Unit Ii PDF
Unit Ii PDF
UNIT – II
D.C. GENERATORS
INTRODUCTION:
The electrical machines deals with the energy transfer
either from mechanical to electrical form or from electrical to
mechanical form, this process is called electromechanical energy
conversion.
An electrical machine which converts mechanical energy into electrical energy is called an
electric generator while an electrical machine which converts electrical energy into the
mechanical energy is called an electric motor.
Classification of electrical machines
As the coil rotates in clock-wise direction and assumes successive positions in the field the,
flux linked with it changes. Hence, an emf is induced in it which is proportional to the rate of
change of flux linkages (e = Ndϕ /dt).
• When the plane of the coil is at right angles to lines of flux i.e. when it is in position
1, then flux linked with the coil is maximum, but rate of change of flux linkages is
minimum. Hence, there is no induced emf in the coil.
• As the coil continues rotating further, the rate of change of flux linkages (and hence
induced emf in it) increases, till position 3 is reached where θ = 90º, the coil plane is
horizontal i.e. parallel to the lines of flux. The flux linked with the coil is minimum
but rate of change of flux linkages is maximum. Hence, maximum emf is induced in
the coil at this position.
Electrical Machines-1
• From 90º to 180º, the flux linked with the coil gradually increases but the rate of
change of flux linkages decreases. Hence, the induced emf decreases gradually till in
position 5 of the coil, it is reduced to zero value.
• From 180º to 360º, the variations in the magnitude of emf are similar to those in the
first half revolution. Its value is maximum when coil is in position 7 and minimum
when in position 1. But it will be found that the direction of the induced current is
the reverse of the previous direction of flow.
For making the flow of current unidirectional in the external circuit, the slip-rings are replaced
by split-rings. The split-rings are made out of a conducting cylinder which is cut into two halves
or segments insulated from each other by a thin sheet of mica or some other insulating
material.
As before, the coil ends are joined to these segments on which rest the carbon or
copper brushes. It is seen that in the first half revolution current flows along (ABMLCD) i.e. the
brush No.1 in contact with segment ‘a’ acts as the positive end of the supply and ‘b’ as the
negative end. In the next half revolution, the direction of the induced current in the coil has
reversed. But at the same time, the positions of segments ‘a’ and ‘b’ have also reversed with
the result that brush No.1comes in touch with the segment which is positive i.e. segment ‘b’ in
this case. Hence, current in the load resistance again flows from M to L. The waveform of the
current through the external circuit is as shown in below. This current is unidirectional but not
continuous like pure direct current.
• The position of brushes is so arranged that the change over of segments ‘a’ and ‘b’
from one brush to the other takes place when the plane of the rotating coil is at
right angles to the plane of the lines of flux. It is so because in that position, the
induced emf in the coil is zero.
Electrical Machines-1
• The current induced in the coil sides is alternating as before. It is only due to the
rectifying action of the split-rings (also called commutator) that it becomes
unidirectional in the external circuit.
• Nature of induced emf: The nature of the induced emf for a conductor rotating in
the magnetic field is alternating. As conductor rotates in a magnetic field, the
voltage component at various positions is different. Hence the basic nature of
induced emf in the armature winding in case of dc generator is alternating. To get dc
output which is unidirectional, it is necessary to rectify the alternating induced emf.
A device which is used in dc generator to convert alternating induced emf to
unidirectional dc emf is called commutator.
Electrical Machines-1
2.2 construction of DC machine:
The dc generators and dc motors have the same general construction. In fact, when the
machine is being assembled, the workmen usually do not know whether it is a dc generator
or motor. Any dc generator can be run as a dc motor and vice-versa.
5. Armature Core
Function
o It has large number of slots in its periphery
o Armature conductor, are placed in this slots
o It is also provide path of low reluctance to the flux produced by field winding
Material used
o High permeability low reluctance materials such as cast or iron are used for armature
core.
o The lamination is provided so as to reduce the loss due to eddy current.
Electrical Machines-1
6. Armature Winding
Function
o Armature conductor are inter connected to form armature Winding
o When armature winding is rotated using prime mover. the magnetic flux and voltage
gets induced in it
o Armature winding is connected to external circuit
Material used
o It is made of conducting material such as copper.
