Datasheet
Subject to technical alteration
Issue date: 22.04.2024 • A140
» APPLICATION
Modern design flush mounting fan coil room thermostat, used for individual control of temperature in commercial, industrial and residential buildings.
It is tailored for two-pipe and four-pipe fan coil units with two-wire electric valves. The device combines digital technology with a large LCD touch
screen display, which enables the 2-point-single room controller to be used intuitively. Integrated 7 day time clock with 4 time programs.
The product should only be used for the intended application. Unauthorised modifications are prohibited! The product must not
be used in relation with any equipment that in case of a failure may threaten, directly or indirectly, human health or life or result
in danger to human beings, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating
equipment.
CAUTION! Risk of electric shock due to live components within the enclosure, especially devices with mains voltage
supply (usually between 90..265 V).
» NOTES ON DISPOSAL
The crossed-out wheelie bin symbol indicates that the product or removable batteries must not be disposed of with household or
commercial waste. Within the EU, you are legally obliged to dispose of the product separately and appropriately in accordance
with the national laws of your country. Alternatively, please contact your supplier or Thermokon Sensortechnik GmbH. Further
information can be found at: www.thermokon.com
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax: -400 · www.thermokon.de · email@thermokon.de
LCF_TOUCH_Modbus_Datasheet_en-us © 2024
Page 2 / 10 Issue date: 22.04.2024
During Assembly:
• Seal mounting box (if present).
• Installation type, air draught, heat source, radiation heat or direct sunlight can affect the measurement.
• Bulding material specific properties of the installation place (brick-, concrete-, partition wall, cavity wall, …) can affect the measurement.
» TECHNICAL DATA
Measuring values temperature
Network technology RS485 Modbus, RTU, half-duplex, baud rate 4.800, 9.600, 19.200 or 38.400, parity: non (2 stopbits), even
or odd (1 stopbit), RS485 bus load: ¼ unit load according to RS485 standard (max. 128 devices)
Sensor NTC10k
Inputs Terminal 7 | 8
input for change-over sensor (NTC 10 K)
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax: -400 · www.thermokon.com email@thermokon.de
LCF_TOUCH_Modbus_Datasheet_en-us © 2024
Issue date: 22.04.2024 Page 3 / 10
Declaration of conformity
The declaration of conformity of the products are available on our website
https://www.thermokon.de/direct/en-gb/categories/lcf-touch
» CONNECTION PLAN
LCF Touch Modbus – Auto mode wiring diagram for 2-pipe fan coil
LCF Touch Modbus – Manual mode wiring diagram for 2-pipe fan coil
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax: -400 · www.thermokon.com email@thermokon.de
LCF_TOUCH_Modbus_Datasheet_en-us © 2024
Page 4 / 10 Issue date: 22.04.2024
» MOUNTING ADVICES
For installing or repairing, please make sure the power for the thermostat has been
turned off.
1. Insert the screw driver in the plastic teeth of the thermostat to open the enclosure.
2. Please follow the wiring diagram to connect the wires.
3. Fix the thermostat base plate to the wall by using the four screw holes with a
distance between the axes of 2.36 in.
4. Fasten base plate and front cover. Do not press the panel in order to protect LCD.
» COMMISSIONING
Setting parameter No. 13, the selection of the fan coil system has to be done. 2-pipe or 4-pipe systems can be selected.
Hysteresis: 1 K + 1 minute delay
Mode selection:
Manual Mode: 2-pipe-System: Cooling → Ventilating → Heating
4-pipe-System: Cooling → Ventilating → Heating → Auto change-over mode (only when parameter No. 14 is set
to 1!)
AUTO-Mode: The mode will be selected automatically.
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax: -400 · www.thermokon.com email@thermokon.de
LCF_TOUCH_Modbus_Datasheet_en-us © 2024
Issue date: 22.04.2024 Page 5 / 10
Auto mode:
Display °C or °F
Display of the units °C or °F can be selected using parameter No. 12. Fahrenheit temperature display range is 32..99 °F, °C temperature display
range is 0..50 °C. Factory default is °C.
Note: Under Parameter No.1 the temperature offset can be adjusted. This feature should be used if the temperature at the mounting place of the
Room Thermostat is not accurate to the average room temperature.
Language selection
You can change the display language with parameter No. 11.
