Data sheet 6ES7416-5HS06-0AB0
SIMATIC S7-400H, CPU 416-5H, central processing unit for S7-400H and S7-
400F/FH, 5 interfaces: 1x MPI/DP, 1x DP, 1x PN and 2 for sync modules, 16 MB
memory (10 MB data/6 MB program)
General information
Product type designation CPU 416-5H PN/DP
HW functional status 1
Firmware version V6.0
Product function
● Isochronous mode No
Engineering with
● Programming package As of STEP 7 V5.5 SP2 with HF1
CiR - Configuration in RUN
CiR synchronization time, basic load 100 ms
CiR synchronization time, time per I/O byte 0 µs
Supply voltage
Rated value (DC) Power supply via system power supply
Input current
from backplane bus 5 V DC, typ. 1.6 A
from backplane bus 5 V DC, max. 1.9 A
from backplane bus 24 V DC, max. 150 mA; 150 mA per DP interface
from interface 5 V DC, max. 90 mA; At each DP interface
Power loss
Power loss, typ. 7.5 W
Memory
Type of memory RAM
Work memory
● integrated 16 Mbyte
● integrated (for program) 6 Mbyte
● integrated (for data) 10 Mbyte
● expandable No
Load memory
● expandable FEPROM Yes; with Memory Card (FLASH)
● expandable FEPROM, max. 64 Mbyte
● integrated RAM, max. 1 Mbyte
● expandable RAM Yes
● expandable RAM, max. 64 Mbyte
Backup
● present Yes
● with battery Yes; all data
● without battery No
Battery
Backup battery
● Backup current, typ. 180 µA; Valid up to 40°C
6ES74165HS060AB0 Subject to change without notice
1/30/2024
Page 1/9 © Copyright Siemens
● Backup current, max. 1 000 µA
● Backup time, max. Dealt with in the module data manual with the secondary conditions and the
factors of influence
● Feeding of external backup voltage to CPU 5 V DC to 15 V DC
CPU processing times
for bit operations, typ. 12.5 ns
for word operations, typ. 12.5 ns
for fixed point arithmetic, typ. 12.5 ns
for floating point arithmetic, typ. 25 ns
CPU-blocks
DB
● Number, max. 16 000; Number range: 1 to 16000
● Size, max. 64 kbyte
FB
● Number, max. 8 000; Number range: 0 to 7999
● Size, max. 64 kbyte
FC
● Number, max. 8 000; Number range: 0 to 7999
● Size, max. 64 kbyte
OB
● Number, max. see instruction list
● Size, max. 64 kbyte
● Number of free cycle OBs 1; OB 1
● Number of time alarm OBs 8; OB 10-17
● Number of delay alarm OBs 4; OB 20-23
● Number of cyclic interrupt OBs 9; OB 30-38
● Number of process alarm OBs 8; OB 40-47
● Number of DPV1 alarm OBs 3; OB 55-57
● Number of startup OBs 2; OB 100, 102
● Number of asynchronous error OBs 9; OB 80-88
● Number of synchronous error OBs 2; OB 121, 122
Nesting depth
● per priority class 24
● additional within an error OB 2
Counters, timers and their retentivity
S7 counter
● Number 2 048
Retentivity
— adjustable Yes
— preset Z 0 to Z 7
Counting range
— lower limit 0
— upper limit 999
IEC counter
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
S7 times
● Number 2 048
Retentivity
— adjustable Yes
— preset No times retentive
Time range
— lower limit 10 ms
— upper limit 9 990 s
IEC timer
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max. Total working and load memory (with backup battery)
6ES74165HS060AB0 Subject to change without notice
1/30/2024
Page 2/9 © Copyright Siemens
Flag
● Size, max. 16 384 byte
● Retentivity available Yes
● Retentivity preset MB 0 to MB 15
● Number of clock memories 8; in 1 memory byte
Local data
● adjustable, max. 64 kbyte
● preset 32 kbyte
Address area
I/O address area
● Inputs 16 kbyte
● Outputs 16 kbyte
Process image
● Inputs, adjustable 16 kbyte
● Outputs, adjustable 16 kbyte
● Inputs, default 1 024 byte
● Outputs, default 1 024 byte
● consistent data, max. 244 byte
● Access to consistent data in process image Yes
Subprocess images
● Number of subprocess images, max. 15
Digital channels
● Inputs 131 072
— of which central 131 072
● Outputs 131 072
— of which central 131 072
Analog channels
● Inputs 8 192
— of which central 8 192
● Outputs 8 192
— of which central 8 192
Hardware configuration
Number of expansion units, max. 21
connectable OPs 95
Multicomputing No
Interface modules
● Number of connectable IMs (total), max. 6
● Number of connectable IM 460s, max. 6
● Number of connectable IM 463s, max. 4; Single mode only
Number of DP masters
● integrated 2
● via CP 10; CP 443-5 Extended
● Mixed mode IM + CP permitted No
● via interface module 0
Number of IO Controllers
● integrated 1
● via CP 0
Number of operable FMs and CPs (recommended)
● FM See manual Automation System S7-400H fault-tolerant systems. Limited by
number of slots and number of connections
● CP, PtP See manual Automation System S7-400H fault-tolerant systems. Limited by
number of slots and number of connections
● PROFIBUS and Ethernet CPs 14; Of which max. 10 CP as DP master
Slots
● required slots 2
Time of day
Clock
● Hardware clock (real-time) Yes
● retentive and synchronizable Yes
● Resolution 1 ms
● Deviation per day (buffered), max. 1.7 s; Power off
6ES74165HS060AB0 Subject to change without notice
1/30/2024
Page 3/9 © Copyright Siemens
● Deviation per day (unbuffered), max. 8.6 s; Power on
Operating hours counter
● Number 16
● Number/Number range 0 to 15
● Range of values SFCs 2, 3 and 4: 0 to 32767 hours SFC 101: 0 to 2^31 - 1 hours
● Granularity 1h
● retentive Yes
