LPF Series-Front Terminal
LPF12-100A(12V100Ah)
Specifications
Rated Voltage 12V
C10,1.80V/cell 100.0Ah
508±2mm (20.0 inches)
110±2mm (4.33 inches)
238.5±2mm (9.39 inches)
238.5±2mm (9.39 inches)
32.0 Kg (70.6 Ibs)
M6
ABS
106.0 Ah (20hr,5.30A,1.80V/cell)
100.0 Ah (10hr,10.0A,1.80V/cell)
(25 0 C ) 96.8 Ah (8hr,12.1A,1.75V/cell)
87.0 Ah (5hr,17.4A,1.75V/cell)
64.3 Ah (1hr,64.3A,1.60V/cell) Layout
1000A (5s)
(25 0 C ) Approx 5.5mΩ
Discharge -15~500C (5~1220F)
Charge -20~400C (-4~1040F)
Storage -15~400C (5~1040F)
25±3 0 C (77±5 0 F )
Initial Charging Current less than 30.0A.Voltage
Cycle Use
14.1V~14.4V at 25 0 C(77 0 F)Temp. Coefficient -30mV/ 0 C
Standby Use Initial Charging Current less than 30.0A. Voltage
13.5V~13.8V at 25 0 C(77 0 F)Temp. Coefficient -20mV/ 0 C
40 0 C (104 0 F) 103%
Effect of temp. to Capacity 25 0 C ( 77 0 F) 100%
00 C ( 32 0 F) 86%
LPF series batteries may be stored for up to 6 months
at 25 0 C(77 0 F) and then a freshening charge is required.
For higher temperatures the time interval will be shorter.
Constant Current Discharge (Amperes) at 25 0 C (77 0 F )
F.V/Time 10min 15min 20min 30min 45min 1h 2h 3h 4h 5h 6h 8h 10h 20h
1.85V/cell 144.6 127.2 114.0 91.6 69.6 56.3 33.6 24.7 19.9 16.7 14.5 11.5 9.56 5.07
1.80V/cell 168.0 146.8 127.2 99.0 74.3 59.5 34.8 25.7 20.5 17.2 14.8 11.9 10.0 5.30
1.75V/cell 185.4 158.0 133.2 103.2 76.8 61.4 35.6 26.1 20.8 17.4 15.1 12.1 10.1 5.35
1.70V/cell 197.4 165.6 138.6 106.0 78.8 62.8 36.2 26.5 21.1 17.6 15.3 12.2 10.2 5.38
1.67V/cell 206.4 171.2 144.0 108.4 80.1 63.7 36.6 26.7 21.3 17.8 15.4 12.3 10.3 5.41
1.60V/cell 215.4 176.0 146.4 110.6 80.9 64.3 37.1 27.0 21.5 18.1 15.6 12.5 10.4 5.44
Constant Power Discharge (Watts/cell) at 25 0 C (77 0 F )
F.V/Time 10min 15min 20min 30min 45min 1h 2h 3h 4h 5h 6h 8h 10h 20h
1.85V/cell 270.0 239.9 217.2 176.4 135.2 109.7 65.8 48.6 39.3 33.1 28.7 22.9 19.1 10.1
1.80V/cell 310.0 273.2 238.8 187.8 143.1 115.3 67.7 50.4 40.3 33.9 29.3 23.6 20.0 10.6
1.75V/cell 336.7 290.5 247.7 194.2 146.6 118.5 69.0 51.0 40.7 34.2 29.7 23.9 20.2 10.7
1.70V/cell 350.5 300.2 255.8 198.3 149.9 120.8 70.1 51.6 41.2 34.4 30.0 24.2 20.3 10.7
1.67V/cell 365.1 309.1 264.7 202.4 151.7 122.2 70.8 51.9 41.5 34.8 30.2 24.4 20.5 10.8
1.60V/cell 370.4 311.5 265.3 203.8 151.9 122.3 71.1 52.2 41.7 35.2 30.6 24.6 20.7 10.8
LPF Series-Front Terminal
LPF12-100A(12V100Ah)
Applications General Features Stand ards
0
• UPS • 12 years design life(25 C ) • Compliance with IEC 60896 standards,
• Specifically ideal for 19 inches EU Battery Directive
• For standard power cabinet
or 23 inches power cabinets
• UL, CE Certified
• Network connection equipment • Front terminals make the installation,
of communication system maintenance and supervision easy
• Manufactured in Leoch®IATF16949,
