Spd44 1 A

The SPD44 Surge Protection Device protects equipment from overvoltage transients and is suitable for single-phase applications. It features a fast response time, long working life, and includes indicators for supply presence. The device is designed for DIN rail mounting and must be installed by qualified personnel.

Uploaded by

Mohammad Altah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
16 views1 page

Spd44 1 A

The SPD44 Surge Protection Device protects equipment from overvoltage transients and is suitable for single-phase applications. It features a fast response time, long working life, and includes indicators for supply presence. The device is designed for DIN rail mounting and must be installed by qualified personnel.

Uploaded by

Mohammad Altah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Type: SPD44

Surge Protection Device


Terminal
Protection Protects equipment against over voltage transients
to IP20 Incorporates both Metal Oxide Varistors and Gas Discharge Tubes
Long working life
Fast response time
Neon indicator for supply presence
Grouped terminals for ease of connections
Suited to single-phase applications
DIN Rail mounting

Dims: to DIN
43880
W. 44mm

• FRONT INDICATION • TECHNICAL SPECIFICATION


Supply voltage Un: (L, N) 230/240V AC/DC
1. Supply present (Orange) neon Frequency range: 48 – 63Hz (AC supplies)
Overvoltage category: III (IEC 60664)
Rated impulse withstand voltage: 4kV (1.2/50µS) IEC 60664

Supply present indication: Orange Neon


Current rating: 16A (when used with a suitable Miniature Circuit
Breaker)
Leakage current: 100µA @ 250V AC
Response time: < 25ns
Capacitance: < 5nF @ 1kHz
Insulation resistance: > 1000 MΩ (applicable to internal Metal Oxide Varistors
➊ only)
Voltage temperature co-efficient: -0.05%/°C (applicable to internal Metal Oxide Varistors
only)
Max. clamping voltage: < 900V (Phase/neutral)
(with current waveform 1.2/50µs < 1300V (Phase/earth)
– Short circuit current 100A ±10A)
Transient withstand capacity: x5 @ 5kA (Phase/neutral)
x3 @ 5kA (Phase/earth)
(8/20µs waveform)
• INSTALLATION Installation work must be carried Ambient temp: -20 to +60°C
out by qualified personnel. Relative humidity: +95% max.
• BEFORE INSTALLATION, ISOLATE THE SUPPLY.
Housing: Grey flame retardant Lexan UL94 V0
• The diagram below shows a typical example whereby the unit is protecting a single phase installation.
Weight: 48g
• Depending on circuit ratings, the fuse size should be chosen accordingly. Mounting option: On to 35mm symmetric DIN rail to BS EN 60715
Terminal conductor size ≤ 2 x 2.5mm2 solid or stranded
Terminal layout/Connections. Approvals: Conforms to IEC.
• Despite only requiring 3 actual connections, additional terminals are provided allowing several wires to
be terminated if required. CE, and RoHS Compliant.
EMC:
Immunity: EN 61000-6-2
Applying power.
Emissions: EN 61000-6-4
• As soon as power is applied, the orange colour “SUPPLY” ➊ neon will illuminate.

Troubleshooting.
• If the orange neon fails to illuminate, check the voltage is present to terminals L and N and within the
working limits of the device
• Also check the external protection fuse has not blown.

• CONNECTION DIAGRAM

• DIMENSIONS
30mm
44mm 49.5mm
63.5mm
85mm

61mm

45mm

Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England SPD44-1-A.DOCX