With or without terminals
DK 1600 G
without terminals
included cable entry: 3 x ESM 40, sealing range Ø 17-30 mm
with two cable entries M 32 from the rear side
lid fasteners sealable without accessories
external brackets for wall fixing included
colour: grey, RAL 7035
rated insulation voltage Ui = 1000 V a.c./d.c.
material PC (Polycarbonate)
degree of protection IP 55 (ESM)
degree of protection IP 66 (AKM)
mounting width 175 mm
mounting height 120 mm
max. installation depth 76 mm
width 210 mm
height 155 mm
depth 92 mm
weight 0,444 kg
in accordance with IEC 60670-22
Drawings
Page 1 of 3
Gustav Hensel GmbH & Co. KG * Gustav-Hensel-Str. 6 * 57368 Lennestadt * Germany * Telefon: +49 (0)2723/609-0 * Fax: +49 (0)2723/60052 * Date: August 27. 2025
Dimension drawing
Detail mass
Page 2 of 3
Gustav Hensel GmbH & Co. KG * Gustav-Hensel-Str. 6 * 57368 Lennestadt * Germany * Telefon: +49 (0)2723/609-0 * Fax: +49 (0)2723/60052 * Date: August 27. 2025
Box walls
Operating and ambient conditions
Application area Suitable for indoor installation and outdoor installation,
protected against weather influences
Ambient temperature Maximum value + 40 °C
Minimum value - 25 °C
Fire protection in the event of internal faults Demands placed on electrical devices from standards and
laws
Minimum requirements
- Glow wire test in accordance with IEC 60695-2-11:
- 650°C for boxes and cable glands
- 850°C for parts of insulating material necessary to retain
current carrying parts in position
Burning behaviour Glow wire test IEC 60695-2-11: 750 °C
UL Subject 94: V-2
flame-retardant
self-extinguishing
Degree of protection against mechanical load IK07 (2 Joule)
Toxic behaviour halogen-free
silicone-free
"halogen-free" in accordance with the examination of the
cables and insulated wires - corrosiveness of fumes - as
per IEC 60754-2
Note: For material properties see technical data.