Unit Iv
Unit Iv
Transformer is a static device which transfers the A.C electrical power from one circuit to
another circuit without changing the frequency, but voltage levels are changed according to
requirement.
The transformer consists of two windings called as Primary Winding and Secondary Winding. The
winding which is connected to ac supply is called primary winding and the winding which is connected
to load is called secondary winding. The symbol of transformer is as shown below.
If the secondary voltage (V2) is greater than primary voltage (V1), then the transformer is called
step up transformer and if the secondary voltage (V 2) is less than primary voltage (V 1), then the
transformer is called step down transformer. In another way, if the secondary winding turns (N 2) is
greater than primary winding turns (N 1), then the transformer is called step up transformer and if the
secondary winding turns (N2) is less than primary winding turns (N 1), then the transformer is called step
down transformer.
The transformer works on mutual induction principle. The transformer consists of two windings
and are placed on laminated core as shown in figure.(1).
Figure (1)
When an AC supply of V1 volts is connected to primary winding, an alternating flux is set up in
the core. This alternating flux is linked with the secondary winding, an emf will induced across
secondary winding called secondary emf (E2) and the same flux is linking with the primary winding
also, it produces an emf called primary emf (E1). Both the primary and secondary emf directions are
opposite to supply voltage (V1) according to Lenz’s law.
Ideal Transformer:
A transformer is said to be an ideal transformer when it obeys the following conditions (or)
properties
(i) The resistance of the winding should be zero
(ii) There should not any leakage flux in the transformer core i.e the total flux produced in the core
links with primary and as well as secondary.
(iii) The total losses in the transformer should be zero i.e the input power is equal to output power.
i.e since the winding resistance and magnetic leakage flux is zero, Copper and Iron (Core)
losses are zero respectively. So the efficiency of the idle transformer is 100%.
Since in ideal transformer the output (VA) equal to input (VA) i.e
E 2 I2 = E 1 I1
but the EMF is proportional to no .of turns (N) i.e E 1 E2 Since it is a ideal transformer,
the primary and secondary winding resistance is zero so E1 V E2 V
= 4 Φm f volts
No. of turns at primary winding N1 = 400 ; No. of turns at primary winding N1 = 1000
Area of core A =60cm2 = 60x10-4 m2 ; Primary voltage V1 = 520 V.
We know that transformation ratio (K) =
Prob: A 25KVA, 1-Ph, 50Hz, 6600/600V transformer has a maximum value of flux in the core is
0.08wb, find the no. of turns in each winding.
Sol: Given that 6600/600V i.e Primary voltage V1 = E1 = 6600V
Secondary voltage V2 = E2 = 600V and Maximum flux Φm = 0.08wb
We know that Primary EMF E1 = 4.44 Φm f N1
= 34 turns
Construction of T/F :
The transformer has two different types of constructions. Those are
(i) Core type transformer (ii) Shell type transformer
Core type construction: In core type construction, the magnetic core is built up with laminations in the
form of L-shape limbs/strips or C & I shape limb as shown in fig. (2) and then the L-shaped limbs or C
& I shape limb are joined as rectangular frame as shown in fig.(3).
In core type transformer, the primary and secondary windings placed on each limb to reduce the
leakage flux as shown in fig.(3). Here a part of core is surrounded by the winding and it has only one
magnetic path.
Shell type shell: In shell type shell, the magnetic core is built up with laminations in the form of E & I-
shape limbs/strips or F & L-shape limbs/strips as shown in fig. (4) and then the E & I-shaped limbs or F
& L-shape limbs/strips are joined as rectangular frame as shown in fig.(5).
In shell type transformer, the primary and secondary windings are wound on central limb only as shown
in fig.(5). Here the winding is surrounded by core and the total magnetic flux is splitted into two equal
halves.
