Elee Ctrical
Elee Ctrical
INTRODUCTION
The Institution of Electrical Engineers (lEE) guide (BS 7671) is used to assist in
design and installation of electrical services. Engineers follow the guide closely to
provide safe and efficient electrical systems in buildings.
The area electricity board's cable, from which the domestic supply is taken, consists
of four lines, three lines each carrying a 240 volt supply and the fourth is the
common return line or neutral which is connected to earth at the transformer or
substation as a safety precaution should a fault occur on the electrical appliance.
Each line or phase is tapped in turn together with the neutral to provide the single-
phase 240 V supply.
The supply or intake cable may enter the building through an underground duct or
via an overhead supply.
The supply cable is terminated in the area board’s fused sealing chamber which
should be sited in a dry accessible position. From the sealing chamber the supply
passes through the meter, which records the electricity consumed in units of
kilowatt/hours, to the consumer unit which has a switch controlling the supply to the
circuit breakers or circuit fuses.
These fuses are a protection against excess current or overload of the circuit since
when overloading occurs, the fuse or circuit breaker will isolate the circuit from the
source of the problem.
Sub-circuits
Distribution Combined in a
The consumer unit should be fitted close to the point of service entry and from here
the service is divided into a number of sub-circuits. It is normal in a domestic
installation to separate power circuits and lighting circuits so that if a fault occurs
then not all socket outlets or lights are isolated.
Sometimes an external cabinet is used for easy meter reading. This is located in an
outside wall as shown below.
Outside
Incoming cable
Foundation
EXTERNAL CABINET
POWER CIRCUITS
When deciding on the number of circuits for a house, a useful rule is; one power
circuit for every 100m2 of floor area. In larger houses this means that two circuits
can be used for power socket outlets, in a two-storey house this would be one
circuit for upstairs and one for downstairs. In some larger houses a separate power
circuit is also installed for the garage / utility area.
In all domestic installations a separate power circuit is required for the cooker since
the electrical demand is likely to be high. The immersion heater in the hot water
cylinder can also be supplied from a separate circuit since a 3kW load is quite high.
Ring circuits are used as a safe and economic method of distribution of electricity
to socket outlets.
The earth conductor may not be covered but the live and neutral are each
separately coated in a PVC covering. The three conductors (L,N & E) can be covered
in an outer covering of PVC to form PVC/PVC Twin and Earth. The typical size of
conductors for a ring circuit for domestic use is 2.5 mm2, this is the cross sectional
area of the conductor. The conductors are pulled through the conduit after it is
installed by a ‘fish’ wire.
Another method of installing a ring circuit may be to distribute the conductors
horizontally under the floor instead of above the ceiling. This reduces the length of
conduit buried in the wall. If a solid cement floor is constructed then the conductors
Steel or plastic
would need to be protected by galvanised steel conduit. conduit buried
If a suspended in wallfloor
timber to
is constructed then a PVC/PVC cable could be clipped to PVC/PVC
protect woodenconductors.
floor joists. This is
the method adopted for two-storey houses, for an upstairs ring circuit.
Twin Socket Conduit contains conductors either
Outlet encapsulated in a cable or individually.
PVC/PVC conduc
incorporating liv
CONSUMER’S MAINS EQUIPMENT and earth (twin
External wall
run at ceiling lev
Internal wall
The consumer's mains equipment is normally fixed close to the point at which the
supply cable enters the building. To meet the requirements of the IEE Regulations it
must provide:
Protection against electric shock is provided by insulating and placing live parts out
of reach in suitable enclosures, earthing and bonding metal work and providing Conduit to cei
fuses or circuit breakers so that the supply is automatically disconnected under fault level.
conditions. To provide overcorrect protection it is necessary to provide a Consumer
device
which will disconnect the supply automatically before the overload current can
cause a rise in temperature which would damage the installation. A fuse or
miniature circuit breaker (MCB) would meet this requirement.
A switch may provide the means of isolation but an isolator differs from a switch in
RING CIRCUIT
that it is intended to be opened when the circuit LAYOUTisINnot
concerned SMALL BUILDING
carrying current.
Its purpose is to ensure the safety of those working on the circuit by making dead
those parts, which are live in normal service. One device may provide both isolation
and switching provided that the characteristics of the device meet the Regulations
for both functions. The switching of electrically operated equipment in normal
service is referred to as functional switching.
