Ups Room

The document provides detailed input data for the UPS Room at the Alfanar - Shoaiba SWRO Plant, including specifications for ventilation, cooling, and heating systems. It outlines the room's dimensions, equipment types, and energy analysis parameters, emphasizing the design airflow rates and thermal loads. Additionally, it includes calculations for both cooling and heating requirements, ensuring the HVAC system is adequately sized for operational efficiency.

Uploaded by

pencoxxx
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
31 views11 pages

Ups Room

The document provides detailed input data for the UPS Room at the Alfanar - Shoaiba SWRO Plant, including specifications for ventilation, cooling, and heating systems. It outlines the room's dimensions, equipment types, and energy analysis parameters, emphasizing the design airflow rates and thermal loads. Additionally, it includes calculations for both cooling and heating requirements, ensuring the HVAC system is adequately sized for operational efficiency.

Uploaded by

pencoxxx
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

Space Input Data

ALFANAR - SHOAIBA SWRO PLANT - 00 04/23/2025


IDOM 12:30

04. UPS ROOM

1. General Details:
Floor Area ............................................................... 72.7 m²
Avg. Ceiling Height ................................................... 3.5 m
Building Weight ..................................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ........................................... User-Defined
OA Requirement 1 ................................................... 100 % of supply air
OA Requirement 2 .................................................. 0.00 L/(s·m²)
Space Usage Defaults ........... ASHRAE Std 62.1-2013

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .............................. Recessed (Unvented) Occupancy ................................................................ 1.0 Person
Wattage ................................................................. 12.00 W/m² Activity Level ...................................... Sedentary Work
Ballast Multiplier ...................................................... 1.00 Sensible .................................................................. 82.1 W/person
Schedule ................................................................. .000 Latent ...................................................................... 79.1 W/person
Schedule ................................................................. .000

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ................................................................... 0.00 W/m² Sensible ....................................................................... 0 W
Schedule ............................................................... None Schedule ............................................................... None
Latent ........................................................................... 0 W
Schedule ............................................................... None
2.3. Electrical Equipment:
Wattage ............................................................... 343.88 W/m²
Schedule ................................................................. .000

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 72.7 0 0

4.1. Construction Types for Exposure H


Roof Type ................. Built-up Roof + 200mm LW Concrete

5. Infiltration:
Design Cooling ........................................................ 0.00 L/s
Design Heating ....................................................... 0.00 L/s
Energy Analysis ...................................................... 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ............................................ Slab Floor On Grade
Floor Area ............................................................... 72.7 m²
Total Floor U-Value ............................................... 2.227 W/(m²·K)
Exposed Perimeter ................................................... 0.0 m
Edge Insulation R-Value ......................................... 0.00 (m²·K)/W

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Ceiling Partition (No partition data).
Area ........................................................................... 9.2 m²
U-Value ................................................................. 3.631 W/(m²·K)
Uncondit. Space Max Temp ................................... 35.0 °C
Ambient at Space Max Temp ................................. 55.0 °C
Uncondit. Space Min Temp .................................... 20.0 °C
Ambient at Space Min Temp .................................... 5.0 °C

Hourly Analysis Program v5.11 Page 1 of 1


04. UPS ROOM Input Data
Project Name: ALFANAR - SHOAIBA SWRO PLANT - 00 04/23/2025
Prepared by: IDOM 12:33

1. General Details:
Air System Name ....................................................................... 04. UPS ROOM
Equipment Type ......................................................... Packaged Rooftop Units
Air System Type ...................................................................... Single Zone CAV
Number of zones ................................................................................................ 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ..................................................... Constant Ventilation Airflow
Ventilation Sizing Method ...................................... Sum of Space OA Airflows
Unocc. Damper Position .......................................................................... Closed
Damper Leak Rate ............................................................................................. 0 %
Outdoor Air CO2 Level .................................................................................. 400 ppm

Central Cooling Data:


Supply Air Temperature ................................................................................ 12.8 °C
Coil Bypass Factor ...................................................................................... 0.100
Cooling Source ........................................................................... Air-Cooled DX
Schedule ................................................................................ JFMAMJJASOND
Capacity Control .................................... Cycled or Staged Capacity - Fan On

Central Heating Data:


Supply Temperature ..................................................................................... 35.0 °C
Heating Source ............................................................. Air Source Heat Pump
Schedule ................................................................................ JFMAMJJASOND
Capacity Control .................................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type .................................................................................. Forward Curved
Configuration ....................................................................................... Draw-thru
Fan Performance .......................................................................................... 7.50 kW
Fan Control ................................................. 1-speed fan, cooling and heating

Duct System Data:


Supply Duct Data:
Duct Heat Gain .................................................................................................. 0 %
Duct Leakage ..................................................................................................... 0 %

Return Duct or Plenum Data:


Return Air Via .............................................................................. Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
04. UPS ROOM x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)

1 24.0 26.0 21.1 15.0 0.83 100 0.0 0.0

Thermostat Schedule .............................................. Fan/Thermostat Schedule


Unoccupied Cooling is ......................................................................... Available

Supply Terminals Data:

Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Diffuser (no Ceiling supply /
1 Not Used - 0.00 L/s/person - - -
reheat) ceiling return

Zone Heating Units:

Zone Unit Heat Source ....................................................... Electric Resistance


Zone Heating Unit Schedule ................................................. JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:

Hourly Analysis Program 5.11 Page 1 of 2


04. UPS ROOM Input Data
Project Name: ALFANAR - SHOAIBA SWRO PLANT - 00 04/23/2025
Prepared by: IDOM 12:33

Hydronic Sizing Specifications:


Chilled Water Delta-T ..................................................................................... 5.6 K
Hot Water Delta-T ......................................................................................... 11.1 K

Safety Factors:
Cooling Sensible .............................................................................................. 10 %
Cooling Latent .................................................................................................. 10 %
Heating ............................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................... Sum of space airflow rates
Space Airflow Sizing Method ............................... Individual peak space loads

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Design OAT ................................................................................................... 35.0 °C
Equipment Sizing .............................................................................. Auto-Sized
Capacity Oversizing Factor ............................................................................... 0 %
ARI Performance Rating ............................................................................. 3.224 EER
DX System Configuration ............................... 1-stage compression, 1 circuit
Conventional Cutoff OAT .............................................................................. 12.8 °C
Low Temperature Operation ...................................................................... Used
Low Temperature Cutoff OAT ..................................................................... -17.8 °C

Central Heating Unit - ASHP


Design OAT ..................................................................................................... 8.3 °C
Equipment Sizing .............................................................................. Auto-Sized
Capacity Oversizing Factor ............................................................................... 0 %
ARI Performance Rating ............................................................................. 3.300 COP
Cutoff OAT ................................................................................................... -26.1 °C
Auxiliary Heating:
Auxiliary Heating Type ................................................ Electric Resistance
Auxiliary Heating Upper Cutoff ................................................................ 4.4 °C

Hourly Analysis Program 5.11 Page 2 of 2


Air System Sizing Summary for 04. UPS ROOM
Project Name: ALFANAR - SHOAIBA SWRO PLANT - 00 04/23/2025
Prepared by: IDOM 12:47

Air System Information


Air System Name ................................. 04. UPS ROOM Number of zones ............................................................. 1
Equipment Class ........................................ PKG ROOF Floor Area ................................................................... 72.7 m²
Air System Type ................................................. SZCAV Location ......................................... Jeddah, Saudi Arabia

