Gek 113575C
Gek 113575C
Digital Energy
 Instruction Manual
 Software Revision: 1.0x
 Manual P/N: 1601- 9111-A4
 Manual Order Code: GEK-113575C
LISTED
*1601-911-A4*
     Copyright © 2015 GE Multilin Inc. All rights reserved.
     EPM 2200 Power Meter Instruction Manual for product revision 1.0x.
     The contents of this manual are the property of GE Multilin Inc. This documentation is
     furnished on license and may not be reproduced in whole or in part without the permission
     of GE Multilin. The manual is for informational use only and is subject to change without
     notice.
     Part number: 1601-9111-A4 (November 2015)
ii
       GENERAL SAFETY PRECAUTIONS - EPM 2200
Note
           • Failure to observe and follow the instructions provided in the equipment manual(s)
             could cause irreversible damage to the equipment and could lead to property
             damage, personal injury and/or death.
           • Before attempting to use the equipment, it is important that all danger and
             caution indicators are reviewed.
           • If the equipment is used in a manner not specified by the manufacturer or
             functions abnormally, proceed with caution. Otherwise, the protection provided by
             the equipment may be impaired and can result in Impaired operation and injury.
           • Caution: Hazardous voltages can cause shock, burns or death.
           • Installation/service personnel must be familiar with general device test practices,
             electrical awareness and safety precautions must be followed.
           • Before performing visual inspections, tests, or periodic maintenance on this device
             or associated circuits, isolate or disconnect all hazardous live circuits and sources
             of electric power.
           • Failure to shut equipment off prior to removing the power connections could
             expose you to dangerous voltages causing injury or death.
           • All recommended equipment that should be grounded and must have a reliable
             and un-compromised grounding path for safety purposes, protection against
             electromagnetic interference and proper device operation.
           • Equipment grounds should be bonded together and connected to the facility’s
             main ground system for primary power.
           • Keep all ground leads as short as possible.
           • At all times, equipment ground terminal must be grounded during device
             operation and service.
           • In addition to the safety precautions mentioned all electrical connections made
             must respect the applicable local jurisdiction electrical code.
           • Before working on CTs, they must be short-circuited.
           • To be certified for revenue metering, power providers and utility companies must
             verify that the billing energy meter performs to the stated accuracy. To confirm the
             meter’s performance and calibration, power providers use field test standards to
             ensure that the unit’s energy measurements are correct.
                                                                                                 iii
              Safety words and definitions
              The following symbols used in this document indicate the following conditions
              Indicates a hazardous situation which, if not avoided, will result in death or serious
Note
injury.
              Indicates a hazardous situation which, if not avoided, could result in death or serious
Note
injury.
moderate injury.
              Warranty
              For products shipped as of 1 October 2013, GE Digital Energy warrants most of its GE
              manufactured products for 10 years. For warranty details including any limitations and
              disclaimers, see the GE Digital Energy Terms and Conditions at
              https://www.gedigitalenergy.com/multilin/warranty.htm
              For products shipped before 1 October 2013, the standard 24-month warranty applies.
iv
                             Table of Contents
VC
Phase 3
                                                         N
                                       Phase 2                         Phase 1
                                       VB                                          VA
                                            Figure 1-1: Three-phase Wye Winding
                 The three voltages are separated by 120o electrically. Under balanced load conditions
                 the currents are also separated by 120o. However, unbalanced loads and other
                 conditions can cause the currents to depart from the ideal 120o separation. Three-
                 phase voltages and currents are usually represented with a phasor diagram. A phasor
                 diagram for the typical connected voltages and currents is shown in Figure 1.2.
                             Usually a wye-connected service will have four wires: three wires for the phases and
                             one for the neutral. The three-phase wires connect to the three phases (as shown in
                             Figure 1.1). The neutral wire is typically tied to the ground or center point of the wye.
                             In many industrial applications the facility will be fed with a four-wire wye service but
                             only three wires will be run to individual loads. The load is then often referred to as a
                             delta-connected load but the service to the facility is still a wye service; it contains
                             four wires if you trace the circuit back to its source (usually a transformer). In this type
                             of connection the phase to ground voltage will be the phase-to-ground voltage
                             indicated in Table 1, even though a neutral or ground wire is not physically present at
                             the load. The transformer is the best place to determine the circuit connection type
                             because this is a location where the voltage reference to ground can be conclusively
                             identified.
VC
Phase 2 Phase 3
VB Phase 1 VA
VBC IC VCA
                                                                               IA
                                                                    IB
                                                                         VAB
                              Figure 1-4: Phasor Diagram, Three-Phase Voltages and Currents, Delta-Connected
                            Another common delta connection is the four-wire, grounded delta used for lighting
                            loads. In this connection the center point of one winding is grounded. On a 120/240
                            volt, four-wire, grounded delta service the phase-to-ground voltage would be 120
                            volts on two phases and 208 volts on the third phase. Figure 1.5 shows the phasor
                            diagram for the voltages in a three-phase, four-wire delta system.
                                                             VC
VCA
VBC N VA
VAB
                                                               VB
                            Figure 1-5: Phasor Diagram Showing Three-phase Four-Wire Delta-Connected System
                                              B
                                                                       Phase B
Phase C
Node "n"
Phase A
                                              A
                                              N
                            Figure 1-6: Three-Phase Wye Load Illustrating Kirchoff’s Law and Blondel’s Theorem
                           Blondel's Theorem is a derivation that results from Kirchoff's Law. Kirchoff's Law states
                           that the sum of the currents into a node is zero. Another way of stating the same thing
                           is that the current into a node (connection point) must equal the current out of the
                           node. The law can be applied to measuring three-phase loads. Figure 1.6 shows a
                           typical connection of a three-phase load applied to a three-phase, four-wire service.
                           Kirchoff's Law holds that the sum of currents A, B, C and N must equal zero or that the
                           sum of currents into Node "n" must equal zero.
                           If we measure the currents in wires A, B and C, we then know the current in wire N by
                           Kirchoff's Law and it is not necessary to measure it. This fact leads us to the
                           conclusion of Blondel's Theorem- that we only need to measure the power in three of
                           the four wires if they are connected by a common node. In the circuit of Figure 1.6 we
                           must measure the power flow in three wires. This will require three voltage coils and
                           three current coils (a three-element meter). Similar figures and conclusions could be
                           reached for other circuit configurations involving Delta-connected loads.
80
70
                                                     60
                                   kilowat t s
50
40
30
20
10
                                                      0
                                                          1    2   3       4   5    6    7      8   9   10   11   12   13    14   15
                                                                                        Time (minutes)
                                                                         Figure 1-7: Power Use over Time
                           As in Table 1.2, the accumulated energy for the power load profile of Figure 1.7 is
                           14.92 kWh.
                           Demand is also a time-based value. The demand is the average rate of energy use
                           over time. The actual label for demand is kilowatt-hours/hour but this is normally
                           reduced to kilowatts. This makes it easy to confuse demand with power, but demand
                           is not an instantaneous value. To calculate demand it is necessary to accumulate the
                           energy readings (as illustrated in Figure 1.7) and adjust the energy reading to an
                           hourly value that constitutes the demand.
                           In the example, the accumulated energy is 14.92 kWh. But this measurement was
                           made over a 15-minute interval. To convert the reading to a demand value, it must be
                           normalized to a 60-minute interval. If the pattern were repeated for an additional
                           three 15-minute intervals the total energy would be four times the measured value or
                           59.68 kWh. The same process is applied to calculate the 15-minute demand value.