• Shield designs protect terminals from
• Power system of special network ISO 45001,ISO 9001 and ISO 14001
short circuit and show good appearance
of local area network certified production facilities
• Unique vent valve design: reduce water
• Power station systems losing and prevent air/spark going inside
Discharge Characteristics Float Charging Characteristics
12V 6V Charge Charging Charging
Battery Battery Volume Current Voltage
(V) (V) Temperature:25 C
0
13 6.5 % (A) (V/cell) 0.1CA-2.25V/cell Temperature: 250C
12 6.0
120 0.10C 2.4
Terminal Voltage(V)
Charged Volume
11 5.5
0.1CA 100 0.08C 2.3
0.2CA Charge Voltage
5.0 0.35CA
10 (Constant 2.25V/cell)
0.6CA 80 0.06C 2.2
2CA 1CA After 50% Discharge
9 4.5
After 100% Discharge
60 0.04C 2.1
8 4.0
40 0.02C 2.0
7 3.5 Charging Current
0.1 2 4 6 10 20 40 60 2 4 6 8 10
20 0C
Min H 0 4 8 12 16 20 24 28 32 36
Discharge Time Charging Time(hours)
Temperature Effects in Relation to Battery Capacity Effect of Temperature on Long Term Float Life
120
18
0.1CA
100 15
Float Life (year)
Capacity(%)
0.25CA
80 12
0.65CA
60 9
1CA
40 6
3
20
0
0 o 20 25 30 35 40 45 (oC)
-20 -10 0 10 20 30 40 50 ( C ) 68 77 86 95 104 113 ( o F)
-4 14 32 50 68 86 104 122 ( o F)
Battery temperature Battery temperature
Sales Offices Worldwide
China Sales Office HongKong Sales Office Singapore Sales Office Australia Sales Office
5th Floor, Xinbaohui Bldg., Nanhai Blvd., Workshop C, 33/F, TML Tower, No. 3 Hoi Shing Road, No. 1 Tech Park Crescent, 2 /29 Tarlington Place, Smithfield. NSW 2164
Nanshan, Shenzhen, China. 518052 Tsuen Wan, New Territories, Hong Kong Singapore 638131 Australia
Tel: +86-755-86036060 (100 lines) Tel: +852 35786666 Tel: +65 68636078 Tel: 02 9756 0950
Fax: +86-755-26067269 Fax: +44 1452 690125 Fax: +65 6863 6079 E-mail: sales.au@leoch.com
E-mail:export@leoch.com E-mail: sales.hk@leoch.com Email: sales.sg@Leoch.com
North America Sales Office UK Sales Office EMEA Sales Office India Sales Office
19751 Descartes 9B Wheatstone Court. Waterwells, Business Park, 1 Deligiorgi St., 121 31 Athens, Shed no.A-53(b), 2nd Stage of Peenya Industrial Area,
Foothill Ranch, CA 92610, USA Gloucester, GL2-2AQ, UK United Kingdom Greece Bangalore North Taluk, Bangalore-560058, India
Tel: 949-588-5853 Tel: +44(0) 1452 729428 / 1452 729696 Tel: +30 210 5760318 (2 lines) Tel: +91-80-23440018/23440019
Fax: 949-588-5966 Fax:+44 1452 690125 E-mail: support_EMEA@leoch.com Fax: +91-80-23440017
E-mail: sales@leoch.us E-mail: Sales.Europe@leoch.com Http:// www.leoch.eu E-mail: indiasales@leoch.com
Http:// www.leoch.us Http:// www.leoch.eu
© 2020 LEOCH. All rights reserved.
Http://www.leoch.com Trademarks and logos are the property of LEOCH and its affiliates unless otherwise noted.
Subject to revisions without prior notice. Publication No.: LB-LPF12-100A-PD-EN-V2.0-202004