Time setting
Press the “ ” button, to set the time. The changing parameter is blinking, press “▲”or“▼”-button to set:
Order: Year→month→day date→day name→hour→minute→Timer ON hour minute→Timer OFF hour minute →year→…
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax: -400 · www.thermokon.com email@thermokon.de
LCF_TOUCH_Modbus_Datasheet_en-us © 2024
Page 6 / 10 Issue date: 22.04.2024
Set timer
Press the “ ”-button, the parameter to be changed is flashing, the timer will be set on or off.
Leave menu:
To delete timer on/off, press the “ ” button, the parameter to be changed is flashing. Then select “ ” or“ , set the time like the
Press the “ ” button for more than 5 seconds, the parameter to be changed is flashing. Press the “ ” button again, the value
needs to be changed, appears. (hour, minute, period). Changes in value by pressing ▲” or“▼”. The following 4 programmable periods
can be set.
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax: -400 · www.thermokon.com email@thermokon.de
LCF_TOUCH_Modbus_Datasheet_en-us © 2024
Issue date: 22.04.2024 Page 7 / 10
» CONFIGURATION
Parameters
= MODE button
In order to change the parameters, please press the MODE button for more than 5 seconds. Please follow figure below. If you are asked to enter
the password, use “▲”or “▼” key to enter each digit of the password. Press MODE button to switch to the next digit.
If the password has been entered correctly, you will see the parameter settings screen as below shown:
Press the MODE button to select the parameter you would like to change. Then use “▲” or “▼” to change the parameter. Please refer to the
parameter table on the following page:
After parameter selection / setting, don’t press any button for 3 seconds to save the settings.
» COMMUNICATION MODBUS
For configuration of the Modbus communication, please look up parameter No. 18 in the parameter table.
Communication-section 1..247
Factory default: 1
Communication-Interface: RS485
Communication-Protocol: Modbus-RTU
Baud Rate: 4800 bps / 9600 bps / 19200 bps / 38400 bps (optional)
Factory default: 9600 bps
Parity: no parity / odd parity / straight parity (optional)
Factory default: no parity
Data: 8 bit
Stop: 2 bit
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax: -400 · www.thermokon.com email@thermokon.de
LCF_TOUCH_Modbus_Datasheet_en-us © 2024
Page 8 / 10 Issue date: 22.04.2024
Press the MODE button to select the parameter you would like to change. Then use “▲” or “▼” to change the parameter. Please refer to the
parameter table on the following page: All parameters are stored within an EEPROM (electrically erasable programmable ROM), ensuring no data
loss if the Thermostat is powered off.
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax: -400 · www.thermokon.com email@thermokon.de
LCF_TOUCH_Modbus_Datasheet_en-us © 2024
Issue date: 22.04.2024 Page 9 / 10
Holding Register:
Register address Description R/W Unit Options Function code
0 0x0000 mode Read / Write NC 1=cool,4=fan,8=heat,16=auto 0x000F
1 0x0001 fan speed Read / Write NC 2=low,4=medium,8=high,128=auto 0x03,00x06,0x10
2 0x0002 set point temperature Read / Write 0.1℃ 1-500(0x01F4),for example:265 and 0x03,00x06,0x10
26.5℃
3 0x0003 on/off Read / Write NC 0=stop,1=run 0x03,00x06,0x10
4 0x0004 temperature lower limit Read / Write 1℃ 1-50(0x0032) 0x03,00x06,0x10
default=16℃
5 0x0005 temperature upper limit Read / Write 1℃ 1-50(0x0032) default=30℃ 0x03,00x06,0x10
6 0x0006 Power failure Read / Write NC 0-keep off power on,1-Memo while the 0x03,00x06,0x10
power failure, 2-switch on while power on
Default=0
7 0x0007 Key-lock Read / Write NC see parameter table: binary notation 0x03,00x06,0x10
Temp=16=0x10
Fan=8=0x08
Clock=4=0x04
Mode=2=0x02
ON/OFF=1=0x01
8 0x0008 Backlight delay Read/Write s 10-150s,default=15s 0x03,00x06,0x10
9 0x0009 change over Read /Write 1℃ 12-24,default=19℃ 0x03,00x06,0x10
temperature cooling (2-
pipe + external temp.
sensor)
10 0x000A change over Read /Write 1℃ 25-45,default=30℃ 0x03,00x06,0x10
temperature heating (2-
pipe + external temp.
