I & O Instructions
I & O Instructions
English (GB)
Installation and operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3
English (GB)
4
English (GB)
7.50 Description of control mode . . . . . . . . . 64 1.2 Notes
7.51 Assisted fault advice . . . . . . . . . . . . . 64 The symbols and notes below may appear in
7.52 Factory settings . . . . . . . . . . . . . . . . 65 Grundfos installation and operating instructions,
safety instructions and service instructions.
8. Servicing the product . . . . . . . . . . . . 66
8.1 Motor . . . . . . . . . . . . . . . . . . . . . 66
8.2 Pump . . . . . . . . . . . . . . . . . . . . . 66 Observe these instructions for explosion-
proof products.
8.3 Cleaning the product . . . . . . . . . . . . . 66
9. Technical data . . . . . . . . . . . . . . . . 66
9.1 Operating conditions . . . . . . . . . . . . . 66 A blue or grey circle with a white graphical
9.2 Electrical data . . . . . . . . . . . . . . . . . 68 symbol indicates that an action must be
taken.
9.3 Megging . . . . . . . . . . . . . . . . . . . . 70
9.4 Other technical data . . . . . . . . . . . . . 70
9.5 Accessories . . . . . . . . . . . . . . . . . . 71 A red or grey circle with a diagonal bar,
possibly with a black graphical symbol,
9.6 Sound pressure level . . . . . . . . . . . . . 71
indicates that an action must not be taken
10. Disposing of the product . . . . . . . . . . 72 or must be stopped.
DANGER
Indicates a hazardous situation which, if
not avoided, will result in death or serious
personal injury.
WARNING
Indicates a hazardous situation which, if
not avoided, could result in death or
serious personal injury.
CAUTION
Indicates a hazardous situation which, if
not avoided, could result in minor or
moderate personal injury.
SIGNAL WORD
Description of the hazard
Consequence of ignoring the warning
• Action to avoid the hazard.
5
English (GB)
6
English (GB)
In some cases, an external antenna may be required. CAUTION
Only Grundfos-approved external antennas may be Crushing of feet
connected to this product, and only by a Grundfos- Minor or moderate personal injury
approved installer.
‐ Wear safety shoes.
2.4 Battery ‐ Attach lifting equipment to the motor
eyebolts.
A Li-ion battery is fitted in the CRE, CRIE, CRNE,
SPKE, MTHE and MTRE pumps. The Li-ion battery
complies with the Battery Directive (2006/66/EC). The
battery does not contain mercury, lead or cadmium. Do not lift the product by the terminal box.
WARNING
4.1 Mounting
Falling objects CAUTION
Death or serious personal injury Crushing of feet
‐ Do not use the motor eyebolts to lift the Minor or moderate personal injury
entire pump if the pump is fitted with a ‐ Fasten the pump securely to a solid
motor of another make than Grundfos and even foundation according to the
MG and MGE. specifications in the installation and
‐ Follow the lifting instructions. operating instructions for the pump.
‐ Use lifting equipment that is approved
for the weight of the product. The product must be installed in a location
with access control to prevent
‐ Persons must keep a safe distance unauthorized access to the product.
from the product during lifting
operations.
‐ Wear personal protective equipment. The product must only be connected to
protected network subnets with strict
access control.
For lifting instructions, see the related
installation and operating instructions for
the pump. 4.2 Cable entries
See the size of the cable entries in the section on
3.2 Inspecting the product other technical data.
CAUTION
Back injury
Minor or moderate personal injury
‐ Use lifting equipment.
7
English (GB)
4.4 Cooling the motor • Connect the product permanently to the mains
supply and activate the built-in standstill heating
• Install the motor allowing a distance of minimum
function.
50 mm (D) between the end of the fan cover and
the wall or another fixed object. Related information
4.6 Drain holes
7.25 Standstill heating
B3 B14 B5
TM071139
TM029037
D
• Position the product with sufficient space around.
• Make sure that the temperature of the cooling air
does not exceed 50 °C. 5. Electrical connection
• Keep cooling fins and fan blades clean.
DANGER
Electric shock
4.5 Installing the product outdoors or in Death or serious personal injury
areas with high humidity
‐ Switch off the power supply to the
If you install the product outdoors or in areas with motor and to the signal relays. Wait at
high humidity, take the following action to avoid least 5 minutes before you make any
condensation on the electronic components. connections in the terminal box. Make
sure that the power supply cannot be
To maintain the UL mark, additional switched on accidentally.
requirements apply to the equipment. See
the appendix concerning installation in the DANGER
USA and Canada. Electric shock
Death or serious personal injury
• Provide the product with a suitable cover.
‐ Check that the supply voltage and
The cover must be large enough to ensure that
frequency correspond to the values
the product is not exposed to direct sunlight, rain
stated on the nameplate.
or snow. Grundfos does not supply covers.
If the power cable is damaged, it must be replaced by
When fitting a cover to the product, the manufacturer, the manufacturer's service partner
observe the instructions for adequate or a similarly qualified person.
cooling. The user or the installer is responsible for correct
earthing and protection according to local regulations.
All operations must be carried out by a qualified
electrician.
TM053496
8
English (GB)
5.1 Protection against electric shock, 3 × 200-240 V
indirect contact Cross section
Power Conductor
WARNING [kW] type [mm2] [AWG]
Electric shock
Death or serious personal injury Solid 1.5 - 10 16-8
1.1 - 1.5
‐ Connect the product to protective earth Stranded 1.5 - 10 16-8
and provide protection against indirect
contact in accordance with local Solid 2.5 - 10 14-8
2.2 - 5.5
regulations. Stranded 2.5 - 10 14-8
Protective-earth conductors must have a yellow and
green (PE) or yellow, green and blue (PEN) colour 5.2.2 Conductors
marking.
Type
5.1.1 Protection against mains voltage transients The conductors are stranded or solid copper.
The product is protected against mains voltage
Temperature rating
transients in accordance with EN 61800-3.
Temperature rating for conductor insulation: 60 °C
5.1.2 Motor protection (140 °F).
The product incorporates thermal protection against Temperature rating for outer cable sheath: 75 °C
slow overloading and blocking. No external motor (167 °F).
protection is required.
Model H, I: The product includes load- and speed- 5.3 Power supply
sensitive motor-overload protection.
DANGER
Model J: The product includes load- and speed-
Electric shock
sensitive motor-overload protection.
Death or serious personal injury
Model K: The product includes load- and speed-
‐ Use the recommended fuse size.
sensitive motor-overload protection with thermal
memory retention.
Related information
5.2 Cable requirements 9.2.1.1 Supply voltage
Cross section The wires in the motor terminal box must be as short
Power Conductor
as possible. Excepted from this is the separated earth
[kW] type [mm2] [AWG] conductor which must be so long that it is the last one
Solid 1.5 - 2.5 16-12 to be disconnected in case the cable is inadvertently
0.25 - 1.5 pulled out of the cable entry.
Stranded 1.5 - 2.5 16-12 For maximum backup fuse, see the section on supply
voltage.
3 × 380-500 V
9
English (GB)
TM078919
L L
PE
Corner earthing is not allowed for supply
voltages above 3 × 240 V and 3 × 480 V,
Example of a mains-connected motor with a main 60 Hz.
switch, backup fuse and additional protection
L1 L1
Pos. Description L2 L2
TM078920
L3 L3
1 RCD, type B PE
PE
L
N
TM053495
L3
Related information L2
L1
9.2.1.1 Supply voltage PE
10
English (GB)
The total leakage current of all the electrical Related information
equipment in the installation must be taken into 9.4 Other technical data
account. You find the leakage current of the motor in
the sections on leakage current and leakage current 5.5.1 Connection terminals, CRE, CRIE, CRNE,
(AC). SPKE and MTRE pumps
This product can cause a direct current in the The CRE, CRIE, CRNE, SPKE and MTRE pumps
protective earth conductor. have a number of inputs and outputs enabling the
pumps to be used in advanced applications where
Overvoltage and undervoltage protection many inputs and outputs are required.
Overvoltage and undervoltage may occur in case The pumps have the following connections:
of unstable power supply or faulty installation. The
• three analog inputs
motor stops if the voltage falls outside the permissible
voltage range. The motor restarts automatically when • one analog output
the voltage is again within the permissible voltage • two dedicated digital inputs
range. Therefore, no additional protection relay is • two configurable digital inputs or open-collector
required. outputs
The motor is protected against transients • Grundfos Digital Sensor input and output
from the power supply according to EN • two Pt100/1000 inputs
61800-3. In areas with high lightning • two LiqTec sensor inputs
intensity, we recommend external lightning • two signal relay outputs
protection.
• GENIbus connection.
Overload protection See the figure below.
If the upper load limit is exceeded, the motor Digital input 1 is factory-set to be start-stop
automatically compensates for it by reducing the input where open circuit results in stop. A
speed and stops if the overload condition persists. jumper is factory-fitted between terminals
The motor remains stopped for a set period. After this 2 and 6. Remove the jumper if digital input
period, the motor automatically attempts to restart. 1 is to be used as external start-stop or
The overload protection prevents damage to the any other external function.
motor. Consequently, no additional motor protection
is required. DANGER
Electric shock
Overtemperature protection Death or serious personal injury
The electronic unit has a built-in temperature sensor ‐ Make sure that the wires to be
as an additional protection. When the temperature connected to the connection groups
rises above a certain level, the motor automatically below are separated from each other
compensates for it by reducing the speed and stops by reinforced insulation in their entire
if the temperature keeps rising. The motor remains lengths.
stopped for a set period. After this period, the motor
automatically attempts to restart.
