Document ID: TE/QMS/F/02
Particulars
Name of Manufacturer
Type of cable
Voltage Grade V
No of cores X size in sqmm
Conductor
a) Material
b) Max. d.c. resistance of conductor at 20° C (ohm/km)
c) Shape of the conductor
Insulation
a) Material
b) Nominal thickness (mm)
c) Core identification
Inner Sheath
a) Material
b) Minim um thickness (mm)
Armouring
a) Material
b) Type of armouring
c) Nominal size of armour (mm)
d) Tolerance on armour dimensions
Outer Sheath
a) Material
b) Thickness (mm)
c) Colour of sheath
Electrical Parameters
a) Max. a.c. resistance of conductor at 90° C
(ohm/km)
b) Calculated Cable reactance (ohm/km)
c) Impedance of cable (ohm/km)
d) Approx. Cable Capacitance (mfd/km)
Maximum conductor temperature under normal operating conditions
Maximum conductor temperature at the termination of
short circuit
(Sho)rt Circuit rating of conductor for the duration of 1 sec (kA)
Continuous Current carrying capacities
(a) In Ground at 30°C (A)
(b) In Air at40°C (A)
Applicable Standard
Approx. overall diameter of the cable in mm
Minimum bending radius
Max. Tensile strength
(i) for Cables pulled with stocking (Newtons)
(ii) for Cables pulled with pulling eyes (N)
Em bossing
Printing
Standard Drum Length (Mtr.)
Non- Standard Drum Length (Mtr.)
CABLES
LT XLPE CABLE
DESIGN CODE :
LVIS09AXSWY2003C004SA002S
3 Core X 4 Sq.mm
Polycab India Ltd
A2XWY
1100
3 Core X 4 Sq.mm
H2/H4 Grade Aluminium as per Class 1 of IS: 8130/201 3, latest
7.41
Solid Circular
XLPE as per IS 7098(Pt-1)/88, Latest
0.7
Red,YeIlow,Blue
Extruded PVC Type ST2 as per IS:5831 / 84
0.3
Galvanised Steel
Round Wire
1.400
+ 0.040 mm
Extruded PVC Type 'ST2' as per IS:5831/ 84
1.24 (Min.)
Black
9.50
0.091 7
CABLES
9.50
0.23
90°C
250°C
0.38
35
32
IS 7098 Part I/88,IS 8130/2013,IS 5831/84, IS 3975/1999 etc.
with latest up to date amendments
14.0 + / - 2.0
12 times Overall diameter
9 x D^2, D is the cable OD in mm
360
POLYCAB ELECTRIC 1 1 00 VOLTS GRADE XLPE
YEAR POLYCAB ELECTRIC 1 1 00 VOLTS GRADE XLPE
CABLE SIZE CABLE
TYPE WITH SEQUENTIAL MARKING
at every one meter interval.
1000 Mtr. +5%
Maximum 5% of order quantity
BLE
3 Core X 6 Sq.mm
Polycab India Ltd
A2XWY
1100
3 Core X 6 Sq.mm
H2/H4 Grade Aluminium as per Class 1 of IS: 8130/201 3,
latest
4.61
Solid Circular
XLPE as per IS 7098(Pt-1)/88, Latest
0.7
Red,YeIlow,Blue
Extruded PVC Type ST2 as per IS:5831 / 84
0.3
Galvanised Steel
Round Wire
1.400
+ 0.040 mm
Extruded PVC Type 'ST2' as per IS:5831/ 84
1.24 (Min.)
Black
5.91
0.086
9.50
0.23
90°C
250°C
0.57
46
42
IS 7098 Part I/88,IS 8130/2013,IS 5831/84, IS
3975/1999 etc. with latest up to date amendments
15.0 + / - 2.0
12 times Overall diameter
9 x D^2, D is the cable OD in mm
540
POLYCAB ELECTRIC 1 1 00 VOLTS GRADE XLPE
YEAR POLYCAB ELECTRIC 1 1 00 VOLTS GRADE XLPE
CABLE SIZE CABLE TYPE WITH SEQUENTIAL MARKING
at every one meter interval.
1000 Mtr. +5%
Maximum 5% of order quantity