APD145C-RP
145 kVA / 116 kW
POWERED by CUMMINS
DIESEL GENERATING SET 400/230 V - 50 Hz - 3 Phase
MODEL APD145C-RP
kVA 145
Standby
Power kW 116
Pf. 0.8 kVA 132
Prime
kW 105.6
Standby: Continuous running at variable load for duration of an emergency. No overload is permitted on these ratings. In accordance with ISO 3046 .
Prime: Continuous running at variable load for unlimited periods with 10% overload available for 1 hour in any 12 hour period. In accordance with ISO 8528,ISO 3046.
High quality, reliable and complete power unit
Compact design
Easy start and maintenance possibility
Every generating set is subject to a comprehensive test program which includes full load testing, checking and provision of all
control and safety shut down functions testing
Fully engineered with a wide range of options and accessories: Canopy, sound proof canopy and on-road trailer
Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.
www.aksaeurope.com
ENGINE
CUMMINS
Model 6BTAA5.9G2
Engine Power Output kWm 130
at rated rpm HP 174
Aspiration and Cooling Turbocharged and Charge Air Cooled
Total Displacement Litre 5.9
No. of Cylinders and Build 6 - Inline
Engine Speed rpm 1500
Bore and Stroke mmxmm 102x120
Compression Ratio 17.3:1
Governor Electronic
Fuel Consumption at full load L/hr 30
Fuel Tank Capacity Litre Canopy: 550
Oil Capacity Litre 16.4
Coolant Capacity Litre 54
Radiator Cooling Air m³/min 148
Air Intake – Engine m³/min 7.2
Exhaust Gas Flow m³/min 19.68
Sound Level(1M) dBA 79.5
Sound Level(7M) dBA 70
Heavy duty Cummins diesel engine Cooling radiator and fan
Four stroke, water cooled, turbocharged & intercooled Starter battery (with lead acid) including Rack and Cables
Direct injection fuel system Flexible fuel connection hoses and manual oil sump drain valve
Electronic Governor system Industrial capacity exhaust silencer and steel bellows
12/24 V D.C. starter and charge alternator Jacket water heater(at automatic models)
Replaceable fuel filter, oil filter and dry element air filter Operation manuals and circuit diagram documents
STAMFORD ALTERNATOR PI144D
Design Brushless single bearing, revolving field
Stator 2/3 pitch
Rotor Single bearing, flexible disc
Insulation System Class H
Standard Temperature Rise 125 - 163°C Continuous
Exciter Type Self Excited
Phase Rotation A (U), B (V), C (W)
Alternator Cooling Direct drive centrifugal blower fan
AC Waveform Total Harmonic Distortion No load < 1.5%. Non distorting balanced linear load < 5%
Telephone Influence Factor (TIF) <50 per NEMA MG1-22.43
Telephone Harmonic Factor (THF) <2%
Brushless, single bearing system, flexible disc, 4 poles Impregnation with tropicalised epoxy varnish
Insulation class H Solid state Automatic Voltage Regulator
Standard degree of protection IP23 Stator winding with 2/3 pitch for improved harmonics
Self-exciting and self-regulating
www.aksaeurope.com
CONTROL SYSTEM
Control supervision and protection panel is mounted on the genset base frame.
The control panel is equipped as follows:
1. Auto Mains Failure Control Panel
Panel equipments:
Control with AMF module
Static battery charger
Emergency stop push button
a) Product description:
Single Gen-set controller for stand-by and prime power applications
InteliLite 4 AMF 9
All-in-one intuitive & powerful PC tool for configuration/monitoring/control, locally or remotely
Easy to install, configure and use
b) Product description:
Stand-by and prime-power application in one unit User setpoints and protections
8 binary outputs, 8 + 1 binary inputs, 3 analog inputs (U/I/R) 5 languages in the controller & Translator functionality
+5 V output reference for analog inputs User Access Management
2 high-current E-Stop binary outputs Cyber security improvement
1 slot for extension plug-in module (Modbus, Internet, SMS, Alternative configurations
inputs/outputs) Multi-purpose schedulers
Extension CAN modules 3 maintenance timers
ECU support (Tier 4 Final, Stage V) Modbus register mapping possibility
RTC with battery back-up (full calendar) Fuel pump management
Power over USB for controller configuration Run Hours source selector
Zero power mode Cut-out: 172 × 112 mm
True RMS measurement
In-built PLC, complemented with a PLC monitoring tool in
InteliConfig
Full remote communications support (AirGate 2.0, WSV)
Internet access using Ethernet / 4G, Modbus TCP/RTU, SNMP
v1/v2c
Active SMS and emails
Detailed history log with up to 150 records
Dual Mutual Standby application support
Remote display
2. Power Outlet Terminal Board Mounted on the Gen-set Base Frame
OPTIONAL EQUIPMENTS
Diesel Engine Panel Accessories
Oil heater Charge ammeter Bulk fuel tank
Alternator Transfer Switch 3Pole Automatic filling system
3/4 Pole Output Circuit Breaker Transfer Switch 4 Pole Fuel-water separator filter
Anti-condensation Heater Earth Fault ,single set Low fuel level alarm
Residential silencer
Enclosure or sound proof canopy
Trailer
Manual oil drain pump
Tool kit for maintenance
www.aksaeurope.com
CHASSIS
The complete gen-set is mounted as whole on a heavy-duty fabricated, steel base frame
Anti-vibration pads are fixed between the engine/ alternator feet and the base frame
Base frame design incorporates an integral fuel tank (Up to 750 kVA)
The generating set can be lifted or carefully pushed / pulled by the base frame
Dial type fuel gauge and drain plug on the fuel tank
Forklift pockets within base frame (up to 500kVA)
DIMENSIONS
OPEN TYPE
DIMENSIONS (LxWxH) mm N/A
DRY WEIGHT kg N/A
SOUND ATTENUATED TYPE
DIMENSIONS (LxWxH) mm 3400x1163x1923
DRY WEIGHT kg 2300
CANOPY(RAL-1015)
All canopy parts are designed with modular principles Exhaust silencer is protected against environment influences
Without welding assembly Thermally insulated engine exhaust system
Doors on each side Emergency stop push button is installed outside of the canopy
All metal canopy parts are painted by electrostatic Easy lifting and moving
polyester powder paint Easy maintenance and operation
www.aksaeurope.com