Related information
9.2.1.2 Leakage current
9.2.2.2 Leakage current (AC)
11
English (GB)
3 GND
15 +24 V
8 +24 V
26 +5 V
23 GND
25 GDS TX
TM078921
+24 V* +24 V* +24 V*/5 V*
+ +
24 GDS RX
+5 V* 7 AI2
12
English (GB)
Terminal Type Function Terminal Type Function
Normally closed Supply to
NC
contact 5 +5 V potentiometer and
Signal relay 1 sensor
C1 Common
(LIVE or PELV) 6 GND Ground
Normally open
NO
contact A GENIbus, A GENIbus, A (+)
Normally closed Y GENIbus, Y GENIbus, GND
NC
contact
Signal relay 2 B GENIbus, B GENIbus, B (-)
C2 Common
(PELV only) 3 GND Ground
Normally open
NO 15 +24 V Supply
contact
8 +24 V Supply
18 GND Ground
Supply to
Digital input/output,
26 +5 V potentiometer and
configurable
sensor
11 DI4/OC2 Open collector: Max.
24 V resistive or 23 GND Ground
inductive Grundfos Digital
25 GDS TX
Pt100/1000 Pt100/1000 sensor Sensor output
19
input 2 input Grundfos Digital
24 GDS RX
Pt100/1000 Pt100/1000 sensor Sensor input
17
input 1 input Analog input:
Analog output: 0-20 mA / 4-20 mA
7 AI2
12 AO 0-20 mA / 4-20 mA 0.5 - 3.5 V / 0-5 V /
0-10 V 0-10 V
9 GND Ground
Analog input:
14 AI3 0-20 mA / 4-20 mA
0-10 V
Digital input,
1 DI2
configurable
LiqTec sensor LiqTec sensor input
21
input 1 (white conductor)
Ground (brown and
20 GND
black conductors)
LiqTec sensor LiqTec sensor input
22
input 2 (blue conductor)
Digital input/output,
configurable.
10 DI3/OC1 Open collector: Max.
24 V resistive or
inductive.
Analog input:
0-20 mA / 4-20 mA
4 AI1
0.5 - 3.5 V / 0-5 V /
0-10 V
Digital input,
2 DI1
configurable
13
English (GB)
NC
Digital input 1 is factory-set to be start-stop C2
input where open circuit results in stop. A OC DI
NO
+24 V* GND
jumper is factory-fitted between terminals 10 DI3/OC1
4 AI1
2 and 6. Remove the jumper if digital input +24 V* +24 V* +24 V*/5 V* 2 DI1
1 is to be used as external start-stop or + +
5 +5 V
any other external function. 6 GND
A GENIbus A
Y GENIbus Y
DANGER B GENIbus B
Electric shock 3 GND
Death or serious personal injury 15 +24 V
TM078922
+ +
14
English (GB)
Terminal Type Function 5.7 Bus connection cable
Digital input, 5.7.1 Connecting a 3-core bus cable, GENIbus
2 DI1
configurable For the bus connection, use a screened 3-core cable
Supply to potentiometer with a cross-sectional area of minimum 0.5 mm2 and
5 +5 V
and sensor maximum 1.5 mm2.
6 GND Ground • If the motor is connected to a unit with a cable
clamp identical to the one on the product, connect
A GENIbus, A GENIbus, A (+) the screen to the cable clamp.
Y GENIbus, Y GENIbus, GND • If the unit has no cable clamp, leave the screen
unconnected at this end.
B GENIbus, B GENIbus, B (-)
3 GND Ground
15 +24 V Supply
A A
8 +24 V Supply Y Y
B B
TM070223
Supply to potentiometer
26 +5 V
and sensor
23 GND Ground
Grundfos Digital Sensor 5.7.2 Replacing a motor
25 GDS TX
output If a 2-core cable is used in the installation, connect it
as shown in the figure below.
Grundfos Digital Sensor
24 GDS RX
input M
Analog input:
0-20 mA / 4-20 mA A 1 1 A
7 AI2 Y Y
TM079070
2
0.5 - 3.5 V / 0-5 V / B
2
B
0-10 V
15
English (GB)
C NO NC C NO NC C NO NC C NO NC C NO NC
Normal
Min.
or
C NO NC C NO NC C NO NC C NO NC C NO NC Max.
Manual
C NO NC C NO NC C NO NC C NO NC C NO NC
Stop
C NO NC C NO NC C NO NC C NO NC C NO NC
16
English (GB)
Grundfos Eye is rotating yellow
There is a warning, but the pump is running.
Normal
Min.
or
C NO NC C NO NC C NO NC C NO NC C NO NC Max.
Manual
C NO NC C NO NC C NO NC C NO NC C NO NC
Stop
C NO NC C NO NC C NO NC C NO NC C NO NC
Normal
Min.
or
C NO NC C NO NC C NO NC C NO NC C NO NC Max.
17
English (GB)
Manual
C NO NC C NO NC C NO NC C NO NC C NO NC
Stop
C NO NC C NO NC C NO NC C NO NC C NO NC
6. Control functions If the power supply to the pump is switched off, the
settings are stored.
6.1 User interfaces Related information
WARNING 6.2 Standard operating panel
Hot surface 6.3 Advanced operating panel
Death or serious personal injury
6.4 Grundfos GO
‐ Only touch the buttons on the display
as the product may be very hot. 7.2 Setpoint
DANGER
Electric shock
Death or serious personal injury
‐ If the operating panel is cracked or
perforated, replace it immediately.
Contact the nearest Grundfos sales
company.
Operating panels
• Standard operating panel.
• Advanced operating panel.
Remote controls
• Grundfos GO
• Grundfos R100 remote control. See the section on
description of functions starting with the section
on setpoint.
18
English (GB)
6.2 Standard operating panel 6.2.1 Setting the setpoint in constant parameter
mode
TM054894
Up/Down: The buttons change the
3
setpoint.
0
Radio communication: The button
enables radio communication with Related information
4
the Grundfos GO and other products
of the same type. 7.8 Analog inputs
Start/Stop: Press the button to 6.2.2 Setting the setpoint in constant curve mode
make the product ready for Set the desired setpoint by pressing the Up or Down
operation or to start and stop the buttons.
product.
The green light fields on the operating panel indicate
Start: If you press the button when
the setpoint set.
the product is stopped, the product
5 starts if no other functions with Example: In Constant curve mode, the motor output
higher priority have been enabled. is between minimum and maximum speed defined by
Stop: If you press the button when Operating range.
the product is running, the product
always stops. When you press the
button, the stop icon appears at the
bottom of the display.
Related information
6.5 Grundfos Eye
7.1 Priority of settings
19
English (GB)
Related information
6.2.3 Setting to maximum speed 7.1 Priority of settings
The motor must not be in operating mode Stop. 6.2.7 Resetting alarms and warnings in products
• Press and hold the Up button until the top light with a standard operating panel
field is on and starts flashing. You can reset a fault indication in one of the following
ways:
H
• Briefly press the Up or Down button.
This is not possible if the buttons have been
locked.
This does not change the setting of the motor.
• Switch off the power supply until the indicator
lights are off.
• Switch the external start and stop input off, and
then on again.
TM054896
H
TM054897
20
English (GB)
6.3 Advanced operating panel Pos. Symbol Description
Left/Right: Press the buttons to
navigate between main menus,
1 displays and digits. When you
change the menu, the display shows
the top display of the new menu.
Up/Down:
2 Press the buttons to navigate
between submenus or change the
value settings.
If you have disabled the possibility
6 3 to make settings with the Enable/
disable settings function, you can
4
enable it again temporarily by
5 pressing these buttons
simultaneously for at least 5
TM054849 seconds.
OK:
4 Press the button to do the following:
• save changed values, reset
Pos. Symbol Description
alarms and expand the value
Grundfos Eye: field
1 The indicator light shows the • enable radio communication with
operating status of the product. the Grundfos GO and other
products of the same type.
2 - Graphical colour display.
When you try to establish radio
Back: communication between the product
3 Press the button to go one step and the Grundfos GO or another
back. product, the green indicator light in
the Grundfos Eye flashes. In the
controller display, a note states that
a wireless device wants to connect
to the product. Press OK on the
product operating panel to allow
radio communication with the
Grundfos GO and other products of
the same type.
Start/Stop: Press the button to
make the product ready for
operation or to start and stop the
product. Start: If you press the
button when the product is stopped,
the product starts if no other
5
functions with higher priority have
been enabled. Stop: If you press the
button when the product is running,
the product always stops. When you
press the button, the stop icon
appears at the bottom of the display.
Home: Press the button to go to the
6
Home menu.
21
English (GB)
Normal
4.90 bar
TM064516
1 2
9 8 7 6 5
Control modeContro
It indicates that the pump has5.00been
bar Const. pressure
5
5.00 bar
stopped via the button. Operaring mode
Operaring mode
Normal
Actual
Con
Actual controlled value
Normal
4.
22
Status Settings Assist
1 2 3
English (GB)
Setpoint Control mode
8
operating in a multipump system.
