0% found this document useful (0 votes)
18 views28 pages

MN705

The document is an installation and operating manual for the Baldor BC154/BCWD140 Series NEMA-4X (IP-65) SCR DC Motor Speed and Torque Control, designed for washdown watertight integrity. It includes safety notices, installation instructions, adjustments, start-up procedures, and troubleshooting guidelines. The manual emphasizes the importance of following safety precautions to prevent electrical shock and equipment damage.

Uploaded by

Igur Eui
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
18 views28 pages

MN705

The document is an installation and operating manual for the Baldor BC154/BCWD140 Series NEMA-4X (IP-65) SCR DC Motor Speed and Torque Control, designed for washdown watertight integrity. It includes safety notices, installation instructions, adjustments, start-up procedures, and troubleshooting guidelines. The manual emphasizes the importance of following safety precautions to prevent electrical shock and equipment damage.

Uploaded by

Igur Eui
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 28

NEMA-4X—IP65

for Catalogs BC154 and BCWD140

6/15 Installation & Operating Manual MN705


Any trademarks used in this manual are the property of their respective owners.

Important:
Be sure to check www.baldor.com to download the latest version of this manual in Adobe
Acrobat PDF format.
Table of Contents
Chapter 1
Introduction
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Safety Notice. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Chapter 2
Installation
Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Power Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Armature Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Permanent Magnet (PM Type). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Shunt Wound Motors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
DC Tachometer Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Remote Speed Reference. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Remote Potentiometer (5K). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Analog Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Remote Start/Stop Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Inhibit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Enable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
RUN/FAULT Relay Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Chapter 3
Adjustments & Start-Up
Important Application Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Motor type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Torque requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Acceleration start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Limitation in use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Setting selectable jumpers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
J1 - Speed and torque mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
J2 - Input AC line voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
J3 - Armature Voltage Output and Tachometer Feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
J4 - Armature Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
J5 - Current Limit Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
J6 – Tachometer Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
J7 - Signal Input Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
TRIMPOT ADJUSTMENTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . 3-6
Minimum Speed (MIN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Maximum Speed (MAX). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Acceleration (ACCEL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Deceleration (DECEL). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Current Limit (CL). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
IR Compensation (IR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Timed Current Limit (TCL). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . 3-7
Jog Speed (JOG). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Install Cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Chapter 4
Troubleshooting
LED Indications & Troubleshooting Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Appendix A
Modification for Subfractional HP Motors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1

MN705 i
ii MN705
Chapter 1
General Information
Introduction
Thank you for purchasing the Baldor BC154/BCWD140 Series NEMA-4X (IP-65) SCR DC Motor
Speed and Torque Control. It is designed for applications requiring washdown watertight integrity. Its
housing is ruggedly constructed of die cast aluminum which is protected with an acrylic coating for
the ultimate in corrosion resistance. All switches are sealed with rubber boots and the main speed
potentiometer has a shaft seal.
Short circuit and transient protection are provided for ultimate in reliability. Electronic overload
protection prevents motor burnout and demagnetization of PM motors. The control can be operated
in either the Speed or Torque mode via jumper selection. The current range, which is also jumper
selectable, eliminates the necessity for calibration of IR Compensation and Current Limit for most
applications. AC line voltage 230/115VAC (jumper selectable), DC armature voltage (180/90VDC) and
feedback type may be Armature/Tachometer.
Standard features include armature fusing (fuse sold separately), electronic start/stop switch, and
an LED indicator array for Power On, Stop and Overload. Although factory set for most applications, a
variety of trim pots allow adjustments of parameters.
SAFETY NOTICE
A Warning statement indicates a potentially hazardous situation which, if not avoided, could result in
injury or death.
A Caution statement indicates a potentially hazardous situation which, if not avoided, could result in
damage to property.
A Note indicates additional information that is not critical to the installation or operation.
WARNING: This equipment may contain voltages as high as 1000 volts! Electrical shock can cause serious or
fatal injury. Only qualified personnel should attempt the start-up procedure or troubleshoot this
equipment.
WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power before you
ensure that all grounding instructions have been followed. Electrical shock can cause serious or fatal
injury.
WARNING: Electrical shock can cause serious or fatal injury. Be sure that all power is disconnected and there is
no voltage present from this equipment or equipment to which it is or will be connected. Electrical
shock can cause serious or fatal injury. Only qualified personnel should attempt the installation and
start-up procedures.
WARNING: Electrical shock can cause serious or fatal injury. Verify there is no voltage phase-to-phase or
phaseto- neutral at the motor leads before connecting motor to this control. Motor may have high
voltage present even when disconnected from this control.
WARNING: Do not use motor overload relays with an automatic reset feature. These are dangerous since the
process may injure someone if a sudden or unexpected automatic restart occurs. If manual reset
relays are not available, disable the automatic restart feature using external control wiring.
WARNING: This unit has an automatic restart feature that will start the motor whenever input power is applied
and a RUN (FWD or REV) command is issued. If an automatic restart of the motor could cause injury to
personnel, the automatic restart feature should be disabled.
WARNING: Using a jumper to eliminate the start/stop function will cause the motor to run at the Main Speed
Potentiometer setting when the AC line is applied.
WARNING: If possible, do not adjust trim pots with the main power applied. Electrical shock can cause serious or
fatal injury. If adjustments are made with the main power applied, an insulated adjustment tool must
be used to prevent shock hazard and safety glasses must be worn.
WARNING: Do not use this drive in an explosive environment. An explosion can cause serious or fatal injury. This
drive is not explosion proof.
WARNING: When the Inhibit jumper is installed, the drive and motor will start and run when AC power is applied,
when power is restored after a momentary power loss, or after an overload or TCL fault is reset. The
user must ensure that automatic start up of the driven equipment will not cause injury to operating
personnel or damage to the driven equipment. The user is responsible for providing suitable audible or
visual alarms or other devices to indicate that the drive may start at any moment. Failure to observe
this warning could result in severe bodily injury or loss of life.

