Automation SA/NV, Vorstlaan/Boulevard du Souverain 36-BP 3A/B, 1170 Brussels, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, 27/F Citicorp Centre, 18 Whitfield Road, Causeway Bay, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846

Headquarters for Dodge and Reliance Electric Products


Americas: Rockwell Automation, 6040 Ponders Court, Greenville, SC 29615-4617 USA, Tel: (1) 864.297.4800, Fax: (1) 864.281.2433
Europe: Rockwell Automation, Brühlstraße 22, D-74834 Elztal-Dallau, Germany, Tel: (49) 6261 9410, Fax: (49) 6261 17741
Asia Pacific: Rockwell Automation, 55 Newton Road, #11-01/02 Revenue House, Singapore 307987, Tel: (65) 351 6723, Fax: (65) 355 1733

U.S. Allen-Bradley Drives Technical Support


Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: support@drives.ra.rockwell.com, Online: www.ab.com/support/abdrives