Transformer on No Load:
A transformer is said to be on No Load when the secondary of the transformer open circuited
and secondary current I2 is zero. Under no load condition, the transformer primary draws a minimum
current called no load current I0. This no load current is usually 5% to 7% of rated current because of
this reason, the copper losses (I02R1) are low and are neglected. Since the secondary winding is opened
the secondary copper losses (I22R2) are zero. Therefore the no load current I 0 lags the primary voltage V 1
by an angle ϕ0 as shown in fig.(6).
No load current I0 =
When the transformer is on load, a current I2 flows through the secondary winding of
transformer. This secondary current setups its own flux Φ 2 in the core, but the direction of this flux Φ 2 is
opposite for the flux set up by the no load current I 0 according to Lenz’s law. Since the flux Φ 2 is
opposite for the flux Φm, the resultant flux (Φm – Φ2) decreases and causes the reduction in self induced
EMF (E1). This causes the additional current I2’ from the supply (called as load component of primary
current). This additional current crates a flux Φ 2’ which is equal in magnitude but opposite to flux Φ 2.
Now the flux in magnetic core is only Φm because the fluxes Φ2 and Φ2’ cancels each other.
From the above discussion it is clear that the flux in the transformer core is constant when the
load on the transformer is varies, hence the core or iron losses are constant irrespective of load
variations. Now the total primary current is the vector sum of I 0 and I2’. The phasor diagrams for
various loads on transformer are as shown below.
To the draw the vector diagram, the flux is taken as reference. The EMFs E 1 and E2 are opposite to
supply voltage V1 according to Lenz’s law. The no-load current I 0 lags the voltage V1 by angle ϕ0. The
additional current I2’ is opposite to current I2. Therefore the total current I1 is the sum of I0 and I2’. When
the transformer is loaded with resistive load, the secondary current I 2 is in phase with secondary voltage
V2. For inductive load, the secondary current I 2 is lags the secondary voltage V 2 by an angle ϕ2 and for
capacitive load, the secondary current I2 is leads the secondary voltage V2 by an angle ϕ2 The phase
angle between the voltage V1 and current I1 is ϕ1.
Losses and Effiency of Transformer:
Since the transformer is a static device, the mechanical losses in transformer are zero. Therefore
the transformer has only Iron losses and Copper losses.
Iron losses (Wi): These losses are also known as constant losses or core losses because these losses
are depend on flux but flux is constant irrespective of load variations in transformer. The Iron losses are
divided into Hysteresis and Eddy current.
Hysteresis losses: The hysteresis losses are given by an empherical formula ie.
Wh Bm1.6 f V watts or
Wh KhBm1.6 f V watts
Where Kh = hysteresis loss constant and is depends on type of material used for transformer core.
Bm = Maximum flux density ; V = volume of core in m3 and f = Frequency in Hzs.
The hysteresis losses are minimized by design the T/F core using the silicon/CRGO steel material.
Eddy current losses: The Eddy current losses are given by an empherical formula ie.
We Bm2 f 2 V2 t2 watts or We Ke Bm2 f 2 V2 t2 watts
Where Ke = Eddy current loss constant and t =Thickness of the transformer core laminations.
Bm = Maximum flux density ; V = volume of core in m3 and f = Frequency in Hzs.
Generally, the thickness of laminations of T/F core may varies from 0.35mm to 0.5 mm for 50Hz. The
eddy current losses are reduced by laminating the transformer core. The total iron losses are reduced by
designing the T/F core with silicon/CRGO steel laminations. Practically, the Iron losses of transformer
are determined by conducting Open Circuit (O.C) test.
Effect of Variations of Frequency & Supply Voltage on Iron Losses:
Let Bm = Maximum flux density;
V = volume of core in m3 and t = thickness of laminations
f = Frequency in Hz.
