S4L1D-D41 Wdg.
311 - Technical Data Sheet
Standards
Stamford industrial alternators meet the requirements of the relevant parts of the BS EN 60034 and the relevant
section of other international standards such as BS5000, VDE 0530, NEMA MG1-32, IEC34, CSA C22.2-100
and As1359. Other standards and certifications can be considered on request.
Quality Assurance
Alternators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001.
            Excitation and Voltage Regulators
           Excitation System
           AVR Type             AS440        MX341     MX321
                                        S4L1D-D41 Wdg.311
Electrical Data
Insulation System                                                    Class H
Stator Winding                                                 Double Layer Lap
Winding Pitch                                                       Two Thirds
Winding Leads                                                          12
Winding Number                                                         311
Number of Poles                                                         4
IP Rating                                                             IP23
RFI Suppression
                                           BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N.
                                                            Refer to factory for others
Waveform Distortion                     NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
Short Circuit Ratio                                                   1/Xd
Steady State X/R Ratio                                                12.29
                                              50 Hz                                       60 Hz
Telephone Interference                        THF<2%                                      TIF<50
Cooling Air                                 0.83 m³/sec                              0.99 m³/sec
Voltage Star                     380        400       415     440           416    440             460   480
kVA Base Rating (Class H) for
Reactance Values                 300        310       310     290           344    370             375   390
Saturated Values in Per Unit at Base Ratings and Voltages
Xd Dir. Axis Synchronous         3.15      2.94      2.73    2.27           3.60   3.46        3.21      3.07
X'd Dir. Axis Transient          0.20      0.19      0.17    0.14           0.22   0.21        0.20      0.19
X''d Dir. Axis Subtransient      0.14      0.13      0.12    0.10           0.15   0.14        0.13      0.12
Xq Quad. Axis Reactance          2.66      2.48      2.30    1.92           3.09   2.97        2.75      2.63
X''q Quad. Axis Subtransient     0.40      0.37      0.34    0.29           0.40   0.39        0.36      0.34
XL Stator Leakage Reactance      0.07      0.06      0.06    0.05           0.09   0.08        0.08      0.07
X2 Negative Sequence Reactance   0.27      0.25      0.23    0.19           0.28   0.27        0.25      0.24
X0 Zero Sequence Reactance       0.10      0.09      0.09    0.07           0.10   0.09        0.09      0.08
Unsaturated Values in Per Unit at Base Ratings and Voltages
Xd Dir. Axis Synchronous         3.78      3.53      3.28    2.73           4.32   4.16        3.85      3.68
                                                      S4L1D-D41 Wdg.311
 Time Constants (Seconds)
                                                                                          0.08
                                                                                          0.019
                                                                                           1.7
 Ta ARMATURE TIME CONST.                                                                  0.018
                                                                                         0.0077
                                        0
                                            C
 Stator Winding Resistance (Ra), per
phase for series connected                                                               0.0124
 Rotor Winding Resistance (Rf)                                                            1.05
 Exciter Stator Winding Resistance                                                         18
 Exciter Rotor Winding Resistance per
 phase                                                                                    0.068
 PMG Phase Resistance (Rpmg) per
                                                                                           1.9
 phase
 Positive Sequence Resistance (R1)                                                       0.0155
 Negative Sequence Resistance (R2)                                                      0.017856
 Zero Sequence Resistance (R0)                                                           0.0155
 Saturation Factors                                              400V                                           480V
 SG1.0                                                            0.31                                           0.31
 SG1.2                                                            1.25                                           1.25
 Mechanical Data
 Shaft and Keys                                 All alternator rotors are dynamically balanced to better than BS6861: Part 1 Grade 2.5 for
                                                  minimum vibration in operation. Two bearing generators are balanced with a half key.