7. Commutator
Function
o It Convert alternating current induce in the current in a unidirectional current
o It collects the current form armature conductor and pass it load with the help of brushes
o It also provide unidirectional torque for dc motor
Material used
o It is made of a large number of edge shaped segments of hard drawn copper.
o The Segments are insulated from each other by thin layer of mica.
o The Segment of commutator is made of copper and insulating material between
segments is mica.
8. Brushes
Function
o Brushes collect the current from commutator and apply it to external load.
o Brushes wear with time and it is should be inspected regularly.
Material used
o Brushes are made of carbon or graphite it is rectangular in shape.
The armature slots are again classified into two different types
a) open type
b) closed type
2.3.1Armature winding in dc machines:
i. Pole Pitch:
Electrical Machines-1
The pole pitch is defined as peripheral distance between center of two adjacent poles in DC
machine. This distance is measured in term of armature slots or armature conductor come
between two adjacent pole centers. This is naturally equal to the total number of armature
slots divided by number of poles in the machine.pole pitch is equal to total numbers of
armature slots divided by total numbers of poles, this can alternatively referred as armature
slots per pole
Coil span is defined as peripheral distance between two sides of a coil, measured in terms of
number of armature slots between them. That means, after placing one side of the coil in a
particular slot, after how many conjugative slots, the other side of the same coil is placed on
the armature. This number is known as coil span.
NOTE:
o If the coil span is equal to the pole pitch, then the armature winding is said to be full -
pitched. At this situation, two opposite sides of the coil lie under two opposite poles.
Hence emf induced in one side of the coil will be in 180° phase shift with emf induced in
the other side of the coil. Thus, total terminal voltage of the coil will be nothing but the
direct arithmetic sum of these two emfs.
o If the coil span is less than the pole pitch, then the winding is referred as fractional
pitched. In this coil, there will be a phase difference between induced emfs in two sides,
less than 180°. Hence resultant terminal voltage of the coil is vector sum of these two
emfs and it is less than that of full-pitched coil. Fractional pitched windings are
purposely used to effect substantial saving in copper of the end connection and
for improving commutation
Electrical Machines-1
2.Wave winding:
In this type, winding always travels ahead avoiding over lapping. It travels like a progressive
wave hence called wave winding. Both coils starting from slot 1 and slot 2 are progressing in
wave fashion. Due to this type of connection, the total number of conductors get divided into
two number of parallel paths always, irrespective of number of poles of machine. As number of
parallel paths is less, it is preferable for low current, high voltage capacity generators
Electrical Machines-1
S.No Lap winding Wave winding
1 Number of parallel paths (A) = poles (P) Number of parallel paths (A) = 2
(always) 2.
2 Number of parallel paths (A) = 2 (always) Number of brush sets required is equal
to two
3 Preferable for high current, low voltage Preferable for highvoltage, low current
capacity generators capacity generators capacity generators
4 Normally used for generators of capacity Preferred for generator of capacity less
more than 500A than 500A
Let
= flux/pole in Wb P = number of poles
Z = No. of armature conductors = No. of slots * conductors/slot
A = No. of parallel paths = P ... for Lap winding
= 2 ... for Wave winding
N = Speed of armature in r.p.m.
Eg = Generated EMF or EMF/parallel path
According to faraday’s laws of electromagnetic induction principle, average induced EMF (Eg) =
ddt
Where d = Flux cut by a conductor in one revolution = P wb
dt = Time taken to complete one revolution
since N no. of revolutions are made by the generator per minute, no. of revolutions are made by
the generator per sec = N / 60
1
Time taken to complete one revolution (dt) = = 60/N
(Ns/60)
P P N
Average value of induced EMF / conductor = =
(60/N) 60
The DC generator has Z no. of armature conductors and are divided into A no. of parallel
paths, then no. of conductors per each parallel path is Z/A.
PN Z
Induced EMF per each parallel path = *
60 A
ZN P
Induced EMF (or) Generated EMF (Eg) = *
60 A
Where A = No. of parallel paths = P for lap winding
Electrical Machines-1
=2 for wave winding
2.4. Armature Reaction:
In a d.c. generator, the purpose of field winding is to produce magnetic field (called main
flux)field flux. Now if a d.c machine is operating as a dc generator an e.m.f is induced in the
armature when driven by a prime mover. If I act as a motor then it carry some armature current
passes through the armature conductors. Every current carrying conductor will set up its own
magnetic field, here called as armature magnetic field.