See the section on Multipump
4.90 bar
Status Settings Assist
Related information
7.42 Run start-up guide
23
English (GB)
6.3.3.2 Status
CRE, CRIE,
Multipump
Status CRNE, SPKE, MTHE, CME
system
MTRE
Operating status ● ● ●
Operating mode, from ● ● ●
Control mode ● ● ●
Pump performance ● ● ●
Actual control. value ● ● ●
Resulting setpoint ● ● ●
Speed ● ● ●
Acc. flow and specific energy ● ● ●
Power and energy consumption ● ● ●
Measured values ● ● ●
Analog input 1 ● ● ●
Analog input 2 ● ● ●
Analog input 3 ● ● 1) ● 1)
Pt100/1000 input 1 ● ● 1) ● 1)
Pt100/1000 input 2 ● ● 1) ● 1)
Analog output ● ● 1) ● 1)
Warning and alarm ● ● ●
Actual warning or alarm ● ● ●
Warning log ● ● ●
Alarm log ● ● ●
Operating log ● ● ●
Operating hours ● ● ●
Fitted modules ● ● ●
Date and time ● ● ●
Product identification ● ● ●
Motor bearing monitoring ● ● ●
Multi-pump system ●
24
English (GB)
CRE, CRIE,
Multipump
Status CRNE, SPKE, MTHE, CME
system
MTRE
System operating status ●
System performance ●
System input power and energy ●
Pump 1, multi-pump system ●
Pump 2, multi-pump system ●
Pump 3, multi-pump system ●
Pump 4, multi-pump system ●
6.3.3.3 Settings
CRE, CRIE,
Multipump
Settings CRNE, SPKE, MTHE, CME
system
MTRE
Setpoint ● ● ●
Operating mode ● ● ●
Set manual speed ● ● ●
Set user-defined speed ● ● ●
Control mode ● ● ●
Setting the proportional pressure ● ● ●
Analog inputs ● ● ●
Analog input 1, setup ● ● ●
Analog input 2, setup ● ● ●
Analog input 3, setup ● ● 2) ● 2)
Pt100/1000 inputs ● ● 2) ● 2)
Pt100/1000 input 1, setup ● ● 2) ● 2)
Pt100/1000 input 2, setup ● ● 2) ● 2)
Digital inputs ● ● ●
Digital input 1, setup ● ● ●
Digital input 2, setup ● ● 2) ● 2)
Digital inputs/outputs ● ● ●
Digital input/output 3, setup ● ● ●
Digital input/output 4, setup ● ● 2) ● 2)
"Signal relays" 1 and 2 (Relay outputs) ● ● ●
Relay output 1 ● ● ●
Relay output 2 ● ● ●
Analog output ● ● 2) ● 2)
25
English (GB)
CRE, CRIE,
Multipump
Settings CRNE, SPKE, MTHE, CME
system
MTRE
Output signal ● ● 2) ● 2)
Function of analog output ● ● 2) ● 2)
Controller settings ● ● ●
Operating range ● ● ●
Setpoint influence ● ● ●
External setpoint function ● ● ●
Predefined setpoints ● ● 2) ● 2)
Monitoring functions ● ● ●
Motor bearing monitoring ● ● ●
Motor bearing maintenance ● ● ●
Limit-exceeded function ● ● ●
LiqTec function ● ● ●
Alarm handling ● ● ●
Special functions ● ● ●
Stop function (Low-flow stop function) ● ● ●
Stop at min. speed ● ● ●
Pipe filling function ● ● ●
Pulse flowmeter setup ● ● ●
Ramps ● ● ●
Standstill heating ● ● ●
Communication ● ● ●
Pump number ● ● ●
Enable/disable radio communication ● ● ●
General settings ● ● ●
Language ● ● ●
Set date and time ● ● ●
Units ● ● ●
Enable/disable settings ● ● ●
Delete history ● ● ●
Define Home display ● ● ●
Display settings ● ● ●
Store actual settings ● ● ●
Recall stored settings ● ● ●
Run start-up guide ● ● ●
26
English (GB)
6.3.3.4 Assist
Normal
You can choose between the following
communication types: 4.90
• radio communication
1
• infrared communication.
Related information
27
English (GB)
Resulting setpoint ● ●
Resulting system setpoint ● 3)
Actual controlled value ● ● ● 3)
Motor speed ● ●
Power consumption ● ●
Power cons., system ● 3)
Energy consumption ● ●
Energy cons., system ● 3)
Acc. flow, specific energy ● ● ● 3)
Operating hours ● ●
Operating hours, system ● 3)
Pt100/1000 input 1 ● ● 4)
Pt100/1000 input 2 ● ● 4)
Analog output ● ● 4)
Analog input 1 ● ●
Analog input 2 ● ●
Analog input 3 ● ● 4)
Digital input 1 ● ●
Digital input 2 ● ● 4)
Digital in/output 3 ● ●
Digital in/output 4 ● ● 4)
Fitted modules ● ●
Pump 1 ● 3)
28
English (GB)
CRE, CRIE, CRNE,
Status CME Multipump system
SPKE, MTRE
Pump 2 ● 3)
Pump 3 ● 3)
Pump 4 ● 3)
29
English (GB)
Standstill heating ● ●
Alarm handling ● ● ●
Motor bearing monitoring ● ●
Service ● ●
Set date and time ● ● 4)
Store actual settings ● ●
Recall stored settings ● ●
Undo ● ● ●
Pump name ● ● ●
Connection code ● ● ●
Units ● ●
30
English (GB)
6.5 Grundfos Eye
The operating condition of the pump is indicated by A
the Grundfos Eye on the operating panel.
TM055993
Grundfos Eye indicator light (A)
Power off
No lights are on.
The motor is not running.
Power on
Two opposite green
indicator lights are The motor is running. The indicator lights are rotating
rotating. in the direction of rotation of the motor when seen from
the non-drive end.
Warning
One yellow indicator light The motor is running. The indicator light is rotating in
is rotating. the direction of rotation of the motor when seen from
the non-drive end.
31
English (GB)
The green indicator light in The Grundfos Eye flashes four times when you press
the middle flashes quickly the Grundfos Eye symbol next to the motor name in
four times. the Grundfos GO.
32
English (GB)
6.6 Bus signal 1. Loosen the four screws (A) and remove the
terminal box cover (B).
The pump supports serial communication via an
RS-485 input. The communication is carried out
according to the Grundfos GENIbus protocol and
enables connection to other pumps as well as a
building management system or another external
A
control system.
Via a bus signal, you can set pump operating
parameters remotely, such as setpoint and operating
mode. At the same time, via the bus, the pump
can provide status information about important
parameters, such as the actual value of the control
parameter, input power and fault indications. B
Contact Grundfos for further information.
TM064081
Grundfos GO are reduced.
33
English (GB)
3. Remove the screw (E). 7. Connect the cable screens of the bus cables to
protective earth via one of the earth clamps (H).
H
TM069906
TM069908
4. Fit the module by aligning it with the three plastic
holders (F) and the connection plug (G). Press the
module home, using your fingers.
F
G
TM069907
34
English (GB)
8. Route the wires for the module through one of the 10. If the module is supplied with an FCC label, fix the
cable glands. label on the terminal box.
TM069909
TM064085
FCC
11. Fit the terminal cover and cross-tighten the four
MGE 71, 80, 90 mounting screws to 6 Nm.
Related information
6.10 Changing the position of the operating panel
Grundfos GO
You can identify the functional module in the Fitted
modules menu under Status.
Motor display
TM070190
35
English (GB)
VARIANT VARIANT
Type : P.C. : INPUT
Hp PB :
OUTPUT VARIANT Type : P.C. : INPUT
Hp PB :
OUTPUT VARIANT
P.N. : Serial no : U in : P2 :
rpm FM :
Hp PB : P.N. : Serial no : U in : P2 :
rpm FM :
Hp PB :
Xxxxxxxxxxx
Xxxxxxxxxxx
E.P. Motor
E.P. Motor
DE : Env.Type : TEFC ~ V n max: rpm FM : DE : Env.Type : TEFC ~ V n max: rpm FM :
HMI : HMI :
NDE: SF : CL: f in : Hz Eff : HMI : Made in Hungary NDE: SF : CL: f in : Hz Eff : HMI : Made in Hungary
Wgt : kg Tamb : F PF: I SF Amp: A I 1/ 1 : A CIM : Wgt : kg Tamb : F PF: I SF Amp: A I 1/ 1 : A CIM :
CIM :
DK - 8850 Bjerringbro, Denmark
CIM :
DK - 8850 Bjerringbro, Denmark
TM061889
TM064013
Functional module variants Operating panel variants
36
English (GB)
1. Loosen the four screws (TX25) of the terminal box 4. Turn the plastic cover 180°.
cover.
180°
TM055354
TM064915 5. Position the plastic cover correctly over the four
rubber pins (C). Make sure that the locking tabs
(A) are placed correctly.
A
A
TM055355
C
A
TM055353
TM064929
37
English (GB)
3 Manual
Maximum speed 5)/User
4
defined speed
5 Stop
6 User defined speed
7 Stop
Maximum speed/User
8
defined speed
9 Minimum speed
10 Start
11 Maximum speed
12 Minimum speed
13 Minimum speed
14 Start
15 Start
5) Stop and Maximum speed settings made with the Grundfos GO or the operating panel can be overruled by another operating-
mode command sent from a bus, for example Start. If the bus communication is interrupted, the motor resumes its previous
operating mode, for example Stop, selected with the Grundfos GO or the operating panel.
38
English (GB)
• Min.: You can use the minimum curve mode in 7.5 Set user-defined speed
periods in which a minimum flow is required.
Use this function to set the motor speed in
When operating according to the minimum curve,
percentage of the maximum speed. When you set the
the pump operates like an uncontrolled pump.
operating mode to User-defined speed, the motor
• Max.: You can use the maximum curve mode starts running at the set speed.
in periods in which a maximum flow is required.
When operating according to the maximum curve, 7.6 Control mode
the pump operates like an uncontrolled pump.
The possible control modes are the following:
• Manual: The pump operates at a manually set
speed. In Manual the setpoint via bus is over- • Proportional pressure
ruled. • Constant pressure (Const. pressure)
• User-defined speed: The motor operates at a • Constant temperature (Const. temp.)
speed set by the user. • Constant differential pressure (Con. diff. press.)
All operating modes are illustrated in the figure below. • Constant differential temperature (Con. diff.
temp.)
H • Constant flow rate (Const. flow rate)
• Constant level (Const. level)
Max.
1 • Constant other value (Const. other val.)
• Constant curve (Const. curve.):
Requires a measured differential pressure and
2
pump data entered into the controller.
Related information
Min. 3 7.7.5 Pump data
7.52 Factory settings
TM064024
speed. 2
With the Grundfos GO, you can set the speed via the Q
Setpoint menu.
Proportional pressure
Related information
7.52 Factory settings
39
English (GB)
TM057880
Δp 7.6.3 Constant temperature
This control mode ensures a constant temperature.
It is a comfort control mode that can be used in
Proportional pressure domestic hot-water systems to control the flow rate
to maintain a constant temperature in the system.
Related information H
7.7.1 Control curve function
7.6.2 Constant pressure
t
We recommend this control mode if the pump is to
deliver a constant pressure, independently of the flow
rate in the system.
TM057900
H
Q
Constant temperature
examples below.
Example:
Q
One external temperature sensor
Constant pressure
TM057884
See the section on assisted pump setup.
The setting range is between 12.5 % and 100 % of t
the maximum head.
Example:
One external pressure sensor
t
TM057885
TM057881
p Related information
7.14 Controller settings
7.52 Factory settings
TM057882
40
English (GB)
H
p
TM057889
Δp
Related information
TM057901
7.14 Controller settings
Q 7.46 Assisted pump setup
7.52 Factory settings
Constant differential pressure
7.6.5 Constant differential temperature
The setting range is between 12.5 % and 100 % of The pump maintains a constant differential
the maximum head. This control mode requires either temperature in the system, and the pump
an internal or external differential-pressure sensor, performance is controlled according to this.
or two external pressure sensors as shown in the
examples below. H
Examples:
• One external differential-pressure sensor:
t
The pump uses the input from the sensor to
control the differential pressure.