sensor)
11 0x000B Fan coil type Read /Write NC 2=cooling&heating 2-pipe 0x03,00x06,0x10
4=cooling&heating 4-pipe
,6=cooling+elec-heater,default=2
12 0x000C 7day 4periods Read /Write NC 0=forbidden,1=allowed ,default=0 0x03,00x06,0x10
programmable
13 0x000D time of the first Read /Write NC hour:min,BCD code data format 0x03,00x06,0x10
temperature zone e,g:08:30=0x0830
14 0x000E temperature setting of Read /Write 1℃ 16-30,default=25℃ 0x03,00x06,0x10
the first temperature
zone
15 0x000F time of the second Read /Write NC hour:min, BCD code data format 0x03,00x06,0x10
temperature zone e,g:14:00=0x1400
16 0x0010 temperature setting of Read /Write 1℃ 16-30,default=26℃ 0x03,00x06,0x10
the second temperature
zone
17 0x0011 time of the third Read /Write NC hour:min,e,g:20:00=0x2000 0x03,00x06,0x10
temperature zone
18 0x0012 temperature setting of Read /Write 1℃ 16-30,default=27℃ 0x03,00x06,0x10
the third temperature
zone
19 0x0013 time of the fourth Read /Write NC hour:min, BCD code data format 0x03,00x06,0x10
temperature zone e,g:02:00=0x0200
20 0x0014 temperature setting of Read /Write 1℃ 16-30,default=28℃ 0x03,00x06,0x10
the fourth temperature
zone
21 0x0015 Individual passwords Read /Write NC 001-999,defaul=260 0x03,00x06,0x10
setting
22 0x0016 Summer/winter time Read /Write NC 0=forbidden,1=allowed ,default=1 0x03,00x06,0x10
23 0x0017 system time-- year Read /Write NC 2000-2099,default=2015 0x03,00x06,0x10
24 0x0018 system time--month Read /Write NC 01-12 0x03,00x06,0x10
25 0x0019 system time--day Read /Write NC 01-31 0x03,00x06,0x10
26 0x001A system time-hour Read /Write NC 00-23 0x03,00x06,0x10
27 0x001B system time-minutes Read /Write NC 00-59 0x03,00x06,0x10
28 0x001C system time--seconds Read /Write NC 00-59 0x03,00x06,0x10
29 0x001D system week Read /Write NC 1=Sun ,2=Mon ,3=Tue ,4=Wed 5=Thu 0x03,00x06,0x10
6=Fri 7=Sat
30 0x001E IR receiver Read /Write NC 0=OFF, 1=ON 0x03,00x06,0x11
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax: -400 · www.thermokon.com email@thermokon.de
LCF_TOUCH_Modbus_Datasheet_en-us © 2024
Page 10 / 10 Issue date: 22.04.2024
Coil
Coil address Description R/W Unit Options Function
code
0 0x0000 working status Read -only NC 0=stop,1=run 0x01
1 0x0001 failure status Read -only NC 0:Non,1:failure 0x01
2 0x0002 VA1 status Read -only NC 0=stop,1=run 0x01
3 0x0003 VA2 status Read -only NC 0=stop,1=run 0x01
Read -only 0=stop,1=run(this function under
4 0x0004 electrical heating status NC 0x01
cooling+electr-heater is available
5 0x0005 low speed status Read -only NC 0=stop,1=run 0x01
6 0x0006 Medium speed status Read -only NC 0=stop,1=run 0x01
7 0x0007 high speed status Read -only NC 0=stop,1=run 0x01
Input Register
Address Description R/W Unit Options Function
code
0 0x0000 return air temperature Read -only 0.1℃ 0-500(0x01F4), for example:245 and 24.5℃ 0x04
1 0x0001 fan status Read -only NC 0=stop,2=low,4=medium,8=High 0x04
2 0x0002 VA1 status Read -only NC 0=stop,1=run 0x04
3 0x0003 VA2 status Read -only NC 0=stop,1=run 0x04
4 0x0004 electrical heating status Read -only NC 0=stop,1=runThis function under 0x04
cooling+electr-heater is available
5 0x0005 working status Read -only NC 0=stop,1=run 0x04
6 0x0006 failure status Read -only NC 0:failure-free, 0x04
1:room temperature sensor alarm
7 0x0007 fan coil type Read -only NC 2:cool&heat 2pipe, 0x04
4:cool&heat 4pipe,
6:cooling+electr-heater
8 0x0008 version Read -only NC 1010(0x03F2)-9999(0x270F),for 0x04
example:1322(0x0456) 13 | 22
communciation protocol version 1.3,
software version 2.2
9 0x0009 External temp sensor Read-only NC 0-00-500(0x01F4),e,g:245=24.5℃ 0x04
» DIMENSIONS (MM)
Display unit
Base plate
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax: -400 · www.thermokon.com email@thermokon.de