0% found this document useful (0 votes)
45 views2 pages

bf502 Ex Ce

Uploaded by

2008yangke
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
45 views2 pages

bf502 Ex Ce

Uploaded by

2008yangke
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

AutroSafe  - BF-502/Ex

Manual call-point with SelfVerify

Features
• Break glass unit for use in harsh environmental
conditions.
• Weather proof.
• Corrosion resistant GRP.
• Protection degree IP-66 and 67.
• Short circuit isolator in each unit.
• Automatic addressing.
• Proven technology.
• Designed to meet the requirement of the major
maritime classification societies.

Applications
BF-502/Ex is a manual call point for use in hazard-
ous area zone 0, 1 or 2. It must be connected to an
approved AutroSafe IS-barrier. The call point has
been designed for use with Autronica’s interactive
Versions
fire alarm system, AutroSafe, and comprises the
SelfVerify function. This function ensures the high- • BF-502* Manual call-point with SelfVerify.
est grade of reliability and the lowest degree of • BF-502/Ex Manual call-point with SelfVerify.
manual testing, because all units comprising this Eexia-version for use in all zones.
function are automatically self-tested once every 24 • BF-502/N* Manual call-point with SelfVerify.
hours. Eexn-version for use in zone 2 only.

The high IP degree and mechanical strength of the * See separate data sheet.
enclosure makes the call point suitable for outdoor Technical Specifications
applications in industrial, maritime and off-shore
installations. Weight 0,5 kg
Material Glass reinforced polyester
The call point must be installed according to local Colour Red
regulations which normally means along escape Voltage 10 - 27V DC
routes, landings and exits. Current consumption
Stand by: 0,3mA
Principle Environm. requirement EN-54
Break glass operation, releasing alarm switch. Degree of protection IP 66
Reset when a new glass is mounted. Working temperature - 20 - + 70°C
Cable inlets 2 x M20
“SelfVerify”, the call-points ability to initiate alarms Maintenance Replace broken glass
is regularly checked. Service Replace if faulty
Certificate NEMKO Ex99E004X
Ex data Ui = 15,75V
Ii = 63mA
Ci = 21,6nF
Li = 0
Pi = 443mW

P-BF502Ex/CE – 011026 Protecting life, environment and property...


 - BF-502/Ex
Manual call-point with SelfVerify

Connections

Order number Description


BF-502/Ex Manual Call-point certified
for use in zone 0, 1, 2
1 2 3 4 5 6

BNB-300/22/EX

1.Pos (+) in
2. Pos (+) out
3. Neg (-) in
4. Neg (-) out
5. Internal connection
6. Internal connection

Dimensions

Dimensions: HxWxD = 126x120x75mm

Autronica Fire and Security AS


Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01.
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99.
Autronica Industrial Ltd., Watford, United Kingdom. Phone: 1923 23 37 68, fax: 1923 22 55 77.

Visit Autronica Fire and Security's Web site: www.autronicafire.com