0% found this document useful (0 votes)
47 views12 pages

Duct Sizing

Uploaded by

Phillips Bokkie
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
47 views12 pages

Duct Sizing

Uploaded by

Phillips Bokkie
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 12

Duct Sizing

1. Design Assumptions

 Flowrate: 4.0 m³/s (4000 L/s)


 Target velocity: 6.0 m/s (to limit air noise and pressure loss)
 Duct material: Galvanised steel
 Application: Supply air duct for a processing area

Retrieved: https://www.engineeringtoolbox.com/velocities-ventilation-ducts-d_211.html

Main Supply Ducts

 Commercial and Industrial Applications: Up to 6–8 m/s (approximately 1,200–


1,600 ft/min)

2. Circular Duct Option

Using the EngineeringToolbox “Duct Velocity and Flow Rate” table, a circular duct diameter
of 922 mm corresponds to a velocity of approximately 6.0 m/s at 4.0 m³/s.

Selected Circular Size:

 Diameter: 922 mm
 Area: 0.667 m²
 Velocity: 6.0 m/s
Retrieved: https://www.engineeringtoolbox.com/duct-velocity-d_928.html

3. Rectangular Duct Option

As an alternative, a rectangular duct has been considere:

Using a practical 2:1 aspect ratio for ease of fabrication and installation:

 Width: 1150 mm ~1200mm


 Height: 580 mm ~600mm
 Area: 0.667 m²

This sizing achieves the same airflow and velocity performance as the circular option and
may be preferred in applications with vertical or spatial constraints.
4. Alternative Scenario: Higher Velocity

If space limitations require a reduced duct size, increasing the design velocity to 7.0 m/s
reduces the required duct area:

A = 0.571m²

This results in:

 Circular duct: Ø ~854 mm


 Rectangular duct: e.g., 1050 mm × 545 mm
However, this introduces trade-offs, including increased noise and static pressure,
and is therefore less favourable for processing zones sensitive to air turbulence and
sound.

Duct Sizing and Pressure Loss Calculation

System Inputs

 Airflow rate: 4.0 m³/s


 Design velocity: 6.0 m/s
 Duct material: Galvanized steel (roughness = 0.15 mm)
 Air density: 1.2 kg/m³
 Kinematic viscosity: Approx. 1.5×10⁻⁵ m²/s

Sizing Result

 Recommended duct diameter: 921 mm

This diameter allows 4.0 m³/s of airflow at 6.0 m/s velocity without exceeding noise or
pressure loss limits for a main duct.

Pressure Loss Summary

Component Loss (Pa)


Straight Duct – 28 m 10.3 Pa
Straight Duct – 19 m 7.0 Pa
90° Elbow 7.6 Pa
Total Pressure Loss 24.8 Pa

Additional Technical Details

 Friction factor (Darcy-Weisbach): 0.01563


 Reynolds number: 368,527 (fully turbulent flow regime)

This result confirms that a 921 mm diameter duct is suitable for HVAC system. The
calculated total pressure drop of ~25 Pa is well within acceptable limits for efficient fan
operation and acoustic performance.

System Flowrate and Design Velocity

 Flowrate: 4.0 m³/s


 Main duct velocity: 6.0 m/s
 Inlet grille velocity: 2.0 m/s
 Diffuser velocity (assumed): 4.0 m/s

Component Losses
Component Value Notes
Inlet Grille Area 0.72 m² 1200 × 600 mm
Grille Entry Loss 1.2 Pa Based on Kₑ = 0.5
Main Duct Losses 24.8 Pa From previous calc (28 m + 90° bend +
19 m)
Diffuser Terminal Area 2.16 m² 3 diffusers (1200 × 600 mm)
Diffuser Losses 9.6 Pa Based on K = 1.0
Total End Losses 10.8 Pa Entry + outlet
Total System Pressure Loss 36.0 Pa End-to-end

Add AHU Losses at filters (check budget quote) (clean, medium, dirty)
Formula Sheet:

1. EngineeringToolBox (HVAC Friction Loss Guidelines)

 Low-pressure HVAC systems typically operate with total pressure losses in the
range of 100–250 Pa across the entire duct network (supply + return).
 A segment pressure loss of <30 Pa for a long straight duct run is considered efficient
and low-resistance.

Source:
EngineeringToolBox – Ductwork pressure loss

2. ASHRAE Fundamentals Handbook

The ASHRAE Handbook recommends:

 Target pressure losses per metre of duct:


o Main ducts: 0.8–1.2 Pa/m
o Branches: 0.5–1.0 Pa/m
 Typical total allowable loss in a well-designed supply system: <250 Pa from fan
outlet to terminal.
Recommended Minimum Branch Lengths (From the Main Duct Takeoff):

🔹 For Rectangular or Round Ducts:

 Straight branch run after takeoff (before any bends or terminals):


Minimum 4 to 6 times the branch diameter (4–6 × D)

Example: For a 200 mm diameter branch, the straight length before a bend,
elbow, or diffuser should be 800–1200 mm.

🔹 Before a branch takeoff (from the main duct):

 Leave 3 to 5 times the branch diameter of straight duct upstream of the takeoff.