                           The demand value associated with the example load is 59.68 kWh/hr or 59.68 kWd.
                           Note that the peak instantaneous value of power is 80 kW, significantly more than the
                           demand value.
                           Figure 1.8 shows another example of energy and demand. In this case, each bar
                           represents the energy consumed in a 15-minute interval. The energy use in each
                           interval typically falls between 50 and 70 kWh. However, during two intervals the
                           energy rises sharply and peaks at 100 kWh in interval number 7. This peak of usage
                           will result in setting a high demand reading. For each interval shown the demand
                           value would be four times the indicated energy reading. So interval 1 would have an
                           associated demand of 240 kWh/hr. Interval 7 will have a demand value of 400 kWh/
                           hr. In the data shown, this is the peak demand value and would be the number that
                           would set the demand charge on the utility bill.
100
80
                                        kilowat t-hours
                                                          60
40
20
                                                           0
                                                                1    2     3     4        5      6    7     8
                                                                               Intervals (15 mins.)
IR V
IX I
                             where θ is the angle between the voltage and the current (see Fig. 1.9).
                             In applications where the voltage and current are not distorted, the Total Power
                             Factor will equal the Displacement Power Factor. But if harmonic distortion is present,
                             the two power factors will not be equal.
                                             500
                                                     Amps
0 Time
– 500
– 1000
1500
1000
500
                              Current (amps)
                                                  0                                                   t
                                                                       a                         2a
–500
–1000
–1500
1000
                       500
                                   Amps
0 Time
                                                                                                           3rd harmonic
                      – 500                                                                                5th harmonic
                                                                                                           7th harmonic
                                                                                                           Total
                                                                                                           fundamental
                             Inductive and capacitive impedance are present in all power systems. We are
                             accustomed to thinking about these impedances as they perform at 60 Hz. However,
                             these impedances are subject to frequency variation.
                             XL = jwL and
                             XC = 1/jwC
                             At 60 Hz, w = 377; but at 300 Hz (5th harmonic) w = 1,885. As frequency changes
                             impedance changes and system impedance characteristics that are normal at 60 Hz
                             may behave entirely differently in the presence of higher order harmonic waveforms.
                             Traditionally, the most common harmonics have been the low order, odd frequencies,
                             such as the 3rd, 5th, 7th, and 9th. However newer, non-linear loads are introducing
                             significant quantities of higher order harmonics.
                             Since much voltage monitoring and almost all current monitoring is performed using
                             instrument transformers, the higher order harmonics are often not visible. Instrument
                             transformers are designed to pass 60 Hz quantities with high accuracy. These devices,
                             when designed for accuracy at low frequency, do not pass high frequencies with high
                             accuracy; at frequencies above about 1200 Hz they pass almost no information. So
                             when instrument transformers are used, they effectively filter out higher frequency
                             harmonic distortion making it impossible to see.
                             However, when monitors can be connected directly to the measured circuit (such as
                             direct connection to a 480 volt bus) the user may often see higher order harmonic
                             distortion. An important rule in any harmonics study is to evaluate the type of
                             equipment and connections before drawing a conclusion. Not being able to see
                             harmonic distortion is not the same as not having harmonic distortion.
                             It is common in advanced meters to perform a function commonly referred to as
                             waveform capture. Waveform capture is the ability of a meter to capture a present
                             picture of the voltage or current waveform for viewing and harmonic analysis.
                             Typically a waveform capture will be one or two cycles in duration and can be viewed
                             as the actual waveform, as a spectral view of the harmonic content, or a tabular view
                             showing the magnitude and phase shift of each harmonic value. Data collected with
                             waveform capture is typically not saved to memory. Waveform capture is a real-time
                             data collection event.
                             Waveform capture should not be confused with waveform recording that is used to
                             record multiple cycles of all voltage and current waveforms in response to a transient
                             condition.
                In his book Power Quality Primer, Barry Kennedy provided information on different
                types of power quality problems. Some of that information is summarized in Table 1.3.
                It is often assumed that power quality problems originate with the utility. While it is
                true that power quality problems can originate with the utility system, many problems
                originate with customer equipment. Customer-caused problems may manifest
                themselves inside the customer location or they may be transported by the utility
                system to another adjacent customer. Often, equipment that is sensitive to power
                quality problems may in fact also be the cause of the problem.
                If a power quality problem is suspected, it is generally wise to consult a power quality
                professional for assistance in defining the cause and possible solutions to the
                problem.
                             In European Union member state countries, this meter is NOT certified for revenue
Note
metering. See the Safety Precautions section for meter certification details.
                             Current Inputs
                             The EPM 2200 meter Current Inputs use a unique dual input method:
                             Method 1: CT Pass Through
                             The CT passes directly through the meter without any physical termination on the meter.
                             This insures that the meter cannot be a point of failure on the CT circuit. This is preferable
                             for utility users when sharing relay class CTs.
                             Method 2: Current “Gills”
                             This unit additionally provides ultra-rugged Termination Pass Through Bars that allow CT
                             leads to be terminated on the meter. This, too, eliminates any possible point of failure at
                             the meter. This is a preferred technique for insuring that relay class CT integrity is not
                             compromised (the CT will not open in a fault condition).
Voltage L-N X X X
Voltage L-L X X X
Current Neutral X
Watts X X X X
VARs X X X X
VA X X X X
Positive watt-hours X
Negative watt-hours X
Net watt-hours X
Positive VAR-hours X
Negative VAR-hours X
Net VAR-hours X
VA-hours X
Frequency X X X
Voltage angles X
Current angles X
% of load bar X
2.2     Specifications
                         POWER SUPPLY
                         Range:.................................................Universal, (90 to 265) VAC @50/60Hz
                         Power consumption: ....................5 VA, 3.5 W
                         VOLTAGE INPUTS (MEASUREMENT CATEGORY III)
                         Range:.................................................Universal, Auto-ranging up to 416 V AC L-N, 721 V AC L-L
                         Supported hookups:.....................3-element Wye, 2.5-element Wye,
                                                                                2-element Delta, 4-wire Delta
                         Input impedance: ..........................1 MOhm/phase
                         Burden: ...............................................0.0144 VA/phase at 120 Volts
                         Pickup voltage:................................10 V AC
                         Connection: ......................................Screw terminal
                         Maximum input wire gauge: ...AWG #12 / 2.5 mm2
                         Fault withstand:..............................Meets IEEE C37.90.1
                         Reading: .............................................Programmable full-scale to any PT ratio
                         CURRENT INPUTS
                         Class 10:.............................................5 A nominal, 10 A maximum
                         Burden: ...............................................0.005 VA per phase maximum at 11 A
                         Pickup current:................................0.1% of nominal
                         Connections: ....................................O or U lug;
                                                                                Pass-through wire, 0.177" / 4.5 mm maximum diameter
                                                                                Quick connect, 0.25" male tab
                         Fault Withstand (at 23°C):..........100 A / 10 seconds, 300 A / 3 seconds, 500 A / 1 second
                         Reading: .............................................Programmable full-scale to any CT ratio
