Week-2, Lecture-7                           Double Pipe Heat Exchanger
Shabina Khanam
              Associate Professor
       Department of Chemical Engineering
                                                                         1
Properties of Organic Liquids
                                2
        Design of Double Pipe Heat Exchanger
Example – 1
   10,000 lb/h of benzene will be heated from 60F to 120F by heat exchange
   with an aniline stream that will be cooled from 150F to 100F. A number of
   16-ft hairpins consisting of 2-in. by 1.25-in. schedule 40 stainless steel pipe
   (k = 9.4 Btu/h. ft. F) are available and will be used for this service. A
   maximum pressure drop of 20 psi is specified for each stream. The specific
   gravity of benzene is 0.879 and that of aniline is 1.022. Determine the
   number and configuration of hairpins that are required.
        Design of Double Pipe Heat Exchanger
Solution of Example – 1
    We begin by assuming that the hairpins are connected in series
    on both sides, since this is the simplest configuration, and that the
    flow pattern is counter-current. We also place the benzene in the
    inner pipe; however, either fluid could be placed in the inner pipe.
         Design of Double Pipe Heat Exchanger
Solution of Example – 1
                                                  (b) Determinetheheat
  First trial                                     loadandanilineflowratebyenergybalanceso
  (a) Fluid properties at the average stream      nthe twostreams.
       temperatures are obtained from figures.     q = (mCP ΔT)B = 10,000x0.42x60
                                                                   = 252,000 Btu/h
                                                         252,000 = (mCP ΔT)A
                        Benzene           Aniline                  = mA x 0.52 x 50
   Fluid property                                             mA = 9692 lb/h
                      (Tavg = 90°F) (Tavg = 125°F)
         μ (cP)            0.55             2.0
   Cp (Btu/lbm.°F)         0.42            0.52
    k (Btu/h.ft.°F)       0.092            0.100
          Design of Double Pipe Heat Exchanger
Solution of Example – 1
(c) CalculatetheLMTD                                            k
           40 − 30                                         hi =   0.023Re0.8 Pr1/3
LMTD =               = 34.76°F                                 Di
               (40)                                                                               1/3
            ln                                   0.092                      0.42 x 0.55 x 2.419
               (30)                         hi =       x 0.023 83217 0.8
                                                 0.115                             0.092
(d) Calculate hiassuming ϕ i=1.0
                                                                         Btu
                                                              hi = 290
                                                                       h. ft 2 ℉
Di = 1.38/12 = 0.115 ft (fromTableB.2)
        4m               4 x 10000
Re =         =
       πDi μ     π x 0.115 x 0.55 x 2.419
        = 83217 ⟹ turbulent flow
       Design of Double Pipe Heat Exchanger
Solution of Example – 1
            Design of Double Pipe Heat Exchanger
Solution of Example – 1
                                                    k
(e) Calculate hoassuming ϕ o=1.0              ho =    0.116 Re2/3 − 125 Pr1/3
                                                   De
D2 = 2.067 in                                           0.1
                                                    =          x 0.116 x 8213 2/3 − 125
D1 = 1.660 in                                         0.0339
               2.067−1.66                                                        1/3
De = D2 − D1 =            = 0.0339ft                          0.52 x 2.0 x 2.419
                         12
                   π
 flow area = Af =       2
                        D12 = 0.00827ft 2
                       D2 −                                           0.1
                   4
                 m                                          Btu
             De                    9692         ho = 283
                 Af   0.0339 ∗ (          )              h. ft 2 . ℉
       Re =         =             0.00827
                μ          2.0 ∗ 2.419
            = 8212 ⟹ transition flow
       Design of Double Pipe Heat Exchanger
Solution of Example – 1
             Design of Double Pipe Heat Exchanger
Solution of Example – 1                    (g) Calculate ϕ iand ϕ oand corrected values of hi and
                                               ho
 (e) Calculate the pipe wall temperature   From Figure, at 108.9oF, μB=0.47 cp and μA=2.4 cp.
