Hadi Saadat
Hadi Saadat
                                    •
 A1so Available from McGraw-Hill
A Schaum's Outline plus the power ofMathcad® software. Use your computer to learn the theory
and solve problems-every number, formula, and graph can be changed and calculated on screen.
Eleetrtc Circuits
Feedback & Control Sysfems
Electromagneties
College Physics
Available at most college bookstores, or for a complete list oftitles and prices, write to:
                          w.WCB
                          _McGraw-Hill
Boston Burr Ridge, IL Dubuque, lA Madison, WI New York San Francisco St. Louis
                Bangkok Bogotá Caracas Lisbon London Madrid
     Mexico City Milan New Delhi Seoul Singapore Sydney Taipei Toronto
WCBlMcGraw-Hill
     A Division of The McGraw-Hill Companies
Copyright © 1999 by The McGraw-Hill Companies, Inc. AH rights reserved. Printed in the United States
of America. Except as permitted under the United States Copyright Act of 1976, no part of this
publication may be reproduced or distributed in any form or by any means, or stored in a data base or
retrievaJ system, without the prior written permission of the publisher.
Disclaimer: The McGraw-Hill Companies make no warranties, either expressed or implied, regarding the
enclosed computer software package, its merchantability, or its fitness for any particular purpose. The
exclusion of implied warranties is not permitted by sorne states. The exclusion may not apply to you. This
waranty provides you with specific legaJ rights. There may be other rights that you may have which may
vary from state to state.
1234567890 DOCDOC9432109
PIN 012235-0
Set ISBN 0-07-561634-3
                                                                  \       I   •           ,
                                                                      \ •.J . (   ~   ¡
Saadat Hadi.
          t
http://www.mhhe.com
                                                   CONTENTS
PREFACE xv
2 BASIC PRINCIPLES                                                     14
  2.1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . .   14
  2.2 POWER IN SINGLE-PHASE AC CIRCUITS . . . . . . . . . ..           15
  2.3 COMPLEX POWER . . . . . . . . . . . . . . . . . . . . . . ..     19
  2.4 THE COMPLEX POWER BALANCE. . . . . . . . . . . . . ..            21
  2.5 POWER FACTOR CORRECTION. . . . . . . . . . . . . . . ..          23
  2.6 COMPLEX POWER FLOW . . . . . . . . . . . . . . . . . . ..        26
  2.7 BALANCED THREE-PHASE CIRCUITS. . . . . . . . . . . ..            30
  2.8 Y-CONNECTED LOADS . . . . . . . . . . . . . . . . . . . . .      32
  2.9 a-CONNECTED LOAD S . . . . . . . . . . . . . . . . . . . ..      34
  2.10 a-y TRANSFORMATION . . . . . . . . . . . . . . . . . . ..       35
  2.11 PER-PHASE ANALYSIS. . . . . . . . . . . . . . . . . . . . ..    36
  2.12 BALANCEDTHREE-PHASEPOWER . . . . . . . . . . . . ..             37
                                                                       vii
vüi   CONTENTS
ties for power systems research and open up new opportunities to young power
engmeers.
    • Generation
    • Transmission and Subtransmission
    • Distribution
    • Loads
1.3.1   GENERATION
Generators - One of the essential components of power systems is the three-
phase ac generator known as synchronous generator or alternator. Synchronous
generators have two synchronously rotating fields: One field is produced by the
rotor driven at synchronous speed and excited by dc current. The other field is pro-
duced in the stator windings by the three-phase armature currents. The de current
for the rotor windings is provided by excitation systems. In the older units, the ex-
citers are de generators mounted on the same shaft, providing excitation through
slip rings. Today's systems use ac generators with rotating rectifiers, known as
brushless excitation systems. The generator excitation system maintains generator
voltage and controls the reactive power fiow. Because they lack the commutator,
ac generators can generate high power at high voltage, typically 30 kV. In a power
plant, the size of generators can vary from 50 MW to 1500 MW.
      The source of the mechanical power, eommonly known as the prime mover,
may be hydraulic turbines at waterfalls, steam turbines whose energy comes from
the burning of coal, gas and nuclear fuel, gas turbines, or occasionally internal com-
bustion engines burning oil. The estimated installed generation capacity in 1998 for
the United States is presented in Table 1.1.
      Stearn turbines operate al relatively high speeds of 3600 or 1800 rpm. The
generators to which they are coupled are eylindrical rotor, two-pole for 3600 rpm or
four-pole for 1800 rpm operation. Hydraulic turbines, particularly those operating
with a low pressure, operate at low speed. Their generators are usually a salient
type rotor with many poles. In a power station several generators are operated in
parallel in the power grid to provide the total power needed. They are connected at
a common point called a bus.
                                                      1.3. MODERN POWER SYSTEM     5
    Today the total installed electric generating capacity is about 760,000 MW.
Assuming the United States population to be 270 million,
                             .          .     760 X 109
              Installed capaclty per caplta = 270 x 106 = 2815 W
      The annual kWh consumption in the United States is about 3, 550 x 109 kWh.
The asset of the investment for investor-owned companies is about 200 billion dol-
lars and they employ close to a half million people.
       With today's emphasis on environmentaI consideration and conservation of
fossil fuels, many alternate sources are considered for employing the untapped
energy sources of the sun and the earth for generation of power. Sorne of these
alternate sources which are being used to sorne extent are solar power, geothermal
power, wind power, tidal power, and biomass. The aspiration for bulk generation
of power in the future is the nuclear fusiono If nuclear fusion is harnessed economi-
cally, it would provide clean energy from an abundant source of fuel, namely water.
      The insulation requirements and other practical desígn problems limít the
generated voltage to low values, usually 30 kV. Thus, step-up transformers are
used for transmission of power. At the receiving end of the transmission lines step-
down transformers are used to reduce the voltage to suitable values for distribution
or utilízation. In a modem utilíty system, the power may undergo four or five trans-
formations between generator and ultimate user.
1.3.3   DISTRIBUTION
The distribution system is that part which connects the distribution substations to
the consumers' service-entrance equipment. The primary distribution lines are usu-
ally in the range of 4 to 34.5 kV and supply the load in a well-defined geographical
area. Sorne small industrial customers are served directly by the primary feeders.
      The secondary distribution network reduces the voltage for utilization by
commercial and residential consumers. Lines and cables not exceeding a few hun-
                                                                           1.3. MODERN POWER SYSTEM   7
    HV
 Substation
            t-                       -           HV
                                              Substation
                                                                                           HV
                                                                                        Substation
          I
              S
              u
                           ~
                                                                   I
                                                                           ~
                                                                                             I
                                                                                          Large
              b
                                          '"          /
              t                                                                         Consumers
              r
              a
              n
              s
              m
              i
              s
                                          /                                            69-138 kV
              s            ~ Network                                       ~
              i
              o
              n            Distribution Substations                                        Gas
          I                                   4-34.5 kV                                   Turbine
                                                                               I             I
  Medium
 Consumers                                                                         Distribution
                                      I                        I                   Transformers
                                 ~                                     ~           Residential
                                                                                   Consumers
                             ~            ~                ¡               ¡       240/120 V
FIGURE 1.1
Basic components of a power system.
