INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-3506-005
                                                                                                                                                  12 Clintonville Road
FMM-1 Monitor Module                                                                                                                         Northford, CT 06472-1653
                                                                                                                                                  Phone: 203.484.7161
SPECIFICATIONS
Normal Operating Voltage:                  15 to 32 VDC
Maximum Current Draw:                      5.0 mA (LED on)
Average Operating Current:                 375 µA (group poll); 350 µA (direct poll); 600 µA Max. (Communicating, IDC Shorted)
EOL Resistance:                            47K Ohms
Maximum IDC Wiring Resistance:             1,500 Ohms
Maximum IDC Voltage:                       11 Volts
Maximum IDC Current:                       450µA
Temperature Range:                         32°F to 120°F (0°C to 49°C)
Humidity:                                  10% to 93% Non-condensing
Dimensions:                                41⁄2˝ H x 4˝ W x 11⁄4˝ D (Mounts to a 4˝ square by 21⁄8˝ deep box.)
Accessories:                               SMB500 Series Electrical Box
Listed to: UL 864 and UL 2610                                                             MOUNTING
                                                                                          The FMM-1 mounts directly to 4-inch square electrical boxes. (See Figure
BEFORE INSTALLING
                                                                                          2). The box must have a minimum depth of 21/8 inches (54 mm). Surface
This information is included as a quick reference installation guide. Refer to
                                                                                          mounted electrical boxes (SMB500-WH) are available from NOTIFIER.
the appropriate Notifier control panel installation manual for detailed system
information. If the modules will be installed in an existing operational system,          FIGURE 2. MODULE MOUNTING
inform the operator and local authority that the system will be temporarily               NOTE: For UL Listed security installations, the FMM-1 must be mounted
out of service. Disconnect power to the control panel before installing the               within the control panel enclosure.
modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The FMM-1 Monitor Module is intended for use in intelligent, two-wire sys-
tems, where the individual address of each module is selected using the built-
in rotary switches. It provides either a 2-wire or 4-wire fault tolerant initiating
device circuit (IDC) for normally open contact fire alarm and supervisory de-
vices, or either normally open or normally closed security devices. The mod-
ule has a panel controlled LED indicator. The FMM-1 can be used to replace
an MMX-1 module in existing systems. FMM-1 is also UL Listed as a com-
mercial proprietary burglar alarm accessory and a commercial central station
burglar alarm accessory.                                                                                                                              ISOLATED
                                                                                                                                                      QUADRANT
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
NOTIFIER system control panel (list available from NOTIFIER).
FIGURE 1. CONTROLS AND INDICATORS
                                                                                                                                                               C1066-00
                                                                                          WIRING
                                                                                          NOTE: All wiring must conform to applicable local codes, ordinances, and
                                                                                          regulations.
                                                                                          1.   	Install module wiring in accordance with the job drawings and appropri-
                                                                                               ate wiring diagrams.
                                                                                          2.   Set the address on the module per job drawings.
                                                                                          3.   Secure module to electrical box (supplied by installer). See Figure 2.
                                                                                          NOTE: All references to power limited represent “Power Limited (Class 2)”.
                                                                                          NOTE: Dispose electronic waste following national and/or local regulations.
                                                                          C1067-00
                                                                                     1                                                                   I56-3506-005
                                                                                                                                                            5/23/2022
FIGURE 3. TYPICAL 2-WIRE INITIATING CIRCUIT CONFIGURATION, NFPA CLASS D OR SECURITY SYSTEMS
NOTE: For UL Listed security installations, the FMM-1 must be mounted within the control panel enclosure.
                                                                               )–(                                                                              )–(
                                                       TO NEXT                                                                                                          FROM PANEL OR
                                                       DEVICE                  )+(                                                                              )+(    PREVIOUS DEVICE
                                                                                            MONITOR
          ANY NUMBER OF UL LISTED CONTACT                                                   MODULE
      CLOSURE DEVICES MAY BE USED. DO NOT MIX                                                                                     CONNECT MODULES TO LISTED COMPATIBLE
        FIRE ALARM INTIATING, SUPERVISORY, OR                                                                                             CONTROL PANELS ONLY
       SECURITY DEVICES ON THE SAME MODULE.
                                                                                                                   )–(
                                                                                                                   )+(
  47K EOL                                                                                                                          SIGNAL LINE CIRCUIT (SLC)
 RESISTOR                                                                                                                                 32 VDC MAX.
  ELR-47K                                                                                                                                TWISTED PAIR
                                                                                                                                       IS RECOMENDED
       INITIATING DEVICE CIRCUIT (IDC) - NFPA CLASS B
          POWER LIMITED: 450µA MAX. @ 11 VDC MAX
                                                                                                  ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
         INSTALL CONTACT CLOSURE DEVICES PER
       MANUFACTURER’S INSTALLATION INSTRUCTIONS.
                                                                                                                                                                                 C0918-05
FIGURE 4. TYPICAL 4-WIRE FAULT TOLERANT INITIATING CIRCUIT CONFIGURATION, NFPA CLASS A
                                                                                      )–(                                                                        )-(
                                                            TO NEXT                                                                                                     FROM PANEL OR
                                                            DEVICE                    )+(                                                                        )+(   PREVIOUS DEVICE
                                                                                             MONITOR
                                                                                             MODULE
                  ANY NUMBER OF UL LISTED CONTACT
              CLOSURE DEVICES MAY BE USED. DO NOT MIX                                                                                 CONNECT MODULES TO LISTED COMPATIBLE
                FIRE ALARM INTIATING, SUPERVISORY, OR                                                                                     NOTIFIER CONTROL PANELS ONLY
               SECURITY DEVICES ON THE SAME MODULE.
                                                                                                                         )–(
                                                                                                                         )+(
                                                                                                                                    SIGNAL LINE CIRCUIT (SLC)
                                                                                                                                           32 VDC MAX.
    EOL RESISTOR IS                                                                                                                  SHIELDED-TWISTED PAIR
      INTERNAL AT                                                                                                                       IS RECOMENDED
    TERMINALS 8 & 9
                                                                                            ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
                   INSTALL CONTACT CLOSURE DEVICES PER
                 MANUFACTURER’S INSTALLATION INSTRUCTIONS.
                                                                                                                                                                                 C0919-00
UL 2610 REQUIREMENTS
This product is intended to be installed in accordance with the following:
     • NFPA 70 - National Electric Code
     • UL 681 - Standard for Installation and Classifcation of Burglar and
       Holdup Alarm Systems
     • UL827 - Standard for Central Station Alarm Services
See panel installation document for specifications on wire sizes to use with
this module.
See relevant control panel for additional information on programming, testing
and maintenance. Testing should be performed annually, as per NFPA72.
The installer should be familiar with and follow the best practices set forth
within ANSI/SIA CP-01 for troubleshooting and reduction in dispatch calls.