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 307.6 kW Load occurs at ..................................................... Jul 1700
Sensible coil load .................................................. 116.7 kW OA DB / WB ...................................................... 54.6 / 38.4 °C
Coil L/s at Jul 1700 ................................................ 2194 L/s Entering DB / WB .............................................. 54.6 / 38.4 °C
Max block L/s ......................................................... 2194 L/s Leaving DB / WB .............................................. 10.6 / 10.6 °C
Sum of peak zone L/s ............................................ 2194 L/s Coil ADP ........................................................................ 5.7 °C
Sensible heat ratio ................................................ 0.379 Bypass Factor ........................................................... 0.100
L/(s kW) ..................................................................... 7.1 Resulting RH .................................................................. 41 %
m²/kW ........................................................................ 0.2 Design supply temp. ................................................... 12.8 °C
W/m² .................................................................... 4230.9 Zone T-stat Check .................................................... 1 of 1 OK
Water flow @ 5.6 K rise ........................................... N/A Max zone temperature deviation .................................. 0.0 K

Central Heating Coil Sizing Data

Max coil load ........................................................... 36.1 kW Load occurs at ..................................................... Des Htg
Coil L/s at Des Htg ................................................. 2194 L/s W/m² .......................................................................... 496.5
Max coil L/s ............................................................ 2194 L/s Ent. DB / Lvg DB ................................................. 5.0 / 18.6 °C
Water flow @ 11.1 K drop ....................................... N/A

Supply Fan Sizing Data

Actual max L/s ....................................................... 2194 L/s Fan motor BHP ........................................................... 9.45 BHP
Standard L/s ........................................................... 2193 L/s Fan motor kW ............................................................. 7.50 kW
Actual max L/(s·m²) .............................................. 30.18 L/(s·m²)

Outdoor Ventilation Air Data


Design airflow L/s ................................................... 2194 L/s L/s/person ............................................................. 2193.96 L/s/person
L/(s·m²) .................................................................. 30.18 L/(s·m²)

Hourly Analysis Program 5.11 Page 1 of 8


Ventilation Sizing Summary for 04. UPS ROOM
Project Name: ALFANAR - SHOAIBA SWRO PLANT - 00 04/23/2025
Prepared by: IDOM 12:47

1. Summary
Ventilation Sizing Method ...................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................... 2194 L/s

2. Space Ventilation Analysis


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s·m²)) (L/s) (% of supply) (L/s)
Zone 1
04. UPS ROOM 1 72.7 1.0 2194.0 0.00 0.00 0.0 100.0 2194.0
Totals (incl. Space Multipliers) 2194.0 2194.0

Hourly Analysis Program 5.11 Page 2 of 8


Air System Design Load Summary for 04. UPS ROOM
Project Name: ALFANAR - SHOAIBA SWRO PLANT - 00 04/23/2025
Prepared by: IDOM 12:47

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 54.6 °C / 38.4 °C HEATING OA DB / WB 5.0 °C / 1.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 73 m² 561 - 73 m² 303 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 73 m² 0 - 73 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 9 m² 344 - 9 m² 37 -
Overhead Lighting 872 W 872 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 25000 W 24999 - 0 0 -
People 1 82 79 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2686 8 0% 0 0
>> Total Zone Loads - 29544 87 - 340 0
Zone Conditioning - 29648 87 - 366 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2194 L/s 0 - 2194 L/s 0 -
Ventilation Load 2194 L/s 79504 190850 2194 L/s 43226 0
Supply Fan Load 2194 L/s 7500 - 2194 L/s -7500 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 116651 190937 - 36092 0
Central Cooling Coil - 116651 190937 - 0 0
Central Heating Coil - 0 - - 36092 -
>> Total Conditioning - 116651 190937 - 36092 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page 3 of 8


Space Design Load Summary for 04. UPS ROOM
Project Name: ALFANAR - SHOAIBA SWRO PLANT - 00 04/23/2025
Prepared by: IDOM 12:47