8   1. THE POWER SYSTEM: AN OVERVIEW
dred feet in length then deliver power to the individual consumers. The secondary
distribution serves most of the customers at levels of 240/120 V, single-phase,
three-wire; 208Y/120 V, three-phase, four-wire; or 480Y/277 V, three-phase, four-
wire. The power for a typical home is derived from a transformer that reduces the
primary feeder voltage to 240/120 V using a three-wire lineo
      Distribution systems are both overhead and underground. The growth of un-
derground distribution has been extremely rapid and as much as 70 percent of new
residential construction is served underground.
1.3.4   LOADS
Loads of power systems are divided into industrial, commercial, and residential.
Very large industrial loads may be served from the transmission system. Large
industrial loads are served directly from the subtransmission network, and small
industrial loads are served from the primary distribution network. The industrial
loads are composite loads, and induction motors form a high proportion of these
load. These composite loads are functions of voltage and frequency and form a
major part of the system load. Commercial and residential loads consist largely
of lighting, heating, and cooling. These loads are independent of frequency and
consume negligibly small reactive power.
      The real power of loads are expressed in terms of kilowatts or megawatts.
The magnitude of load varies throughout the day, and power must be available to
consumers on demando
      The daily-Ioad curve of a utility is a composite of demands made by various
c1asses of users. The greatest value of load during a 24-hr period is called the peak
or maximum demando Smaller peaking generators may be commissioned to meet
the peak load that occurs for only a few hours. In order to assess the usefulness
of the generating plant the load factor is defined. The load factor is the ratio of
average load over a designated period of time to the peak load occurring in that
periodo Load factors may be given for a day, a month, or ayear. The yearly, or
annual load factor is the most useful since ayear represents a full cyc1e of time.
The daily load factor is
                          Dail L.F. = average load                             (1.1)
                              y        peak load
Multiplying the numerator and denominator of (1.1) by a time period of 24 hr, we
have
    Daily L.F. = average load x 24 hr    energy consumed during 24 hr
                                                                           (1.2)
                  peak load x 24 hr            peak load x 24 hr
The annualload factor is
                                _ total annual energy
                   Annua1 L ..
                             F - --------'--                               (1.3)
                                  peak load x 8760 hr
                                                        1.3. MODERN POWER SYSTEM      9
      Generally there is diversity in the peak load between different c1asses ofloads,
which improves the overall system load factor. In order for a power plant to operate
economically, it must have a high system load factor. Today's typical system load
factors are in the range of 55 to 70 percent.
      There are a few other factors used by utilities. Utilization factor is the ratio of
maximum demand to the installed capacity, and plant factor is the ratio of annual
energy generation to the plant capacity x 8760 hr. These factors indicate how well
the system capacity is utilized and operated.
      A MATLAB function barcycle(data) is developed which obtains a plot of the
load cyc1e for a given intervalo The demand interval and the load must be defined
by the variable data in a three-column matrix. The first two columns are the de-
mand interval and the third column is the load value. The demand interval may be
minutes, hours, or months, in ascending order. Hourly intervals must be expressed
in military time.
Example 1.1
The daily load on a power system varies as shown in Table 1.2. Use the barcycle
function to obtain a plot of the daily load curve. Using the given data compute the
average load and the daily load factor (Figure 1.2).
          Interval, hr Load,MW
      12 A.M. - 2 A.M.     6
       2       - 6         5
       6           9      10
       9       - 12       15
      12 P.M. - 2 P.M.    12
       2       - 4        14
       4       - 6        16
       6           8      18
       8        -10                16
      10      - 11                 12
      11      - 12 A.M.             6
The followmg commands
data = [ O       2       6
         2       6       5
         6       9      10
            9   12      15
           12   14      12
10    1. THE POWER SYSTEM: AN OVERVIEW
           14 16 14
           16 18 16
           18 20 18
           20 22 16
           22 23 12
           23 24   6];
P = data(: ,3);                         % Column array of load
Dt = data(:, 2) - data(:,l); % Column array of demand interval
W ,,;, P'*Dt;             %Total energy, area under the curve
Pavg = W/sum(Dt)                                %Average load
Peak = max (P)                                     % Peak load
LF = Pavg/Peak*100                       % Percent load factor
barcycle (data)                         % Plots the load cycle
xlabel('Time, hr'), ylabel('P, MW')
result in
         18
         16
         14
 P,      12
MW 10
            8
            6
            40              5       10              15   20   25
                                         Time, hr
FIGURE 1.2
Daily load cycle for Example 1.1.
       Pavg      =   11.5417
       Peak      =   18
       LF            64.12
                                                        1.4. SYSTEM PROTECfION   11
     • Balanced fault
     • Symmetrical components and unbalanced fault
     • Stability studies
     • Power system control
       Many MATLAB functions are developed for the aboye studies thus allowing
the student to concentrate on analysis and design of practical systems and spend
less time on programming.
PROBLEMS
1.1. The demand estimation is the starting point for planning the future electric
     power supply. The consistency of demand growth over the years has led
     to numerous attempts to tit mathematical curves to this trend. One of the
     simplest curves is
                                      P     Poea(t-to )
       where a is the average per unit growth rate, P is the demand in year t, and
       Po is the given demand at year too
       Assume the peak power demand in the United States in 1984 is 480 GW with
       an average growth rate of 3.4 percent. Usíng MATLAB, plot the predicated
       peak demand in GW from 1984 to 1999. Estímate the peak power demand
       for the year 1999.
1.2. In a certain country, the energy consumption is expected to double in 10
     years. Assuming a simple exponential growth given by
                                          P = Poe at
       calculate the growth rate a.
CHAPTER
       2
BASIC PRINCIPLES
2.1   INTRODUCTION
The concept of power is of central importance in electrical power systems and is
the main topic of this chapter. The typical student will already have studied much
of this material, and the review here will serve to reinforce the power concepts
encountered in the electric circuit theory.
      In this chapter, the ftow of energy in an ac circuit is investigated. By using
various trigonometric identities, the instantaneous power p(t) is resolved into two
components. A plot of these components is obtained using MATLAB to observe that
ac networks not only consume energy at an average rate, but also borrow and retum
energy to its sources. This leads to the basic definitions of average power P and
reactive power Q. The volt-ampere S, which is a mathematical formulation based
on the phasor forms of voltage and current, is introduced. Then the complex power
balance is demonstrated, and the transmission inefficiencies caused by loads with
low power factors are discussed and demonstrated by means of several examples.