        hi tavg + ho (Do / Di )Tavg        Therefore,
 Tw   =                                             ϕi = 0.55/0.47 0.14 = 1.0222
             hi + ho (Do / Di )
                                                      ϕo = 2.0/2.4 0.14 = 0.9748
                        1.66                                                Btu
         290 ∗ 90 + 283       125
 Tw =                   1.38                       hi = 290 1.0222 = 296
                        1.66                                             h. ft 2 . ℉
              290 + 283
                        1.38
                  Tw = 108.9°F                                                    Btu
                                                   ho = 283 0.9748 = 276
                                                                               h. ft 2 . ℉
            Design of Double Pipe Heat Exchanger
Solution of Example – 1                                   (j) Calculate the required surface area and
                                                          number of hairpins.
(h) For liquid organic process chemicals such as          q = UD AΔTin
benzene and aniline, a value of 0.001 h.ft2.oF /Btu can           q
be considered.                                            A=
                                                               UD ΔTin
(i) Compute the overall heat-transfer coefficient.              252,000
                                                          A=                = 81.5ft 2
                                                               89 ∗ 34.76
                                                          The external surface area per foot of 1.25-in.
         1.66         (1.66/ 12 )ln(1.66/ 1.38 )    1     schedule 40 pipe is 0.435 ft2.
UD =                +                            +                          81.5
      296 x 1.38                2 x 9.4            276    Therefore, L =         = 187.4ft
                                     −1                                    0.435
              0.001 ∗ 1.66                                Since each 16-ft hairpin contains 32 ft of
          +                + 0.001
                   1.38                                   pipe,
           Btu                                                                     187.4
UD = 89                                                   Number of hairpins =            = 5.9 ⇒ 6
        h. ft 2 . ℉                                                                  32
                                                          Thus, six hairpins are required.
       Design of Double Pipe Heat Exchanger
Solution of Example – 1
            Design of Double Pipe Heat Exchanger
Solution of Example – 1                                         0.0267(6 ∗ 32)(961,538)2
                                                      ∆Pf =
                                                                        1.38
 (k) Calculate the pressure drop for the benzene            7.50 ∗ 1012       ∗ 0.879 ∗ 1.022
                                                                         12
 stream (inner pipe).                                 ∆Pf = 6.1 psi
 The friction factor is calculated from Equation:     The pressure drop in the return bends is obtained:
 f = 0.3673Re−0.2314 = 0.3673 83,217 −0.2314
 f = 0.0267                                           ∆Pr = 1.6 ∗ 10−13 (2𝑁𝐻𝑃 − 1)G2 /𝑠
 Af = 0.0104 ft 2                                     ∆Pr = 1.6 ∗ 10−13 (2 ∗ 6 − 1) 961,538 2 /0.879
       m      10,000
 G=        =           = 961,538 lbm/h. ft 2          ∆Pr = 1.85 psi
       Af     0.0104
 The pressure drop in the straight sections of pipe   Since the nozzle losses associated with the inner
 is calculated using Equation:                        pipes are negligible, the total pressure drop, ΔPi, is:
               fLG2                                   ∆Pi = ∆Pf + ∆Pr = 6.1 + 1.85 = 7.95 ≅ 8.0 psi
 ∆Pf =
        7.50 ∗ 1012 Di sϕ
       Design of Double Pipe Heat Exchanger
Solution of Example – 1
            Design of Double Pipe Heat Exchanger
Solution of Example – 1                                          0.0456(6 ∗ 32)(1,171,947)2
                                                       ∆Pf =
  (l) Calculate the pressure drop for the aniline            7.50 ∗ 1012 ∗ 0.0339 ∗ 1.022 ∗ 0.9748
  stream (annulus).