Circuits are controlled by switchgear, which is assembled so that the circuit may be
operated safely under normal conditions, isolated automatically under fault
conditions, or isolated manually for safe maintenance.
These requirements are met by good workmanship and the installation of proper
materials such as switches isolators, fuses or circuit breakers.
In practice it is the aim to bring the Electrical supply to the appliance with as small a
loss of voltage through the conductor as possible. This means that the wiring must
have the smallest resistance that is economical.
EARTHING SYSTEMS
These have been designated in the IEE Regulations using the letters: T, N,
C and S. These letters stand for:
When these letters are grouped, they form the classification of a type of
system.
The first letter denotes how the supply source is earthed.
The second denotes how the metalwork of an installation is earthed. The
third and fourth indicate the functions of neutral and protective
conductors.
TT SYSTEM
TN-S SYSTEM
A TN-S system has the supply source directly connected to earth, the
installation metalwork connected to the neutral of the supply source via
the lead sheath of the supply cable, and the neutral and protective
conductors throughout the whole system performing separate functions.
The resistance around the loop P-B-N-E should be no more than 0.8 ohms.
TN-C-S SYSTEM
A TN-C-S system is as the TN-S but the supply cable sheath is also the
neutral, i.e. it forms a combined earth/neutral conductor known as a PEN
(protective earthed neutral) conductor.
The installation earth and neutral are separate conductors.
This system is also known as PME (protective multiple earthing).
The resistance around the P-B-N-N loop should be less than 0.35 ohms.
The TT method is used mostly in country areas with overhead transmission lines. In
contrast to the TN-S system there is no metallic path from the consumer's terminals
back to the sub-station transformer secondary windings. Because the earth path
may be of high resistance, a residual current circuit-breaker (R.C.C.B.) is often fitted
so that if a fault current flows in the earth path then a trip disconnects the phase
supply.
For protection against indirect contact in domestic premises, every socket outlet
requires an RCCB with a maximum rated current of 30mA.
The TN-S system of wiring uses the incoming cable sheath as the earth return
path and the phase and neutral have separate conductors. The neutral is then
connected to earth back at the transformer sub-station.
Remember in TN-S, the T stands for earth (terre), N for neutral and S denotes that
the protective (earth) and neutral conductors are separate.
The TN-C-S system has only two conductors in the incoming cable, one phase and
the other neutral. The earth is linked to the neutral at the consumer unit. The
neutral therefore is really a combined earth/neutral conductor hence the name PME.
In order to avoid the risk of serious electric shock, it is important to provide a path
for earth leakage currents to operate the circuit protection, and to endeavour to
maintain all metalwork at the same potential. This is achieved by bonding together
all metalwork of electrical and non-electrical systems to earth.
The path for leakage currents would then be via the earth itself in TT systems or by
a metallic return path in TN-S or TN-C-S systems.
NOTES
Older houses in towns use TNS (solid) i.e. separate earth say cable
sheath.
Around Towns new houses use (PME) TNCS i.e. neutral and earth shared.
Single House in country with own transformer uses TT i.e. own buried
earth electrode.
Petrol stations, Swimming pools, Changing rooms etc. are not allowed to
be PME.
LAMPS
The oldest source of artificial light is the flame from fires, from candles and from oil
lamps where light is produced as one of the products of chemical combustion.
Modern sources of artificial light convert electrical energy light energy and are of
two general types: incandescent sources and discharge sources.
Incandescent Lamps
Discharge Lamps
Further details of these lamps and their properties are given in the following
sections.
Incandescent Lamps
To prevent oxidation (burning) of the metal the tungsten coil is sealed inside a glass
envelope and surrounded by an inert atmosphere of uncreative gases such as argon
and nitrogen. During the operation of the lamp tungsten is evaporated from the
filament and deposited on the glass causing it to blacken. The filament therefore
thins and weakens and must eventually break.
The simple tungsten lamp, such as a light bulb, is the oldest, shortest-lived and
least efficient type of electrical light source and is being replaced by more efficient
lamps. But the properties of filament lamps have been greatly improved by using
halogen gases and lower voltages, as described below, and these lamps are useful
in modern lighting design.
figure 1.2.
FIG. 1.2
The filament lamp produces a spectral distribution of light which is continuous but
deficient in blue. This quality of light is seen as 'warm' and is considered generally
suitable for social and domestic applications.