      Next, the transmission of complex power between two voltage sources is con-
sidered, and the dependency of real power on the voltage phase angle and the de-
pendency of reactive power on voltage magnitude is established. MATLAB is used
convenientIy to demonstrate this idea graphically.
      Finally, the balanced three-phase circuit is examined. An important property
of a balanced three-phase system is that it delivers constant power. That is, the
14
                                             2.2. POWER IN SINGLE-PHASE AC ClRCUITS     15
  power delivered does not fluctuate with time as in a single-phase system. For the
  purpose of analysis and modeling, the per-phase equivalent circuit is developed for
  the three-phase system under balanced condition.
             i(t)
 +
v(t)
 FIGURE 2.1
 Sinusoidal source supplying a load.
(2.2)
 The instantaneous power p(t) delivered to the load is the product of voltage v(t)
 and current i(t) given by
 In Example 2.1, MATlAB is used to plot the instantaneous power p(t), and the
 result is shown in Figure 2.2. In studying Figure 2.2, we note that the frequency of
 the instantaneous power is twice the source frequency. AIso, note that it is possible
 for the instantaneous power to be negative for a portion of each cyc1e. In a passive
 network, negative power implies that energy that has been stored in inductors or
 capacitors is now being extracted.
       It is informative to write (2.3) in another form using the trigonometric identity
                                       1               1
                      cosAcosB = 2 cos(A - B)        + '2 cos(A + B)                  (2.4)
16   2. BASIC PRINCIPLES
which results in
                       1
           p(t) =      '2 VmIm[cos(Ov -    Oí) + cos(2wt + Ov + Oí)]
                       1
                   = '2VmIm{COS(Ov - Oí)      + cos[2(wt + Ov)          (Ov - Oí)]}
                       1
                   =   '2 VmIm[cos(Ov -    Oi) + cos 2(wt + Ov) cos(Ov - Oí)
                       +sin 2(wt + Ov) sin(Ov - OdJ
The root-mean-square (nns) value of v(t) is IVI = Vm/v'2 and the nns value of
i(t) is 111 = Im/v'2 . Let 0= (Ov - Oí)' The aboye equation, in tenns ofthe nns
values, is reduced to
     p(t) = IVIIII cos 0[1 + cos 2(wt + Ov)] + IVIIII sin Osin 2(wt + Ov)
            ....                                 I   "                                J
                                Y'                                  v
                              PR(t)                               px(t)                   (2.5)
                        Energy ftow into                 Energy borrowed and
                           the circuit                   returiled by the circuit
where O is the angle between voltage and current, or the impedance angle. O is
positive ifthe load is inductive, (Le., current is lagging the voltage) and Ois negative
if the load is capacitive (i.e., current is leading the voltage).
       The instantaneous power has been decomposed into two components. The
first component of (2.5) is
This is the power absorbed by the resistive component of the load and is also re-
ferred to as the active power or real power. The product of the nns voltage value
and the nns current value IVIIII is called the apparent power and is measured in
units of volt ampere. The product of the apparent power and the cosine of the angle
between voltage and current yields the real power. Because cos Oplays a k.ey role in
the detennination of the average power, it is called power factor. When the current
lags the voltage, the power factor ís considered lagging. When the current leads the
voltage, the power factor is considered leadíng.
      The second component of (2.5)
pulsates with twice the frequency and has an average value of zero. This compo-
nent accounts for power oscillating into and out of the load because of its reactive
element (inductive or capacitive). The amplitude of this pulsating power is called
reactive power and is designated by Q.
Both P and Q have the same dimensiono However, in order to distinguish between
the real and the reactive power, the term "var" is used for the reactive power (var is
an acronym for the phrase "volt-ampere reactive"). For an inductive load, current is
lagging the voltage, O = (Ov - Od > O and Q is positive; whereas, for a capacitive
load, current is leading the voltage, O = (Ov - Od < O and Q is negative.
       A careful study of Equations (2.6) and (2.8) reveals the following character-
istics of the instantaneous power.
   • For apure resistor, the impedance angle is zero and the power factor is unity
     (UPF), so that the apparent and real power are equal. The electric energy is
     transformed into thermal energy.
   • If the circuit is purely inductive, the current lags the voltage by 90° and the
     average power is zero. Therefore, in a purely inductive circuit, there is no
     transformation of energy from electrical to nonelectrical formo The instanta-
     neous power at the terminal of a purely inductive circuit oscillates between
     the circuit and the source. When p(t) is positive, energy is being stored in
     the magnetic field associated with the inductive elements, and when p(t) is
     negative, energy is being extracted from the magnetic fields of the inductive
     elements.
   • If the load is purely capacitive, the current leads the voltage by 90°, and the
     average power is zero, so there is no transformation of energy from electri-
     cal to nonelectrical formo In a purely capacitive circuit, the power oscillates
     between the source and the electric field associated with the capacitive ele-
     ments.
Example 2.1
The supply voltage in Figure 2.1 is given by v( t) = 100 cos wt and the load is
inductive with impedance Z = 1.25L60° n. Determine the expression for the
instantaneous current i(t) and the instantaneous power p(t). Use MATIAB to plot
i(t), v(t), p(t), PR(t), and px(t) over an interval of Oto 271'.
                     1     -    100LO° _     L_   °
                      max -    1.25L600 - 80    60 A
18    2. BASIC PRINCIPLES
50 4000
2000
-50 O
3000 2000
2000 I - - + - - - f - - - \ - - - + - - O
1000 -2000
therefore
The following statements are used to plot the aboye instantaneous quantities and
the instantaneous terms given by (2.6) and (2.8).
Vm = 100; thetav = O;      %Voltage amplitude and phase angle
Z = 1.25; gama = 60;     % Impedance magnitude and phase angle
thetai = thetav - gama;        % Current phase angle in degree
theta = (thetav - thetai)*pi/180;           %Degree to radian
1m = Vm/Z;                                 % Current amplitude
wt = 0:.05:2*pi;                           %wt from O to 2*pi
v = Vm*cos(wt);                        % Instantaneous voltage
                                                                        2.3. COMPLEX POWER   19
The rms voltage phasor of (2.1) and the rms current phasor of (2.2) shown in Fig-
ure 2.3 are
                                                   ~Q           p
FIGURE 2.3
Phasor diagram and power triangle for an inductive load (lagging PF).
S = V1* P+ jQ (2.10)
         I            V
                                                                P
FIGURE 2.4
Phasor diagram and power triangle for a capacitive load (leading PF).