Kh = hysteresis loss constant and Ke = eddy current loss constant
The iron losses of a transformer are Wi = Wh + We ------------- (1)
The hysteresis losses are given as Wh Bm1.6 f V
Wh KhBm1.6 f V
Wh KhBm1.6 f
The Eddy current losses are given as We Bm2 f 2 V2 t2
We Ke Bm2 f 2 V2 t2
We Ke Bm2 f 2
Iron losses Wi = KhBm1.6 f + Ke Bm2 f 2 ----------------- (2)
Copper losses (Wcu): These losses occur due to resistance of the transformer windings. Let R 1 and R2 are
internal resistance of primary and secondary windings, I 1 and I2 are full currents of primary and
secondary windings.
The primary winding copper losses are given by I12R1
The secondary winding copper losses are given by I22R2.
Total copper losses (Wcu) = I12R1 + I22R2 Full load copper losses
Total copper losses at x load (Wcu) = x2 (I12R1 + I22R2)
The copper losses are also known as variable losses because they are proportional to square of the load
current. Practically, these losses are determined by conducting Short Circuit (S.C) test on transformer.
Total losses: The total losses in T/F are the sum of iron losses and full load copper losses i.e
Total losses = Iron losses (Wi) + full load copper losses (Wcu) For full load
Total losses for x load = Wi + x2 full load copper losses
Effiency (η): The Effiency of the transformer are defined as the ratio of output power (P 0) to input
power (Pi) i.e
Effiency (η) =
Effiency (η) =
Input = V1I1CosΦ1 , Iron losses = Wh + We and Total copper losses Wcu = I12R01
Effiency (η) =
1
To get max. Effiency, differentiating above equation on both sides w.r.t to I and equate it to zero i.e
2
i 1 01
W =I R
i.e for maximum Effiency, the condition is full load copper losses(variable losses) are equal to iron
losses(Constant losses)
Maximuneffiency (ηmax) =
Referred Values:
(i) All parameters referred to secondary side:
If R1 is the primary winding resistance and is transferred to
secondary, let this transferred resistance as R1’ as shown in fig.(11).
I1 and I2 are the full load primary and secondary currents. Now
copper losses of primary winding is equal to copper losses of
secondary winding i.e
I12 R1 = I22 R1’
R1’ = K2 R1
Total equivalent resistance referred to secondary is R02 = R2 + R1’
= R2 + K 2 R 1
Where Transformation Ratio (K) =
Similarly
Reactance transformed to secondary is X1’ = K2 X1
Total equivalent resistance referred to secondary is X02 = X2 + X1’ = X2 + K2 X1
Impedance transformed to secondary is Z1’ = K2 Z1
Total equivalent impedance referred to secondary is Z02 = Z2 + Z1’ = Z2 + K2 Z1
or
Z02 =
(ii) All parameters referred to primary side:
If R2 is the secondary winding resistance and is transferred to primary, let this transferred
resistance as R2’ as shown in fig.(12). I1 and I2 are the full load primary and secondary currents. Now
copper losses of secondary winding is equal to copper losses of primary winding i.e
I22 R2 = I12 R2’
R2’ = R2/ K2
Total equivalent resistance referred to primary is R01 = R1 + R2’
= R1 + R2/ K2
Where Transformation Ratio (K) =
Similarly
Reactance transformed to primary is X2’ = X2/ K2
Total equivalent resistance referred to primary is X01 = X1 + X2’ = X1 + X2/ K2
Since the effect of no load current I0 is negligible on R1+jX1 impedance, so the no load parallel branch is
moved towards supply voltage V1 as shown below
The above figure represents the exact equivalent circuit of 1-ph transformer.
(i) Equivalent circuit referred to primary:
If all the secondary quantities are referred to the primary, we get the equivalent circuit of the
transformer referred to the primary as shown in Fig. (5).
i. Let R2’, X2’ and ZL’ are the resistance, reactance and load impedance of secondary winding
referred to primary and are determined by dividing R2, X2 and ZL with K2
i.e R2’ = R2 / K2 , X2’ = X2 / K2 and ZL’ = ZL / K2
ii. Similarly voltage and EMF are divided by K and current is multiplied by K. i.e V 2’ = V2 / K ,
E2’ = E2 / K and I2’ = K I2.