                         ISOLATION
                         All Inputs and Outputs are galvanically isolated to 2500 V AC
                         ENVIRONMENTAL
                         Storage:..............................................–20 to 70°C
                         Operating: .........................................-20 to 70°C
                         Humidity: ...........................................up to 95% RH, non-condensing
                         Faceplate rating:............................NEMA 12 (water resistant), mounting gasket included
                         METER ENCLOSURE ENVIRONMENTAL
                         Storage:..............................................–20 to 70°C
                         Operating: .........................................-10 to 50°C
                         Humidity: ...........................................up to 95% RH, non-condensing
                         Faceplate rating:............................NEMA 1 (Indoor Use)
                         Pollution degree .............................II
                         Overvoltage Category.................III (this product is designed for indoor use only)
                         MEASUREMENT METHODS
                         Voltage and current: ....................True RMS
                         Power: .................................................Sampling at 400+ samples/cycle on all channels measured; readings
                                                                                 simultaneously
                         A/D conversion: ..............................6 simultaneous 24-bit analog-to-digital converters
                         UPDATE RATE
                         All parameters: ...............................Up to 1 second
                         COMMUNICATIONS FORMAT
                         Types: ..................................................RS485 port through back plate plus KYZ Pulse (Com Option S)
                                                                                  RS485 serial port and RJ45 Ethernet port through backplate (Com
                                                                                  Option B)
                              COMMUNICATIONS PORTS
                              Protocols: .......................................... Modbus RTU, Modbus ASCII (Com Option S)
                                                                                    Modbus TCP/IP, BACnet MS/TP Serial (Com Option B)
                              Baud rate:......................................... 9600 to 57600 bps
                              Port address: ................................... 001 to 247
                              Data format:.................................... 8 bits, no parity
                              MECHANICAL PARAMETERS
                              Dimensions: ..................................... 4.25" × 4.85" × 4.85" (L × W × H)
                                                                                     105.4 mm × 123.2 mm × 123.2 mm (L × W × H)
                              Mounting:.......................................... mounts in 92 mm square DIN or ANSI C39.1, 4-inch round cut-out
                              Weight:............................................... 2 pounds / 0.907 kg
                              METER ENCLOSURE MECHANICAL PARAMETERS
                              Dimensions: ..................................... 8.08" × 11.06" × 13.50" (L × W × H)
                                                                                     205.23 mm × 280.92 mm × 342.9 mm (L × W × H)
                              Weight:............................................... 25 pounds / 11.4 kg
                              KYZ/RS485 PORT SPECIFICATIONS
                              RS485 Transceiver; meets or exceeds EIA/TIA-485 Standard:
                              Type: ................................................... Two-wire, half duplex
                              Min. Input Impedance: ............... 96kΩ
                              Max. Output Current: .................. ±60mA
                              WH PULSE
                              KYZ output contacts (and infrared LED light pulses through face plate):
                              Pulse Width: .................................... 40ms
                              Full Scale Frequency: ................. 6Hz
                              Contact type: ................................. Solid State – SPDT (NO – C – NC)
                              Relay type: ....................................... Solid state
                              Peak switching voltage: ............ DC ±350V
                              Continuous load current: ......... 120mA
                              Peak load current: ....................... 350mA for 10ms
                              On resistance, max.: ................... 35Ω
                              Leakage current: .......................... 1μA@350V
                              Isolation: ........................................... AC 3750V
                              Reset State: ..................................... (NC - C) Closed; (NO - C) Open
                              Infrared LED:
                              Peak Spectral Wavelength: ..... 940nm
                              Reset State: ..................................... Off
2.3 Compliance
CE Compliant
RF Immunity IEC61000-4-3
APPROVALS
                                                                                           UL61010-1
                               North America     UL Recognized                             C22.2. No 61010-1 (PICQ7)
                                                                                           File e200431
2.4    Accuracy
                         For 23 °C, 3 Phase balanced Wye or Delta load.
2 For unbalanced voltage inputs where at least one crosses the 150V auto-scale threshold
              NOTE
                         In = Nominal (5A)
                         Imax = Full Scale
Mechanical Installation
3.1     Introduction
                             The EPM 2200 meter can be installed using a standard ANSI C39.1 (4" Round) or an IEC
                             92mm DIN (Square) form. In new installations, simply use existing DIN or ANSI punches. For
                             existing panels, pull out old analog meters and replace with the EPM 2200 meter. The
                             various models use the same installation. See Chapter 4 for wiring diagrams.
                          ANSI Mounting
                          Rods (screw-in)
                             DIN
                             Mounting
                             Brackets
                                     4.     Secure from back of panel with lock washer and nut on each threaded rod.
                                            Use a small wrench to tighten. Do not overtighten. The maximum installation
                                            torque is 0.4 Newton-Meter.
                                NEMA12 mounting
                                         gasket
threaded rods
                              lock washer
                                  and nut
                                                                                      DIN mounting
                                                                                      bracket
                                                                                   top-mounting
                                                                                   bracket groove
                                                                                      bottom mounting
                                                                                      bracket groove
#8 screw
                         Remove (unscrew)
                         ANSI studs for DIN
                         Installation
Electrical Installation
                            •   GE requires the use of Fuses for voltage leads and power supply and Shorting Blocks
                                to prevent hazardous voltage conditions or damage to CTs, if the meter needs to be
                                removed from service. CT grounding is optional, but recommended.
                            The current inputs are only to be connected to external current transformers provided
Note
                            by the installer. The CT's shall be Listed or Approved and rated for the current of the
                            meter used.
                            If the equipment is used in a manner not specified by the manufacturer, the protection
                            provided by the equipment may be impaired.
                                Current gills
                                (nickel-plated
                                brass stud)
                             CT wire passing
                             through the meter
                             Current gills
                             removed
                                Crimp CT
                                terminations
                      Power supply
                      inputs                                                                  RS485 outputs
                                                                                              (do not place voltage
                                                                                              on these terminals!)
                      Voltage
                      inputs
        4.2.1    Description
                               Choose the diagram that best suits your application and maintains the CT polarity.
                               (1) Wye, 4-Wire with no PTs and 3 CTs, no PTs, 3 Element on page 4–8.
                                     (1a) Dual Phase Hookup on page 4–9.
                                     (1b) Single Phase Hookup on page 4–10.
                               (2) Wye, 4-Wire with no PTs and 3 CTs, 2.5 Element on page 4–11.
                               (3) Wye, 4-Wire with 3 PTs and 3 CTs, 3 Element on page 4–12.
                               (4) Wye, 4-Wire with 2 PTs and 3 CTs, 2.5 Element on page 4–13.
                               (5) Delta, 3-Wire with no PTs, 2 CTs on page 4–14.
                               (6) Delta, 3-Wire with 2 PTs, 2 CTs on page 4–15.
                               (7) Delta, 3-Wire with 2 PTs, 3 CTs on page 4–16.
                               (8) Current-Only Measurement (Three-Phase) on page 4–17.
                               (9) Current-Only Measurement (Dual-Phase) on page 4–18.
                               (10) Current-Only Measurement (Single-Phase) on page 4–19.
        4.2.2     (1) Wye, 4-Wire with no PTs and 3 CTs, no PTs, 3 Element
                             For this wiring type, select 3 EL WYE (3-element Wye) in the meter programming setup.