V= ZI (2.11)
From (2.12) it is evident that complex power S and impedance Z have the same
angle. Because the power triangle and the impedance triangle are similar triangles,
the impedance angle is sometimes calIed the power angle.
      Similarly, substituting for I from (2.11) into (2.10) yields
(2.14)
FlGURE2.S
Three loads in parallel.
For the three loads shown in Figure 2.5, the total complex power is given by
Example2.2
In the aboye circuit V = 1200LO° V, Z1 = 60 + jO n , Z2 = 6 + j12 n and
Z3     30 j30 n. Find the power absorbed by each load and the total complex
power.
22    2. BASIC PRINCIPLES
FIGURE 2.6
Current phasor diagram and power plane diagram.
It can be seen from (2.7) that the apparent power will be larger than P if the power
factor is less than 1. Thus the current 1 that must be supplied will be larger for
PF < 1 than it would be for P F         1, even though the average power P supplied
is the same in either case. A larger current cannot be supplied without additional
cost to the utility company. Thus, it is in the power company's (and its customer's)
best interest that major load s on the system have power factors as c10se to 1 as
possible. In order to maintain the power factor close to unity, power companies
install banks of capacitors throughout the network as needed. They also impose an
additional charge to industrial consumers who operate at 10w power factors. Since
industrialloads are inductive and have low lagging power factors, it is beneficial to
install capacitors to improve the power factor. This consideration is not important
for residential and small commercial customers because their power factors are
c10se to unity.
Example2.3
Two 10ads Zl    100 + jO O and Z2      10 + j20 O are connected across a 200-V
nns, 60-Hz source as shown in Figure 2.7.
(a) Find the total real and reactive power, the power factor at the source, and the
total current.
                                                                                           Q
                1               l¡               h                 le
                                                    100        I
Qc
FIGURE 2.7
Circuit for Example 2.3 and the power triangle.
                 1      =   200'::0°    = UO°   A
                    1         100
                 1 -        200'::0° -        _·S A
                    2 -     10 + j20 - 4       J
                 SI = VI;              200'::0°(2 - jO) = 400 W   + jO var
                 S2     =   V 12       200'::0°(4 + jS) =   SOO W + j1600 var
24   2. BASIC PRINCIPLES
Total real power P = 1200 W at the new power factor 0.8 lagging. Therefore
                   Zc
                           1V1 2(200)2
                                        -j57.14 n
                        S~       j700
                            106
                   e = 27f(60)(57.14) 46.42 f.LF
The total power and the new current are
Example2.4
Three loads are connected in parallel across a 1400-V rms, 60-Hz single-phase
supply as shown in Figure 2.8.
(a) Find the total kW, kvar, kVA, and the supply power factor.
                                                           2.5. POWER FACTOR CORRECTION   25
J JI
1400 V 1 2
FIGURE 2.8
Circuit for Example 2.4.
     An inductive load has a lagging power factor, the capacitive load has a lead-
ing power factor, and the resistive load has a unity power factor.
ForLoad 1:
                       8= P       + jQ = 8 1 + 82 + 83
                           =    (35 + j120) + (10 j40) + (15 + JO)
                           =    60 kW + j80 kvar 100L53.13 kVA
(b) A capacitor of negligible resistance is connected in parallel with the aboye loads
to improve the power factor to 0.8 lagging. Determine the kvar rating of this ca-
pacitor and the capacitance in ¡.¡,F.
26    2. BASIC PRINCIPLES
Total real power P = 60 kW at the new power factor of 0.8 lagging results in the
new reactive power Q'.
                               e' =    cos- 1 (0.8) = 36.87°
                              Q'   = 60tan(36.87°) = 45 kvar
Therefore, the required capacitor kvar is
                               Qc = 80 - 45 = 35 kvar
and
                                       IVI 2  14002 _ _ . n
                            Xc         8*c = j35 , 000 - )56
                                           106
                             e=        211"(60)(56) = 47.37 ¡.tF
FIGURE 2.9
1\vo interconnected voltage sources.
Let the phasor voltage be VI =           IVl1Ló 1 and V2 = 1V21Ló2. For the assumed direc-
tion of current
            1    -   IVdLó1 -1V21Ló2 _ IVI Ia _ _ 1"V21 LO                   _
             12 -           IZIL¡              - IZI   1   ¡       IZI   2       ¡
                                                        2.6. COMPLEX POWER FLOW      27
Thus, the real and reactive power at the sending end are
                               2
                 P12   =   lZf cos 1- !VIIZI1!V21 cos(¡. + 61 -
                           !VI 1                                  62 )           (2.16)
Power system transmission lines have small resistance compared to the reactance.
Assuming R = O (i.e., Z = X L90° ), the aboye equations become
(2.18)
(2.19)
Since R = O, there are no transmission line losses and the real power sent equals
the real power received.
      From the aboye results, for a typical power system with small R/ X ratio, the
following important observations are made :
(2.20)
       3. For maintaining transient stability, the power system is usualIy operated with
          smallload angle Ó. Also, from (2.19) the reactive power flow is determined
          by the magnitude difference of terminal voltages, (Le., Q ex: !VII - 1V21).
 Example2.S
 Two voltage sources VI = 120L-5 V and V2 = 100LO V are connected by a short
 line of impedance Z = 1 + j7 n as shown in Figure 2.9. Determine the real and
 reactive power supplied or received by each source and the power los s in the lineo
                       100LO° - 120L 5°
                121                         = 3.135L69.98° A
                               1 + j7
                         1:
                8 12 = V 1 2 376.2L105.02°      -97.5 W + j363.3 var
                8 21 = V2 121 = 313.5L -69.98° = 107.3 W - j294.5 var
  Also, since Ql is positive and Q2 is negative, source 1 delivers 363.3 var and source
• 2 receives 294.5 var, and the reactive power los s in the line is 68.6 varo The reactive
  power 10ss in the line can be ~hecked by
                                    2
                      QL = Xlh21        =   (7)(3.135)2 = 68.8 var
 Example2.6
 This example concems the direction of power flow between two voltage sources.
 Write a MATIAB prograrn for the system of Example 2.5 such that the phase an-
 gle of source 1 is changed from its initial value by ±30° in steps of 5°. Voltage
 magnitudes of the two sources and the voltage phase angle of source 2 is to be kept
 constant. Compute the complex power for each source and the line loss. Tabulate
 the real power and plot PI , P2, and PL versus voltage phase angle ó. The following
 commands
                                          2.6. COMPLEX POWBR FLOW   29
result in
     1000
      800
      600
      400
      200
JaUS     O
     -200
     -400
     -600
     -800
  -1002.
            40      -30         -20        -10      O       10        20        30
                                 Source # 1 Voltage Phase Angle
FIGURE 2.10
Real power versus voltage phase angle o.