You can set the sensor manually or via the Assist
menu. See the section on assisted pump setup.
TM057954
Q
Δp
This control mode requires either two temperature
sensors or one external differential-temperature
sensor. See the examples below.
The temperature sensors can either be analog
sensors connected to two of the analog inputs, or
two Pt100/1000 sensors connected to the Pt100/1000
TM057887
p p
41
English (GB)
Related information
t 7.14 Controller settings
7.52 Factory settings
TM057894
Δt
7.6.7 Constant level
t
The pump maintains a constant level independently
• One external differential-temperature sensor: of the flow rate.
The pump uses the input from the sensor to H
control the differential temperature.
You can set the sensor manually or via the Assist
menu. See the section on assisted pump setup.
TM057931
TM057941
Δt
L
TM057955
Q TM057896
1
Constant flow rate • One external level sensor with filling function
L
This control mode requires an external flow sensor.
See the example below.
Example:
TM057965
Related information
TM057895
42
English (GB)
7.6.8 Constant other value 7.8 Analog inputs
Use this control mode to control a value not The available inputs depend on the functional module
available in the Control mode menu. To measure fitted in the pump:
the controlled value, connect a sensor to one of
the analog inputs. The controlled value is shown in
percentage of the sensor range. FM 200 6) FM 300 6)
Function (terminal)
(standard) (advanced)
Related information
Analog input 1,
7.52 Factory settings ● ●
setup (4)
7.6.9 Constant curve
Analog input 2,
You can set the pump to operate according to a ● ●
setup (7)
constant curve, like an uncontrolled pump.
Analog input 3,
The desired speed can be set in percentage of the - ●
setup (14)
maximum speed in the range from 13 to 100 %.
6) See the section on identification of the functional module.
H
If you want to set the analog input for a feedback
sensor, we recommend that you do this via the
Assisted pump setup menu. See the section on
assisted pump setup.
If you want to set an analog input for other purposes,
you can do this manually.
You can set the analog inputs via the Setup, analog
input menu. See the section on setup, analog input.
TM057957
43
English (GB)
5 Electrical signal
11
1 DPT 3 13 6 14
Q Select signal type:
PT PT TT PT TT
• 0.5-3.5 V
2 4 12 8 16 15
7
DPT DPT Q • 0-5 V
PT DPT DTT TT
• 0-10 V
• 0-20 mA
9 10
• 4-20 mA.
LT LT
Sensor range, minimum value
Set the minimum value of the connected sensor.
TM062328
Sensor range, maximum value
Set the maximum value of the connected sensor.
Press. 1, external 6
Analog input Analog input for
Press. 2, external 7 Parameter
for sensor 1 sensor 2
Diff. press., ext. 8 Pressure, Differential Differential
Storage tank level 9 option 1 pressure, inlet pressure, outlet
44
English (GB)
If you want to set the Pt100/1000 input for a feedback FM 200 8) FM 300 8)
sensor, we recommend that you do this via the Function (terminal)
Assisted pump setup menu. See the section on (standard) (advanced)
assisted pump setup. Digital input 1, setup
● ●
If you want to set a Pt100/1000 input for other (2 and 6)
purposes, you can do this manually.
Digital input 2, setup
You can set the analog inputs via the Setup, analog - ●
(1 and 9)
input menu. See the section on setup, analog input.
If you make the manual setting via the Grundfos GO, 8) See the section on the identification of the functional
you need to enter the menu for the Pt100/1000 input module.
under the Settings menu.
To set a digital input, make the settings below.
Function
The Pt100/1000 inputs can be set to the following Function
functions: Select one of the following functions:
• Not active • Not active: When set to Not active, the input has
• Feedback sensor: The sensor is used for the no function.
selected control mode. • External stop: When the input is deactivated
• Ext. setpoint infl.: See the section on the (open circuit), the pump stops.
external setpoint function. • Min. (minimum speed): When the input is
• Other function. activated, the pump runs at the set minimum
speed.
Measured parameter
• Max. (maximum speed): When the input is
Select one of the parameters listed to be measured in activated, the pump runs at the set maximum
the system by the PT100/1000 sensor connected to speed.
the actual PT100/1000 input. • User-defined speed: When the input is activated,
1 2 the motor runs at a speed set by the user.
TT TT • External fault: When the input is activated, a
timer is started. If the input is activated for more
TM064012
4 3
DTT than 5 seconds, the pump stops and a fault is
TT
indicated. This function depends on input from
external equipment.
Overview of PT100/1000 sensor locations • Alarm resetting: When the input is activated, a
possible fault indication is reset.
• Dry running: When this function is selected, lack
Parameter Pos. of inlet pressure or water shortage (dry running)
can be detected, and if that occurs, the pump
Liquid temp. 1 stops. The pump cannot restart as long as the
Temperature 1 2 input is activated. This requires the use of an
accessory, such as the following:
Temperature 2 3
- a pressure switch installed on the inlet side of
Ambient temp. Not shown the pump
- a float switch installed on the inlet side of the
Measuring range pump.
-50 to 204 °C. • Accumulated flow: When this function is
selected, the accumulated flow can be registered.
Related information This requires the use of a flowmeter that can give
6.8 Identification of the functional module a feedback signal as a pulse per defined volume
of water. See the section on pulse flowmeter
7.16 External setpoint function setup.
7.46 Assisted pump setup • Predefined setpoint digit 1 (applies only to
7.47 Setup, analog input digital input 2): When digital inputs are set to
7.52 Factory settings predefined setpoint, the pump operates according
to a setpoint based on the combination of
7.10 Digital inputs the activated digital inputs. See the section on
predefined setpoints.
Available inputs depend on the functional module
fitted in the pump:
45
English (GB)
DO 3/4
DI
1
TM064463
T input T input
A
T1 T2 T1
Example of configurable digital inputs/outputs
B
T1 T2 T1 T2
Pos. Description
TM064949
C 1 External controller
T1 T2 T1 T2
46
English (GB)
Possible functions, digital input/output 3 T input > T1 + T2 T input < T1 + T2
Function if output
Function if input
(See details in the DI
(See details in the T input T input
section on Signal
section on digital
relays 1 and 2 (Relay
inputs)
outputs)) A
T1 T2 T1
Not active Not active
External stop Ready B
Min. Alarm T1 T2 T1 T2
Max. Operation
TM064949
C
User-defined speed Pump running
T1 T2 T1 T2
External fault Warning
Alarm resetting Limit 1 exceeded
Dry running Limit 2 exceeded Duration timer function of digital inputs
Accumulated flow Digital input 1, state
Predefined setpoint Digital input 2, state Pos. Description
digit 2 Digital input 3, state
Active output DI Digital input
Digital input 4, state
Local motor stop A Mode A
B Mode B
Possible functions, digital input/output 4
C Mode C
Function if output
Function if input
(See details in the Related information
(See details in the
section on Signal
section on digital 6.8 Identification of the functional module
relays 1 and 2 (Relay
inputs ) 7.10 Digital inputs
outputs))
7.12 "Signal relays" 1 and 2 (Relay outputs)
Not active Not active
7.52 Factory settings
External stop Ready
Min. Alarm 7.12 "Signal relays" 1 and 2 (Relay outputs)
Max. Operation
The pump incorporates two signal relays for potential-
User-defined speed Pump running free signalling. For further information, see the
External fault Warning section on megging.
Alarm resetting Limit 1 exceeded
Function
Dry running Limit 2 exceeded
You can configure the signal relays to be activated by
Accumulated flow Digital input 1, state one of the following incidents:
Predefined setpoint Digital input 2, state • Not active
digit 3 Digital input 3, state • Ready: The pump can be running or is ready to
Active output Digital input 4, state run and no alarms are present.
Local motor stop • Alarm: There is an active alarm and the pump is
stopped.
Duration timer mode (only for input) • Operating (Operation): Operating equals Running
Select the duration timer mode: but the pump is still in operation when the pump
is stopped due to low flow. See the section on
• Not active
low-flow detection.
• active with interrupt (mode A)
• Running (Pump running): The pump is running.
• active without interrupt (mode B)
• Warning: There is an active warning.
• active with after-run (mode C).
• Digital input 1: If digital input 1 is activated, the
Select the duration time (T2). output is also activated.
It is the time that, together with the mode, determines • Digital input 2: If digital input 2 is activated, the
how long the selected function is active. output is also activated.
Range: 0 to 15,000 seconds. • Digital input 3: If digital input 3 is activated, the
output is also activated.
47
English (GB)
48
English (GB)
• Limit 1 exceeded and Limit 2 exceeded Constant
Kp Ti
differential pressure
Signal Limit-exceeded function
range Output not
[V, mA] Output active
active Δp
0.5 0.5
0-10 V 0V 10 V Δp
0-20 mA 0 mA 20 mA p p
4-20 mA 4 mA 20 mA
L1
Δp
Signal Flow rate
range [%]
[V, mA] 0 100 200 L1: Distance in metres between the pump and the
sensor.
0-10 V 0V 5V 10 V
0-20 mA 0 mA 10 mA 20 mA
Kp
4-20 mA 4 mA 12 mA 20 mA
Constant Heating Cooling Ti
temperature system system
The reading is a percentage of the range between 0 11) 12)
and 200 % of the nominal flow.
Related information
0.5 -0.5 10 + 5L2
6.8 Identification of the functional module t
L2
7.52 Factory settings
L2
7.14 Controller settings t
0.5 -0.5 30 + 5L2
The pumps have a factory default setting of gain (Kp)
and integral time (Ti).
However, if the factory setting is not the optimum 11) In
heating systems, an increase in pump performance
setting, you can change the gain and the integral results in a rise in temperature at the sensor.
time: 12) In
cooling systems, an increase in pump performance
• Set the gain within the range from 0.1 to 20. results in a drop in temperature at the sensor.
• Set the integral-action time within the range from
0.1 to 3600 seconds. If you select 3600 seconds, L2: Distance in metres between the heat exchanger
the controller functions as a PI controller. and the sensor.
Furthermore, you can set the controller to inverse
control. Constant differential
Kp Ti
This means that if you increase the setpoint, the temperature
speed is reduced. In case of inverse control, you
must set the gain within the range from -0.1 to -20.