LINE
N A B C
                                                                                                               Power
                                 CT
                                                                                                               Supply
                                 Shorting
                                                                                                               Connection
                                 Block                                                                  GND
                                      Earth Ground                                                             FUSE
                                                                                                        L(+)
                                                                        HI          HI      HI                              L(+)
                                                                                                        N(-)   3A
                                                                                                                            N(-)
                                                                        lc         lb      la           Vref
                                                                        LO          LO      LO          Va
                                                                                                        Vb
                                                                                                        Vc
                                                                             FUSES
                                                                             3 x 0.1A
       N A B C
                LOAD
               LINE
        N    A        B   C
                                     CT
                                     Shorting                                                        Power
                                     Block                                                           Supply
                                                                                                     Connection
                                          Earth Ground                                      GND
                                                                                            L(+)     FUSE
                                                                  HI          HI   HI                             L(+)
                                                                                            N(-)     3A
                                                                                                                  N(-)
                                                                 lc          lb    la       Vref
                                                                 LO          LO    LO       Va
                                                                                            Vb
                                                                                            Vc
                                                                                                 x
                                                                       FUSES
                                                                       2 x 0.1A
        N    A        B   C
              LOAD
             LINE
       N    A       B   C
                                 CT
                                 Shorting
                                 Block
                                                                                                    Power
                                      Earth Ground                                                  Supply
                                                                                                    Connection
                                                                                           GND
                                                                                           L(+)     FUSE
                                                               HI      HI      HI                                L(+)
                                                                                           N(-)     3A
                                                                                                                 N(-)
                                                              lc      lb      la           Vref
                                                              LO       LO      LO          Va
                                                                                           Vb
                                                                                                x
                                                                                           Vc
                                                                                                x
                                                                    FUSE
                                                                    0.1A
       N    A       B   C
             LOAD
        4.2.3    (2) Wye, 4-Wire with no PTs and 3 CTs, 2.5 Element
                               For this wiring type, select 2.5EL WYE (2.5-element Wye) in the meter programming setup.
LINE
N A B C
                                                                                                             Power
                                     CT
                                                                                                             Supply
                                     Shorting
                                                                                                             Connection
                                     Block                                                            GND
                                          Earth Ground                                                       FUSE
                                                                                                      L(+)
                                                                          HI          HI   HI                             L(+)
                                                                                                      N(-)   3A
                                                                                                                          N(-)
                                                                         lc          lb    la         Vref
                                                                         LO           LO   LO         Va
                                                                                                      Vb
                                                                                                      Vc
                                                                               FUSES
                                                                               2 x 0.1A
         N A B C
                LOAD
Figure 4-8: 4-Wire Wye with no PTs and 3 CTs, 2.5 Element
LINE
N A B C
                                                                                                                  Power
                                 CT
                                                                                                                  Supply
                                 Shorting
                                                                                                                  Connection
                                 Block                                                                     GND
                                      Earth Ground                                                                FUSE
                                                                                                           L(+)
                                                                         HI         HI        HI                               L(+)
                                                                                                           N(-)   3A
                                                                                                                               N(-)
                                                                         lc        lb        la            Vref
                                                                         LO        LO        LO            Va
                                                                                                           Vb
                                                                                                           Vc
                                                                              FUSES
                                                                              3 x 0.1A
                                                Earth Ground
         N A B C
                LOAD
        4.2.5    (4) Wye, 4-Wire with 2 PTs and 3 CTs, 2.5 Element
                               For this wiring type, select 2.5EL WYE (2.5-element Wye) in the meter programming setup.
LINE
N A B C
                                                                                                           Power
                                     CT
                                                                                                           Supply
                                     Shorting
                                                                                                           Connection
                                     Block                                                          GND
                                          Earth Ground                                                     FUSE
                                                                                                    L(+)
                                                                         HI         HI   HI                             L(+)
                                                                                                    N(-)   3A
                                                                                                                        N(-)
                                                                         lc        lb    la         Vref
                                                                         LO         LO   LO         Va
                                                                                                    Vb
                                                                                                    Vc
                                                                              FUSES
                                                                              2 x 0.1A
                                                     Earth Ground
          N A B C
                LOAD
Figure 4-10: 4-Wire Wye with 2 PTs and 3 CTs, 2.5 Element
LINE
A B C
                          CT
                          Shorting
                          Block
                                                                                            L(+)   FUSE
                                                             HI          HI   HI                                L(+)
                                                                                            N(-)   3A
                                                                                                                N(-)
                                                            lc          lb    la            Vref
                                                            LO           LO   LO            Va
                                                                                            Vb
                                                                                            Vc
                                                                  FUSES
                                                                  3 x 0.1A
       A B C
        LOAD
LINE
A B C
                                     CT
                                     Shorting
                                     Block
                                                                                                        L(+)   FUSE
                                                                             HI          HI   HI                            L(+)
                                                                                                        N(-)   3A
                                                                                                                            N(-)
                                                                             lc         lb    la        Vref
                                                                             LO          LO   LO        Va
                                                                                                        Vb
                                                                                                        Vc
                                                                                  FUSES
                                                                                  2 x 0.1A
Earth Ground
                A B C
                LOAD
LINE
A B C
                                 CT                                                                                Power
                                 Shorting                                                                          Supply
                                 Block                                                                             Connection
                                                                                                            GND
                                      Earth Ground                                                                 FUSE
                                                                                                            L(+)
                                                                           HI          HI       HI                              L(+)
                                                                                                            N(-)   3A
                                                                                                                                N(-)
                                                                          lc          lb        la          Vref
                                                                          LO           LO       LO          Va
                                                                                                            Vb
                                                                                                            Vc
                                                                                FUSES
                                                                                2 x 0.1A
Earth Ground
                A B C
                LOAD
LINE
A B C
                                                                                                          Power
                                     CT
                                                                                                          Supply
                                     Shorting
                                                                                                          Connection
                                     Block                                                         GND
                                          Earth Ground                                                    FUSE
                                                                                                   L(+)
                                                                            HI    HI    HI                             L(+)
                                                                                                   N(-)    3A
                                                                                                                       N(-)
                                                                           lc    lb    la          Vref
                                                                            LO    LO    LO         Va              20VAC
                                                                                                          FUSE     Minimum
                                                                                                   Vb
                                                                                                   Vc     0.1A
                A     B     C
                    LOAD
                                Even if the meter is used only for current measurement, the unit requires a AN volts
Note
                                reference. Please ensure that the voltage input is attached to the meter. AC control power
                                can be used to provide the reference signal.
LINE
A B
                                 CT
                                 Shorting
                                 Block
                                                                                                  L(+)   FUSE
                                                                       HI    HI       HI                              L(+)
                                                                                                  N(-)    3A
                                                                                                                      N(-)
                                                                      lc    lb       la           Vref
                                                                       LO    LO       LO          Va              20VAC
                                                                                                         FUSE     Minimum
                                                                                                  Vb
                                                                                                  Vc     0.1A
             A    B
                 LOAD
                            Even if the meter is used only for current measurement, the unit requires a AN volts
Note
                            reference. Please ensure that the voltage input is attached to the meter. AC control power
                            can be used to provide the reference signal.
LINE
N A
                                     CT
                                     Shorting
                                     Block
Earth Ground
                                                                                                          Power
                                                                                                          Supply
                                                                                                          Connection
                                                                                                   GND
                                                                                                   L(+)   FUSE
                                                                            HI    HI    HI                             L(+)
                                                                                                   N(-)    3A
                                                                                                                       N(-)
                                                                           lc    lb     la         Vref
                                                                            LO    LO    LO         Va              20VAC
                                                                                                          FUSE     Minimum
                                                                                                   Vb
                                                                                                   Vc     0.1A
                   N      A
                    LOAD
                               Even if the meter is used only for current measurement, the unit requires a AN volts
Note
                               reference. Please ensure that the voltage input is attached to the meter. AC control power
                               can be used to provide the reference signal.
                             The Communication Options available for the EPM 2200 are connected and used in
                             different ways.
                             •                                 Com Option S: Modbus/KYZ output is explained here in Chapter 5.