Examination of Figure 2.10 shows that the ftow of real power along the intercon-
nection is detennined by the angle difference of the tenninal voltages. Problem 2.9
requires the development of a similar program for demonstrating the dependency
of reactive power on the magnitude difference of tenninal voltages.
ECn
FIGURE 2.11
(a) Positive, or ABC, phase sequence. (b) Negative. or ACB, phase sequence.
                                    EAn   = IEpILO°
                                    EBn   = IEpIL-120°                           (2.21)
                                    ECn   = IEpIL-240°
In power systems, great eare is taken to ensure that the loads of transmission lines
are balanced. For balaneed loads, the terminal voltages of the generator VAn, VBn
and VCn and the phase voltages Van, Vbn and Ven at the load terminals are balanced.
For "phase A," these are given by
FIGURE 2.12
A Y-connected generator supplying a Y-connected load.
                                    Van   = ¡VpILO°
                                    Vbn   = ¡VpIL-120°                        (2.24)
                                    Ven     IVpIL-240°
where ¡Vpl represents the magnitude ofthe phase voltage (line-to-neutral voltage).
     The line voltages al the load terminals in terms of the phase voltages are found
by the application of Kirchhoff's voltage law
 The voltage phasor diagram of the Y-connected loads of Figure 2.12 is shown
in Figure 2.13. The relationship between the line voltages and phase voltages is
demonstrated graphical1y.
                                                      2.8. Y-CONNECTED LOADS   33
FIGURE 2.13
Phasor diagram showing phase and line voltages.
    If the rms value of any of the line voltages is denoted by VL, then one of the
important characteristics of the Y-connected three-phase load may be expressed as
(2.26)
      Thus in the case of Y-connected loads, the magnitude of the line voltage is
v'3 times the magnitude of the phase voltage, and for a positive phase sequence,
the set of line voltages leads the set of phase voltages by 30°.
      The three-phase currents in Figure 2.12 also possess three-phase symmetry
and are given by
(2.27)
                                                                            (2.28)
34   2. BASIC PRINCIPLES
a la
FIGURE 2.14
A ~-connecled load.
     It is clear from the inspection of the circuit that the line voltages are the same
as phase voltages.
                                                                                  (2.29)
Consider the phasor diagram shown in Figure 2.15, where the phase current lab is
arbitrarily chosen as reference. we have
                                     lab     IlpILO°
                                     lbe = IlpIL-120°                            (2.30)
                                     lea = IlpIL-240°
             lbe
FIGURE 2.15
Phasor diagram showing phase and line currenls.
                                                                      2.10. .6.-YTRANSFORMATION   35
     The relationship between phase and Une currents can be obtained by applying
Kirchhoff's current law at the comers of ~.
          la   = lab -lea = Ilpl(L:::O° -
                                     lL-2400) = J31 1pIL-30°
          h = lbe -lab = Ilpl(lL-120° -lLOO) = J311pIL-150°                                   (2.31)
          le = lea - he = Ilpl(lL-240° -lL-1200) = J311pIL90°
 The relationship between the Une currents and phase currents is demonstrated
graphically in Figure 2.15.
      If the rms of any of the Une currents is denoted by h, then one of the impor-
tant characteristics of the ~-connected three-phase load may be expressed as
                                                                                              (2.32)
Thus in the case of ~-connected loads, the magnitude of the line current is J3
times the magnitude of the phase current, and with positive phase sequence, the set
of line currents lags the set of phase currents by 30°.
                                      h       b           e
                    (a)                                                   (b)
FIGURE 2.16
(a) t. to (b) Y-connection.
FIGURE 2.17
Phasor diagram showing phase and Une voltages.
The phasor diagram in Figure 2.17 shows the relationship between balanced phase
and line-to-line voltages. From this phasor diagram, we find
                                     1 _ 3Van
                                      a - Zt1
or
                                          Zt1
                                    Van = ala                              (2.36)
                                                 Zt1
                                      ZY=a                                 (2.38)
Since the neutral carnes no current, a neutral wire of any impedance may be re-
placed by any other impedance, including a short circuit and an open circuito The
retum line may not actually exist, but regardless, a line of zero impedance is in-
c1uded between the two neutral points. The balanced power system problems are
then solved on a "per-phase" basis. It is understood that the other two phases carry
identical currents except for the phase shift.
      We may then look at only one phase, say "phase A," consisting of the source
VAn in series with Z L and Zp, as shown in Figure 2.18. The neutral is taken as
datum and usually a single-subscript notation is used for phase voltages.
FIGURE 2.18
Single-phase circuit for per-phase analysis.
where IVpl and ¡Ipl are the magnitudes of the nns phase voltage and current, re-
spectively. The total instantaneous power is the sum of the instantaneous power of
each phase, given by
                                                                            (2.42)
 Substituting for the instantaneous voltages and currents from (2.40) and (2.41) into
(2.42)
The three double frequency cosine tenns in (2.43) are out of phase with each other
by 120° and add up to zero, and the three-phase instantaneous power is
(2.44)
o=   Ov - Oi is the angle between phase voltage and phase current or the impedance
angle.
      Note that although the power in each phase is pulsating, the total instanta-
neous power is constant and equal to three times the real power in each phase. In-
deed, this constant power is the main advantage of the three-phase system over the
single-phase system. Since the power in each phase is pulsating, the power, then,
is made up of the real power and the reactive power. In order to obtain fonnula
symmetry between real and reactive powers, the concept of complex or apparent
power (8) is extended to three-phase systems by defining the three-phase reactive
power as
                               Q3</> = 3 IVpIIIpI sin O                      (2.45)
Thus, the complex three-phase power is
(2.46)
or
                                                                               (2.47)
     Equations (2.44) and (2.45) are sometimes expressed in tenns of the nns
magnitude of the line voltage and the nns magnitude of the line current. In a Y-
connected load the phase voltage IVpl = IVLI/V3 and the phase current Ip = h.
                                               2.12. BALANCED THREE-PHASE POWER   39
In the 6.-connection Vp = VL and IIpl = Ihl/J3. Substituting for the phase volt-
age and phase currents in (2.44) and (2.45), the real and reactive powers for either
connection are given by
                                                                              (2.48)
and
                                                                              (2.49)
A comparison of the last two expressions with (2.44) and (2.45) shows that the
equation for the power in a three-phase system is the same for either a Y or a 6.
connection when the power is expressed in terms of line quantities.
      When using (2.48) and (2.49) to calculate the total real and reactive power,
remember that eis the phase angle between the phase voltage and the phase current.
As in the case of single-phase systems for the computation of power, it is best to
use the complex power expression in terms of phase quantities given by (2.47).
The rated power is customarily given for the three-phase and rated voltage is the
line-to-line voltage. Thus, in using the per-phase equivalent circuit, care must be
taken to use per-phase voltage by dividing the rated voltage by J3.