TABLE 1.1.A. Component Loads For Space "04. UPS ROOM" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.7 °C / 37.1 °C HEATING OA DB / WB 5.0 °C / 1.3 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 73 m² 715 - 73 m² 303 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 73 m² 0 - 73 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 9 m² 286 - 9 m² 37 -
Overhead Lighting 872 W 872 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 25000 W 24999 - 0 0 -
People 1 82 79 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2695 8 0% 0 0
>> Total Zone Loads - 29649 87 - 340 0

TABLE 1.1.B. Envelope Loads For Space "04. UPS ROOM" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²·K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 73 0.259 - 715 - 303

Hourly Analysis Program 5.11 Page 4 of 8


System Psychrometrics for 04. UPS ROOM
Project Name: ALFANAR - SHOAIBA SWRO PLANT - 00 04/23/2025
Prepared by: IDOM 12:47

July DESIGN COOLING DAY, 1700

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 54.6 0.03747 2194 400 79504 190850
Vent - Return Mixing Outlet 54.6 0.03747 2194 400 - -
Central Cooling Coil Outlet 10.6 0.00793 2194 400 116651 190937
Central Heating Coil Outlet 10.6 0.00793 2194 400 0 -
Supply Fan Outlet 13.4 0.00793 2194 400 7500 -
Cold Supply Duct Outlet 13.4 0.00793 2194 400 - -
Zone Air - 24.6 0.00794 2194 403 29648 87
Return Plenum Outlet 24.6 0.00794 2194 403 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.207 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2946.2 W/(L/s)
Site Altitude = 4.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 29544 Cooling 29648 24.6 2194 403 0 0

Hourly Analysis Program 5.11 Page 5 of 8


System Psychrometrics for 04. UPS ROOM
Project Name: ALFANAR - SHOAIBA SWRO PLANT - 00 04/23/2025
Prepared by: IDOM 12:47

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 5.0 0.00265 2194 400 -43226 0
Vent - Return Mixing Outlet 5.0 0.00265 2194 400 - -
Central Cooling Coil Outlet 5.0 0.00265 2194 400 0 0
Central Heating Coil Outlet 18.6 0.00265 2194 400 36092 -
Supply Fan Outlet 21.5 0.00265 2194 400 7500 -
Cold Supply Duct Outlet 21.5 0.00265 2194 400 - -
Zone Air - 21.3 0.00265 2194 400 -366 0
Return Plenum Outlet 21.3 0.00265 2194 400 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.207 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2946.2 W/(L/s)
Site Altitude = 4.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 -340 Deadband -366 21.3 2194 400 0 0

Hourly Analysis Program 5.11 Page 6 of 8


System Psychrometrics for 04. UPS ROOM
Project Name: ALFANAR - SHOAIBA SWRO PLANT - 00 04/23/2025
Prepared by: IDOM 12:47

Location: Jeddah, Saudi Arabia


Altitude: 4.0 m.
Data for: July DESIGN COOLING DAY, 1700
1.
2. Outdoor Air
CentralFan
Cooling Coil Outlet 0.040
3.
4. Supply
Room Air Outlet 1

0.035

Specific Humidity ( kg/kg )


0.030

0.025

0.020

0.015

2 3 4 0.010

0.005

0.000
0 5 10 15 20 25 30 35 40 45 50 55
Temperature ( °C )

Hourly Analysis Program 5.11 Page 7 of 8


System Psychrometrics for 04. UPS ROOM
Project Name: ALFANAR - SHOAIBA SWRO PLANT - 00 04/23/2025
Prepared by: IDOM 12:47

Location: Jeddah, Saudi Arabia


Altitude: 4.0 m.
Data for: WINTER DESIGN HEATING
0.020
1. Outdoor Air
2. Central Heating Coil Outlet
3. Supply Fan Outlet
4. Room Air 0.018

0.016

Specific Humidity ( kg/kg )


0.014

0.012

0.010

0.008

0.006

0.004
1 2 3
4
0.002

0.000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program 5.11 Page 8 of 8