                             •                                 Com Option B: BACnet MS/TP with Modbus TCP/IP Internet is explained in Chapter 7 on
                                                               page 7-1.
                                                                                                EPM2200 Meter
                                                                                                RS485 Connection
            From other RS-485 device:
                                             -                                                -
                      - Connect (-) to (-)
                      - Connect (+) to (+)  +                                                 +
                      - Connect Shield (SH)
                        to Shield (SH)        SH                                                  SH
                                                        Twisted Pair, Shielded Cable
                                                       Figure 5-3: 2-wire RS485 Connection
                             •   Use a shielded twisted pair cable 22 AWG (0.33 mm2) or larger, grounding the shield at
                    NOTE
                                 one end only.
                             •   Establish point-to-point configurations for each device on a RS485 bus: connect ’+’
                                 terminals to ’+’ terminals; connect ’-’ terminals to ’-’ terminals.
                             •   You may connect up to 31 meters on a single bus using RS485. Before assembling the
                                 bus, each meter must be assigned a unique address: refer to the GE Communicator
                                 Instruction Manual.
                             •   Protect cables from sources of electrical noise.
                             •   Avoid both “Star” and “Tee” connections (see Figure 5.5).
                             •   No more than two cables should be connected at any one point on an RS485 network,
                                 whether the connections are for devices, converters, or terminal strips.
                             •   Include all segments when calculating the total cable length of a network. If you are
                                 not using an RS485 repeater, the maximum length for cable connecting all devices is
                                 4000 feet (1219.20 meters).
                             •   Connect shield to RS485 Master and individual devices as shown in Figure 5.4. You
                                 may also connect the shield to earth-ground at one point.
                             •   Termination Resistors (RT) may be needed on both ends of longer length transmission
                                 lines. However, since the meter has some level of termination internally, Termination
                                 Resistors may not be needed. When they are used, the value of the Termination
                                 Resistors is determined by the electrical parameters of the cable.
                             Figure 5-4 shows a representation of an RS485 Daisy Chain connection.
                             You can use the Elements and Buttons on the EPM 2200 meter face to view meter
                             readings, reset and/or configure the meter, and perform related functions. You can also
                             use the GE Communicator software to configure the meter through communication.
                             The following sections explain meter programming, first by using the faceplate and then
                             with GE Communicator software.
                                        Reading                                                   Parameter
                                  type indicator                                                  designator
                                  % of Load Bar
                                                                                                 Scale Selector
                                           MENU                                                  ENTER
                                           button                                                button
                                                                                                  RIGHT
                                       DOWN
                                                                                                  button
                                       button
                             Using Menu, Enter, Down and Right Buttons, perform the following functions:
                                 • View Meter Information
                                 • Enter Display Modes
                                 • Configure Parameters (Password Protected)
                                 • Perform Resets
                                 • Perform LED Checks
                                 • Change Settings
                                 • View Parameter Values
                                 • Scroll Parameter Values
                             The EPM 2200 has three MODES:
                                 • Operating Mode (Default)
                                 • Reset Mode
                                 • Configuration Mode.
                             The MENU, ENTER, DOWN and RIGHT buttons navigate through the modes and navigate
                             through all the screens in each mode.
                             In this chapter, a typical set up will be demonstrated. Other settings are possible. The
                             complete Navigation Map for the Display Modes is in Appendix A of this manual. The meter
                             can also be configured with software (see GE Communicator Instruction Manual).
        6.1.3    Start Up
                             Upon Power Up, the meter will display a sequence of screens. The sequence includes the
                             following screens:
                             •   Lamp Test Screen where all LEDs are lighted
                             •   Lamp Test Screen where all digits are lighted
                             •   Firmware Screen showing build number
                             •   Error Screen (if an error exists)
                             If auto-scrolling is enabled, the EPM 2200 will then automatically Auto-Scroll the
                             Parameter Designators on the right side of the front panel. Values are displayed for each
                             parameter.
                             The KILO or MEGA LED lights, showing the scale for the Wh, VARh and VAh readings.
                             An example of a Wh reading is shown here.
                             •    If you push ENTER again, the Main Menu continues to scroll. (The DOWN button does
                                  not change the screen.)
                             •    If you push the RIGHT button, the rSt All? YES screen appears. Press Enter to perform
                                  a reset.
                                  If Password protection is enabled in the software for reset, you must enter the four
Note
                            PASS or FAIL:
                            2.    When all 4 digits have been entered, push ENTER.
                                  If the correct Password has been entered, rSt ALL donE appears and the screen
                                  returns to Auto-Scroll the Parameters. (In other Modes, the screen returns to the
                                  screen to be changed. The left digit of the setting is flashing and the Program (PRG)
                                  LED flashes on the left side of the meter face.)
                            .
                                  If an incorrect Password has been entered, PASS ---- FAIL appears and the screen
                                  returns to rSt ALL? YES.
                            .
                                    4.      Push the DOWN Button to scroll all the parameters: scroll, CT, PT, connection
                                            (Cnct) and port.
                                            The active parameter is always flashing and displayed in the A screen.
7. Use the RIGHT button to scroll to change the value from no to YES.
                                     8.   When the Stor ALL? YES message is displayed, press ENTER to change the
                                          setting.
                            The Stor ALL donE message will appear and the meter will reset.
                             This will display the and the Ct-n (CT numerator) screen.
                                     2.     Press ENTER again to change to display the Ct-d (CT denominator) screen.
                            The Ct-S value can be “1”, “10”, or “100”. Refer to Programming the screen for configuration
                            mode. on page 6–7 for instructions on changing values.
                            Example settings for the Ct-S value are shown below:
                                    200/5 A: set the Ct-n value for “200” and the Ct-S value for “1”
                                    800/5 A: set the Ct-n value for “800” and the Ct-S value for “1”
                                    2000/5 A: set the Ct-n value for “2000” and the Ct-S value for “1”.
                                    10000/5 A: set the Ct-n value for “1000” and the Ct-S value for “10”.
                            The value for amps is a product of the Ct-n and the Ct-S values.
Note
                   NOTE
                                    4.   Press ENTER to scroll through the other CFG parameters.
                                         Pressing DOWN or RIGHT displays the password screen (see Reset Mode on
                                         page 7–4 for details).
                                    5.   Press MENU to return to the main configuration menu.
                             The Pt-S value can be “1”, “10”, or “100”. Refer to Programming the Configuration Mode
                             Screens on page 7–7 for instructions on changing values.
                             Example settings for the Pt-n, Pt-d, and Pt-S values are shown below:
                                     2.   Press ENTER when Cnct is the "active" parameter (i.e. it is in the A screen and
                                          flashing).
                            This will display the Cnct (Connection) screen. To change this setting, use the RIGHT button
                            to scroll through the three settings. Select the setting that is right for your meter.
                            The possible Connection configurations are
                                  • 3-element Wye (3 EL WYE)
                                  • 2.5-element Wye (2.5EL WYE)
                                  • 2 CT Delta (2 Ct deL)
                            as shown below:
                            If you have an EPM 2200 meter with Com Option B (BACnet), the RS485 port is used only for
Note
                                                                    Address 005
                             Refer to Programming the Configuration Mode Screens above for details on changing
                             values.
                                 • The next POrt screen is the baud rate (bAUd). The current baud rate is displayed on
                                   the “B” screen. Refer to Programming the Configuration Mode Screens above for
                                   details on changing values. The possible baud rate screens are shown below.