“The effect of the armature flux on the distribution of main field flux is called as
armature reaction”
This results in weakening and disorting the main field flux. This distortion and field weakening
takes place in both generators and motors. The action of armature flux on the main flux is known
as armature reaction.
• The geometrical neutral axis (G.N.A.) is the axis that bisects the angle between the
centre line of poles.
• The magnetic neutral axis (M. N. A.) is the axis drawn perpendicular to the mean
direction of the flux passing through the centre of the armature. Clearly, no e.m.f. is
produced in the armature conductors along this axis because then they cut no flux. With
no current in the armature conductors, the M.N.A. coincides with G, N. A. as shown in
Fig. In order to achieve sparkless commutation, the brushes must lie along M.N.A.
Concept of Armature Reaction:
➢ To understand the concept of armature reaction, consider a two pole d.c.generator without
any load. Let the main field flux produced by the main field mmf IfNf is along the phasor
OA=ϕf show below
➢ When the dc machine is loaded current flowing through the armature winding these currents
are shown by dot under S pole and X under N pole. These armature current setup armature
flux shown by vertical line OB = ϕa with field unexcited.
➢ if DC machine working as Generator then it is rotated in clockwise direction , if it act as a
motor it rotates in antilock wise direction.
Electrical Machines-1
➢ The path of armature flux is perpendicular to the main field flux in other words the path of
the armature flux cross the main field flux path. Thus the effect of armature flux on the
main field flux is entirely cross magnetizing and it is for the reason that the flux created by
by the armature mmf is called cross flux.
➢ When current flowing through the armature and field winding the resultant flux distribution
is obtained by superimposing the two fluxes shown in fig.3
➢ It is seen that the armature flux aids the main flux at the upper end of the N-pole and lower
end of the S –pole, therefore at these two pole ends (tips) the armature flux strengthens the
main field flux. Mean while at the remaining two tips the armature flux weakens the main
field flux . if there is no magnetic saturation then the amount of strengthening and weakening
of main flux are equal and resultant flux remains unaltered from its no load. But in practical
magnetic saturation does not occour as a consequence the strengthening effect is less
compared to the weakening effect and resultant flux decrese from the no load value.this is
called as DEMAGNETISING EFFECT
➢ The GNA(Geometric Neutral Axis ) is always along the q-axis of dc machine.MNA (magnetic
neutral axis) is perpendicular to the resultant field flux.
➢ The MNA at no laod coincides with the GNa at no load. When the DC machine is loaded the
MNA is shifted from GNA. This shift depends on the magnitude of armature current. Thus
greater the magnitude of armature current more will be shifting of the MNA from GNA.
Electrical Machines-1
The use of a compensating winding considerably increases the cost of a machine and is justified
only for machines intended for severe service e.g., for high speed and high voltage machines
Note. When a conductor passes a pair of poles, one cycle of voltage is generated. We say one
cycle contains 360 electrical degrees. Suppose there are P poles in a generator. In one
revolution, there are 360 mechanical degrees and 360 *P/2 electrical degrees.
Electrical Machines-1
2.4.4.Cross-Magnetizing Ampere-Turns Per Pole (ATc/Pole)
We now calculate the cross-magnetizing ampere-turns per pole (ATc/pole).
(found as above)
Cross-magnetizing ampere-turns/pole are
2.5.Commutation:
The fig shows the schematic diagram of 2-pole lap-wound generator. There are two
parallel paths between the brushes. Therefore, each coil of the winding carries one half (Ia/2 in
this case) of the total current (Ia) entering or leaving the armature
Note that the currents in the coils connected to a brush are either all towards the brush
(positive brush) or all directed away from the brush (negative brush). Therefore, current in a
coil will reverse as the coil passes a brush. This reversal of current as the coil passes & brush is
called commutation. The reversal of current in a coil as the coil passes the brush axis is called
commutation.
When commutation takes place, the coil undergoing commutation is short circuited by
the brush. The brief period during which the coil remains short circuited is known as
commutation period Tc. If the current reversal is completed by the end of commutation
period, it is called ideal commutation. If the current reversal is not completed by that time, then
Electrical Machines-1
sparking occurs between the brush and the commutator which results in progressive damage to
both.