Example 2.7
A three-phase line has an impedance of 2 + j4 O as shown in Figure 2.19.
2+j40
FIGURE 2.19
Three-phase circuit diagram for Example 2.7.
The Une feeds two balanced three-phase loads that are connected in parallel. The
first load is Y-connected and has an impedance of 30+ j40 O per phase. The second
load is 6.-connected and has an impedance of 60 j45 O. The line is energized
at the sending end from a three-phase balanced supply of line voltage 207.85 V.
Taking the phase voltage Va as reference, determine:
       (a) The current, real power, and reactive power drawn from the supply.
40    2. BASIC PRINCIPLES
(a) The ~-connected load is transformed into an equivalent Y. The impedance per
phase of the equivalent Y is
                            Z2   = 60       j45 = 20 - j15 O
                                        3
The phase voltage is
                                 VI   = 207.85 = 120 Y
                                          J3
The single-phase equivalent circuit is shown in Figure 2.20.
        1         2+j40
a
                                            +      l¡               12
                                                   300              200
    VI = 120LOoy                         V2
                                                   j400              -j150
n~----------------------~------~
FIGURE 2.20
Single-phase equivalent circuit for Example 2.7.
                               1 = VI = 120LO° = 5 A
                                   Z      24
The three-phase power supplied is
(c) The current per phase in the Y-connected load and in the equivalent Y of the Ll
load is
                       V2        110           .                       °
              l¡   =   Zl   =    30 + j40 = 1-)2     = 2.236L -   63.4 A
The phase current in the original Ll-connected load, Le., 1ab is given by
It is clear that the sum of load powers and line losses is equal to the power delivered
from the supply, Le.,
Example2.8
A three-phase line has an impedance of 0.4 + j2. 7 n per phase. The line feeds two
balanced three-phase loads that are connected in parallel. The first load is absorb-
ing 560.1 kVA at 0.707 power factor lagging. The second load absorbs 132 kWat
unity power factor. The line-to-line voltage at the load end of the line is 3810.5 V.
Determine:
     (a) The magnitude of the line voltage at the source end of the lineo
     (b) Total real and reactive power loss in the lineo
     (c) Real power and reactive power supplied at the sending end of the lineo
42   2. BASIC PRINCIPLES
       1      0.4 + j2.7D.
a~~--~~rn~----~~------~
                                     +     l¡
n~------------------~------~
FIGURE 2.21
Single-phase equivalent diagram for Example 2.8.
                                 V2 = 3810.5 = 2200 V
                                           V3
The single-phase equivalent circuit is shown in Figure 2.21.
The total complex power is
The magnitude of the line voltage at the sending end of the line is
8 S(31/» = 8 R (31/»     + 8 L (31/» = (528 + j396) + (12 + j81) = 540 kW + j477 kvar
                                            2.12. BALANCED THREE-PHASE POWER     43
PROBLEMS
2.1. Modify the program in Example 2.1 such that the following quantities can
     be entered by the user:
     The peak: amplitude Vm , and the phase angle B'IJ of the sinusoidal supply
     v(t) = Vm cos(wt + B'IJ)' The impedance magnitude Z, and the phase angle
     'Y of the load.
     The program should produce plots for i(t), v(t), p(t), Pr(t) and Px(t), sim-
     ilar to Example 2.1. Run the program for Vm = 100 V, B'IJ         O and the
     following loads:
     (a) From Pr(t) and Px(t) plots, estimate the real and reactive power for each
     load. Draw a conclusion regarding the sign of reactive power for inductive
     and capacitive loads.
     (b) Using phasor values of current and voltage, calculate the real and reactive
     power for each load and compare with the results obtained from the curves.
     (c) Ifthe above loads are all connected across the same power supply, deter-
     mine the total real and reactive power taken from the supply.
2.5. Two loads connected in parallel are supplied from a single-phase 240-V rms
     source. The two loads draw a total real power of 400 kW at a power factor
     of 0.8 lagging. One of the loads draws 120 kW at a power factor of 0.96
     leading. Find the complex power of the other load.
2.6.    The load shown in Figure 2.22 consists of a resistance R in parallel with a
        capacitor of reactance X. The load is fed from a single-phase supply through
        a line of impedance 8.4 + jl1.2 O. The rms voltage at the load terminal is
        1200LO° V rms, and the load is taking 30 kVA at 0.8 power factor leading.
        (a) Find the values of R and X.
        (b) Determine the supply voltage V.
8.4 + jl1.2 O
V -jX
FIGURE 2.22
Circuit for Problem 2.6.
       +   1
                  0.8
                                                      8 3 = 5kVA
 200LO° V
                                                      atO.8 PF lag
                             -j16
FlGURE2.23
Circuit for Problem 2.7.
                                            2.12. BALANCED THREB-PHASB POWER      45
       (a) Find the complex powers SI, S2 for the two impedances, and S3 for the
       motor.
       (b) Determine the total power taken from the supply, the supply current, and
       the overall power factor.
       (c) A capacitor is connected in parallel with the loads. Find the kvar and the
       capacitance in JLF to improve the overall power factor to unity. What is the
       new line current?
2.8. Two single-phase ideal voltage sources are connected by atine of impedance
     of 0.7 + j2.4 nas shown in Figure 2.24. VI = 500L16.26° V and V2 =
     585 L0° V. Find the complex power for each machine and determine whether
     they are delivering or receiving real and reactive power. Also, find the real
     and the reactive power loss in the lineo
0.7 + j2.4 n
500L16.26° V 585LO° V
FIGURE 2.24
Circuit for Problem 2.8.
2.9. Write a MATlAB program for the system of Example 2.6 such that the volt-
     age magnitude of source 1 is changed from 75 percent to 100 percent of
     the given value in steps of 1 V. The voltage magnitude of source 2 and the
     phase angles of the two sources is to be kept constant. Compute the complex
     power for each source and the tine loss. Tabulate the reactive powers and
     plot Q 1> Q2, and Q L versus voltage magnitude !VII. From the results, show
     that the flow of reactive power along the interconnection is determined by
     the magnitude difference of the terminal voltages.
2.10. A balanced three-phase source with the following instantaneous phase volt-
      ages
                               Van   = 2500cos(wt)
                               Vbn     2500cos(wt - 120°)
                               Ven   = 2500cos(wt - 240°)
46 2. BASIC PRINCIPLES
2.12. Repeat Problem 2.11 with the same three-phase impedances arranged in a .6.
      connection. Take Vab as reference.
                  1 + j2n
ao-------'\N\
 IVLI =   207.85 V
                                         b
bo-----~~ ~nn~----                    ____<                15 + j18n
Co-----'V\¡'V\t-'
FIGURE 2.25
Circuit for Problem 2.13.