  The friction factor is calculated from Equation:     ∆Pf = 47.5 psi
  f = 0.3673Re−0.2314 = 0.3673 8212 −0.2314
  f = 0.0456                                           Since this value greatly exceeds the allowed
        m        9692                                  pressure drop, the minor losses will not be
  G=       =             = 1,171,947 lbm/h. ft 2       calculated. This completes the first trial.
        Af    0.00827
  The pressure drop in the straight sections of pipe
  is again calculated using Equation with the pipe     Summary:
  diameter replaced by the equivalent diameter:        The pressure drop on the annulus side is too large.
                fLG2                                   The Reynolds number in the annulus is less than
  ∆Pf =                                                10,000.
         7.50 ∗ 1012 De sϕ
             Design of Double Pipe Heat Exchanger
Solution of Example – 1                               𝑅𝑒i → 83,217 0.55/2.0 ≅ 23,000
                                                      𝑅𝑒o → 8212 2.0/0.55 ≅ 30,000
Since, the dimensions of the hairpins are fixed
                                                      Hence, switching the fluids will result in fully turbulent
in this problem, there are relatively few options
                                                      flow on both sides of the exchanger.
for modifying the design. Two possibilities are:
                                                      To estimate the effect on pressure drops, assume that
(1) Switch the fluids, i.e., put the aniline in the
                                                      the number of hairpins does not change. Then the main
inner pipe and the benzene in the annulus.
                                                      factors affecting ΔP are f and s. Hence,
(2) Connect the annuli in parallel.
Effects of these changes on Reynolds numbers
                                                      ∆P ∼ f/s ∼ Re−0.2314 s−1
and pressure drops can be estimated as:                                   −0.2314
(1) Switch the fluids. Since the flow rates of the                23,000
                                                      ∆Pf,i → 6.1                 (1.022/0.879)−1 ≅ 7 psi
two streams are approximately the same, the                       83,000
                                                                              −0.2314
Reynolds numbers are essentially inversely                           30,000
proportional to the viscosity. Thus,                  ∆Pf,o   → 47.5                    (0.879/1.022)−1
                                                                      8200
                                                                  ≅ 41 psi
             Design of Double Pipe Heat Exchanger
Solution of Example – 1                        (2) Connect the annuli in two parallel banks. This change
                                               will have no effect on the fluid flowing in the inner pipe.
                                               For the fluid in the annulus; however, both the flow rate
                                               and the length of the flow path will be halved. Therefore,
 Clearly, switching the fluids does not        𝑅𝑒o → 8212 ∗ 1/2 ≅ 4100
 reduce the annulus-side pressure drop         Assuming that the number of hairpins does not change,
 nearly enough to meet the design              ∆Pf,o ∼ fG2 L
                                                                      −0.2314
 specification (unless the number of                           4100
 hairpins is reduced by a factor of at least   ∆Pf,o → 47.5                   (1/2)2 ∗ (1/2) ≅ 7 psi
                                                               8200
 two, which is very unlikely).
                                               Apparently this modification will take care of the
                                               pressure-drop problem, but will push the Reynolds
                                               number further into the transition region.
                                               Although neither modification by itself will correct the
                                               problems with the initial design, in combination they
                                               might. Hence, we consider a third alternative.
             Design of Double Pipe Heat Exchanger
Solution of Example – 1
 (3) Switch the fluids and connect the annuli in two
 parallel banks. The Reynolds numbers will become:
 𝑅𝑒i ≅ 23,000                                          It appears that this alternative will
 𝑅𝑒o ≅ 15,000                                          meet all design requirements.
 The pressure drops will become (assuming no change    However, it is necessary to perform
 in the number of hairpins):                           the detailed calculations because hi,
                                                       ho and the mean temperature
 ∆Pf,i ≅ 7 psi                                         difference will all change, and
                        −0.2314                        hence the number of hairpins can
                 15,000
 ∆Pf,o   → 47.5                (1/2)2                  be expected to change as well.
