MM ENGINEERS
F – 428 SECTOR 63 NOIDA (UP) 201301
An ISO 9001:2015 Co.
Relay setting calculation for INCOMER – 1 [SST-1]
Parameters for transformer:-
Transformer rating : 7.5MVA, 220kV/33kV
Full load current (LV): 131.31A
Full load current (HV): 19.68A
CT RATIO:- 200/1A
51 OVERCURRENT
Direction Non Directional
I>Current Set A 0.72168784 110% of the rated Value
Function DT
Time Delay s 2
I>>Current Set A 0.78729582 120% of the rated Value
Function DT
Time Delay s 0.5
EARTH
51N FAULT
Direction Non Directional
IN>Current Set A 0.13121597 20% of the rated Value
Function DT
Time Delay s 2
IN>>Current Set A 0.19682396 30% of the rated Value
Function DT
Time Delay s 0.5
Voltage Protection
27 Under Voltage Phase‐Phase
Measurement Mode
80% of rated
Voltage Set V 88 Voltage
Time Delay s 5
MM ENGINEERS
F – 428 SECTOR 63 NOIDA (UP) 201301
An ISO 9001:2015 Co.
59 Over Voltage
Measurement Mode Phase‐Phase
Voltage Set V 121 110% of rated Voltage
Time Delay s 0.5