2.5.1.Ideal commutation
Let us discuss the phenomenon of ideal commutation (i.e., coil has no inductance) in one
coil in the armature winding shown in Fig.. For this purpose, we consider the coil A. The brush
width is equal to the width of one commutator segment and one mica insulation.
Suppose the total armature current is 40 A. Since there are two parallel paths, each coil
carries a current of 20 A
• In Fig (i), the brush is in contact with segment 1 of the commutator. The commutator
segment 1 conducts a current of 40 A to the brush; 20 A from coil A and 20 A from the
adjacent coil as shown. The coil A has yet to undergo commutation.
• As the armature rotates, the brush will make contact with segment 2 and thus short-circuits
the coil A as shown in Fig. (ii). There are now two parallel paths into the brush as long as the
short-circuit of coil A exists. Fig (ii) shows the instant when the brush is one-fourth on
segment 2 and three-fourth on segment 1. The brush again conducts a current of 40 A; 30 A
through segment 1 and 10 A through segment 2. Note that current in coil A (the coil
undergoing commutation) is reduced from 20 A to 10 A.
• Fig. (iii) shows the instant when the brush is one-half on segment 2 and one-half on segment
1. The brush again conducts 40 A; 20 A through segment 1 and 20 A through segment 2 (Q
now the resistances of the two parallel paths are equal). Note that now. current in coil A is
zero.
Electrical Machines-1
• Fig. (iv) shows the instant when the brush is three-fourth on segment2 and one-fourth on
segment 1. The brush conducts a current of 40 A; 30 A through segment 2 and 10 A through
segment 1. Note that current in coil A is 10 A but in the reverse direction to that before the
start of commutation.
• Fig. (v) shows the instant when the brush is in contact only with segment 2. The brush again
conducts 40 A; 20 A from coil A and 20 A from the adjacent coil to coil A. Note that now
current in coil A is 20 A but in the reverse direction. Thus the coil A has undergone
commutation. Each coil undergoes commutation in this way as it passes the brush axis. Note
that during commutation, the coil under consideration remains short circuited by the brush.
Above Fig. shows the current-time graph for the coil A undergoing commutation. The
horizontal line AB represents a constant current of 20 A upto the beginning of commutation.
From the finish of commutation, it is represented by another horizontal line CD on the
opposite side of the zero line and the same distance from it as AB i.e., the current has exactly
reversed (- 20 A). The way in which current changes from B to C depends upon the
conditions under which the coil undergoes commutation. If the current changes at a uniform
rate (i.e., BC is a straight line), then it is called ideal commutation as shown in Fig.Under
NOTE:
The ideal commutation cannot be attained in practice. This is mainly due to the fact that the
armature coils have appreciable inductance. When the current in the coil undergoing
commutation changes, self-induced e.m.f. is produced in the coil. This is generally called
reactance voltage. This reactance voltage opposes the change of current in the coil
undergoing commutation.
such conditions, no sparking will take place between the brush and the commutator
This reactance voltage makes commutation occurs more slowly than it would be under ideal
commutation.
This is illustrated in Fig. The straight line RC represents the ideal commutation whereas
the curve BE represents the change in current when self-inductance of the coil is taken into
account. Note that current
CE (= 8A in 2.9) is flowing from the commutator segment 1 to the brush at the instant
when they part company. This results in sparking just as when any other current carrying circuit
is broken. The sparking results in overheating of commutator brush contact and causing
damage to both..
Electrical Machines-1
The commutation period is very small, say of the order of 1/500 second
Let the current in the coil undergoing commutation change from + I to - I (amperes) during the
commutation. If L is the inductance of the coil, then reactance voltage is given by
𝑑𝑖 2𝑖
Ec = Lc 𝑑𝑡 or Ec = Lc𝑇𝑐
2.5.3.Methods of Improving Commutation
To make the commutation satisfactory we have to make sure that the current flowing
through the coil completely reversed during the commutation period attains its full value.
There are three main methods of improving commutation. These are
1.Resistance commutation
2.E.M.F. commutation
3.Compensating windings
1.Resistance Commutation
In this method of commutation we use high electrical resistance brushes for getting spark
less commutation. This can be obtained by replacing low resistance copper brushes with high
resistance carbon brushes.