This allows uniform airflow approaching the branch and avoids eddies from
nearby fittings.

total required air supply (m³/s)


Stage 1: Determine Total Required Flow

1. Start with known loads:


o Your system must supply 4 m³/s of fresh air (likely to high-occupancy or
process areas).
o Now, determine how much additional air is needed for vestibules and any
other zones.
2. Typical flowrate recommendations for vestibules (to maintain overpressure):
o 0.3 to 0.5 m³/s per vestibule (depending on size, door usage, and adjacent
pressure zones)
o Example:
 If you have 3 vestibules:
👉 3 × 0.4 m³/s = 1.2 m³/s
3. Total system supply:
o Main process area: 4 m³/s
o Vestibules: 1.2 m³/s
➤ Total: 5.2 m³/s

Stage 2: Duct Sizing Based on Total Flow

Your main duct must be sized for 5.2 m³/s.


Using a velocity of 6 m/s, you’d need:
A square duct of approximately 950 mm × 950 mm
Or a round duct with diameter ≈ 1,050 mm

🔹 Step 3: Flow Distribution to Branches

Assign flowrates to each branch based on:

 Room air change requirements (ACH)


 Room function & pressure requirement
 Size (volume)

Distribute like this:

Zone Flowrate (m³/s) Notes


Portioning/Process 4.0 High occupancy or process load
Vestibule 1 0.4 To pressurize and block infiltration
Vestibule 2 0.4
Vestibule 3 0.4
Total 5.2

🔹 Step 4: Duct Branching

 Main duct supplies 5.2 m³/s


 Install dampers at each branch to regulate flow
 Use manual or automatic volume control dampers (VCDs)
 Balance system with commissioning airflow measurements

✅ Summary

 Determine air demand per zone based on occupancy, purpose, and pressurization
goals.
 Size your main duct for total required flow.
 Distribute flow to branches by assigning realistic flowrates and install control
dampers for tuning.

To size ducts for 0.4 m³/s to each vestibule, follow this simple process:

🔹 Step 1: Choose Design Velocity

For vestibule supply ducts, use a moderate velocity to:

 Prevent noise
 Avoid excessive pressure drop

Recommended range:

 4–5 m/s (industry standard for branch ducts to small rooms)

Let’s go with 4.5 m/s.

🔹 Step 2: Apply Duct Sizing Formula

A=QVA = \frac{Q}{V}A=VQ

Where:

 AAA = area in m²
 QQQ = airflow in m³/s (0.4 m³/s)
 VVV = velocity in m/s (4.5 m/s)

A=0.44.5=0.0889 m2A = \frac{0.4}{4.5} = 0.0889 \text{ m}^2A=4.50.4=0.0889 m2

🔹 Step 3: Convert to Duct Dimensions

📦 Rectangular Duct:

Choose standard aspect ratio, say 1:2 (height × width).

Let height = 300 mm


Then width =

0.08890.3=0.2967 m= 300 mm\frac{0.0889}{0.3} = 0.2967 \text{ m} = \


text{~}300 mm0.30.0889=0.2967 m= 300 mm

✅ 300 mm × 300 mm duct (a square option that’s easy to fabricate)

🔵 Circular Duct:

A=πD24⇒D=4Aπ=4×0.0889π≈0.336 mA = \frac{\pi D^2}{4} \Rightarrow D = \sqrt{\


frac{4A}{\pi}} = \sqrt{\frac{4×0.0889}{\pi}} ≈ 0.336 mA=4πD2⇒D=π4A=π4×0.0889
≈0.336 m

✅ Use Ø350 mm circular duct

🔹 Summary Table
Flowrate Velocity Area Needed Rectangular Duct Circular Duct
0.4 m³/s 4.5 m/s 0.089 m² 300 × 300 mm Ø350 mm

For grille/diffuser sizing in your vestibule with an airflow of 0.4 m³/s, here’s how to select
the appropriate size:

🔹 Step 1: Target Face Velocity

To ensure quiet operation and proper throw in small areas like vestibules:

 Recommended face velocity: 2.0 – 2.5 m/s


(per ASHRAE and typical SANS acoustic best practices)

Let’s use 2.2 m/s as our target.

🔹 Step 2: Calculate Grille Area

A=QV=0.42.2=0.182 m2A = \frac{Q}{V} = \frac{0.4}{2.2} = 0.182 \text{ m}^2A=VQ


=2.20.4=0.182 m2

🔹 Step 3: Select Standard Grille/Diffuser Size

Choose a standard rectangular supply grille size close to this area:

Size (mm) Area (m²)


600 × 300 0.18
625 × 300 0.187
600 × 400 0.24

✅ 600 × 300 mm grille = 0.18 m², perfect for 0.4 m³/s @ 2.2 m/s face velocity.

🔹 Optional – Circular Diffuser (if ceiling-mounted)

If using a ceiling diffuser:

D=4Aπ=4×0.182π≈0.48 mD = \sqrt{\frac{4A}{\pi}} = \sqrt{\frac{4×0.182}{\pi}} ≈ 0.48 \


text{ m}D=π4A=π4×0.182≈0.48 m

✅ Ø500 mm circular diffuser


🔹 Final Recommendation

Application Airflow (m³/s) Grille Type Size Velocity (m/s)


Vestibule 0.4 Supply grille 600 × 300 mm ~2.2
Vestibule 0.4 Diffuser (opt.) Ø500 mm ~2.2

You might also like