Fig.5: Equivalent circuit of the transformer referred to the primary
we know that R01 = R1 + R2’ & X01 = X1 + X2’, the above citcuit diagram can redrawn as shown below
Consider the approximate equivalent circuit of T/F referred to secondary and its vector diagram as
shown below
=0
=0
- I2 =0
TanΦ2 = Φ2 =
i.e the voltage regulation of T/F is maximum, when the load angle Φ2 =
The zero voltage regulation of T/F may obtained for leading or capacitive loads,
Voltage Regulation = =0
I2 =0
TanΦ2 = Φ2 =
i.e the voltage regulation of T/F is maximum, when the load angle Φ2 =
.e., μr =
B-H curves are very useful to analyze the magnetic circuit. If value of flux density and dimension of
magnetic circuit is known than from B-H curve total ampere turn can be easily known.
Magnetic hysteresis
The phenomenon of lagging behind of induction flux density (B) behind the magnetizing force (H) in
magnetic material is called magnetic hysteresis.
Hysteresis loop is a four quadrant B – H graph from where the hysteresis loss, coercive force and
retentively of magnetic material are obtained.
To understand hysteresis loop, we suppose to take a magnetic material to use as a core around which
insulated wire is wound.
The coils is connected to the supply (DC) through variable resistor to vary the current I. We know that
current I is directly proportional to the value of magnetizing force (H).
When supply current I = 0, so no existence of flux density (B) and magnetizing force (H). The
corresponding point is o in the graph above.
When current is increased from zero value to a certain value, magnetizing force and flux density both
are set up and increased following the path o to a.
For a certain value of current, flux density becomes maximum (Bm). The point indicates the magnetic
saturation or maximum flux density of this core material. All element of core material get aligned
perfectly.
When the value of current is decreased from its value of magnetic flux saturation, H is decreased along
with decrement of B not following the previous path rather following the curve a to b.
The point b indicates H = 0 for I = 0 with a certain value of B. This lagging of B behind H is called
hysteresis.
The point b explains that after removing of magnetizing force (H), magnetism property with little
value remains in this magnetic material and it is known as residual magnetism (Br) or residual flux
density.
If the direction of the current I is reversed, the direction of H also gets reversed. The increment of H in
reverses direction following path b – c decreases the value of residual magnetism that gets zero at point
c with certain negative value of H. This negative value of H is called coercive force (Hc)
Now B gets reverses following path c to d. At point‘d’, again magnetic saturation takes place but in
opposite direction with respect to previous case. At point‘d’, B and H get maximum values in reverse
direction.
If decrease the value of H in this direction, again B decreases following the path d. At point e, H gets
zero valued but B is with finite value.
The point e stands for residual magnetism (-Br) of the magnetic core material in opposite direction
with respect to previous case.
If the direction of H again reversed by reversing the current I, then residual magnetism or residual
flux density (-Br) again decreases and gets zero at point ‘f’ following the path e to f.
Again further increment of H, the value of B increases from zero to its maximum value or saturation
level at point a following path f to a.
Hard and soft material hysteresis loop are given below.
Now, the Flux Density (B) is proportional to Flux for a given core area.
B is related to H by the B-H curve of the core material.
H is related to the magnetizing current by the number of turns with fixed core length.
Thus, if the B-H curve is straight line (linear), then the magnetizing current wave-shape will be
sinusoidal for a sinusoidal applied voltage.
However, in practical cases, we design voltage transformers for economy and to reduce size and
price, we push up the working value of B well above the linear region of the B-H curve.
Hence we get a non-sinusoidal magnetizing current waveform even if the applied voltage is
sinusoidal.
A non-sinusoidal magnetizing current implies harmonic content in it.
If you design the transformer with low values of B such that it is in the linear region of the B-H
curve, then you will get sinusoidal magnetizing current with sinusoidal applied voltage.