Electrical Machines-1
We can clearly see from the picture that the current IC from the coil C may reach to the brush in
two ways in the commutation period. One path is direct through the commutator segment b
and to the brush and the 2nd path is first through the short-circuit coil B and then through the
commutator segment a and to the brush. When the brush resistance is low, then the current
IC from coil C will follow the shortest path, i.e. the 1st path as its electrical resistance is
comparatively low because it is shorter than the 2nd path.
When high resistance brushes are used, then as the brush moves towards the commutator
segments, the contact area of the brush and the segment b decreases and contact area with
the segment a increases. Now, as the electrical resistance is inversely proportional to the
contact area of then resistance Rb will increase and Ra will decrease as the brush moves. Then
the current will prefer the 2nd path to reach to the brush. Thus by this method of improving
commutation, the quick reversal of current will occur in the desired direction.
2. E.M.F. Commutation::
The main reason of the delay of the current reversing time in the short circuit coil during
commutation period is the inductive property of the coil. In this type of commutation, the
reactance voltage produced by the coil due to its inductive property, is neutralized by
producing a reversing emf in the short circuit coil during commutation period.
Reactance Voltage:
The voltage rise in the short circuit coil due to inductive property of the coil, which opposes
the current reversal in it during the commutation period, is called the reactance voltage.
We can produce reversing emf in two ways
i.By brush shifting.
ii.By using inter-poles or commutating poles.
3.Compensating Windings
This is the most effective mean of eliminating the problem of armature reaction and flash
over by balancing the armature mmf. Compensating windings are placed in slots provided in
pole faces parallel to the rotor (armature) conductors.
The major drawback with the compensating windings is that they very costly. Their use is
mainly for large machines subject to heavy overloads or plugging and in small motors subject to
sudden reversal and high acceleration.
Electrical Machines-1
iii.Self-excited DC Generators
Electrical Machines-1
These are the generators whose field magnets are energized by the current supplied by
themselves. In these type of machines field coils are internally connected with the armature. Due to
residual magnetism some flux is always present in the poles. When the armature is rotated some emf
is induced. Hence some induced current is produced. This small current flows through the field coil as
well as the load and thereby strengthening the pole flux. As the pole flux strengthened, it will produce
more armature emf, which cause further increase of current through the field. This increased field
current further raises armature emf and this cumulative phenomenon continues until the excitation
reaches to the rated value. According to the position of the field coils the Self-excited DC generators
may be classified as…
A. Series wound generators
B. Shunt wound generators
C. Compound wound generators
The generators in which shunt field winding is in parallel with both series field and armature
winding as shown in figure.
Shunt field current, Ish=V/Rsh
Armature current, Ia= series field current,
Isc= IL+Ish Voltage across the load,
V=Eg-Ia Ra-Isc Rsc=Eg-Ia (Ra+Rsc) [∴Ia=Ics]
Power generated, Pg= Eg×Ia
Power delivered to the load, PL=V×IL
In a compound wound generator, the shunt field is stronger than the series field. When the series field
assists the shunt field, generator is said to be commutatively compound wound.
On the other hand if series field opposes the shunt field, the generator is said to be differentially
compound wound
• At rated speed, the voltage across the armature due to residual magnetism is small, E 1 as
shown in the figure. But this voltage is also across the field circuit whose resistance is R f Thus,
the current which flows in the field circuit I1, is also small.
Electrical Machines-1
• When I1 flows in the field circuit of the generator ,an increase in m.m.f results. That is I fTf
increase.
• Voltage E2 is now impressed across the field, causing a large current I2 to flow in the field
circuit. I2Tf is an increased m.m.f., which produces generated voltage E3·
• E3 yields I3 in the field circuit, producing E4. But E4 causes I4 to flow in the field producing
E5 ;and so on, up to E8, the maximum value,…
• The process continues until that point where the field resistance line crosses. the
magnetization curve in Fig. Here the process stops. The induced voltage produced, when
impressed across the field circuit, produces a current flow that in turn produces an induced
voltage of the same magnitude. Eg. as shown in the figure.
Note:: The maximum field circuit resistance (for a given speed) with which the shunt generator would just
excite is known as its critical field resistance
An external characteristic curve shows the relation between terminal voltage (V) and the load current
(IL). Terminal voltage V is less than the generated emf Eg due to voltage drop in the armature circuit.
