Copyright 2018 National Fire Protection Association (NFPA®).
Licensed, by agreement, for individual use and download on 09/16/2018 to nfcss@WPI.edu. No other reproduction or transmission in any form permitted without
                             written permission of NFPA®. For inquiries or to report unauthorized use, contact licensing@nfpa.org. This NFCSS All Access subscription expires on July 1, 2019.
         13-462                                                                 INSTALLATION OF SPRINKLER SYSTEMS
           Other protection features should be considered to limit the                                                       iv.
                                                                                                                              Pitting, nodules, tubercles, or carbuncles
         extent of potential fire damage, including the following:                                                            inside piping or valves
         (1)  Very high density sprinkler systems                                                                       v.    Foreign material in water during drain tests or
         (2)  Quick-response sprinklers                                                                                       plugging of inspector’s test connection(s)
         (3)  Early-warning smoke detection                                                                             vi. Plugged sprinklers
         (4)  Spacers between carriages or, for automated systems,                                                      vii. Plugged piping in sprinkler systems disman‐
              automatic park mode to increase flue spaces between                                                             tled during building alterations
              carriages upon activation of a fire alarm or during idle                                                  viii. Frequent false tripping of a dry pipe valve(s)
              periods                                                                                                         with indications of corrosion inside the
         (5) Metal vertical barriers in the middle of the shelf                                                               valve(s)
         (6) Open-top shelving                                                                                          ix. A 50 percent increase in the time required for
         [909:A.9.12.24.4.1.3]                                                                                                water to travel to the inspector’s test connec‐
                                                                                                                              tion after the valve trips during a full flow trip
         A.26.29.1.3.2 The system should be designed to confine fire                                                          test of a dry pipe sprinkler system when
         growth to the compact storage module of origin or the shelving                                                       compared to the original system acceptance
         range of origin. [909:A.9.12.24.4.1.4(A)]                                                                            test
                                                                                                             [909: A.9.12.13.3.3]
         A.26.29.2.1 Proper pitching is an important element in reduc‐
         ing the risk of corrosion. The pitch requirements included in                                          These options are based on those specified by this standard
         this standard should be considered the minimum acceptable                                           for applications where water supplies are known to be corro‐
         pitch. Where adequate clearance is provided to permit the                                           sive. They are recommended in this code for steel dry pipe and
         system to be installed without causing interferences with struc‐                                    preaction systems because the levels of corrosion found in
         tural elements or causing low points, pitches exceeding this                                        these systems are unacceptable for cultural resource facilities.
         minimum requirement such as 1∕2 in./10 ft (4 mm/m) should                                           Although this standard also allows the option of treating all
         be considered. [909:A.9.12.13.3.1]                                                                  water that enters the system with an approved corrosion inhibi‐
                                                                                                             tor, experience using this option has not been satisfactory in
     N A.26.29.2.2 Due to heightened concerns regarding the issues                                           cultural resource facilities due to potential formation of exter‐
       associated with corrosion, additional auxiliary drainage is                                           nal crystals on piping and potential reduction in the service life
       needed for all preaction systems, regardless of whether or not                                        of gaskets in mechanical couplings. This standard includes the
       the protected area is subject to freezing. [909:A.9.12.13.3.2.1]                                      additional option of using a special listed pre-primed preaction
     N A.26.29.2.3 A plan to address piping corrosion should include                                         system, in which the piping is normally filled with water.
       one or more of the following:                                                                            [909:A.9.12.13.3.3]
         (1)     Installation of sprinkler piping that is corrosion resistant
                 – Galvanized steel piping is not considered corrosion                                       A.26.33.1.11 The quantities and pressure of water for fire
                        {23188f7b-d887-4151-ae08-bc5f4d1ab905}
                 resistant for the purposes of this recommendation.
                 Galvanized coatings can corrode where water and oxygen
                                                                                                             extinguishing indicated in 26.33.1.11 are based on limited test‐
                                                                                                             ing and should be considered subject to change as additional
                 are present inside system piping. When galvanized coat‐                                     data become available. It is recommended that spray coverage
                 ings fail, the remaining uncoated steel corrodes at an                                      tests be carried out at maximum altitude for manned opera‐
                 accelerated rate.                                                                           tions. [99B: A.4.5.2.5.1]
         (2)     Installation of a special listed pre-primed preaction                                       A.26.34.1.1.1 See 4.3.3 of NFPA 120 for unique requirements
                 system, filled with water under normal conditions.                                          for protecting this unusual type of occupancy.
         (3)     Use of a continuous source of dry inert gas for pressure
                 maintenance.                                                                            N A.26.34.1.3.3(8) Pipe hangers should be designed to support
         (4)     Testing of the water supply for corrosivity prior to connec‐                              five times the weight of the water-filled pipe plus 250 lb
                 tion to the sprinkler system.                                                             (114 kg) at each point of piping support. Hanger rods should
         (5)     Equipping any source of compressed air used for pressure                                  be at least 3∕8 in. (9.5 mm) thick for pipe up to 4 in. (102 mm).
                 maintenance with an air dryer or nitrogen separator.                                      U hooks should be at least 5∕16 in. (8 mm) thick for pipes up to
         (6)     Implementation of an approved plan for maintaining and                                    2 in. (50.8 mm). Eye rods should be at least 3∕8 in. (9.5 mm)
                 monitoring the interior conditions of the pipe at estab‐                                  thick for pipe up to 4 in. (102 mm). This information is taken
                 lished intervals and locations, including all of the follow‐                              from Chapter 17 of this standard. [120:A.9.4.6.3.2(8)]
                 ing:
                                                                                                             A.26.35.1.2 Underground shaft mines that use diesel-powered
                 (a)     Testing water flow devices between the semiannual                                   equipment generally employ underground diesel fuel storage
                         tests using a means that does not introduce fresh                                   areas to facilitate equipment refueling. Adit-type mines in the
                         water into the system                                                               western United States can initially locate diesel fuel storage and
                 (b)     Drying system piping before returning systems to                                    refueling facilities on the surface; however, as the active mine
                         service after trip tests or other incidents that intro‐                             workings progress further from the adit portal(s), these facili‐
                         duce water into system piping beyond the riser                                      ties usually are moved underground. [122:A.11.3.1]
                 (c)     Inspecting for obstructions when any of the follow‐
                         ing conditions are observed:                                                           A common means of fire protection currently found in many
                                                                                                             underground diesel fuel storage areas is a fixed water sprinkler
                         i.      Pinhole leaks                                                               system. The federal Mine Safety and Health Administration
                         ii.     Frequent operation of system air compres‐                                   (MSHA) currently approves such systems for this application.
                                 sor(s)                                                                      The consensus of the committee is that this situation represents
                         iii.    Corrosion on the outside of pipe joints,                                    a significant safety hazard. According to the NFPA Fire Protection
                                 fittings, or sprinklers
         2019 Edition