MN705 1-1
SAFETY NOTICE Continued
WARNING: Do not use start/stop, inhibit or enable functions as a safety disconnect. Use only an AC line
disconnect for that purpose. Failure to observe this warning could result in severe bodily injury or loss
of life.
Caution: Disconnect motor leads (A1 and A2) from control before you perform a Dielectric Withstand test on the
motor. Failure to disconnect motor from the control will result in extensive damage to the control. The
control is tested at the factory for high voltage / leakage resistance as part of Underwriter Laboratory
requirements.
Caution: Do not connect AC power to the Motor terminals A1 and A2. Connecting AC power to these terminals
may damage the control.
Caution: Baldor recommends not to use Grounded Leg Delta transformer power leads that may create ground
loops. Instead, we recommend using a four wire Wye.
Caution: Suitable for use on a circuit capable of delivering not more than 5,000 RMS symmetrical short circuit
amperes listed here at rated voltage.
Caution: Adjusting the current limit above 150% of the motor nameplate rating can cause overheating and
demagnetization of the PM motor.
Caution: Do not leave the motor in a locked rotor condition for more than a few seconds since motor damage
may occur.
Caution: Shunt wound motors may be damaged if field windings remain energized for an extended period of
time without armature rotation.

Receiving
Each control is thoroughly tested at the factory and carefully packaged for shipment.
When you receive your control, there are several things you should do immediately.
1. Observe the condition of the shipping container and report any damage immediately to the
commercial carrier that delivered your control.
2. Verify that the part number you received is the same as the part number listed on your purchase order.
3. Do not unpack until ready for use.

Table 1-1 Electrical Ratings


Model InputVoltage Max. AC Load Output Max. Output Max. Field Maximum Fuse or
Number (VAC- 50/60Hz) Current Voltage Current Current Power Breaker
(Amps RMS) (VDC) (ADC) (ADC) HP (kW) (Amps)
BC154 115 15.0 0 to 90 10.2 1.13 1 (0.75) 20
BCWD140 230 15.0 0 to 180 10.2 1.13 2 (1.5) 20
230 15.0 0 to 90 10.2 1.13 1 (0.75) 20

Table 1-2 Performance Specifications


Parameter Specification Factory Setting
AC Line Input Voltage (VAC ±10%) 115 / 230 230
AC Line Frequency (Hz) 50 / 60 -
Armature Voltage Range at 115VAC Line (VDC) 0 to 130* -
Armature Voltage Range at 230VAC Line (VDC) 0 to 220* 180
Field Voltage at 115VAC Line (VDC) 100 / 50 -
Field Voltage at 230VAC Line (VDC) 200 / 100 -
Horsepower at 115VAC 1 / 50-1
Horsepower at 230VAC 1 / 25-2
Ambient Temperature Range (°C / °F) 0-40 / 32-104 -
Operating Humidity Range (% Relative, Non-Condensing) 0-95 -
Storage Temperature (°C / °F) -25 to +85 /-13 to +185 -
Speed Range (Ratio) 50:1 -
Speed Regulation (Armature Feedback, % Base Speed) ±1 -
Speed Regulation (Tachometer Feedback, % Set Speed) ±1 -