Therefore, external characteristic curve lies below the internal characteristic curve. External characteristics
are very important to determine the suitability of a generator for a given purpose. Therefore, this type of
characteristic is sometimes also called as performance characteristic or load characteristic.
The curve which gives the relation between field current (If) and the generated voltage (E0) in the
armature on no load is called magnetic or open circuit characteristic of a DC generator. The plot of this curve
Electrical Machines-1
is practically same for all types of generators, whether they are separately excited or self-excited. This curve
is also known as no load saturation characteristic curve of DC generator.
Let us consider a separately excited DC generator giving its no load voltage E0 for a constant field
current. If there is no armature reaction and armature voltage drop in the machine then the voltage will
remain constant. Therefore, if we plot the rated voltage on the Y axis and load current on the X axis then the
curve will be a straight line and parallel to X-axis as shown in figure below. Here, AB line indicating the no
load voltage (E0).
When the generator is loaded then the voltage drops due to two main reasons-
1. Due to armature reaction,
2. Due to ohmic drop (IaRa).
II. Internal or Total Characteristics:
Therefore, the same current flows through armature winding, field winding and the load. Let, I = I a = Isc = IL
Here, Ia = armature current
Isc = series field current
IL = load current
There are three most important characteristics of series wound DC generator which is discussed below
Due to residual magnetism the curves start from a point A slightly up from the origin O. The upper
portions of the curves are bend due to saturation. The external load resistance of the machine needs to be
maintained greater than its critical value otherwise the machine will not excite or will stop running if it is
already in motion. AB, AC and AD are the slops which give critical resistances at speeds N 1, N2 and N3. Here,
N 1 > N 2 > N 3.
Electrical Machines-1
Critical Load Resistance of Shunt Wound DC Generator is the minimum external load resistance which is
required to excite the shunt wound generator.
The terminal voltage can always be maintained constant by adjusting the of the load terminal. When the load
resistance of a shunt wound DC generator is decreased, then load current of the generator increased as
shown in above figure. But the load current can be increased to a certain limit with (upto point C) the
decrease of load resistance. Beyond this point, it shows a reversal in the characteristic. Any decrease of load
resistance, results in current reduction and consequently, the external characteristic curve turns back as
shown in the dotted line and ultimately the terminal voltage becomes zero. Though there is some voltage due
to residual magnetism.
We know, Terminal voltage
Electrical Machines-1
Now, when IL increased, then terminal voltage decreased. After a certain limit, due to heavy load current and
increased ohmic drop, the terminal voltage is reduced drastically. This drastic reduction of terminal voltage
across the load, results the drop in the load current although at that time load is high or load resistance is
low.
That is why the load resistance of the machine must be maintained properly. The point in which the
machine gives maximum current output is called breakdown point. point C in the picture).
Applications:
o They are used for supplying field excitation current in DC locomotives for regenerative breaking.
o This types of generators are used as boosters to compensate the voltage drop in the feeder in various
types of distribution systems such as railway service.
o In series arc lightening this type of generators are mainly used
The latter is rarely used in practice. Therefore, we shall discuss the characteristics of cumulatively-
compounded generator. It may be noted that external characteristics of long and short shunt compound
generators are almost identical.
External characteristic
Fig. shows the external characteristics of a cumulatively compounded generator. The series excitation aids
the shunt excitation. The degree of compounding depends upon the increase in series excitation with the
increase in load current
Electrical Machines-1
(i) If series winding turns are so adjusted that with the increase in load current the terminal voltage
increases, it is called over-compounded generator. In such a case, as the load current increases, the
series field m.m.f. increases and tends to increase the flux and hence the generated voltage. The
increase in generated voltage is greater than the IaRa drop so that instead of decreasing, the terminal
voltage increases as shown by curve A.
(ii) If series winding turns are so adjusted that with the increase in load current, the terminal voltage
substantially remains constant, it is called flat-compounded generator. The series winding of such a
machine has lesser number of turns than the one in over-compounded machine and, therefore, does
not increase the flux as much for a given load current. Consequently, the full-load voltage is nearly
equal to the no-load voltage as indicated by curve B
(iii) If series field winding has lesser number of turns than for a flat-compounded machine, the
terminal voltage falls with increase in load current as indicated by curve C m Fig. (3.14). Such
a machine is called under-compounded generator.