The cost of a tungsten filament lamp is low and its installation is simple, but the
relatively short life (1000 hours) of the lamp can cause the labour costs of
replacement to be high. The low luminous efficacy of the lamp produces high
electrical running costs. Only about 5 per cent of the electrical energy is converted
to visible light and most of the energy consumed is given of as heat, especially
radiant (infra-red) heat.
Incandescent lamps come in a variety of shapes and sizes and have a number of
different fittings: Bayonet cap (BC), Small Bayonet cap (SBC), Edison screw (ES or
E27) and Small Edison Screw (SES or E14). The Edison screw types are becoming
more popular in the UK. Several different coatings are also available with the
following properties: Pearl is an all over frosting which diffuses the light and is best
used in a light fitting with shades. Clear bulbs are more attractive when used in
fittings where the bulb is visible or a sparkle is required such as crystal chandeliers.
3. Reflecting Lamps
The relatively large size of the standard tungsten filament lamp makes it difficult to
control the direction of the light.
Spot lamps (PAR) are filament lamps with the glass bulb silvered inside and
shaped to form a parabola with the filament at the focus. This arrangement gives a
directional beam of light which is available in different widths of beam. Sealed beam
lamps use similar techniques.
Crown-silvered lamps (CSL) are standard filament lamps where the glass bulb is
silvered in front. When this lamp is used with a special external reflector it also
gives narrow beams of light.
4. Tungsten-Halogen Lamps
Halogen bulbs produce a very attractive light which closely resembles sunlight.
They are more efficient than incandescent bulbs using only half the energy to
produce the same light output and last twice as long. Generally they are small
lamps which generate a lot of heat so they can only be used in light fittings
designed to cope with the higher temperatures. There are two main types of
halogen lamp available in the domestic market:
Tungsten-halogen lamps have filaments which run at higher temperatures with the
presence of a small quantity of a halogen gas, such as iodine or bromine. When
tungsten evaporates from the filament it is deposited on the hot wall of the lamp
where it combines with the iodine. This new compound is a vapour which carries the
tungsten back onto the lamp and re-deposits it on the hot filament, while the iodine
is also re-cycled.
In order to run at higher temperatures the envelope of the tungsten-halogen lamp is
made of quartz instead of plain glass. The heat-resistance of the quartz allows the
construction of a very small bulb for applications such as spot lamps, projectors and
car headlamps where directional control of light is important. Tungsten-halogen
lamps also have the general advantages over simple tungsten lamps of increased
efficiency and longer life.
The small size of these lamps gives them good directional qualities which make
them popular in shops for the display of goods. The relatively low heat output of
low-voltage systems is also an important property in stores where high levels of
illumination can cause overheating.
Discharge Lamps
Apart from the well-known tubular fluorescent lamp, gas discharge lamps have in
the past been restricted to outdoor lighting, such as for roadways where their
generally poor colour qualities have not been important. Modern types of discharge
lamp have a colour rendering that is good enough for large-scale lighting inside
buildings such as factories and warehouses. Continuing technical advances are
producing more discharge lamps suitable for interior lighting and the high efficacy
of such lamps can give significant savings in the energy use of buildings.
1. Fluorescent Lamps
Fluorescent gas discharge lamps work by passing an electric current through a gas
or vapour so that a luminous arc is established within a glass container.
The energised gas atoms emit ultra-violet (UV) radiation and some blue green
light. A coating of fluorescent powders on the inside of the glass absorbs the UV
radiation and re-radiates this energy in the visible part of the spectrum. The
fluorescent coating therefore increases the efficiency of the system and allows the
colour quality of the light to be controlled.
When the main switch is closed, the mains In this system the cathodes are
heated
because they are close together, a glow not strike until the preheating
period is
FIG 2.1
FLUORESCENT LAMPS
FIG 3.1
In the mercury halide (MBI) lamp, metallic halides are added to the basic gas
discharge in order to produce better colour rendering and to raise the efficacy.
Low pressure sodium lamp with Low pressure sodium lamp with
U-shaped arc tube enclosed in specially formed arc tube sealed into
clear outer glass tube, and with a clear glass outer tube.
cap at one end only. Usual ratings - 60W, 140W and 200W.
High pressure sodium lamp with sintered High pressure sodium lamp generally
as
aluminium oxide arc tube and elliptical SON but with a tubular clear glass outer
Properties Of Lamps
Luminous Efficacy
The ability of a lamp to convert electrical energy to light energy is measured by its
efficacy which is given by the following formula.