                             Refer to Programming the Configuration Mode Screens above for details on changing
                             values. The three protocol selections are shown below.
                                      3.   Press ENTER to scroll through the other CFG parameters.
                                      4.   Press DOWN or RIGHT to display the Password screen (see Reset Mode on
                                           page 7–4 for details).
                                      5.   Press MENU to return to the main Configuration menu.
                Parameter designator
                 Available by Software                                   Possible Readings
                Option (see Order Code
                         table)
VAh C1 KVAH
                             Readings or groups of readings are skipped if not applicable to the meter type or hookup,
Note
                                                                                                            Watt-Hour
                                                                                                            Test Pulse
Comparator
Results
Table 6–3: Infrared & KYZ Pulse Constants for Accuracy Testing
                             Connecting in Default communication mode does not apply to the EPM 2200 meter with
Note
                             Com Option B.
                     NOTE
5. You will see the Device Status screen, confirming connection to your meter. Click OK.
                             7.   You will see the Device Profile screen. The tabs at the top of the screen allow you to
                                  navigate between setting screens (see below).
                                  • COM1 is not used by the EPM 2200 meter with Com Option S.
Note
                                  • If you have an EPM 2200 meter with Com Option B (BACnet), the RS485 port is used
                     NOTE
                                    only for BACnet and is not programmed.
                             Valid Communication Settings
                             •    COM2 (RS485)
                                  •   (1-247)
                                  • Protocol (Modbus RTU, ASCII)
                          If the Update fails, the software asks if you want to try to Update again.
Note
NOTE
                          If you click Cancel before Save or Update, you will lose any changes you have made to the
Note
                          Device Profile.
                  NOTE
NOTE
                              You must specify Primary and Secondary Voltage in Full Scale. Do not use ratios! The PT
                              Denominator should be the Secondary Voltage level.
                    WARNING
                              Example:
                              A 14400/120 PT would be entered as:
                              PT Num: 1440
                              PT Denom: 120
                              Multiplier: 10
                              This example would display a 14.40kV.
                              Example CT Settings:
                              200/5 Amps: Set the Ct-n value for 200, Ct-Multiplier value for 1.
                              800/5 Amps: Set the Ct-n value for 800, Ct-Multiplier value for 1.
                              2,000/5 Amps: Set the Ct-n value for 2000, Ct-Multiplier value for 1.
                              10,000/5 Amps: Set the Ct-n value for 1000, Ct-Multiplier value for 10.
                              Example PT Settings:
                              277/277 Volts Pt-n value is 277, Pt-d value is 277, Pt-Multiplier is 1.
                              14,400/120 Volts: Pt-n value is 1440, Pt-d value is 120, Pt-Multiplier value is 10.
                              138,000/69 Volts: Pt-n value is 1380, Pt-d value is 69, Pt-Multipier value is 100.
                              345,000/115 Volts: Pt-n value is 3470, Pt-d value is 115, Pt-Multiplier value is 100
                              345,000/69 Volts: Pt-n value is 345, Pt-d value is 69, Pt-Multiplier value is 1000.
NOTE
NOTE
                          If incorrect values are entered on the Energy and Display screen the following message
Note
                          appears:
                  NOTE
                             Current, CT, PT and Energy Settings will cause invalid energy accumulator values.
                             Change the inputted settings until the message disappears.
SETTINGS
                                 The EPM 2200 Meter is shipped with Password Disabled; there is NO DEFAULT
Note
                                 PASSWORD)
                     NOTE
                             The fields are as follows:
                             •   Enable Password for Reset: click to enable
                             •   Enable Password for Configuration: click to enable
                             •   Change Password: click to change
                             •   Device Designation: optional user-assigned label
                             The Communication Options available for the EPM 2200 are connected and used in
                             different ways.
                             •                                    Com Option S: Modbus/KYZ output is explained in Chapter 5 on page 5-1.
                             •                                    Com Option B: BACnet MS/TP with Modbus TCP/IP Internet is explained in here in
                                                                  Chapter 7.
                                locates the requested property of the requested object and sends the value to the client.
                                Other classes of service requests have to do with alarms and events; file uploading/
                                downloading; managing remote device operation; and virtual terminal functions.
                                The EPM 2200 meter communicates BACnet MS/TP protocol though its RS485 serial port,
                                allowing it to act as a BACnet device in any BACnet application. The meter also has a Web
                                interface via its RJ45 Ethernet port that you can use to remotely set up the BACnet MS/TP
                                and for Modbus TCP/IP configuration. The Ethernet port can also track energy readings
                                through the internet using any standard Web browser. The EPM 2200 meter uses BACnet
                                MS/TP (master-slave/token-passing), which is designed to run at speeds of 1 Mbps or less
                                over twisted pair wiring, and in which the device takes turns being a master and a slave,
                                dependent on whether it is sending or receiving data.
                                For more detailed information, visit the BACnet website at www.bacnet.org.
                              * For optimal accuracy and resolution the accumulators’ attributes are factory preset to: 6
                              digits, no fractions – zero decimal places and kilo multiplier (Modbus register address:
                              30,006, decimal). We recommended you maintain these settings all of the time.
                                  • Right-click on the LAN connection you want to use and click Properties.
                                    You will see the screen shown below.
                                  • Scroll and highlight Internet Protocol TCP/IP, then click the Properties
                                    button.
                                    You will see the screen shown below.
                                  • Click the Use the Following IP Address radio button and enter:
                                          • IP Address: 10.0.0.100
                                          • Subnet Mask: 255.255.255.0
                                  • Click OK.
                                    The Local Area Connection Properties screen redisplays.
                                  • Click OK.
                             2.   Use an Ethernet cable to connect the meter to your LAN port.
                                                                                               Insert Ethernet
                                                                                               Cable here
                             3.   Open your web browser and connect to the meter at the default address by typing
                                  http://10.0.0.1.
                             If this doesn’t work, reset the meter to this default address by pressing the Reset button for
Note
5. Click OK. You will see the BACnet MS/TP Interface webpage, shown below.
                              6.   Click TCP/IP and BACnet Settings on the left side of the webpage to see the page
                                   shown below. Use this page to change the default IP address (10.0.0.1) to an IP
                                   address in the same subnet as your Network. Contact your System Administrator if
                                   you are unsure of the correct address to use.
                                  • Modbus TCP Port for TCP to RTU Router - the default port is 502. As long as this
                                    field is not 0, the router is enabled, which lets the meter communicate with
                                    Modbus TCP/IP Master devices.
                                  • Enable BACnet/IP Control Objects - Check this box to allow direct access to
                                    Modbus registers. If enabled, the Control Objects are represented by the following
                                    three Analog-Value BACnet Objects:
                                          •    500001 is a writeable object called MOD_ID_TARGET (“target device
                                              identifier to be read/written”). Since the meter has a hard-coded Modbus
                                              address of “1” only this value needs to be entered before first access to a
                                              Modbus register. The default = -1.0. -1.0 also means do not execute
                                              #500003 (neither read nor write).
                                          •    500002 is a writeable object called MOD_REGISTER (“register to be read/
                                              written”); for example, “1000” to access the first register of volts A-N. The
                                              default = -1.0 after any reboot. -1.0 also means do not execute #500003
                                              (neither read nor write).
                                          • 500003 is a readable/writeable value called MOD_VALUE (“value to be read
                                            from or written to select register”).
                                          The MOD_REGISTER resets with -1.0 after each Read/Write (whether or not
                                          successful), from/to MOD_VALUE with valid MOD_ID_TARGET and
                                          MOD_REGISTER. MOD_REGISTER will also be set to -1.0 30 seconds after it is
                                          written to.