Δt
Δt
t
L2
49
English (GB)
L2: Distance in metres between the heat exchanger 7.15 Operating range
and the sensor.
Set the operating range as follows:
1. Set the minimum speed within the range from
Constant flow rate Kp Ti fixed minimum speed (5) to user-set maximum
speed (2).
Q 0.5 0.5
2. Set the maximum speed within the range from
user-set minimum speed (4) to fixed maximum
speed (1).
Constant pressure Kp Ti The range between the user-set minimum and
maximum speed is the operating range (3).
0.5 0.5
100 % 1
p
p 0.5 0.5
67 % 2
Constant level Kp Ti
L
3
-10 0
10 0 24 % 4
10 % 5
TM069817
General rules of thumb:
0%
If the controller is too slow-reacting, increase the
gain.
If the controller is hunting or unstable, dampen the
system by reducing the gain or increasing the integral Pos. Description
time.
1 Fixed maximum speed
Related information 2 User-set maximum speed
7.52 Factory settings
3 Operating range
4 User-set minimum speed
5 Fixed minimum speed
Related information
7.52 Factory settings
50
English (GB)
7.16 External setpoint function Example with constant curve with linear influence
You can influence the setpoint by an external signal, Actual setpoint: actual input signal × (setpoint - user-
either via one of the analog inputs or, if an advanced set minimum speed) + user-set minimum speed.
functional module (FM 300) is fitted, via one of the At a user-set minimum speed of 25 %, and a setpoint
Pt100/1000 inputs. of 85 % and an external setpoint of 60 %, the actual
setpoint is the following:
Before you can enable the function, you
must set one of the analog inputs or 0.60 × (85 - 25) + 25 = 61 %
Pt100/1000 inputs to External setpoint
B
function.
100 C
See the sections on analog inputs and Pt100/1000
inputs. F 85
TM064525
[bar] 0 20 mA
4 20 mA
D -50 204 C
C
Example of setpoint influence with constant curve
2 100
F 1.2
Pos. Description
E 0 0
A External setpoint signal
0 A 100 % B B Speed [%]
0.5 3.5 V
0 5V C Fixed maximum speed
0 10 V
TM064165
51
English (GB)
0
0 100 % X 0
0.5 3.5 V X
0 5V 0 100 %
0.5 3.5 V
TM070255
0 10 V
0 20 mA 0 5V
TM070254
4 20 mA 0 10 V
-50 204 °C 0 20 mA
4 20 mA
-50 204 °C
Pos. Description
X External input signal from 0 to 100 % Pos. Description
Digital inputs
Pos. Description Setpoint
2 3 4
X External input signal from 0 to 100 %
0 0 0 Normal setpoint or Stop
Y Setpoint influence from 0 to 100 %
1 0 0 Predefined setpoint 1
A Normal
0 1 0 Predefined setpoint 2
B Stop
52
English (GB)
Digital inputs selected action can take place. You can set up to
Setpoint four limit-exceeded functions, meaning that you can
2 3 4 monitor four different parameters or two to four limits
1 1 0 Predefined setpoint 3 of the same parameter simultaneously.
Note that when using Limit 1-3 exceeded in a
0 0 1 Predefined setpoint 4 multipump system, the selected action has an impact
1 0 1 Predefined setpoint 5 on the system, for example, if Action is set to Stop,
then the system stops.
0 1 1 Predefined setpoint 6
Limit 4 exceeded in a multipump system is a local
1 1 1 Predefined setpoint 7 function. The selected action only has an impact on
the single pump, for example, if Action is set to Stop,
0: Open contact then only the single pump stops.
1: Closed contact
For Limit 4 exceeded in a multipump
Example system, the action always leads to a pump
stop, alarm and stop or a warning.
The figure shows how you can use the digital inputs
to set seven predefined setpoints. Digital input 2 is
The function requires setting the following
open, and digital inputs 3 and 4 are closed. If you
parameters:
compare with the table above, you can see that
Predefined setpoint 6 is activated. Measured
Set the measured parameter to be monitored.
DI 4 SP 7
Limit
DI 3 7 6 SP 6
5 Set the limit that activates the function.
DI 2 SP 5
4 Hysteresis band
SP 4
SPA 3 Set the hysteresis band for when the function must be
SP 3
2 deactivated again.
SP 2
1 Limit exceeded when
0 SP 1
Set the function to be activated when the selected
parameter exceeds or drops below the set limit.
TM070083
SP N • above limit:
Stop The function is activated if the measured
parameter exceeds the set limit.
• below limit:
Pos. Description
The function is activated if the measured
DI Digital input parameter drops below the set limit.
SP Setpoint Action
SPA Actual setpoint If the value exceeds a limit, you can set an action.
The following actions are available:
SPN Normal setpoint • Not active:
Stop Stop The pump remains in its current state. Use this
setting if you only want to activate a signal relay
If all digital inputs are open, the motor stops or runs output when the limit is reached.
at the normal setpoint. Set the desired action with • Stop:
the Grundfos GO or with the HMI 300 or HMI 301 The pump stops.
operating panel. • Min.:
Related information The pump reduces the speed to minimum speed.
7.52 Factory settings • Max.:
The pump increases the speed to maximum
7.18 Limit-exceeded function speed.
Use this function to monitor a measured parameter • User-defined speed:
or one of the internal values such as speed, motor The pump runs at a speed set by the user.
load or motor current. If a set limit is reached, a
53
English (GB)
TM070085
Measured parameter and Limit exceeded when A
functions.
5 6
X
The auto defined text can be overwritten by selecting
the alarm or warning text option Limit X exceeded.
The following list shows the auto-defined texts: X: Time in seconds
• Limit X exceeded Y: Pressure in bar
• Low inlet pressure
• High discharge pressure Pos. Parameter Setting
• High pressure 1 Measured Discharge pressure
• Low pressure
2 Limit 5 bar
• High temperature
• Low temperature 3 Hysteresis band 2 bar
• High flow 4 Limit exceeded when below limit
• Low flow
5 Detection delay 5 seconds
• High level
• Low level 6 Resetting delay 8 seconds
• High diff. pressure Limit-exceeded
A -
• Low diff. pressure function active
• High conductivity. - Action Warning
Detection in Stop
Related information
Enable this function to prevent the pump from
monitoring the limit while the pump is in the Stop 7.12 "Signal relays" 1 and 2 (Relay outputs)
state. 7.52 Factory settings
Resetting delay You can enable the function of the LiqTec sensors
in this display. A LiqTec sensor protects the pump
The resetting delay is the time from the point
against dry running.
when the measured parameter differs from the set
limit, including the set hysteresis band, to the point The function requires that a LiqTec sensor is fitted
when the function is reset. and connected to the pump.
54
English (GB)
When you enable the LiqTec function, it stops operation period are minimised. In this case,
the pump if dry running occurs. Restart the pump the stop function uses the factory-set values
manually if it stops due to dry running. of the minimum flow (Qmin2) and other internal
parameters. See the figure below.
Dry running detection delay
• User-defined mode (Customised operating
You can set a detection delay to make sure the mode): The pump uses the parameters set for
pump is given a chance to start up before the LiqTec ΔH and minimum flow (Qmin3) respectively for the
function stops it due to dry running.
stop function. See the figure below.
Range: 0-254 seconds.
H
Related information
7.52 Factory settings
TM064267
• High-comfort mode
• User-defined mode (Customised operating Q min2 Q min1 Q
Q min3
mode).
When the low-flow stop function is active, the flow Difference between start and stop pressures (ΔH)
is monitored. If the flow becomes lower than the and minimum flow rate
set minimum flow (Qmin), the pump changes from
continuous operation at constant pressure to start-
stop operation and stops if the flow reaches zero. Pos. Description
The advantages of enabling Low-flow stop function
1 Stop pressure
are the following:
• There is no unnecessary heating from the 2 Start pressure
pumped liquid.
• The wear of the shaft seals is reduced. In start-stop operation, the pressure varies between
• There is reduced noise from operation. the start and stop pressures. See the figure above.
In User-defined mode (Customised operating
The disadvantages of enabling Low-flow stop
mode), ΔH is factory-set to 10 % of the actual
function may be the following:
setpoint. ΔH can be set within the range from 5 to
• The delivered pressure is not completely constant 30 % of the actual setpoint.
as it fluctuates between the start and stop
The pump changes to start-stop operation if the flow
pressures.
becomes lower than the minimum flow rate.
• The frequent starts and stops of the pump may in
some applications cause acoustic noise. The minimum flow rate is set in percentages of
the nominal flow rate of the pump. See the pump
The impact of the above disadvantages very much nameplate.
depends on the setting selected for the stop function.
In User-defined mode (Customised operating
The High-comfort mode setting minimises pressure mode), the minimum flow rate is factory-set to 10 %
fluctuations and acoustic noise. of the nominal flow rate.
Select Energy-optimal mode if the main priority is to
reduce the energy consumption as much as possible. Low-flow stop function
Possible settings of the stop function: A low flow can be detected in two ways:
• Energy-optimal mode: The pump automatically 1. One possibility is a built-in low-flow detection
adjusts the parameters for the stop function so function that is active if none of the digital inputs
that the energy consumption during the start- are set for flow switch.
stop operation period is minimised. In this case, • Low-flow detection function: The pump checks
the stop function uses the factory-set values the flow regularly by reducing the speed for a
of the minimum flow (Qmin1) and other internal short time. If there is no or only a small change
parameters. See the figure below. in pressure, this means that there is low flow.
• High-comfort mode: The pump automatically The speed is increased until the stop pressure
adjusts the parameters for the stop function (actual setpoint + 0.5 × ΔH) is reached and
so that the disturbances during the start-stop
55
English (GB)
TM038583
PT
• If the flow rate is higher than the set minimum 1 2
flow rate, the pump returns to continuous
operation at constant pressure.
• If the flow rate is still lower than the set Position of the non-return valve and pressure
minimum flow rate (Qmin), the pump continues sensor in a system with a positive inlet pressure
in start-stop operation until the flow rate is
higher than the set minimum flow rate (Qmin).
When the flow rate is higher than the set Pos. Description
minimum flow rate (Qmin), the pump returns to
1 Pump
continuous operation.