2.14. Three parallel three-phase Ioads are supplied from a 207.85-V rms, 60-Hz
      three-phase supply. The loads are as follows:
       (a) What is the total system kW, kvar, power factor, and the supply current
       per phase?
       (b) What is the system power factor and the supply current per phase when
       the resistive load and induction motor are operating but the capacitor bank is
       switched off?
2.15. Three loads are connected in parallel across a 12.47 kV three-phase supply.
       Load 1: Inductive load, 60 kW and 660 kvar.
       Load 2: Capacitive load, 240 kW at 0.8 power factor.
       Load 3: Resistive load of 60 kW.
       (a) Find the total complex power, power factor, and the supply current.
       (b) A Y-connected capacitor bank is connected in parallel with the loads.
       Find the total kvar and the capacitance per phase in ¡.tF to improve the overall
       power factor to 0.8 lagging. What is the new line current?
IVLI = 346.41 V
                                  b             180
120
FIGURE 2.26
Circuit for Prob1em 2.16.
CHAPTER
       3
GENERATOR AND
TRANSFORMER MODELS;
THE PER-UNIT SYSTEM
3.1 INTRODUCTION
Before the power systems network can be solved, it must first be modeled. The
three-phase balanced system is represented on a per-phase basis, which was de-
scribed in Section 2.10. The single-phase representation is also used for unbalanced
systems by means of symmetrical components which is treated in a later chapter.
In this chapter we deal with the balanced system, where transmission lines are rep-
resented by the 7r model as described in Chapter 4. Other essential components
of a power system are generators and transformers; their theory and construction
are discussed in standard electric machine textbooks. In this chapter, we represent
simple models of generators and transformers for steady-state balanced operation.
      Next we review the one-line diagram of a power system showing generators,
transformers, transmission lines, capacitors, reactors, and loads. The diagram is
usually limited to major transmission systems. As a rule, distribution circuits and
small loads are not shown in detail but are taken into account merely as lumped
loads on substation busses.
48
                                                 3.2. SYNCHRONOUS GENERATORS      49
,,
FIGURE 3.1
Elementary two-pole three-phase synchronous generator.
an air gap flux of 4> per pole and is revolving at constant angular velocity w, the
flux linkage of the coil varíes with the position of the rotor mmfaxis wt, where
wt is measured in electrical radians from coil aa' magnetic axis. The flux linkage
for an N-tum concentrated coil aa' will be maximum (N4)) at wt = O and zero
at wt    1f' /2. Assuming distributed winding, the flux linkage Aa will vary as the
cosine of the angle wt. Thus, the flux linkage with coil a is
Aa = N4>coswt (3.1)
                            ea   = - dA
                                     dt = wNA.'
                                            'f'smwt
                                         = Emax sin wt                        (3.2)
                                                         1f'
                                         = Emax cos(wt - 2')
where
E = 4.44fN<jJ (3.3)
The magnetic field of the rotor revolving at constant speed induces three-phase
sinusoidal voltages in the annature, displaced by 27r /3 radians. The frequency of
the induced annature voltages depends on the speed at which the rotor mns and
on the number of poles for which the machine is wound. The frequency of the
annature voltage is given by
                                         Pn
                                    f    260
                                                                                (3.5)
where n is the rotor speed in rpm, referred to as synchronous speed. During nonnal
conditions, the generator operates synchronously with the power grid. This results
in three-phase balanced currents in the annature. Assuming current in phase a is
lagging the generated emf ea by an angle '!/J, which is indicated by tine mn in
Figure 3.1, the instantaneous annature currents are
                           ia   = I max sin(wt
                           ib = I max sin(wt                                    (3.6)
ie = I max sin(wt
According to (3.2) the generated emf ea is maximum when the rotor magnetic axis
is under phase a. Since ia is lagging ea by an angle '!/J. when line mn reaches
the axis of coil aal , current in phase a reaches its maximum value. At any instant
of time, each phase winding produces a sinusoidally distributed mmf wave with
íts peak along the axis of the phase winding. These sinusoidally distributed fields
can be represented by vectors referred to as space phasors. The amplitude of the
sinusoidalIy distributed mmf fa((}) is represented by the vector Fa along the axis of
phase a. Similarly, the amplitude ofthe mmfs fb((}) and fe((}) are shown by vectors
Fb and Fe along their respective axis. The mmf amplitudes are proportionaI to the
52   3. GENERATOR AND TRANSFORMER MODELS; THB PBR-UNIT SYSTBM
Using the trigonometric identity sin a cos a = (1/2) sin 2a, the above expression
becomes
                         +sin2(wt                 411" )J
                                                       3
The above expression is the sum of three sinusoidal functions displaced from each
other by 211"/3 radians, which adds up to zero, i.e., FI = O.
     The sum of quadrature components results in
 F2 = Fm sin(wt - 'I/J) sin(wt - 'I/J) + Fm sin(wt               'I/J   2;) sin(wt - 'I/J      211")
                                                                                               3
       +Fm sin(wt - 'I/J -       ~) sin(wt -      'I/J
Using the trigonometric identity sin 2 a = (1/2)(1               cos 2a), the above expression
becomes
                    Fm [3 - cos 2(wt - 'I/J) + cos 2(wt2- 1
               F2 = 2                                     'I/J 1 "
                                                               - 3)
                                              411"
                      +cos2(wt-'l/J-          3)J
The sinusoidal terms of the above expression are displaced from each other by
211" /3 radians and add up to zero, with F2 = 3/2Fm. Thus, the amplitude of the
resultant annature mmf or stator mmf becomes
                                              3
                                       Fs =   '2 Fm                                            (3.8)
                                                                            3.2. SYNCHRONOUS GENERATORS   S3
                              \
                                  \
                                      \
                                                                        /
                                                                    /
                                                                /
                                                            /
                                                        /
                                                    /
                                                /
                                          I /
                                            /
                                          I
                             ~--~~~-------------'E
                         /
                     /
                 /
             /
         /
    /'
m
FIGURE 3.2
Combined phasor/vector diagram for one phase of a cylindrical rotor generator.
      We thus conclude that the resultant annature mmf has a constant amplitude
perpendicular to line mn, and rotates at a constant speed and in synchronism
with the field mmf Fr. To see a demonstration of the rotating magnetic field, type
rotfield at the MATlAB prompt.
      A typical synchronous machine field alignment for operation as a generator is
shown in Figure 3.2, using space vectors to represent the various fields. When the
rotor is revolving at synchronous speed and the annature current is zero, the field
rnmf Fr produces the no-load generated emf E in each phase. The no-load gen-
erated voltage which is proportional to the field current is known as the excitatíon
voltage. The phasor voltage for phase a, which is lagging Fr by 90°, is combined
with the mmf vector diagram as shown in Figure 3.2. This combined phasor/vector
diagram leads to a circuit model for the synchronous machine. Jt must be empha-
sized that in Figure 3.2 rnmfs are space vectors, whereas the emfs are time phasors.