                             7.   Click OK to process your changes. You will see the following message
You still need to activate the configuration for the changes to take effect.
                             You can change all settings back to their default by clicking the Restore Default button at
Note
                                   • Max Info Frames - this is the maximum number of information frames the node is
                                     allowed to send before it needs to pass the token.
                                   • Max Master - this is the highest allowable address for master nodes (cannot be
                                     higher than 127); a Max master greater than 36 is recommended for data sets.
                              9.   Click the Advanced button to display additional settings.
NOTE
                              12. Click the Confirm button to process the changes. You will see the message shown
                                  below (the IP Address shown in the link is just an example).
                              13. The meter resets. Connect the meter Ethernet cable to your Network (remove it from
                                  your PC). You can now connect to the meter through your Network using the new IP
                                  address.
Reset Button
                                    Figure 7-1: Backplate of EPM 2200 meter, showing Reset Button placement
                              Using an implement such as a ballpoint pen tip, press and hold the Reset button for 30
                              seconds. The Ethernet card will be reset to its default settings.
                              To access this web page from any of the other pages, click Home on the left side of the
Note
                              page.
                     NOTE
                              This web page shows the current power, power factor, accumulated energy, and peak
                              demand readings from the meter. You can download all of the meter BACnet data by
                              clicking the Download data.csv button. You will see the following screen:
                              This screen gives you the option to open or save an Excel file with the BACnet meter data.
                                  • Click Open to open an Excel file with the meter’s BACnet data.
                                  • Click Save to save a copy of the Excel file.
                                  • Click Cancel to close the screen without opening or saving the file.
                                  An example file is shown below:
                                  Scroll to see all of the objects on the screen. The following items are shown for each
                                  BACnet Object:
                                  • Name
                                  • Object
                                  • Value
                                  • Units
                                  • OK (Reliability)
                                  • Description
                              Use this page to change the Administrator Login and Password for this interface. We
                              recommend that you change the Login and Password rather than continuing to use the
                              default sign-on (be sure to store this information someplace safe).
                                  This page lists information and any Error log for the meter.
                                  • To erase the Error log, click the Clear Log button.
                                             • Click the Restore Default button to restore all settings to the factory
                                               default values.
                                             • Click the Discard Changes button to restore all settings to the last saved
                                               configuration.
A.1     Introduction
                             The EPM 2200 meter can be configured and a variety of functions performed using the
                             buttons on the meter face.
                             •                          An Overview of the Elements and Buttons on the meter face, and programming using
                                                        the buttons can be found in Chapter 6 on page 6-1.
                             •                          The meter can also be programmed using software (see the GE Communicator
                                                        Instruction Manual).
STARTUP
sequence completed
                                                                                                                                     MENU
                                                                                                   ENTER
MENU
                                                                                                   DOWN
   * Configuration Mode is
                                                                                                                        MENU
   not available during a
   Programmable Settings                                                                  MAIN MENU Screen
   update via a COM port.
                                                                                                BUTTONS
      MENU                       Returns to previous menu from any screen in any mode
ENTER Indicates acceptance of the current screen and advances to the next one
                              all screens
           single                                       group of
                             for a display                                 action taken              button
           screen                                       screens
                                 mode
                                                                VOLTS_LN_MA
                              VOLTS_LN               RIGHT                         RIGHT      VOLTS_LN_MIN
                                                                     X
                       DOWN2
               (from any VOLTS_LN screen)                                             DOWN2
                                                                                                      See Note 1
                                                                    RIGHT
                          DOWN2
                  (from any VOLTS_LL screen)
                                                                                                                                   See Note 1
                                                                                                 RIGHT
                        DOWN2
                  (from any AMPS screen)                                                          DOWN2
                                                                                                                                                                 See Note 1
                                                                                                     RIGHT
       DOWN2
                          DOWN2
                 (from any W_VAR_PF screen)
                                                                                                      See Note 1
                                                                    RIGHT
                          DOWN2
                  (from any VA_FREQ screen)
                                                                                                                                     See Note 1
                                                                                   RIGHT
                          DOWN2
                    (from any KWH screen)
                                                                                                                                     See Note 1
                                                                                   RIGHT
                          DOWN2
                   (from any KVARH screen)
                                                   MENU
                                                 (from any
                                               operating mode
                                                                            to Main Menu
                                                  screen)
                                                                             see sheet 1
ENTER
is password required?
                                                                                                                                   2 sec
                                                                                       yes
ENTER
           ENTER
                                                                                                                              RESET_PW_FAIL:
                        reset all max &                                         is password                                  PASS
                                                         yes                                               no
                          min values                                              correct?                                   ####
                                                                                                                             FAIL
                      RESET_CONFIRM:
                     RST
                     ALL
                     DONE
2 sec.
                                                                             MENU
                                                                           (from any
                    to previous operating                                 reset mode
                        mode screen                                         screen)
                         see sheet 2
                                                                        to Main Menu
                                                                        see sheet 1
           CONFIG_MENU:                   ENTER
         CT (blinking)                                                                                    ENTER                                               ENTER
         PT
         CNCT                                                       CTN_EDIT:                                                     CTD_SHOW:                                CT_MULT_EDIT:
                                                              CT-N                                                           CT-D                                       CT-S                           DOWN or
                                                      DOWN                                  RIGHT
                                            increment         ####                              blink                        1 or 5                                     1 or 10 or 100                  RIGHT
                                              blinking        (one # blinking if edit)          next                                                                    (choice blinking if edit)            show
            DOWN
                        MENU                    digit                                           digit                                                                                                        next
                                                                                                                                                                                                            choice
                                                                                                                       ENTER
           CONFIG_MENU:                     ENTER
         PT (blinking)
         CNCT
                                                                                                          ENTER                                               ENTER
         PORT
           CONFIG_MENU:
         PASS2 (blinking)                                                                                                   ENTER2
                                            ENTER
         SCRL
         CT
                                                                                                             Notes:
                                                                                                             1. Initial access is view-only. View access shows the existing settings. At the
                                                               PASSWORD_EDIT:                                first attempt to change a setting (DOWN or RIGHT pressed), password is
    CONFIG_MENU screen                                DOWN    PASS                          RIGHT
   scrolls through 6 choices,               increment         #### (one # blinking)             blink        requested (if enabled) and access changes to edit. Edit access blinks the digit
   showing 3 at a time. The                   blinking                                          next         or list choice eligible for change and lights the PRG LED.
    top choice is always the                    digit                                           digit        2. Skip over password edit screen and menu selection if access is view-only.
   "active" one, indicated by                                                                                3. Scroll setting may be changed with view or edit access.
      blinking the legend.                                                                                   4. ENTER accepts an edit; MENU abandons it.
                                                                                                                                                                         CFG_ENTER_PW:
                                                                                                                                                                        PASS
                                           SAVE_YES:                                       save new                                                            DOWN                                  RIGHT
         any changes?        yes                                      ENTER                                                                                             ### (one # blinking)
                                                                                          configuration                                                                                                           yes
                                      STOR
                                                                                                                                                        increment                                         blink
                                      ALL?