2. The other possibility is a flow switch connected to 2 Non-return valve
one of the digital inputs. 3 Pressure sensor
• Flow switch: When the digital input is activated
for more than 5 seconds due to low flow, 4 Diaphragm tank
the speed is increased until the stop pressure
(actual setpoint + 0.5 × ΔH) is reached, and Set minimum flow
the pump stops. When the pressure falls to Set the minimum flow rate (Qmin) in this display.
start pressure, the pump restarts. If there is This setting determines at which flow rate the system
still no flow, the pump quickly reaches the stop is to change from continuous operation at constant
pressure and stops. If there is flow, the pump pressure to start-stop operation. The setting range is
continues operating according to the setpoint. 5 to 30 % of the rated flow rate.
Operating conditions for the low-flow stop
Related information
function
7.52 Factory settings
You can only use the stop function if the system
incorporates a pressure sensor, a non-return valve
7.21 Stop at min. speed
and a diaphragm tank.
This stop function can be utilised in, for example,
constant level applications where a boost of pressure
Always install the non-return valve before is not needed. This stop function differs from the low-
the pressure sensor and diaphragm tank. flow stop but the purpose is the same. The pump
stops if there is no or low consumption.
This function monitors the speed of the pump. When
4 the PI-controller has forced the speed of the pump to
minimum according to the feedback value, the pump
3 stops after a set period of time. It remains stopped
2 until the feedback value starts to drop and the PI-
controller starts the pump again.
• Enable Stop at min. speed
Enables the function Stop at min. speed.
TM0385821
• Delay
1
The delay time during which the pump must be
running at minimum speed before it stops.
• Restart speed
Position of the non-return valve and pressure It is the speed in percentage when the pump must
sensor in system with suction lift operation start again, hysteresis. It must be set higher than
the minimum speed of the pump.
56
English (GB)
Startup takes place in two phases: • Max. time reaction: reaction of the pump if the
1. Filling phase: The pipes are slowly filled with maximum filling time is exceeded:
water. When the pressure sensor of the system - warning
detects that the pipes are filled, phase two begins. - alarm (pump stops).
2. Pressure build-up phase: The system pressure • Pressure build-up time: ramp time from when
is increased until the setpoint is reached. The the filling pressure is reached until the setpoint
pressure build-up takes place over a pressure must be reached.
build-up time. If the setpoint is not reached within
a given time, a warning or an alarm can be given, When you activate this function, the
and the pumps can be stopped at the same time. function always starts when the pump has
been in operating mode Stop and is
P changed to Normal.
1 2
3
Related information
7.52 Factory settings
Related information
9
7.10 Digital inputs
7.52 Factory settings
Filling and pressure build-up phases
7.24 Ramps
The ramps determine how quickly the product can
Pos. Description accelerate and decelerate during start and stop or
1 Filling phase (constant-curve operation) setpoint changes.
You can make the following settings:
Pressure build-up phase (constant-pressure
2 • acceleration time, 0.1 to 300 s
operation)
• deceleration time, 0.1 to 300 s.
3 Setpoint
The times apply to the acceleration from 0 rpm to a
4 Filling pressure fixed maximum speed, and the deceleration from a
5 Actual value fixed maximum speed to 0 rpm, respectively.
At short deceleration times, the deceleration of the
6 Setpoint ramp-up product may depend on load and inertia as there is
7 Filling time no possibility of actively braking the product.
If the power supply is switched off, the deceleration of
8 Pressure build-up time
the product only depends on the load and inertia.
9 Maximum filling time
P Pressure
t(s) Time (sec)
Setting range
• Filling speed: fixed speed of the pump during the
filling phase.
• Filling pressure: the pressure that the pump
must reach before the maximum filling time.
• Max. filling time: the time in which the pump
must reach the filling pressure.
57
English (GB)
TM069798
The pump increases the speed to maximum.
6 7 • User defined speed:
The pump runs at the speed set by the user.
The affected inputs are the following:
Pos. Description • Analog input 1
Y Speed • Analog input 2
• Analog input 3
X Time
• Grundfos Direct Sensor
1 Fixed maximum • Pt100/1000 input 1
2 User-set maximum • Pt100/1000 input 2
• Liqtec input.
3 User-set minimum
4 Fixed initial ramp 7.27 Motor bearing monitoring
5 Fixed final ramp Use this function to select whether or not you want to
monitor the motor bearings.
6 Ramp time up
You can make the following settings:
7 Ramp time down • Active
• Not active.
Related information
When the function is set to Active, a counter in the
7.52 Factory settings controller starts counting the running hours of the
bearings. The running hours are calculated based
7.25 Standstill heating on the motor speed. When a predefined limit is
Use this function to avoid condensation in humid reached, a warning indicates that the bearings must
environments. be replaced or relubricated.
When you set the function to Active and the product If you change the function to Not active,
is in operating mode Stop, a low AC voltage is the counter continues to count. However,
applied to the motor windings. The voltage is not high no warning is given when it is time to
enough to make the motor rotate, but ensures that replace the bearings. If you change the
sufficient heat is generated to avoid condensation in function to Active again, the accumulated
the product, including the electronic parts in the drive. running hours are used to recalculate the
replacement time.
Remember to remove the drain plugs and
fit a cover over the product. 7.28 Service
7.28.1 Motor bearing service
Related information This display shows when to replace the motor
7.52 Factory settings bearings. The controller monitors the operating
pattern of the motor and calculates the period
7.26 Alarm handling between bearing replacements.
58
English (GB)
Displayable values: • Select date format:
• in 2 years - YYYY-MM-DD
• in 1 year - DD-MM-YYYY
• in 6 months - MM-DD-YYYY.
• in 3 months • Select time format:
• in 1 month - HH:MM 24-hour clock
• in 1 week - HH:MM am/pm 12-hour clock.
• Now! • Set date.
7.28.2 Bearing replacements • Set time.
The display shows the number of bearing Related information
replacements made during the lifetime of the motor.
6.8 Identification of the functional module
7.28.3 Motor bearing maintenance 7.52 Factory settings
When the bearing monitoring function is active, a
warning is given when the motor bearings must be 7.33 Units
replaced. This function is only available in the HMI 300 and HMI
1. Replace the motor bearings. 301 operating panels.
2. Press Bearings replaced. Use this function to select SI or US units. You can
make the setting for all parameters or customize for
7.29 Pump number each individual parameter.
59
English (GB)
Set the Home display to show up to four user-defined 3. Enter a connection code and press OK.
parameters. You can change the code in the Connection
code menu at any time. The old code is not
Related information
required.
7.52 Factory settings
7.42 Run start-up guide
7.37 Display settings
The function is only available in the HMI 300 and HMI
This function is only available in the HMI 300 or HMI 301 operating panels.
301 operating panels. The startup guide automatically starts when you start
Use this function to adjust the display brightness. You the product for the first time. You can always run it
can also set whether or not the display is to switch off later. It guides you through the general settings of the
if no buttons are activated for a period of time. product.
Related information To run the startup guide, go to Settings > General
settings > Run start-up guide.
7.52 Factory settings
Related information
7.38 Store actual settings 6.8 Identification of the functional module
Use this function to store the current settings to 7.6 Control mode
enable the user to go back to a previous set of
7.31 Language
settings.
7.32 Set date and time
7.39 Recall stored settings 7.46 Assisted pump setup
60
English (GB)
4. Read the description for this control mode. Related information
5. Select which analog input to use as sensor input. 7.2 Setpoint
6. Select the sensor function according to where the 7.8 Analog inputs
sensor is installed in the system. See the section
7.9 Pt100/1000 inputs
on analog inputs.
7. Select the electrical input signal according to the 7.48 Setting of date and time
sensor specifications.
This function is only available in the HMI 300 and HMI
8. Select the measuring unit according to the sensor
301 operating panels.
specifications.
9. Set the minimum and maximum sensor range The inputs and outputs available depend on the
values according to the sensor specifications. functional module fitted in the motor.
10. Set the desired setpoint.
11. Set the gain and integral time of the controller. Functional module Setting of date and time
See the section on the controller. FM110 -
12. Type the desired pump name.
FM310 ●
13. Check the summary of settings and confirm them.
FM311 ●
On the advanced operating panel
1. Open the Assist menu.
The function guides you through the following
2. Select Assisted pump setup. settings:
3. Select the control mode Const. pressure. • Select date format
4. Select which analog input to be used as sensor • Set date
input.
• Select time format
5. Select the measured parameter which is to be
• Set time.
controlled. See the section on analog inputs.
6. Select the measuring unit according to the sensor Related information
specifications. 6.8 Identification of the functional module
7. Set the minimum and maximum sensor range
7.32 Set date and time
values according to the sensor specifications.
8. Select electrical input signal according to the 7.49 Setup of multipump system
sensor specifications.
The function Setup of multi-pump system enables
9. Set the desired setpoint.
the control of two motors connected in parallel
10. Set the gain and integral time of the controller. without external controllers. The pumps or motors in a
See the section on the controller. system communicate with each other via the wireless
11. Check the summary of settings and confirm them GENIair connection or the wired GENI connection.
by pressing [OK]. You can set a multipump system via the master motor
Related information which is the first selected motor.
If several pumps or motors in the system have
7.2 Setpoint
sensors, they can all function as the master and
7.6 Control mode take over the master function if the other fails. This
7.8 Analog inputs provides additional redundancy in the multimotor
7.14 Controller settings system.
You can choose between the following multimotor
7.47 Setup, analog input functions:
This menu is only available in the Alternating operation
advanced operating panel.
Alternating operation serves as a duty and standby
This menu guides you through the following: operating mode, and is possible with two pumps or
two motors of the same size and type connected in
Setup, analog input
parallel. The main purpose of the function is to ensure
• Analog inputs 1 to 3. an even amount of running hours, and to ensure that
• Pt100/1000 input 1 and 2. the other pump or motor starts if the duty pump or
• Adjusting the setpoint. motor stops due to an alarm.
• Summary.
61
English (GB)
You can choose between two alternating operating Select Running pump sensor if the sensor is placed
modes: on or across individual pumps, for example, if the
• Alternating operation, time: sensor is installed behind non-return valves, or if it is
not able to measure the output from all pumps.
The change from one pump or motor to the other
is based on time. This setting is only available in alternating
operation and cascade operation.
