0% found this document useful (0 votes)
16 views2 pages

DB Mezz

The document outlines the electrical specifications and load distribution for a restaurant's electrical panel designated as DB-REST, with a focus on lighting, sockets, and air conditioning circuits. It includes details such as circuit breakers, cable types, and connected loads, indicating a total required load of 69,380 VA. The installation is scheduled for execution on August 14, 2025, and is mounted on the ground floor with a feeder capacity of 125 A.

Uploaded by

Wassim Daher
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
16 views2 pages

DB Mezz

The document outlines the electrical specifications and load distribution for a restaurant's electrical panel designated as DB-REST, with a focus on lighting, sockets, and air conditioning circuits. It includes details such as circuit breakers, cable types, and connected loads, indicating a total required load of 69,380 VA. The installation is scheduled for execution on August 14, 2025, and is mounted on the ground floor with a feeder capacity of 125 A.

Uploaded by

Wassim Daher
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

RESTAURANT

DESIGNATION : DB-REST PANEL TYPE: IP 44 DATE: 14/08/2025


LOCATION: GROUND FLOOR Feed Cab. Leng (m): 10 FILE: .XLS
MOUNTING: SURFACE FEEDER CB (A) : 125 STATUS : FOR EXECUTION

REF POLES RATE SECTION R Y B TOT. DESCRIPTION


Nb A mm² VA VA VA VA
MS 4 125 4x50mm²+1x25E 35200 35200 35000 105400 Coming from ATS

LIGHTING
Earth Leakage With Switch Disconnector For
CB-L 4 16 Lighting
30 mA

L1 1+N 16 3 x 2.5 mm² 700 700 LIGHTING


L2 1+N 16 3 x 2.5 mm² 700 700 LIGHTING
L3 1+N 16 3 x 2.5 mm² 700 700 LIGHTING-BATHROOM
L4 1+N 16 0 SPARE
L5 1+N 16 0 SPARE
L6 1+N 16 0 SPARE

30 mA
CB-P 4 40 Earth Leakage Circuit Breakers For Sockets
SOCKET

R1 1+N 20 3 x 4 mm² 700 700 Sockets


R2 1+N 20 3 x 4 mm² 700 700 Sockets
R3 1+N 20 3 x 4 mm² 700 700 Sockets
R4 1+N 20 3 x 4 mm² 700 700 Sockets
R5 1+N 20 3 x 4 mm² 2500 2500 DOOR FREEZER
R6 1+N 20 3 x 4 mm² 2500 2500 DOOR REFRIGERATOR
UNDERCOUNTER DISHWASHER 540
1500 1500
R7 1+N 20 3 x 4 mm² DISHES/HOUR
R8 1+N 20 3 x 4 mm² 700 700 FRIDGE-5
R9 1+N 20 3 x 4 mm² 700 700 KITCHEN EQUIPMENT-1
R10 1+N 20 3 x 4 mm² 700 700 KITCHEN EQUIPMENT-2
R11 4 20 5 x 4 mm² 500 500 500 1500 Socket
R12 4 32 4 x 10 mm²+10E 2500 2500 2500 7500 Spare

30 mA
CB-P 4 32 Earth Leakage Circuit Breakers For Sockets
SOCKET

R1 1+N 20 3 x 4 mm² 2100 2100 SANDWICH GRILL


R2 1+N 20 3 x 4 mm² 2100 2100 SANDWICH GRILL
R3 1+N 20 3 x 4 mm² 2100 2100 HOT WATER DISPENSER
R4 1+N 20 3 x 4 mm² 1000 1000 ESPRESSO COFFEE MACHINE
DISPLAY REFRIGERATOR - TARTE
1000 1000
R5 1+N 20 3 x 4 mm² TROPEZIEME
R6 1+N 20 3 x 4 mm² 1000 1000 DISPLAY REFRIGERATOR - SANDWICHERIE
R7 1+N 20 3 x 4 mm² 700 700 COFFEE GRINDER
UNDERCOUNTER DISPLAY REFRIGERATOR
1000 1000
R8 1+N 20 3 x 4 mm² 2 GLASS DOORS
UNDERCOUNTER DISPLAY REFRIGERATOR
1000 1000
R9 1+N 20 3 x 4 mm² 2 GLASS DOORS
R10 1+N 20 3 x 4 mm² 700 700 UNDERCOUNTER REFRIGERATOR FOR MILK
R11 1+N 20 3 x 4 mm² 700 700 UNDERCOUNTER GLASSWASHER
R12 1+N 20 3 x 4 mm² 700 700 WARMER DISPLAY

A/C

Earth Leakage With Switch Disconnector For


CB-P 4 32 Power

P1 4 20 5 x 4 mm² 1800 1800 1800 5400 AC-1


P2 4 20 5 x 4 mm² 1800 1800 1800 5400 AC-2
P3 4 20 5 x 4 mm² 1800 1800 1800 5400 AC-3
P4 2 20 3 x 4 mm² 2000 2000 AC-4
P5 2 25 3 x 6 mm² 3000 3000 AC-5
P6 2 20 3 x 4 mm² 1200 1200 EF
P7 4 20 3 x 4 mm² 1200 1200 EWH-1
P8 4 20 3 x 4 mm² 1200 1200 EWH-2
RESTAURANT
DESIGNATION : DB-REST PANEL TYPE: IP 44 DATE: 14/08/2025
LOCATION: GROUND FLOOR Feed Cab. Leng (m): 10 FILE: .XLS
MOUNTING: SURFACE FEEDER CB (A) : 125 STATUS : FOR EXECUTION
P9 4 80 4x35mm²+1x16E 14900 14200 14900 44000 DB-MEZZ

MS 2 20 2x4mm²+1x4E 1500 0 0 1500 Coming from MDB-UPS

UPS Sockets
CB-P 2 20
30 mA
U1 1+N 10 3 x 2.5mm² 750 750 SOCKETS
U2 1+N 16 3 x 2.5mm² 750 750 LOWCURRENT DEVICES
U3 1+N 16 0

BREAK. CAPACITY: 6 KA CIRCUITS BREAKERS CONNECTED LOAD (VA) DIVERSITY REQUIRED LOAD (VA)
A VA FACTOR VA
FRAME RATE R Y B TOTAL
LIGHTING CB 40 16 700 700 700 2100 1 2100
SOCKET CB 40 20 7300 6900 6200 20400 0.6 12240
SOCKET CB 40 20 6600 6900 6200 19700 0.6
A/C CB 40 20 22700 22800 23300 68800 0.8 55040
MAIN SWITCH 200 125 37300 37300 36400 111000 0.63 69380

UPS 40 20 1500 0 0 1500 1 1500