Applications of Compound Wound DC Generators
Among various types of DC generators, the compound wound DC generators are most widely used
because of its compensating property. Depending upon number of series field turns, the cumulatively
compounded generators may be over compounded, flat compounded and under compounded. We can get
desired terminal voltage by compensating the drop due to armature reaction and ohmic drop in the in the
line. Such generators have various applications.
o Cumulative compound wound generators are generally used for lighting, power supply purpose and
for heavy power services because of their constant voltage property. They are mainly made over
compounded.
o Cumulative compound wound generators are also used for driving a motor.
o For small distance operation, such as power supply for hotels, offices, homes and lodges, the flat
compounded generators are generally used.
o The differential compound wound generators, because of their large demagnetization armature
reaction, are used for arc welding where huge voltage drop and constant current is required.
Electrical Machines-1
2. To connect the 2 generators with the 1 existing working generators, first we have to bring the speed
of the prime mover of the 2nd generator to the rated speed. At this point switch S 4 is closed
3. The circuit breaker V2 (voltmeter) connected across the open switch S2 is closed to complete the
circuit. The excitation of the generator 2 is increased with the help of field rheostat till it
generates voltage equal to the voltage of bus-bars.
4. The main switch S2 is then closed and the generator 2 is ready to be paralleled with existing
generator. But at this point of time generator 2 is not taking any load as its induced e.m.f. is equal to
bus-bar voltage. The present condition is called floating, that means ready for supply but not
supplying current to the load.
5. In order to deliver current from generator 2, it is necessary that its induced e.m.f. E should be greater
than the bus-bars voltage V. By strengthening the field current, the induced e.m.f. of generator 2
could be improved and the current supply will get started. To maintain bus-bar voltage, the field of
generator 1 is weakened so that value remains constant.
Field current I given by
The value of current output depends upon the values of E1 and E3 which could be managed by field rheostats
to keep the bus-bars voltage constant.
Precautions During Parallel Connection
o The specification of each generator is different from one another. When they are synchronized
together, their speed are locked into the overall speed of the system.
o The entire load of the system should be distributed in all the generators.
o There should be a controller for keeping check on parameters of the engine. This can be done with
modern digital controllers which are available in market.
o Voltage regulation in the whole system plays an important role. In case of voltage drop in one unit
compare with other units, end up bearing the whole voltage load of the system of parallel
generators.
o While connecting terminals to the bus-bars, extra precaution should be made. If generator is
connected with wrong polarity of the bar, it may result to a short circuit.
The parallel arrangement of DC series generators:
The two DC series motors are disconnected from the supply mains and are connected in parallel to the
resistors. During braking the motors continue to run due to kinetic energy of train and act as self excited dc
series generators generating emfs. The kinetic energy is converted in to heat and dissipated in the resistors.
This is how DC series generators work while operating in parallel.
Without Equalizing Bar:
Let two DC machines (I and II) of resistance R (the armature and field resistance), induced emfs E1 and E2
operate in parallel, as shown in the first figure.
When the induced emfs E1 and E2 are equal they will share the equal load. There is a problem when
the induced emfs are different in two machines. When one of the induced emf becomes greater than another
induced emf a circulating current will flow. If E1 becomes slightly greater than E2, then a current i will
circulate in clockwise direction, as shown by dotted lines in the first figure. The magnitude of the circulating
current i will be (E1-E2)/R .
Now total current supplied by machine I will be (I + i) and of machine II (I - i). So the series field
current of machine I increases, also characteristic of a DC series generator is a rising characteristics. Thus the
induced emf of machine I (E1) will rise and induced emf of machine II will fall. Thus the difference of the two
induced emfs E1 am E2 will increase, which will cause further increase in circulating current. Thus the effect is
cumulative and if there were no fuse or automatic switch in the circuit, the current it machine II will be
reversed. This would reverse the direction of induced emf E2 and resultant emf in the circuit would be [E - (-
E2)] i.e. (E1 + E2) and circulating current (E1+ E2)/2R.
Thus the two emfs will then act in series around a circuit of very low resistance and conditions are
virtually those of a short-circuit on the two machines resulting in damage of the machines. We have to avoid
this short circuit problem for the parallel operation of DC series generators.
Electrical Machines-1