• Alternating operation, energy:
The change from one pump or motor to the other 7.49.4 Setting up a multipump system
is based on energy consumption. You can set up a multipump system in the following
If the duty pump or motor fails, the other pump or ways:
motor starts. • Grundfos GO and wireless motor connection
Backup operation • Grundfos GO and wired motor connection
• HMI 300 or HMI 301 operating panel and wireless
Backup operation is possible with two motors of
motor connection
the same size and type connected in parallel. One
motor is operating continuously. The backup motor is • HMI 300 or HMI 301 operating panel and wired
operated for a short time each day to prevent seizing motor connection.
up. If the duty motor stops due to a fault, the backup
Related information
motor starts.
7.29 Pump number
Cascade operation
7.40 Pump name
This function is available with up to 4 motors installed 7.46 Assisted pump setup
in parallel. The motors must be of the same size and
if used with pumps, the pumps must be of the same 7.49.4.1 Grundfos GO and wireless motor
model. connection
• The performance is adjusted to the demand 1. Power on both motors.
through cutting pumps in or out and through
parallel control of the pumps in operation. 2. Establish contact to one of the motors with the
• The controller maintains a constant process value Grundfos GO.
through continuous adjustment of the speed of the 3. Set the needed analog and digital inputs via
pumps. the Grundfos GO, according to the connected
• Pump changeover is automatic and depends on equipment and the required functionality.
load, operating hours and fault detection.
• All pumps in operation run at the same speed. 4. Assign a name to the motor using the Grundfos
GO.
• The number of pumps in operation also depends
on the energy consumption of the pumps. If 5. Disconnect the Grundfos GO from the motor.
only one pump is required, two pumps run at
a lower speed if this results in a lower energy 6. Establish contact to the other motor.
consumption.
7. Set the needed analog and digital inputs via
• If several pumps or motors in the system have a
the Grundfos GO, according to the connected
sensor, they can all function as the master and
equipment and the required functionality.
take over the master function if the other fails.
8. Assign a name to the motor using the Grundfos
7.49.1 Alternating operation, time
GO.
The Alternating operation, time menu sets the
interval of alternation between two pumps. 9. Select the Assist menu and Setup of multi-
This setting is only available in alternating mode. pump system.
7.49.2 Time for pump changeover 10. Select the desired multimotor function.
The Time for pump changeover menu sets the time 11. Press the Right button to continue.
of day for pump changeover to take place.
This setting is only available in alternating operation. 12. Set the time when the alternation between the two
motors is to take place.
7.49.3 Sensor to be used
This step applies only if you have
This function defines the sensor for controlling the selected Alternating operation, time
pump system. and if the motors are fitted with the
Select Master pump sensor if the sensor is placed FM310 or FM311.
in a way where it can measure the output from all the
pumps in the system, for example, in the manifold. 13. Press the Right button to continue.
62
English (GB)
14. Select Radio as the communication method 15. Set the time when the alternation between the two
between the two motors. motors is to take place.
15. Press the Right button to continue. This step applies only if you have
selected Alternating operation, time
16. Select pump 2 (motor 2). and if the motors are fitted with the
FM310 or FM311.
17. Select the pump from the list.
16. Press the Right button to continue.
Use OK or the Radio communication
button to identify the pump. 17. Select Bus as the communication method
between the two motors.
2. Power on both motors. 23. When you have finish the setup and the dialog
box disappears, wait for the green indicator light in
3. Establish contact to one of the motors with the the middle of the Grundfos Eye to light up.
Grundfos GO.
7.49.4.3 HMI 300 or HMI 301 and wireless motor
4. Set the required analog and digital inputs via connection
the Grundfos GO, according to the connected 1. Power on both motors.
equipment and the required functionality.
2. On both motors, set the analog and digital inputs
5. Assign a name to the motor using the Grundfos according to the connected equipment and the
GO. required functionality.
6. Assign motor number 1 to the motor. 3. Select the Assist menu on one of the motors and
7. Disconnect the Grundfos GO from the motor. Setup of multi-pump system.
8. Establish contact to the other motor. 4. Press the Right button to continue.
9. Set the analog and digital inputs according 5. Select Wireless as the communication method
to the connected equipment and the required between the two motors.
functionality by the Grundfos GO. 6. Press the Right button to continue.
10. Assign a name to the motor using the Grundfos 7. Select the desired multimotor function.
GO.
8. Press the Right button three times to continue.
11. Assign motor number 2 to the motor.
9. Press OK to search for other motors.
12. Select the Assist menu and Setup of multi-
The green indicator light in the middle of the
pump system (multimotor setup).
Grundfos Eye flashes on the other motors.
13. Select the desired multimotor function.
10. Press OK or the Radio communication button
14. Press the Right button to continue. on the motor that is to be added to the multimotor
system.
63
English (GB)
7.49.4.4 HMI 300 or HMI 301 and wired motor 3. Press the Right button to continue.
connection
4. Press OK to confirm Disable.
1. Connect the two motors with each other with
a 3-core screened cable between the GENIbus 5. Press the Right button to continue.
terminals A, Y, B.
6. Press OK to confirm.
2. Set the needed analog and digital inputs
according to the connected equipment and the 7.50 Description of control mode
required functionality.
This function is only available in the HMI 300 and HMI
3. Assign motor number 1 to the first motor. 301 operating panels.
The function describes each of the control modes
4. Assign motor number 2 to the other motor. available for the product.
5. Select the Assist menu on one of the motors and
Related information
the Setup of multi-pump system.
7.6 Control mode
6. Press the Right button to continue.
7.51 Assisted fault advice
7. Select Wired GENIbus as the communication
method between the two motors. This function provides guidance and corrective
actions in the event of product failure.
8. Press the Right button twice to continue.
64
English (GB)
7.52 Factory settings
● Function enabled
❍ Function disabled
- Function not available
65
English (GB)
66
English (GB)
9.1.2.2 Ambient temperature during operation A
500
3 × 200-240 V 3 × 380-500 V 480
460 IE5
Minimum -20 °C -20 °C 440
Maximum 40 °C 50 °C 420
TM069866
400
The motor can operate with the rated power output 380 B
500 1500 2500 3500
(P2) at 50 °C, but continuous operation at higher
temperatures reduces the expected product life. If the Supply voltage for three-phase motor in relation to
motor is to operate at ambient temperatures between altitude
50 and 60 °C, select an oversized motor. Contact
Grundfos for further information.
Pos. Description
9.1.3 Installation altitude
Installation altitude is the height of the installation site A Supply voltage [V]
above sea level. B Altitude [m]
Motors installed up to 1000 m above sea level can be
loaded 100 %. A
The motors can be installed up to 3500 m above sea
level. 250
240
Motors installed more than 1000 m above
sea level must not be fully loaded due to 230
the low density and consequent low 220
cooling effect of the air.
210
TM069867
Y 200 B
0 500 1500 2500 3500
100
Supply voltage for single-phase motor in relation to
90 altitude
80
70
Pos. Description
TM055243
67
English (GB)
68
English (GB)
9.2.3 Inputs and outputs Screened cable: 0.5 - 1.5 mm2, 28-16 AWG.
Earth reference: Maximum cable length: 500 m excluding
All voltages refer to earth. All currents return to earth. potentiometer.
Absolute maximum voltage and current limits: Potentiometer connected to +5 V, GND, any AI:
Exceeding the following electrical limits may result in Use maximum 10 kΩ.
severely reduced operating reliability and motor life. Maximum cable length: 100 m.
Relay 1: Analog output, AO:
Maximum contact load: 250 VAC, 2 A or 30 VDC, 2 A. Current sourcing capability only.
Relay 2: Voltage signal:
Maximum contact load: 30 VDC, 2 A. • range: 0-10 VDC
GENI terminals: -5.5 to 9.0 VDC or less than 25 • minimum load between AO and GND: 1 kΩ
mADC. • short-circuit protection: Yes.
Other input/output terminals: -0.5 to 26 VDC or less Current signal:
than 15 mADC.
• ranges: 0-20 and 4-20 mADC
Digital inputs, DI:
• maximum load between AO and GND: 500 Ω
Internal pull-up current greater than 10 mA at Vi equal
• open-circuit protection: Yes.
0 VDC.
Internal pull-up to 5 VDC (currentless for Vi greater Tolerance: -0 / +4 % of full scale (maximum-point
coverage).
than 5 VDC).
Certain low logic level: Vi less than 1.5 VDC. Screened cable: 0.5 - 1.5 mm2, 28-16 AWG.
Maximum cable length: 500 m.
Certain high logic level: Vi greater than 3.0 VDC.
Pt100/1000 inputs, Pt:
Hysteresis: No.
Temperature range:
Screened cable: 0.5 - 1.5 mm2, 28-16 AWG.
• Minimum: -30 °C. 88 Ω / 882 Ω.
Maximum cable length: 500 m.
• Maximum: 180 °C. 168 Ω / 1685 Ω.
Open-collector digital outputs, OC:
Measurement tolerance: ± 1.5 °C.
Current sinking capability: 75 mADC, no current
sourcing. Measurement resolution: less than 0.3 °C.
Load types: Resistive or inductive. Automatic range detection, Pt100 or Pt1000: Yes.
Low-state output voltage at 75 mADC: maximum 1.2 Sensor fault alarm: Yes.
VDC. Screened cable: 0.5 - 1.5 mm2, 28-16 AWG.
Low-state output voltage at 10 mADC: maximum 0.6 Use the Pt100 for short wires.
VDC. Use the Pt1000 for long wires.
Overcurrent protection: Yes. LiqTec sensor inputs:
Screened cable: 0.5 - 1.5 mm2, 28-16 AWG. Use Grundfos LiqTec sensor only.
Maximum cable length: 500 m. Screened cable: 0.5 - 1.5 mm2, 28-16 AWG.
Analog inputs, AI: Grundfos Digital Sensor input and output, GDS:
Voltage signal ranges: Use Grundfos Digital Sensor only.
• 0.5 - 3.5 VDC, AL AU Power supplies:
• 0-5 VDC, AU +5 V:
• 0-10 VDC, AU. • output voltage: 5 VDC -5 % / +5 %
Voltage signal: Ri greater than 100 kΩ at 25 °C. • maximum current: 50 mADC (sourcing only)
Leak currents may occur at high operating • overload protection: Yes.
temperatures. Keep the source impedance low. +24 V:
Current signal ranges: • output voltage: 24 VDC -5 % / +5 %
• 0-20 mADC, AU • maximum current: 60 mADC (sourcing only)
• 4-20 mADC, AL AU. • overload protection: Yes.