                                                                                                                                                          blinking                                        next
                                      yes (blinking)
                                                                                                                                                            digit                                         digit
                                                                                   SAVE_CONFIRM:                                                                               ENTER
                                                                                 STOR
              no                                                                 ALL
                            MENU              RIGHT RIGHT                        DONE                                                                                        is password
                                                                                                                                                                               correct?             to the originating
                                                                                                                                                                                                      EDIT screen
                                                                                             2 sec.                  no
                                            SAVE_NO:
       to Main Menu                   STOR                                                  reboot
                            MENU                                                                           to previous operating
                                      ALL?
         see sheet 1                  no (blinking)                            ENTER                           mode screen
                                                                                                                see sheet 2
B.1     Introduction
                             The Modbus Map for the EPM 2200 Meter gives details and information about the possible
                             readings of the meter and about the programming of the meter.
                             The EPM 2200 can be programmed using the buttons on the face plate of the meter (6.1
                             Programming Using the Faceplate). The meter can also be programmed using software. For
                             a Programming Overview, see section 6.4 GE Communicator Programming Overview of this
                             manual. For further details see the GE Communicator Instruction Manual.
Register                                          0                                                                             1
Byte                         0                                        1                                    0                                        1
Bit         7       6   5    4    3   2     1     0   7   6   5   4       3   2   1   0   7   6   5    4       3   2   1    0       7   6   5   4       3   2   1   0
Meaning     s       e   e    e    e   e     e     e   e   m m m m m m m m m m m m m m m m m m m m m m m
            sign                 exponent                                                              mantissa
                                      The formula to interpret a Floating Point Value is: -1sign x 2exponent-127 x 1.mantissa =
                                      0x0C4E11DB9
                                      -1sign x 2137-127 x 1.11000010001110111001
                                      -1 x 210 x 1.75871956
                                      -1800.929
                                      Formula Explanation
                                      C4E11DB9 (hex)              11000100 11100001 00011101 10111001 (binary)
                                      The sign of the Mantissa (and therefore the number) is 1, which represents a negative
                                      value.
                                      The Exponent is 10001001 (binary) or 137 decimal.
                                      The Exponent is a value in excess of 127, so the Exponent value is 10.
                         NOTE
                                    Mantissa = the positive fraction after the decimal point
Status Block
                                                                                                                       read-only
1387 - 1387 5000          - 5000 Meter Status               UINT16 bit-mapped          --exnpch        exnpch = EEPROM block 1
                                                                                       ssssssss        OK flags (e=energy,
                                                                                                       x=max, n=min,
                                                                                                       p=programmable settings,
                                                                                                       c=calibration, h=header),
                                                                                                       ssssssss = state (1=Run,
                                                                                                       2=Limp, 10=Prog Set
                                                                                                       Update via buttons,
                                                                                                       12=Prog Set Update via
                                                                                                       communication port.)
1389 - 138A 5002 - 5003 Time Since Reset                    UINT32 0 to 4294967294     4 msec          wraps around after max       2
                                                                                                       count
                                                                                                       Block Size:                  4
                                                          Commands Section4
Resets Block9                                                                                                          write-only
4E1F - 4E1F 20000 - 20000 Reset Max/Min Blocks UINT16 password5                                                                     1
4E20 - 4E20 20001 - 20001 Reset Energy         UINT16 password5                                                                     1
                          Accumulators
                                                                                                       Block Size:                  2
Encryption Block
                                                                                                                            read/write
658F - 659A 26000 - 26011 Perform a Secure                     UINT16                                     encrypted command to    12
                          Operation                                                                       read password or change
                                                                                                          meter type
                                                                                                          Block Size:             12
7536 - 7536 30007 - 30007 Operating Mode                       UINT16 bit-mapped       00000000          eeeeeeee = op mode           1
                          Screen Enables                                               eeeeeeee          screen rows on(1) or off(0),
                                                                                                         rows top to bottom are
                                                                                                         bits low order to high order
7537 - 753D 30008 - 30014 Reserved                                                                                                    7
753E - 753E 30015 - 30015 User Settings Flags                  UINT16 bit-mapped       ---g--nn srp--wf- g = enable alternate full    1
                                                                                                         scale bargraph current
                                                                                                         (1=on, 0=off)
                                                                                                         nn = number of phases for
                                                                                                         voltage & current screens
                                                                                                         (3=ABC, 2=AB, 1=A, 0=ABC)
                                                                                                         s = scroll (1=on, 0=off)
                                                                                                         r = password for reset in
                                                                                                         use (1=on, 0=off)
                                                                                                         p = password for
                                                                                                         configuration in use (1=on,
                                                                                                         0=off)
                                                                                                         w = pwr dir (0-view as
                                                                                                         load, 1-view as generator)
                                                                                                         f = flip power factor sign
                                                                                                         (1=yes, 0=no)
7549 - 7549 30026 - 30026 COM2 setup                        UINT16 bit-mapped           ----dddd -ppp-   dddd = reply delay (* 50 1
                                                                                        bbb
                                                                                                         msec)
                                                                                                         ppp = protocol (1-Modbus
                                                                                                         RTU, 2-Modbus ASCII)
                                                                                                         bbb = baud rate (1-9600,
                                                                                                         2-19200, 4-38400, 6-
                                                                                                         57600)
754A - 754A 30027 - 30027 COM2 address                      UINT16 1 to 247             none                                      1
754B - 754B 30028 - 30028 Not Used                          N/A                                                                   1
                                      ASCII characters packed 2 per register in high, low order and without any termination
             ASCII                    characters. For example, "EPM2200" would be 4 registers containing 0x5378, 0x6172,
                                      0x6B31, 0x3030.
             SINT16/UINT16            16-bit signed / unsigned integer.
                                      32-bit signed / unsigned integer spanning 2 registers. The lower-addressed register is the
             SINT32/UINT32            high order half.
                                      32-bit IEEE floating point number spanning 2 registers. The lower-addressed register is the
             FLOAT                    high order half (i.e., contains the exponent).
                                      All registers not explicitly listed in the table read as 0. Writes to these registers will be
                  1                   accepted but won't actually change the register (since it doesn’t exist).
                                      Meter Data Section items read as 0 until first readings are available or if the meter is not in
                  2                   operating mode. Writes to these registers will be accepted but won't actually change the
                                      register.
                      Register valid only in programmable settings update mode. In other modes these registers
             3        read as 0 and return an illegal data address exception if a write is attempted..
                      Meter command registers always read as 0. They may be written only when the meter is in
             4        a suitable mode. The registers return an illegal data address exception if a write is
                      attempted in an incorrect mode.
                      If the password is incorrect, a valid response is returned but the command is not executed.
             5        Use 5555 for the password if passwords are disabled in the programmable settings.
             6        M denotes a 1,000,000 multiplier.
             7        Not applicable to EPM 2200
                      Writing this register causes data to be saved permanently in EEPROM. If there is an error
             8        while saving, a slave device failure exception is returned and programmable settings mode
                      automatically terminates via reset.
                      Reset commands make no sense if the meter state is LIMP. An illegal function exception will
             9        be returned.
             10       Energy registers should be reset after a format change.
             11       N/A
             13       N/A
                      All 3 voltage angles are measured for Wye and Delta hookups. For 2.5 Element, Vac is
                      measured and Vab & Vbc are calculated. If a voltage phase is missing, the two voltage
             14       angles in which it participates are set to zero. A and C phase current angles are measured
                      for all hookups. B phase current angle is measured for Wye and is zero for other hookups. If
                      a voltage phase is missing, its current angle is zero.
                      If any register in the programmable settings section is set to a value other than the
             15       acceptable value then the meter will stay in LIMP mode. Please read the comments section
                      or the range for each register in programmable settings section for acceptable settings.
             16       N/A