Clock synchronization
● supported Yes
● to MPI, master Yes
● to MPI, slave Yes
● to DP, master Yes
● to DP, slave Yes
● in AS, master Yes
● in AS, slave Yes
● on Ethernet via NTP Yes; As client
Time difference in system when synchronizing via
● Ethernet, max. 10 ms; Via NTP
● MPI, max. 200 ms
Interfaces
Number of RS 485 interfaces 2
Number of other interfaces 2; Fiber-optic interface
Optical interface No
1. Interface
Interface type MPI/PROFIBUS DP
Isolated Yes
Interface types
● RS 485 Yes
● Output current of the interface, max. 150 mA
Protocols
● MPI Yes
● PROFIBUS DP master Yes
● PROFIBUS DP slave No
MPI
● Number of connections 44; If a diagnostics repeater is used on the line, the number of connection
resources on the line is reduced by 1
● Transmission rate, max. 12 Mbit/s
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication No
— S7 communication Yes
— S7 communication, as client Yes
— S7 communication, as server Yes
PROFIBUS DP master
● Number of connections, max. 32; If a diagnostics repeater is used on the line, the number of connection
resources on the line is reduced by 1
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 32
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication No
— S7 communication Yes
— S7 communication, as client Yes
— S7 communication, as server Yes
— Equidistance No
— Isochronous mode No
— SYNC/FREEZE No
6ES74165HS060AB0 Subject to change without notice
1/30/2024
Page 4/9 © Copyright Siemens
— Activation/deactivation of DP slaves No
— Direct data exchange (slave-to-slave No
communication)
— DPV1 Yes
Address area
— Inputs, max. 2 kbyte
— Outputs, max. 2 kbyte
User data per DP slave
— User data per DP slave, max. 244 byte
— Inputs, max. 244 byte
— Outputs, max. 244 byte
— Slots, max. 244
— per slot, max. 128 byte
PROFIBUS DP slave
● Number of connections No configuration of CPU as DP slave
2. Interface
Interface type PROFINET
Isolated Yes
automatic detection of transmission rate Yes; Autosensing
Autonegotiation Yes
Autocrossing Yes
Change of IP address at runtime, supported No
Interface types
● RJ 45 (Ethernet) Yes
● Number of ports 2
● integrated switch Yes
Protocols
● PROFINET IO Controller Yes
● PROFINET IO Device No
● PROFINET CBA No
● PROFIBUS DP master No
● PROFIBUS DP slave No
● Open IE communication Yes
● Web server No
● Point-to-point connection No
● Media redundancy Yes
PROFINET IO Controller
● Transmission rate, max. 100 Mbit/s
Services
— PG/OP communication Yes
— S7 communication Yes
— Isochronous mode No
— Shared device Yes; Single mode only
— Prioritized startup No
— Number of connectable IO Devices, max. 256; In redundant mode via both interfaces
— Number of connectable IO Devices for RT, max. 256
— of which in line, max. 256
— Activation/deactivation of IO Devices No
— IO Devices changing during operation (partner No
ports), supported
— Device replacement without swap medium Yes
— Send cycles 250 µs, 500 µs, 1 ms, 2 ms, 4 ms
— Updating time 250 µs to 512 ms, minimum value depends on the number of configured user
data and the configured single or redundant mode
Address area
— Inputs, max. 8 kbyte
— Outputs, max. 8 kbyte
— User data consistency, max. 1 024 byte
Open IE communication
● Number of connections, max. 94
● Local port numbers used at the system end 0, 20, 21, 25, 102, 135, 161, 34962, 34963, 34964, 65532, 65533, 65534,
65535
6ES74165HS060AB0 Subject to change without notice
1/30/2024
Page 5/9 © Copyright Siemens
● Keep-alive function, supported Yes
3. Interface
Interface type PROFIBUS DP
Interface types
● RS 485 Yes
● Output current of the interface, max. 150 mA
Protocols
● PROFIBUS DP master Yes
● PROFIBUS DP slave No
PROFIBUS DP master
● Number of connections, max. 32
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 125
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication No
— S7 communication Yes
— S7 communication, as client Yes
— S7 communication, as server Yes
— Equidistance No
— Isochronous mode No
— SYNC/FREEZE No
— Activation/deactivation of DP slaves No
— Direct data exchange (slave-to-slave No
communication)
— DPV0 Yes
— DPV1 Yes
Address area
— Inputs, max. 8 kbyte
— Outputs, max. 8 kbyte
User data per DP slave
— User data per DP slave, max. 244 byte
— Inputs, max. 244 byte
— Outputs, max. 244 byte
— Slots, max. 244
— per slot, max. 128 byte
4. Interface
Interface type Pluggable synchronization submodule (FO)
Plug-in interface modules Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0
5. Interface
Interface type Pluggable synchronization submodule (FO)
Plug-in interface modules Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0
Protocols
Redundancy mode
Media redundancy
— Switchover time on line break, typ. 200 ms
— Number of stations in the ring, max. 50
SIMATIC communication
● S7 routing Yes
Open IE communication
● TCP/IP Yes; via integrated PROFINET interface and loadable FBs
— Number of connections, max. 94
— Data length, max. 32 kbyte
— several passive connections per port, supported Yes
● ISO-on-TCP (RFC1006) Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs
— Number of connections, max. 94
— Data length, max. 32 kbyte; 1 452 bytes via CP 443-1 Adv.
