TBD Series Diversified Electronics atcdiversified.com 800.727.
5646
\\\ OPERATION
Supply voltage is continuously applied to the input. An external isolated
switch between pins 5 and 6 controls the timer. When closed, the relay ener-
gizes. Opening the switch initiates the delay period. Upon completion of the
delay period, the relay de-energizes. If the control switch recloses during the
delay period, the relay remains energized and the timer resets to zero.
NOTE: The TBD Series is available in an 8-pin SPDT and an 11-pin DPDT
configuration.
DIP SWITCH OPERATION
Digital selection of the time delay is accomplished by the use of ten (10) binary
switches, each marked with a time increment. The time periods, of which there are
R five (5) ranges, represented by each switch in the ON position is added together to
TD obtain the desired time delay. No more trial-by-error adjustments.
tch
Off-Delay DIP Swi SUPPLY VOLTAGE
CONTROL SWITCH
\\\ SPECIFICATIONS OUTPUT TIME DELAY
0.1 to 102.3 SEC in 0.1 SEC
A
Increments
1.0 to 1,023 SEC in 1.0 SEC \\\ WIRING
B Increments STANDARD OPTION
TIME DELAY 10 to 10,230 SEC in 10 SEC
RANGE
C Increments
0.1 to 102.3 MIN in 0.1 MIN
D Increments
1.0 top 1,023 MIN in 1.0 MIN
E Increments
OUTPUT SPDT 10 A @ 250 VAC or 24 VDC, resistive
RATING DPDT 5 A @ 240 VAC
±2% or ±50 mSEC; RB-08/PF083A RB-11/PF113A
Setting
ACCURACY
whichever is greater \\\ DIMENSIONS (INCHES)
±0.1% or ±8.3 mSEC; whichever is
Repeat
greater
Before
100 mSEC
Time Out
RESET TIMES
After
Time Delay Relays // TBD Series
50 mSEC
Time Out
SUPPLY 12, 24, 48, 120 or 240 VAC,
VOLTAGE 50/60 Hz; or DC; ±10%
FALSE TRANSFER No
REVERSE
POLARITY Yes MODEL NUMBER > > > > > > TBD D
PROTECTED Control Voltage
POWER 12 Volts DC 12 D
3 VA, approximately
REQUIRED 24 Volts AC/DC 24 A
DUTY CYCLE Continuous 48 Volts DC 48 D
120 Volts AC/DC 120 A
TEMPERATURE Operate 32° to 131°F (0° to +55°C) 240 Volts AC 240 A
RATING Storage -49° to 185°F (-45° to +85°C) Time Delay Range
Mechanical 10 million operations, minimum 0.1 to 102.3 SEC in 0.1 SEC Increments A
LIFE
1.0 to 1,023 SEC in 1.0 SEC Increments B
EXPECTANCY Electrical 100,000 Operations @ rated load 10 to 10,230 SEC in 10 SEC Increments C
INDICATORS LED glows when relay is energized. 0.1 to 102.3 MIN in 0.1 MIN Increments D
1.0 to 1,023 MIN in 1.0 MIN Increments E
ISOLATION 1,500 volts, input/output
Option
WEIGHT 0.4 lbs. DPDT, 5 Amps @120 VAC, 11-Pin D
62