The electrical running costs of a lamp can be calculated from its efficacy.
The luminous efficacy of a lamp varies with its type and its wattage so exact data
should be obtained from the manufacturer.
Life
The luminous efficacy of a lamp decreases with time and for a discharge lamp it
may fall by as much as 50 per cent before the lamp fails. The nominal life of a
lamp is usually determined by the manufacturer by considering the failure rate of a
particular model of lamp combined with its fall in light output. In a large installation
it is economically desirable that all the lamps are replaced at the same time on a
specified maintenance schedule.
Colour Temperature
The qualities of light emitted by heated objects depend upon the temperature of the
radiating object and this fact can be used to describe the colour of light. A
theoretically perfect radiator, called a 'black body', is used as the standard for
comparison.
The correlated colour temperature (CCT) of a light source is the absolute
temperature of a perfect radiator when the colour appearance of the radiator best
matches that of the light source.
This method of specifying colour quality is most suitable for light sources that emit
a continuous spectrum, such as those giving various types of 'white' light. The lower
values of colour temperature indicate light with a higher red content. Some
examples of colour temperatures are given below.
Colour Rendering
The colour appearance of a surface is affected by the quality of light from the
source. Colour rendering is the ability of a light source to reveal the colour
appearance of surfaces. This ability is measured by comparing the appearance of
objects under the light source with their appearance under a reference source such
as daylight.
The same colours, viewed with different light sources, can appear very different.
When choosing clothing from a department store we can find that when we get
home and take it into different lighting conditions it looks different. This because
the different light sources that the article was viewed under gave different colour
appearances.
GLS bulbs and some fluorescent tubes give average to poor colour rendering but
the advanced fluorescent tubes and metal halide lighting can provide excellent
colour rendition.
The colour appearance of a lamp is affected by its operating temperature and a
white source of light can be related to a ‘black body radiator’, this is known as
correlated colour temperature (CCT).
Correlated Colour
Temperature (CCT) CCT class
(oK)
The table below gives typical colour rendering properties for lamps.
COMPARING LAMPS
COLOUR
LUMEN
LAMP REFERENCE WATTAGE
OUTPUT
APPEARANCE
Incandescent bulb GLS 60 Warm 710
1. Decorative lighting
2. Commercial lighting
3. Industrial lighting
4. Outdoor lighting
5. Emergency lighting
Decorative lighting
Downlights
The above photo shows fixed position downlights in compact fluorescent or low
voltage tungsten halogen lamp versions.
Specialised Downlights
The heat lamp shown below emits radiant heat and is used in Bathrooms and
shower areas to provide heat.
The infrared output which is unaffected by draughts, warms the body without
heating the surrounding air.
leads.
Uplights
Control Spots are easily positioned in any direction to create incisive lighting for
special projects, or simply to light awkward corners and blind spots, providing the
most comprehensive solution to almost every lighting opportunity.
Wide selection of mains and low voltage tungsten halogen and high intensity
discharge lamps provides spectrum of effects from narrow beam to high intensity
spotlighting.
Museum Lighting
Lighting the object with the correct quantity of light in the right place is the task
below.
Walls Lights
Some decorative spheres are shown for use with compact fluorescent lamps, with a
variety of mounting options.
Available in 18W and 26W 4 limb versions
Tungsten halogen and compact fluorescent lamps can be used in this wall light
shown below.
Fibre Optics
Designer Lighting
Table Lamps
Commercial lighting.
This includes Fluorescent fittings as follows;
Fluorescent Fittings
Slimline Fluorescent
Slimline fluorescent luminaires are suitable for use in a very wide range of
applications, particularly those where there is limited mounting space available.
The most common applications are advertising and display lighting, concealed
lighting, under cupboard lighting etc.
Reflector Fluorescent
TYPICAL USES:
Offices, banks, conference areas, schools, shops: areas with VDTs; refurbishment’s.
18W, 36W, 58W standard T8 tubes.
* Profiled louvre version for effective lighting of shops and general areas.
Fluorescent Battens
TYPICAL USES
Factories, workshops, stores, offices, shops, concealed lighting etc.
Twin Batten
A twin batten luminaire specifically for the 26mm energy saving lamps.
APPLICATIONS:
Recessed Fluorescent
TYPICAL USES
MOUNTING
Recessed.
* For exposed ceilings grids – wide variety of applications ideal for areas where
VDTs are used.
