0% found this document useful (0 votes)
11 views2 pages

Modulo de Monitoreo

The document provides installation and maintenance instructions for the FMM-1 Monitor Module, detailing specifications, mounting requirements, and wiring guidelines. It emphasizes the need for compatibility with NOTIFIER control panels and adherence to local codes and UL standards. Additionally, it includes information on testing and maintenance protocols to ensure proper operation of the module in fire alarm and security systems.

Uploaded by

alberto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
11 views2 pages

Modulo de Monitoreo

The document provides installation and maintenance instructions for the FMM-1 Monitor Module, detailing specifications, mounting requirements, and wiring guidelines. It emphasizes the need for compatibility with NOTIFIER control panels and adherence to local codes and UL standards. Additionally, it includes information on testing and maintenance protocols to ensure proper operation of the module in fire alarm and security systems.

Uploaded by

alberto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

INSTALLATION AND MAINTENANCE INSTRUCTIONS

I56-3506-005
12 Clintonville Road

FMM-1 Monitor Module Northford, CT 06472-1653


Phone: 203.484.7161

SPECIFICATIONS
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 5.0 mA (LED on)
Average Operating Current: 375 µA (group poll); 350 µA (direct poll); 600 µA Max. (Communicating, IDC Shorted)
EOL Resistance: 47K Ohms
Maximum IDC Wiring Resistance: 1,500 Ohms
Maximum IDC Voltage: 11 Volts
Maximum IDC Current: 450µA
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10% to 93% Non-condensing
Dimensions: 41⁄2˝ H x 4˝ W x 11⁄4˝ D (Mounts to a 4˝ square by 21⁄8˝ deep box.)
Accessories: SMB500 Series Electrical Box

Listed to: UL 864 and UL 2610 MOUNTING


The FMM-1 mounts directly to 4-inch square electrical boxes. (See Figure
BEFORE INSTALLING
2). The box must have a minimum depth of 21/8 inches (54 mm). Surface
This information is included as a quick reference installation guide. Refer to
mounted electrical boxes (SMB500-WH) are available from NOTIFIER.
the appropriate Notifier control panel installation manual for detailed system
information. If the modules will be installed in an existing operational system, FIGURE 2. MODULE MOUNTING
inform the operator and local authority that the system will be temporarily NOTE: For UL Listed security installations, the FMM-1 must be mounted
out of service. Disconnect power to the control panel before installing the within the control panel enclosure.
modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The FMM-1 Monitor Module is intended for use in intelligent, two-wire sys-
tems, where the individual address of each module is selected using the built-
in rotary switches. It provides either a 2-wire or 4-wire fault tolerant initiating
device circuit (IDC) for normally open contact fire alarm and supervisory de-
vices, or either normally open or normally closed security devices. The mod-
ule has a panel controlled LED indicator. The FMM-1 can be used to replace
an MMX-1 module in existing systems. FMM-1 is also UL Listed as a com-
mercial proprietary burglar alarm accessory and a commercial central station
burglar alarm accessory. ISOLATED
QUADRANT
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
NOTIFIER system control panel (list available from NOTIFIER).
FIGURE 1. CONTROLS AND INDICATORS

C1066-00

WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations.
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer). See Figure 2.

NOTE: All references to power limited represent “Power Limited (Class 2)”.
NOTE: Dispose electronic waste following national and/or local regulations.

C1067-00

 1 I56-3506-005
5/23/2022
FIGURE 3. TYPICAL 2-WIRE INITIATING CIRCUIT CONFIGURATION, NFPA CLASS D OR SECURITY SYSTEMS
NOTE: For UL Listed security installations, the FMM-1 must be mounted within the control panel enclosure.
)–( )–(
TO NEXT FROM PANEL OR
DEVICE )+( )+( PREVIOUS DEVICE

MONITOR
ANY NUMBER OF UL LISTED CONTACT MODULE
CLOSURE DEVICES MAY BE USED. DO NOT MIX CONNECT MODULES TO LISTED COMPATIBLE
FIRE ALARM INTIATING, SUPERVISORY, OR CONTROL PANELS ONLY
SECURITY DEVICES ON THE SAME MODULE.
)–(
)+(

47K EOL SIGNAL LINE CIRCUIT (SLC)


RESISTOR 32 VDC MAX.
ELR-47K TWISTED PAIR
IS RECOMENDED

INITIATING DEVICE CIRCUIT (IDC) - NFPA CLASS B


POWER LIMITED: 450µA MAX. @ 11 VDC MAX

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED


INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER’S INSTALLATION INSTRUCTIONS.
C0918-05

FIGURE 4. TYPICAL 4-WIRE FAULT TOLERANT INITIATING CIRCUIT CONFIGURATION, NFPA CLASS A
)–( )-(
TO NEXT FROM PANEL OR
DEVICE )+( )+( PREVIOUS DEVICE

MONITOR
MODULE
ANY NUMBER OF UL LISTED CONTACT
CLOSURE DEVICES MAY BE USED. DO NOT MIX CONNECT MODULES TO LISTED COMPATIBLE
FIRE ALARM INTIATING, SUPERVISORY, OR NOTIFIER CONTROL PANELS ONLY
SECURITY DEVICES ON THE SAME MODULE.

)–(
)+(

SIGNAL LINE CIRCUIT (SLC)


32 VDC MAX.
EOL RESISTOR IS SHIELDED-TWISTED PAIR
INTERNAL AT IS RECOMENDED
TERMINALS 8 & 9

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED


INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER’S INSTALLATION INSTRUCTIONS.

C0919-00

UL 2610 REQUIREMENTS
This product is intended to be installed in accordance with the following:
• NFPA 70 - National Electric Code
• UL 681 - Standard for Installation and Classifcation of Burglar and
Holdup Alarm Systems
• UL827 - Standard for Central Station Alarm Services
See panel installation document for specifications on wire sizes to use with
this module.
See relevant control panel for additional information on programming, testing
and maintenance. Testing should be performed annually, as per NFPA72.
The installer should be familiar with and follow the best practices set forth
within ANSI/SIA CP-01 for troubleshooting and reduction in dispatch calls.

NOTIFIER® and Honeywell® are registered trademarks of Honeywell International, Inc.


 2 I56-3506-005
©2022 NOTIFIER. 5/23/2022