                  8200
             ∗ (1/2)(0.879/1.022) ≅ 6 psi
            Design of Double Pipe Heat Exchanger
Solution of Example – 1
Second trial
(a) Calculate the LMTD correction factor for the
series/parallel configuration. Aniline in the inner pipe
is the series stream and benzene in the annulus is the
parallel stream. Therefore,
Ta = 150 °F; ta = 60 °F                                  Substituting into F Equation gives:
Tb = 100 °F; tb = 120 °F
                                                                0.8333 − 2
                                                         F=
P = (t b − t a )/ (Ta − t a )                                 2 0.8333 − 1
             = (120 − 60)/ (150 − 60) = 0.667               ln 1 − 0.6667 / 1 − 0.6667 ∗ 0.8333
R = (Ta − Tb )/ (t b − t a )                                            0.8333 − 2                  2
             = (150 − 100)/ (120 − 60) = 0.8333          ln                                    +
                                                            0.8333 1 − 0.6667 ∗ 0.8333     1/2   0.8333
x = 2 (number of parallel branches)                      F = 0.836
            Design of Double Pipe Heat Exchanger
Solution of Example – 1                            (c) Calculate hoassuming ϕ o=1.0
                                                               m                    5000
                                                          De           0.0339  ∗ (        )
                                                               Af                 0.00827
 (b) Calculate hiassuming ϕ i=1.0                  Re =             =
         4m                4 ∗ 9692                          μ            0.55 ∗ 2.419
 Re =           =                                              = 15,405 ⟹ turbulent flow
        πDi μ        π ∗ 0.115 ∗ 2 ∗ 2.419
 = 22,180 ⟹ turbulent flow                                k
       k                                           ℎo =      ∗ 0.023Re0.8 Pr1/3
 ℎi = ∗ 0.023Re0.8 Pr1/3                                  Di
      Di                                                     0.092
        0.1                                                                          0.8            1/3
                                                          =         ∗ 0.023 15,405         6.0764
 ℎi =        ∗ 0.023 22,180 0.8 25.158       1/3
                                                            0.0339
      0.115
              Btu
 ℎi = 176                                                        Btu
           h. ft 2 . ℉                             ℎo = 255
                                                              h. ft 2 . ℉
            Design of Double Pipe Heat Exchanger
Solution of Example – 1                               (f) Calculate UD
(d) Calculatethepipewall temperature                          Do      Do ln(Do / Di )  1 R Di Do
                                                      UD =          +                 + +
                             1.66                             ℎi Di         2k         ℎo  Di
       176 ∗ 125 + 255                90
Tw =                         1.38         ≅ 103°F
                                                                           −1
                           1.66                                  + R Do
            176 + 255
                           1.38
(e) Calculate ϕ iand ϕ oand corrected values of hi and          1.66          (1.66/ 12 )ln(1.66/ 1.38 )
ho                                                     UD =                +
                                                             170 ∗ 1.38                 2 ∗ 9.4
At 103 F, μA = 2.6 cp and μB =0.5 cp
       o
                                                                                                    −1
                 0.14                                                  1     0.001 ∗ 1.66
ϕi = 2.0/2.6          = 0.9639                                   +         +               + 0.001
ϕo = 0.55/0.5      0.14
                        = 1.0134                                     258          1.38
                                Btu                               Btu
ℎi = 176 ∗ 0.9639 = 170                                UD = 69
                             h. ft 2 . ℉                       h. ft 2 . ℉
                                 Btu
ℎo = 255 ∗ 1.0134 = 258
                              h. ft 2 . ℉
            Design of Double Pipe Heat Exchanger
Solution of Example – 1                                     (h) Calculate the pressure drop for the aniline
(g) Calculate the required surface area and number of       stream (inner pipe).
hairpins.                                                   f = 0.3673Re−0.2314
q = UD AFΔTin                                                          = 0.3673 22,180 −0.2314
          q            252,000                              f = 0.03625
A=             =                      = 125.7ft 2                m       9692
     UD 𝐹ΔTin 69 ∗ 0.836 ∗ 34.76                            G=       =           = 931,923 lbm/h. ft 2
     125.7                                                       Af     0.0104
L=          = 289ft                                                   0.03625(10 ∗ 32)(931,923)2
     0.435                                                  ∆Pf =
                         289                                                     1.38
Number of hairpins =          = 9.0 ⇒ 9                            7.50 ∗ 1012          ∗ 1.022 ∗ 0.9639
                         32                                                       12
Thus, nine hairpins are required. However, the equation                = 11.9 psi
for the LMTD correction factor is based on the
assumption that both parallel branches are identical.