TYPICAL USES
DESCRIPTION
APPLICATIONS
VARIATIONS
Available from 27W to 60W with circular fluorescent lamps and in 16W, 28W and
38W 2D energy saving versions.
Fluorescent Square
APPLICATIONS
for General Purpose commercial, Hospital General Areas, Hospital Wards and
Colleges -
Decorative Bulkhead
Used in environments where a wall or vertical light source is required but for a more
decorative situation.
Fittings: GLS, 2D and PL.
Industrial lighting
High Bay
APPLICATION
Low bay luminaires have been designed with a shallow profile to enable modern high intensity ligh
sources to be used in situations involving lower mounting heights or restricted head room due to
LOCATION:
VARIATIONS
Available either with high pressure sodium, metal halide or mercury vapour lamps.
Industrial Reflector
FEATURES
of 150-400 watts.
APPLICATIONS
Outdoor lighting
This includes Bollards, Floodlights, column Mounted Lights and Lanterns
Bollards
The bollard posts shown below are manufactured from extruded aluminium finished
in textured black powder polyester coat.
Floodlights
Most floodlights offer a variety of lamp options to meet most area and site lighting
requirements.
These floodlights are particularly suited to small area and security lighting.
The floodlight shown below is for exterior use.
The floodlight shown above is for use with Discharge lamps up to 400 Watts.
APPLICATIONS
High pressure sodium floodlight for security applications, building facades and
perimeters, car parks, loading bays and precincts.
The floodlight shown above uses a 70W elliptical SON lamp with internal ignitor
* Especially suitable for local area lighting from low mounting heights of 3-5m for
close offset lighting of buildings
Floodlighting Buildings
* 150W and 250W SON-T lamps for economy and long life
* Low glare version available for tennis courts and similar applications
TYPICAL USES:
Exterior: Building facades, signs, sports areas, security lighting, car parks, area
floodlighting.
LAMPS:
Lamps that can be used include high pressure sodium and metal halide.
Lanterns
These are used for major traffic routes utilising a variety of light sources.
The light shown below is used for city centres, pedestrian areas, parks and
residential thoroughfares.
Lamps used can be high pressure sodium, metal halide or mercury vapour.
The lantern shown below uses the same types as the above fitting.
Exit Signs
The exit signs shown below are suspended from the ceiling.
They utilise 8W fluorescent lamps.
Bulkhead
Lighting Levels
The CIBSE (Chartered Institute of Building Services Engineers) produces a Code for
Interior Lighting which gives lighting requirements for areas.
uminance
Activity Area
(lux)
100 Casual seeing Corridors, changing rooms, stores
150 Some perception of detail Loading bays, switch rooms, plant rooms
200 Continuously occupied Foyers, entrance halls, dining rooms
300 Visual tasks moderately easy Libraries, sports halls, lecture theatres.
500 Visual tasks moderately difficult General offices, kitchens, laboratories, retail shops.
750 Visual tasks difficult Drawing offices, meat inspection, chain stores.
General inspection, electronic assembly, paintwork,
1000 Visual tasks very difficult
supermarkets.
1500 Visual tasks extremely difficult Fine work and inspection, precision assembly.
2000 Visual tasks exceptionally difficult Assembly of minute items, finished fabric inspection.
Educational
Healthcare - Wards
Offices
Retail Premises
The recommended design maintained illuminance over the task area in any room
where office work is carried out is generally in the range 300 to 500 lux.
Where the tasks are mainly screen based, such as data retrieval or telephone sales,
then illuminances at the lower end of this range should be used.
Where the tasks are mainly document based, such as writing or copy typing, then
500 lux will be required.
Where there are visually more onerous tasks, such as proof reading or technical
drawing, even higher levels should be considered.
The minimum level set by the Health and Safety Executive for any permanently
occupied area is 200 lux.
For recommendations of illuminance, colour rendering and glare see Schedule in the
Code for Lighting a summary of key values are given below.
Illuminance
Area
(lux)
Lifts 100
Corridors and stairs 100
Toilets 100
Canteens 300
Mess rooms 150 - 300
Plant rooms 150 - 300
Store rooms 100
More illuminance values are given for a range of industrial buildings in the Guides.
Lumen Method
CIBSE Lighting Guides give values of illuminance that are suitable for
various areas.
The section - Lighting Levels in these notes also gives illuminance values.
The lumen method is used to determine the number of lamps that should
be installed for a given area or room.