● UDP Yes; via integrated PROFINET interface and loadable FBs
— Number of connections, max. 94
6ES74165HS060AB0 Subject to change without notice
1/30/2024
Page 6/9 © Copyright Siemens
— Data length, max. 1 472 byte
Web server
● supported No
Isochronous mode
Equidistance No
communication functions / header
PG/OP communication Yes
● Number of connectable OPs without message processing 95
● Number of connectable OPs with message processing 95; When using Alarm_S/SQ and Alarm_D/DQ
Data record routing Yes
Global data communication
● supported No
S7 basic communication
● communication function / S7 basic communication No
S7 communication
● supported Yes
● as server Yes
● as client Yes
● User data per job, max. 64 kbyte
● User data per job (of which consistent), max. 462 byte; 1 variable
S5 compatible communication
● supported Yes; (via CP max. 10 and FC AG_SEND and FC AG_RECV)
● User data per job, max. 8 kbyte
● User data per job (of which consistent), max. 240 byte
● Number of simultaneous AG-SEND/AG-RECV orders per 64/64
CPU, max.
Standard communication (FMS)
● supported Yes; Via CP and loadable FB
Number of connections
● overall 96
● usable for PG communication
— reserved for PG communication 1
— adjustable for PG communication, max. 0
● usable for OP communication
— reserved for OP communication 1
— adjustable for OP communication, max. 0
● usable for S7 basic communication
— reserved for S7 basic communication 0
— adjustable for S7 basic communication, max. 0
● usable for S7 communication
— reserved for S7 communication 0
— adjustable for S7 communication, max. 0
● usable for routing
— reserved for routing 0
— adjustable for routing, max. 0
S7 message functions
Number of login stations for message functions, max. 95; Max. 95 with Alarm_S/SQ and Alarm_D/DQ (OPs); max. 16 with Alarm,
Alarm_8, Alarm_8P, Notify and Notify_8 (e.g. WinCC)
Symbol-related messages No
SCAN procedure No
Program alarms Yes
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 1 000; Simultaneously active alarm_S/SQ blocks or alarm_D/DQ blocks
Alarm 8-blocks Yes
● Number of instances for alarm 8 and S7 communication 10 000
blocks, max.
● preset, max. 1 200
Process control messages Yes
Number of archives that can log on simultaneously (SFB 37 64
AR_SEND)
Test commissioning functions
Status block Yes
6ES74165HS060AB0 Subject to change without notice
1/30/2024
Page 7/9 © Copyright Siemens
Single step Yes
Number of breakpoints 16
Status/control
● Status/control variable Yes; Up to 16 variable tables
● Variables Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters
● Number of variables, max. 70
Forcing
● Forcing Yes
● Forcing, variables Inputs/outputs, bit memories, distributed I/Os
● Number of variables, max. 512
Diagnostic buffer
● present Yes
● Number of entries, max. 3 200
— adjustable Yes
— preset 120
Service data
● can be read out Yes
EMC
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas Yes
● Limit class B, for use in residential areas No
configuration / header
Configuration software
● STEP 7 Yes
configuration / programming / header
● Command set see instruction list
● Nesting levels 7
● Access to consistent data in process image Yes
● System functions (SFC) see instruction list
● System function blocks (SFB) see instruction list
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC Yes
— GRAPH Yes
— HiGraph® Yes
configuration / programming / number of simultaneously active SFC / header
— RD_REC 8
— WR_REC 8
— WR_PARM 8
— PARM_MOD 1
— WR_DPARM 2
— DPNRM_DG 8
— RDSYSST 8
— DP_TOPOL 1
configuration / programming / number of simultaneously active SFB / header
— RDREC 8
— WRREC 8
Know-how protection
● User program protection/password protection Yes
● Block encryption Yes; With S7 block Privacy
Dimensions
Width 50 mm
Height 290 mm
Depth 219 mm
Weights
Weight, approx. 995 g
last modified: 9/7/2023
6ES74165HS060AB0 Subject to change without notice