Therefore, use two banks of five hairpins, for a total of
ten hairpins.
           Design of Double Pipe Heat Exchanger
Solution of Example – 1                          (i) Calculate the pressure drop for the benzene
                                                 stream (annulus).
∆Pr = 1.6 ∗ 10−13 (2𝑁𝐻𝑃 − 1)G2 /𝑠                The friction factor is calculated from Equation:
                                                 f = 0.3673Re−0.2314 = 0.3673 8212 −0.2314
∆Pr = 1.6 ∗ 10−13 (2 ∗ 10
                                                             = 0.03945
          − 1) 931,923 2 /1.022                        m        5000
∆Pr = 2.6 psi                                    G=       =             = 604,595 lbm/h. ft 2
                                                       Af     0.00827
                                                               fLG2
Since, the nozzle losses associated with the     ∆Pf =
                                                        7.50 ∗ 1012 De sϕ
inner pipes are negligible, the total pressure                0.03945(5 ∗ 32)(604,595)2
drop, ΔPi, is:                                   ∆Pf =
                                                        7.50 ∗ 1012 ∗ 0.0339 ∗ 0.879 ∗ 1.0134
                                                 ∆Pf = 10.2 psi
∆Pi = ∆Pf + ∆Pr = 11.9 + 2.6 = 14.5 psi          ∆Pr = 1.6 ∗ 10−13 (2𝑁𝐻𝑃 − 1)G2 /𝑠
                                                 ∆Pr = 1.6 ∗ 10−13 (2 ∗ 5 − 1) 604,595 2 /0.879
                                                 ∆Pr = 0.6 psi
            Design of Double Pipe Heat Exchanger
Solution of Example – 1                                   (j) Calculate the over-surface and over-design.
                                                                               −1
                                                                  1
 Assume the nozzles are made from 1-in. schedule 40       UC =       − R D,tot
 pipe having a flow area of 0.006ft2 (Table B.2). Then,           UD
      m       5000
 G=       =         = 833,333 lbm/h. ft 2                    1                             −1
      Af     0.006                                        =     − 0.001(1 + 1.66/1.38)
 Assuming internal return bends, Equation gives:             69
 ∆Pn = 2 ∗ 10−13 𝑁𝐻𝑃 G𝑛2 /𝑠                                         Btu
                                                          = 81.4
                 5 833,333 2                                     h. ft 2 . ℉
          −13
 = 2 ∗ 10      ∗
                    0.879                                          q
 ∆Pn = 0.79 psi                                           A𝐶 =
                                                               UC 𝐹ΔTin
 The total pressure drop for the benzene is:
                                                                     252,000
 ∆Po = ∆Pf + ∆Pr + ∆Pn = 10.2 + 0.6 + 0.79                A𝐶 =                      ≅ 107ft 2
 ∆Po ≅ 11.6 psi                                                81.4 ∗ 0.836 ∗ 34.76
                                                          A = π𝐷𝑜 𝐿 = 0.435 ∗ 10 ∗ 32 = 139ft 2
            Design of Double Pipe Heat Exchanger
Solution of Example – 1
                    A − A𝐶 139 − 107
 Over − surface =            =              ≅ 30%
                      A𝐶           107
 The required surface area is 125.7 ft2 from Step (g).
 Therefore, the over-design is:
                   139 − 125.7
 Over − design =                ≅ 10.6%
                       125.7
Thank You!
             26