The luminous flux output (lumens) of each lamp needs to be known as well
as details of the luminaires and the room surfaces.
Usually the illuminance is already specified e.g. office 500 lux, kitchen 300
lux, the designer chooses suitable luminaires and then wishes to know how
many are required.
E x A
N =
F x UF x MF
where,
Example 1
Find the number of lamps required if each lamp has a Lighting Design
Lumen (LDL) output of 18,000 lumens.
PLAN
N = 53.33
N = 54 lamps.
Spacing
This means, for example, that for a room with an illumination level of 500
lux, if this is taken as the minimum level, then the maximum level in
another part of the room will be no higher than 714 lux as shown below.
Using data in the previous example show the lighting design layout below.
3/2 = Spacing / 4
24 / 6 = 4 rows of lamps
This can be shown below. Half the spacing is used for the ends of rows.
60 metres
24 metres
Half spacing = 3 m
Scale 1 cm = 4 metres
Factory Plan
The number of lamps in each row can be calculated by dividing the total
number of lamps found in example 1 by the number of rows.
= 2.14 metres
60 metres
4.28 metres
6m
24 metres
60 metres
6m
24 metres
The spacing previously was 6 m between rows and 4.28 m between lamps.
Installed Flux
Sometimes it is useful to know the total amount of light or flux, which has
to be put into a space.
Example 3
50m
2.0 m
2.5 m
Factory Plan
The output of the lamps in the above example may be found from
catalogues. For a 65-Watt fluorescent lamp the Lighting Design Lumens
(LDL) is 4400 lm.
(a)
= 4 x 25 x 2 x 4400
= 880,000 lumens
(b)
= 1760 lm/m2.
Example 4
A room measures 15m x 7m x 3.6m high and the design illumination is 200
lux on the working plane (0.85 metres above the floor).
N = 19.3
N = 20 lamps
For shallow fittings, the mounting height (H m) may be taken as the distance
form the ceiling to the working plane.
Spacing / Hm ratio:
15 metres
2.33 m
7 metr
2.142 m
Scale 1 cm = 1 metre
Room Plan
Example 5
A room, as shown below, has a design illumination is 500 lux on the working
plane (0.85 metres above the floor).
12 metres
(a)
N = 55.15
N = 56 lamps.
(b)
(c)
Lighting Design
Quantity of light
The amount of light emitted from a light fitting is given in lumens (lm)
The catalogues of light fittings give outputs in lumens; a selection is shown in the
table below.
One lux is equal to 1 lumen per square metre …….. 1 lux = 1 lm/m2.
The CIBSE (Chartered Institute of Building Services Engineers) produces a Code for
Interior Lighting which gives lighting requirements for areas.
300 Visual tasks moderately easy Libraries, sports halls, lecture theatres.
Visual tasks moderately General offices, kitchens, laboratories,
500
difficult retail shops.
Drawing offices, meat inspection, chain
750 Visual tasks difficult
stores.
General inspection, electronic
1000 Visual tasks very difficult
assembly, paintwork, supermarkets.
Fine work and inspection, precision
1500 Visual tasks extremely difficult
assembly.
Visual tasks exceptionally Assembly of minute items, finished
2000
difficult fabric inspection.
Quality of light
Artificial light from lamps can be emitted in various colour spectra and at different
angles fro emitter to receiver.
There are several aspects to be aware of for good design, for example; glare, colour
appearance and colour rendering.
Glare
Discomfort glare may cause irritation if the occupier is under the effect of a badly
designed system.
Also disability glare can be dangerous if a task is to be carried out and glare has an
adverse effect on the operator.
Limiting Glare Index
Colour Appearance
This is the apparent colour of the light emitted by the lamp and is quantified by its
correlated colour temperature (CCT).
Most lamps produce some form of white light from cool to warm.
Colour Rendering
The CIE colour rendering index is used to compare lamps and quantify how good
they are at reproducing colour.
A set of test colours is reproduced by the lamp of interest relative to how they are
reproduced by an appropriate standard light source.
Some lamps provide good colour rendering properties and this may be necessary in
areas where accurate colour appearance is important such as, car sales showrooms
and clothes retail outlets.
Most rooms have a minimum colour rendering of 80 in the CIE index.
Some rooms where colour is important such as Health Care, Product Colour
Inspection and Art Rooms have an Index of 90.
DAYLIGHT
Since the quality and quantity of daylight is a useful addition to artificial light in
buildings, the challenge to designers is to make use of daylight in an effective way.