                                                                1 Bearing                                     2 Bearings
 SAE Adaptor                                                   SAE 0.5, 1                                        N/A
 Moment of Inertia                                            4.0771 kgm2                                        N/A
 Weight Wound Stator                                             415 kg                                          N/A
 Weight Wound Rotor                                              361 kg                                          N/A
 Weight Complete Alternator                                      940 kg                                          N/A
 Shipping weight in a Crate                                     1010 kg                                          N/A
 Packing Crate Size                                        155 x 87 x 107(cm)                                    N/A
 Maximum Over Speed                                                             2250 RPM for two minutes
             S4L1D-D41 Wdg.311
       THREE PHASE EFFICIENCY CURVES
50Hz                                   60Hz
                                                                     S4L1D-D41 Wdg.311
                                                    Locked Rotor Motor Starting Curves - Separately Excited
                                                                                               380V           400V 415V   440V
                                    35
                                    30
                                    25
PER CENT TRANSIENT VOLTAGE DIP
                                    20
                                    15
                                    10
                                           0
                                                0   200        400        600         800              1000               1200   1400
                                                                            LOCKED ROTOR kVA
                                                                                                416V          440V    460V480V
                                           35
                                           30
                                           25
          PER CENT TRANSIENT VOLTAGE DIP
                                           20
                                           15
                                           10
                                            5
                                                                 S4L1D-D41 Wdg.311
                                                  Locked Rotor Motor Starting Curves - Self Excited
                                                                                         380V 400V      415V                440V
                                   35
                                   30
                                   25
PER CENT TRANSIENT VOLTAGE DIP
                                   20
                                   15
                                   10
                                    0
                                        0   100     200    300     400      500          600         700         800       900     1000
                                                                         LOCKED ROTOR kVA
                                                                                  416V               440V      460V 480V
                                   35
                                   30
                                   25
  PER CENT TRANSIENT VOLTAGE DIP
                                   20
                                   15
                                   10
                                    5
                                            S4L1D-D41 Wdg.311
                                  Three-phase Short Circuit Decrement Curve
                      10000
                                                                                   SYMM.   ASYMMETRICAL
     CURRENT (Amps)
                       1000
                        100
                          0.001   0.01                         0.1             1                          10
                                                 TIME (secs)
                                         Sustained Short Circuit = 1200 Amps
                      10000
                                                                                   SYMM.   ASYMMETRICAL
CURRENT (Amps)
                      1000
                       100
                         0.001    0.01                         0.1             1                          10
       S4L1D-D41 Wdg.311
Typical Alternator Operating Charts
                                                    S4L1D-D41 Wdg.311
                                          RATINGS AT 0.8 POWER FACTOR
       Class - Temp Rise       Standby - 163/27°C         Standby - 150/40°C           Cont. H - 125/40°C          Cont. F - 105/40°C
          Series Star (V)   380    400    415    440    380    400    415    440    380    400    415    440    380    400    415    440
 50                 kVA     330    340    340    320    320    330    330    310    300    310    310    290    280    285    285    270
  Hz
                     kW     264    272    272    256    256    264    264    248    240    248    248    232    224    228    228    216
           Efficiency (%)   92.1   92.3   92.6   93.2   92.3   92.5   92.7   93.3   92.7   92.9   93.1   93.6   93.1   93.3   93.4   93.8
               kW Input     287    295    294    275    277    285    285    266    259    267    266    248    241    244    244    230
          Series Star (V)   416    440    460    480    416    440    460    480    416    440    460    480    416    440    460    480
 60                 kVA     375    410    415    430    365    400    400    415    344    370    375    390    315    340    345    355
  Hz
                     kW     300    328    332    344    292    320    320    332    275    296    300    312    252    272    276    284
           Efficiency (%)   92.4   92.2   92.5   92.6   92.5   92.4   92.7   92.8   92.8   92.9   93.1   93.1   93.2   93.2   93.4   93.5
               kW Input     325    356    359    372    316    346    345    358    296    319    322    335    270    292    295    304
De-Rates
All values tabulated above are subject to the following reductions:
     - 5% when air inlet filters are fitted
     - 3% for every 500 meters by which the operating altitude exceeds 1000 meters above mean sea level
     - 3% for every 5°C by which the operational ambient temperature exceeds 40°C
     - For any other operating conditions impacting the cooling circuit please refer to applications
Note: Requirement for operating in an ambient exceeding 60°C and altitude exceeding 4000 meters must be
referred to applications.