Ups Room
Ups Room
1. General Details:
Floor Area ............................................................... 72.7 m²
Avg. Ceiling Height ................................................... 3.5 m
Building Weight ..................................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ........................................... User-Defined
OA Requirement 1 ................................................... 100 % of supply air
OA Requirement 2 .................................................. 0.00 L/(s·m²)
Space Usage Defaults ........... ASHRAE Std 62.1-2013
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .............................. Recessed (Unvented) Occupancy ................................................................ 1.0 Person
Wattage ................................................................. 12.00 W/m² Activity Level ...................................... Sedentary Work
Ballast Multiplier ...................................................... 1.00 Sensible .................................................................. 82.1 W/person
Schedule ................................................................. .000 Latent ...................................................................... 79.1 W/person
Schedule ................................................................. .000
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 72.7 0 0
5. Infiltration:
Design Cooling ........................................................ 0.00 L/s
Design Heating ....................................................... 0.00 L/s
Energy Analysis ...................................................... 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ............................................ Slab Floor On Grade
Floor Area ............................................................... 72.7 m²
Total Floor U-Value ............................................... 2.227 W/(m²·K)
Exposed Perimeter ................................................... 0.0 m
Edge Insulation R-Value ......................................... 0.00 (m²·K)/W
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ..................................... Ceiling Partition (No partition data).
Area ........................................................................... 9.2 m²
U-Value ................................................................. 3.631 W/(m²·K)
Uncondit. Space Max Temp ................................... 35.0 °C
Ambient at Space Max Temp ................................. 55.0 °C
Uncondit. Space Min Temp .................................... 20.0 °C
Ambient at Space Min Temp .................................... 5.0 °C
1. General Details:
Air System Name ....................................................................... 04. UPS ROOM
Equipment Type ......................................................... Packaged Rooftop Units
Air System Type ...................................................................... Single Zone CAV
Number of zones ................................................................................................ 1
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
04. UPS ROOM x1
T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Diffuser (no Ceiling supply /
1 Not Used - 0.00 L/s/person - - -
reheat) ceiling return
Safety Factors:
Cooling Sensible .............................................................................................. 10 %
Cooling Latent .................................................................................................. 10 %
Heating ............................................................................................................... 0 %
5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Design OAT ................................................................................................... 35.0 °C
Equipment Sizing .............................................................................. Auto-Sized
Capacity Oversizing Factor ............................................................................... 0 %
ARI Performance Rating ............................................................................. 3.224 EER
DX System Configuration ............................... 1-stage compression, 1 circuit
Conventional Cutoff OAT .............................................................................. 12.8 °C
Low Temperature Operation ...................................................................... Used
Low Temperature Cutoff OAT ..................................................................... -17.8 °C
Calculation Months ..................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 307.6 kW Load occurs at ..................................................... Jul 1700
Sensible coil load .................................................. 116.7 kW OA DB / WB ...................................................... 54.6 / 38.4 °C
Coil L/s at Jul 1700 ................................................ 2194 L/s Entering DB / WB .............................................. 54.6 / 38.4 °C
Max block L/s ......................................................... 2194 L/s Leaving DB / WB .............................................. 10.6 / 10.6 °C
Sum of peak zone L/s ............................................ 2194 L/s Coil ADP ........................................................................ 5.7 °C
Sensible heat ratio ................................................ 0.379 Bypass Factor ........................................................... 0.100
L/(s kW) ..................................................................... 7.1 Resulting RH .................................................................. 41 %
m²/kW ........................................................................ 0.2 Design supply temp. ................................................... 12.8 °C
W/m² .................................................................... 4230.9 Zone T-stat Check .................................................... 1 of 1 OK
Water flow @ 5.6 K rise ........................................... N/A Max zone temperature deviation .................................. 0.0 K
Max coil load ........................................................... 36.1 kW Load occurs at ..................................................... Des Htg
Coil L/s at Des Htg ................................................. 2194 L/s W/m² .......................................................................... 496.5
Max coil L/s ............................................................ 2194 L/s Ent. DB / Lvg DB ................................................. 5.0 / 18.6 °C
Water flow @ 11.1 K drop ....................................... N/A
Actual max L/s ....................................................... 2194 L/s Fan motor BHP ........................................................... 9.45 BHP
Standard L/s ........................................................... 2193 L/s Fan motor kW ............................................................. 7.50 kW
Actual max L/(s·m²) .............................................. 30.18 L/(s·m²)
1. Summary
Ventilation Sizing Method ...................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................... 2194 L/s
TABLE 1.1.A. Component Loads For Space "04. UPS ROOM" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 0000 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.7 °C / 37.1 °C HEATING OA DB / WB 5.0 °C / 1.3 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 73 m² 715 - 73 m² 303 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 73 m² 0 - 73 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 9 m² 286 - 9 m² 37 -
Overhead Lighting 872 W 872 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 25000 W 24999 - 0 0 -
People 1 82 79 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2695 8 0% 0 0
>> Total Zone Loads - 29649 87 - 340 0
TABLE 1.1.B. Envelope Loads For Space "04. UPS ROOM" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²·K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 73 0.259 - 715 - 303
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.207 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2946.2 W/(L/s)
Site Altitude = 4.0 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.207 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2946.2 W/(L/s)
Site Altitude = 4.0 m
0.035
0.025
0.020
0.015
2 3 4 0.010
0.005
0.000
0 5 10 15 20 25 30 35 40 45 50 55
Temperature ( °C )
0.016
0.012
0.010
0.008
0.006
0.004
1 2 3
4
0.002
0.000
0 5 10 15 20 25 30 35
Temperature ( °C )