When the annature is carrying balanced three-phase currents, Fs is produced per-
pendicular to line mn. The interaction of annature mmf and the field mmf, known
as armature reaction, gives rise to the resultant air gap mmf Fsr . The resultant mmf
Fsr is the vector sum of the field mmf Fr and the annature mmf Fs. The resultant
mmf is responsible for the resultant air gap flux 4>sr that induces the generated emf
on-load, shown by E sr . The annature mmf Fa induces the emf E ar , known as the
armature reaction voltage, which is perpendicular to FIJ. The voltage Ear leads
S4   3. GENERATOR AND TRANSFORMER MODELS; THE PER-UNIT SYSTEM
FIGURE 3.3
Synchronous machine equivalent circuito
                 E                              v
                        rt%~_~{a_---11
     01
FIGURE 3.4
Synchronous machíne connected to an ínfinite bus.
      Figure 3.5 shows the phasor diagram of the generator with tenninal voltage
as referenee for exeitations eorresponding to lagging, unity, and leading power fac-
torso The voltage regulation of an alternator is a figure of merit used for eompari-
E E
                                     ~                           M3>
                            E
la V V
FIGURE 3.5
Synchronous generator phasor diagram.
son with other machines. It is defined as the pereentage ehange in terminal voltage
from no-load to rated load. This gives an indication of the ehange in field eurrent
required to rnaintain system voltage when going frorn no-load to rated load at sorne
specifie power factor.
the no-load voltage. Since this is not a practical method for very large machines,
an accurate analytical method recommended by IEEE as given in reference [43]
may be used. An approximate method that provides reasonable results is to con-
sider a hypothetical linearized magnetization curve drawn to intersect the actual
magnetization curve at rated voltage. The value of E calculated from (3.12) is then
used to find the field current from the linearized curve. Finally, the no-load voltage
corresponding to this field current is found from the actual magnetization curve.
(3.14)
Thus El sin 81 is a constant, and the locus of El is on the line ej. In Figure 3.6,
phasor diagrams are drawn for three armature currents. Application of (3.12) for a
lagging power factor armature current lal results in El. If (J is zero, the generator
operates at unity power factor and armature current has a minimum value, shown
by la2, which results in E2. Similarly, Es is obtained corresponding to laS at a
leading power factor. Figure 3.6 shows that the generation of reactive power can
r
                                3.3. STEADY-STATE CHARACTERISTICS- CYLINDRICAL ROTOR   57
    FIGURE 3.6
    Variation of field current at constant power.
(3.16)
Thus, the real power P3</> and reactive power Q3</> are
                               IEIIVI
                      P3</> = 3--¡z:r cosb' - ó) - 3
                                                         1V12 cos')'             (3.19)
                                                         1Zs1
                               IEIIVI .
                     Q3</> = 3--¡z:r smb' -     ó) - 3
                                                         1V12 sm')'
                                                               .                 (3.20)
                                                         1Zs1
If Ra is neglected, then Zs = jXs and')'      90°. Equations (3.19) and (3.20) reduce
to
Equation (3.21) shows that if IEI and IVI are held fixed and the power angle ó
is changed by varying the mechanical driving torque, the power transfer varies
sinusoidally with the angle ó. From (3.21), the theoretical maximum power occurs
when ó = 90°
                                             IEIIVI
                              Pmax (3</»   = 3~                                  (3.23)
                                                                                 (3.24)
204     6. POWER FLOW ANALYSIS
or in matrix form
    CI - (f¡)(0)                                                                           b.. (O)
                                   (~) (O)                              (~)(O)                 Xl
      C2 -   (12)(0)
                           =
                                   (!!h.) (O)
                                     8Xl
                                                                        (~ )(0)
                                                                          8x n
                                                                                           b.. x (O)
                                                                                                2
or
                                    b..X(k) = [J(k)¡-l b..C(k)                                         (6.19)
and the Newton-Raphson algorithm for the n-dimensional case becomes
                                    X(k+l) = X(k)         + b..X(k)                                    (6.20)
where
                               b.. (k)
                                  Xl
                               b.. X (k)
                                    2
                                                                      [ el -
                                                                        C2 -
                                                                                 (Jl)(k)
                                                                                 (12)(k)
                                                                                           1
             b..X(k)   =                        and     b..C(k)   =                                    (6.21)
                                                                                 ..
                               b.. (k)
                                  Xn
                                                                        en -     (Jn)(k)
       J(k) is called the Jacobian matrix. Elements of this matrix are the partial
derivatives evaluated at X(k). It is assumed that J(k) has an inverse during each
iteration. Newton's method, as applied to a set of nonlinear equations, reduces the
problem to solving a set of linear equations in order to determine the values that
improve the accuracy of the estimates.
       The solution of (6.19) by inversion is very inefficient. It is not necessary
to obtain the inverse of J(k). Instead, a direct solution is obtained by optimally
ordered triangular factorization. In MATLAB, the solution of linear simultaneous
equations b..C = J b..X is obtained by using the matrix division operator \ (i.e.,
b..X = J \ b..C) which is based on the triangular factorization and Gaussian elim-
ination.
486   11. STABILITY
       A    = [O 1 ; -37.705 -2.617] ;
       r    = eig(A)
result in
       r    =
                -1.3   +   6.00i
                -1.3   +   6.00i
      The linearized model for small disturbances is very useful when the system
is extended to include the govemor action and the effect of automatic voltage reg-
ulators in a multimachine system. The linearized model allows the application of
the linear control system analysis and compensation, which will be dealt with in
Chapter 12.
The transient stability studies involve the determination of whether or not synchro-
nism is maintained after the machine has been subjected to severe disturbance.
This may be sudden application of load, loss of generation, los s of large load, or a
fault on the system. In most disturbances, oscillations are of such magnitude that
linearization is not permissible and the nonlinear swing equation must be solved.
      A method known as the equal-area criterion can be used for a quick predic-
tion of stability. This method is based on the graphical interpretation of the energy
stored in the rotating mass as an aid to determine if the machine maintains its sta-
bility after a disturbance. The method is only applicable to a one-machine system
connected to an infinite bus or a two-machine system. Because it provides physi-
cal insight to the dynamic behavior of the machine, application of the method to
analysis of a single machine connected to a large system is considered here.
      Consider a synchronous machine connected to an infinite bus. The swing
equation with damping neglected as given by (11.21) is
                               2
                              d6 =   'Ir   Jo (P.   _ P. )
                              dt2     H         m      e