Current signal: Ri is equal 292 Ω. Digital outputs, relays:
Current overload protection: Yes. Change to voltage Potential-free changeover contacts.
signal.
Minimum contact load when in use: 5 VDC, 10 mA.
Measurement tolerance: -0 / +3 % of full scale
Screened cable: 0.5 - 2.5 mm2, 28-12 AWG.
(maximum-point coverage).
69
English (GB)
Maximum cable length: 500 m. Immunity: The motor fulfils the requirements for
Bus input: industrial areas.
Grundfos GENIbus protocol, RS-485. Contact Grundfos for further information.
Screened 3-core cable: 0.5 - 1.5 mm2, 28-16 AWG. Enclosure class
Maximum cable length: 500 m. Standard: IP55 (IEC 34-5).
Optional: IP66 (IEC 34-5).
9.3 Megging
Insulation class
Do not meg an installation incorporating MGE motors
as the built-in electronics may be damaged. F (IEC 85).
70
English (GB)
9.5 Accessories Sound pressure
The following are the communication interface Maximum level
modules intended for use with the product: speed ISO 3743
Motor Speed
stated on
[kW] nameplate rpm [dB(A)]
Communication rpm 1-phase 3-phase
Protocol
interface module motors motors
GENIbus CIM 50 1500 - 48
2000
LonWorks (Single) CIM 100 2000 - 55
PROFIBUS DP CIM 150 3000 - 57
2.2 4000
Modbus RTU CIM 200 4000 - 64
BACnet MS/TP CIM 300 4000 - 58
5900
Modbus TCP, BACnet IP, 5900 - 68
PROFINET, GiC/GRM IP, CIM 500
EtherNet IP 1500 - 48
2000
2000 - 55
Installing a communication interface module not listed
3000 - 60
above might affect the compliance level of the 3 4000
product. 4000 - 69
4000 - 64
9.6 Sound pressure level 5900
5900 - 74
71
English (GB)
72
Grundfos companies
Argentina Colombia Hong Kong
Bombas GRUNDFOS de Argentina S.A. GRUNDFOS Colombia S.A.S. GRUNDFOS Pumps (Hong Kong) Ltd.
Ruta Panamericana km. 37.500industin Km 1.5 vía Siberia-Cota Conj. Potrero Unit 1, Ground floor, Siu Wai industrial
1619 - Garín Pcia. de B.A. Chico, Centre
Tel.: +54-3327 414 444 Parque Empresarial Arcos de Cota Bod. 29-33 Wing Hong Street & 68 King Lam
Fax: +54-3327 45 3190 1A. Street, Cheung Sha Wan
Cota, Cundinamarca Kowloon
Australia Tel.: +57(1)-2913444 Tel.: +852-27861706 / 27861741
GRUNDFOS Pumps Pty. Ltd. Fax: +57(1)-8764586 Fax: +852-27858664
P.O. Box 2040
Regency Park Croatia Hungary
South Australia 5942 GRUNDFOS CROATIA d.o.o. GRUNDFOS South East Europe Kft.
Tel.: +61-8-8461-4611 Buzinski prilaz 38, Buzin Tópark u. 8
Fax: +61-8-8340-0155 HR-10010 Zagreb H-2045 Törökbálint
Tel.: +385 1 6595 400 Tel.: +36-23 511 110
Austria Fax: +385 1 6595 499 Fax: +36-23 511 111
GRUNDFOS Pumpen Vertrieb www.hr.grundfos.com
Ges.m.b.H. India
Grundfosstraße 2 Czech Republic GRUNDFOS Pumps India Private
A-5082 Grödig/Salzburg GRUNDFOS Sales Czechia and Slovakia Limited
Tel.: +43-6246-883-0 s.r.o. 118 Old Mahabalipuram Road
Fax: +43-6246-883-30 Čajkovského 21 Thoraipakkam
779 00 Olomouc Chennai 600 097
Belgium Tel.: +420-585-716 111 Tel.: +91-44 2496 6800
N.V. GRUNDFOS Bellux S.A.
Boomsesteenweg 81-83 Denmark Indonesia
B-2630 Aartselaar GRUNDFOS DK A/S PT GRUNDFOS Pompa
Tel.: +32-3-870 7300 Martin Bachs Vej 3 Graha intirub Lt. 2 & 3
Fax: +32-3-870 7301 DK-8850 Bjerringbro Jln. Cililitan Besar No.454. Makasar,
Tel.: +45-87 50 50 50 Jakarta Timur
Bosnia and Herzegovina Fax: +45-87 50 51 51 ID-Jakarta 13650
GRUNDFOS Sarajevo E-mail: info_GDK@grundfos.com Tel.: +62 21-469-51900
Zmaja od Bosne 7-7A www.grundfos.com/DK Fax: +62 21-460 6910 / 460 6901
BiH-71000 Sarajevo
Tel.: +387 33 592 480 Estonia Ireland
Fax: +387 33 590 465 GRUNDFOS Pumps Eesti OÜ GRUNDFOS (Ireland) Ltd.
www.ba.grundfos.com Peterburi tee 92G Unit A, Merrywell Business Park
E-mail: grundfos@bih.net.ba 11415 Tallinn Ballymount Road Lower
Tel.: + 372 606 1690 Dublin 12
Brazil Fax: + 372 606 1691 Tel.: +353-1-4089 800
BOMBAS GRUNDFOS DO BRASIL Fax: +353-1-4089 830
Av. Humberto de Alencar Castelo Finland
Branco, 630 OY GRUNDFOS Pumput AB Italy
CEP 09850 - 300 Trukkikuja 1 GRUNDFOS Pompe Italia S.r.l.
São Bernardo do Campo - SP FI-01360 Vantaa Via Gran Sasso 4
Tel.: +55-11 4393 5533 Tel.: +358-(0) 207 889 500 I-20060 Truccazzano (Milano)
Fax: +55-11 4343 5015 Tel.: +39-02-95838112
France Fax: +39-02-95309290 / 95838461
Bulgaria Pompes GRUNDFOS Distribution S.A.
Grundfos Bulgaria EOOD Parc d’Activités de Chesnes Japan
Slatina District 57, rue de Malacombe GRUNDFOS Pumps K.K.
Iztochna Tangenta street no. 100 F-38290 St. Quentin Fallavier (Lyon) 1-2-3, Shin-Miyakoda, Kita-ku
BG - 1592 Sofia Tel.: +33-4 74 82 15 15 Hamamatsu
Tel.: +359 2 49 22 200 Fax: +33-4 74 94 10 51 431-2103 Japan
Fax: +359 2 49 22 201 Tel.: +81 53 428 4760
E-mail: bulgaria@grundfos.bg
Germany Fax: +81 53 428 5005
GRUNDFOS GMBH
Canada Schlüterstr. 33 Kazakhstan
GRUNDFOS Canada inc. 40699 Erkrath Grundfos Kazakhstan LLP
2941 Brighton Road Tel.: +49-(0) 211 929 69-0 7' Kyz-Zhibek Str., Kok-Tobe micr.
Oakville, Ontario Fax: +49-(0) 211 929 69-3799 KZ-050020 Almaty Kazakhstan
L6H 6C9 E-mail: infoservice@grundfos.de Tel.: +7 (727) 227-98-55/56
Tel.: +1-905 829 9533 Service in Deutschland:
Fax: +1-905 829 9512 kundendienst@grundfos.de
Korea
GRUNDFOS Pumps Korea Ltd.
China Greece 6th Floor, Aju Building 679-5
GRUNDFOS Pumps (Shanghai) Co. Ltd. GRUNDFOS Hellas A.E.B.E. Yeoksam-dong, Kangnam-ku, 135-916
10F The Hub, No. 33 Suhong Road 20th km. Athinon-Markopoulou Av. Seoul, Korea
Minhang District P.O. Box 71 Tel.: +82-2-5317 600
Shanghai 201106 PRC GR-19002 Peania Fax: +82-2-5633 725
Tel.: +86 21 612 252 22 Tel.: +0030-210-66 83 400
Fax: +86 21 612 253 33 Fax: +0030-210-66 46 273
Latvia
SIA GRUNDFOS Pumps Latvia
Deglava biznesa centrs
Augusta Deglava ielā 60
LV-1035, Rīga,
Tel.: + 371 714 9640, 7 149 641
Fax: + 371 914 9646
Grundfos companies
Poland Switzerland
GRUNDFOS Pompy Sp. z o.o. GRUNDFOS Pumpen AG
ul. Klonowa 23 Bruggacherstrasse 10
Baranowo k. Poznania CH-8117 Fällanden/ZH
PL-62-081 Przeźmierowo Tel.: +41-44-806 8111
Tel.: (+48-61) 650 13 00 Fax: +41-44-806 8115
Fax: (+48-61) 650 13 50 Taiwan
Portugal GRUNDFOS Pumps (Taiwan) Ltd.
Bombas GRUNDFOS Portugal, S.A. 7 Floor, 219 Min-Chuan Road
Rua Calvet de Magalhães, 241 Taichung, Taiwan, R.O.C.
Apartado 1079 Tel.: +886-4-2305 0868
P-2770-153 Paço de Arcos Fax: +886-4-2305 0878
Tel.: +351-21-440 76 00 Thailand
Fax: +351-21-440 76 90 GRUNDFOS (Thailand) Ltd.
Romania 92 Chaloem Phrakiat Rama 9 Road
GRUNDFOS Pompe România SRL Dokmai, Pravej, Bangkok 10250
S-PARK BUSINESS CENTER, Clădirea Tel.: +66-2-725 8999
A2, etaj 2 Fax: +66-2-725 8998
Str. Tipografilor, Nr. 11-15, Sector 1, Cod
013714
Bucuresti, Romania
Tel.: 004 021 2004 100
E-mail: romania@grundfos.ro
98358864
ECM: 1406337
www.grundfos.com
06.2025
Trademarks displayed in this material, including but not limited to Grundfos and the Grundfos logo, are registered trademarks owned by The Grundfos Group. © 2025 Grundfos Holding A/S, all rights reserved.