For daylight calculations and design it is assumed that the sky is overcast and direct
sunlight is not used. The amount of illumination from a uniform overcast sky at
most is 35,000 lux in July at noon. However a standard figure of 5000 lux may be
used for calculations.
Window location, shape and size will determine the amount of light from outside
that enters a building and how far that light penetrates into the core of the building.
To assess the influence of window size, shape and position the daylight at a point in
a room is quantified by use of the daylight factor.
DAYLIGHT FACTOR
The daylight factor is the ratio of internal illuminance at a point in a room to the
external illuminance.
Internal Illuminance
Daylight factor = X 100%
External Illuminance
Like other light measurements the internal illuminance is normally taken at the
horizontal working plane level i.e. 0.85 metres above floor level.
Average Minimum
daylight
Area
Daylight
factor factor
Commercial Buildings:
General office 5% 2%
Classroom 5% 2%
Dwellings:
Kitchen 2%
Living room 1%
Bedroom 0.5%
Example 1
Calculate the illuminance at a point in a room given the daylight factor of 5% if the
external illuminance is 9500 lux.
Internal Illuminance
X 100%
Daylight factor =
External Illuminance
Therefore:
From the above table the recommended daylight factor for a kitchen is 2%.
CONTOURS
2%
5%
10%
15% 15%
20% 20%
Plan
Daylight factor contours
WINDOWS
Windows facing the direction of the sun (south in the northern hemisphere) will
receive more daylight than those facing in the opposite direction.
Tall windows will push the daylight factor contours back into a room while wide
windows give a better distribution across the width of a room but do not let the light
penetrate to the back.
To obtain an internal illuminance of 500 lux the daylight factor would need to be
about 10% in the U.K., this is higher than is normally expected, therefore artificial
light is added to daylight in most buildings. Artificial sources of light are needed at
night time anyway, but this does not mean that we should neglect window design.
One design process is used to ensure that the back of a room is not dull. It uses the
formula as follows:
Where;
L = depth of room from window to back wall (m)
RB = average reflectance of the half of the interior at the back of the room.
H = m x Cp x T.
Where:
H = Heat load in system (kW)
m = Mass flow rate of water (kg/s)
Cp = Specific heat capacity of water (4.187 kJ/kg degC)
T = Water temperature difference between flow and return
(10degC for L.T.H.W.)
Therefore: m = H / (Cp x T)
Q = ( m / ) x 3600
Where:
Q = Flow rate in m3/hr
= Density of water (1000 kg/m3)
2. Find the pressure drop across the valve in bars for a valve authority of 0.5
using the following formula:
Pvalve = Pcircuit.
1 bar = 100,000
2
N/m
1 bar = 100
2
kN/m .
NOTE: The pressure drop around the circuit refers to that part of the
circuit where the water flow varies.
Therefore:
EXAMPLE 1.
m = 40 / (4.2 x 10)
m = 0.95 kg/s
Q = ( m / ) x 3600
Where:
Q = Flow rate in m3/hr
= Density of water (1000 kg/m3)
2. Find the pressure drop across the valve in bars for a valve authority of 0.5
using the following formula:
Pvalve = 20 kN/m2.
Kv = 3.42 / 0.4472
Kv = 7.65
4. Select a valve from a catalogue with this value of Kv.
(Pvalve )0.5 = Q / Kv
Pvalve = (Q / Kv )2
Pvalve = ( 3.42 / 8 ) 2
Pvalve
Pvalve + Pcircuit
Valve authority =
If a 11/4” valve had been chosen then the Kv from the catalogue
would be 12 and the valve authority would be:
Pvalve = (Q / Kv )2
Pvalve = ( 3.42 / 12 ) 2
Pvalve = 0.08123 bar
Pvalve = 8.123 kN/m2.
Valve authority =
Some manufacturers recommend that MIXING valves are positioned in the flow
with the pump positioned in the return pipe. Also for DIVERTINGapplications
the valve is to be positioned in the return pipe with the pump in the return pipe as
shown below.
Satchwell Recommendations:
MIXING AND DIVERTING APPLICATIONS
These valves must always be installed with two inlet streams and
one outlet stream i.e. as mixers. Reversal of this direction will cause
vibration and water hammer which will damage both valve and
actuator.
For diverting applications the valve must therefore be fitted in the
return pipe.
The water will be diverted with respect to the load, but will mix in
the valve.