1-2 MN705
Chapter 2
Installation
WARNING: Do not use this drive in an explosive environment. An explosion can cause serious or fatal injury.
This drive is not explosion proof.
Introduction
The BC154/BCWD140 is intended to be installed in a vertical position on a flat surface free of
moisture, metal chips, or corrosive atmosphere.
Control installation must ensure unrestricted air flow through the heatsink cooling fins.
Note: If drive is mounted in other than a vertical position, decrease maximum allowable ambient
temperature by 10°C.
Enclosure - When mounting the BC154 or BCWD140 in an enclosure, it must be large enough to
provide proper heat dissipation. If full rating is required, a minimum enclosure size of 12W x 12D
x 24H should be used. Smaller enclosures may be used if full rating is not required or if adequate
ventilation, or auxiliary cooling methods are used.
Front Cover - The BC154/BCWD140 case is designed with a hinge so that when the front cover is
open, all wiring stays intact. To open the cover, the four cover screws must be loosened so they no
longer are engaged in the case bottom. See Figure 2-1.
Note: Front cover screws are captive.
Figure 2-1 Captive Cover Screws

Captiive Scre w BC154 / BCWD140 Case


Cover (Not to Scale)
Gasket 4 1
Case

2 3

Tighten the four case captive screws in the 1- 4 sequence.


Tor que Speci fication: 12 lb -in (14 kg -cm)

Mounting
1. Refer to mounting hole locations shown in Figure 2-2. Locate and drill mounting holes.
2. Securely mount control to flat mounting surface using appropriate hardware.
3. Open cover (refer to Figure 2-1) so that electrical installation can be performed.
Power Connection Refer to Figure 2-3 for connections.
1. Connect AC line voltage to terminals L1 and L2. See Table 2-1.
Set both jumpers J2A and J2B to the correct input line voltage of 115 or 230VAC.
This control does not contain AC line fuses.
A 25 amp rated fuse or circuit breaker can be to protect the unit from catastrophic failure.
2. Connect ground wire (earth) to green ground screw terminal. See Figure 2-3 and Table 2-1.

MN705 2-1
Table 2-1 Terminal Block Wiring Information
Terminal Block Terminal Supply Wire Size (AWG - Copper) Tightening Torque Specification
Minimum Maximum lbs- in kg-cm
TB1 A1, A2, L1, L2 22 12 12 14
TB2 F1, F2 22 14 3.5 4
TB3 T+, T- 22 14 3.5 4
TB4 N.O., COM, N.C. 22 14 3.5 4

Figure 2-2 Mounting Hole Locations


5.866 (149.50)
5.00 (127.00)
5.472 (139.00)
4.055 (103.00)
2.736
(69.50)

ON STOP OL

DC MOTOR SPEED CONTROL

50
40 60

30 70

20 80

8.228 10 90

(209.00) 0 % 100

FWD

BRK

8.875 REV

(225.50 NEMA-4X / IP-65

9.488 START RUN

(241.00)
STOP JOG

Use 0.25" (9) Mounting Screws

Armature Connection
1. Select the proper fuse size for your motor. See Table 2-2.
Control will not operate if fuse is not installed.
Fuse type should be Littlefuse 326 ceramic, Buss ABC, or equivalent.
Table 2-2 suggests appropriate armature fuse ratings. However, the specific application may
require larger fuse ratings based on ambient temperature, CL set point and duty cycle of operation.
(Fuse rating is based upon 1.7 times the motor current rating.)
2. Install the correct fuse in the ARM FUSE fuse holder on circuit board. See Figure 2-3.
3. Connect the armature leads: see PM type or Shunt Wound type.

2-2 MN705
Table 2-2 Armature Fuse Chart
Motor Horsepower DC Motor Fuse Rating
Current (A) (A)
90VDC 180VDC
1/8 1/4 1.3 2
1/6 1/3 1.7 2-1/2
1/4 1/2 2.5 4
1/3 3/4 3.3 5
1/2 1 5.0 8
3/4 1-1/2 7.5 12
1 2 10.0 20

Permanent Magnet (PM Type)


Connect motor armature leads to A1(+) and A2(-). See Figures 2-4 and 2-5.
Set jumper J3 to the proper position 90V (90 VDC motors) or 180V (180 VDC motors).
Note: 180 VDC motors must be used with 230VAC line. 90 VDC motors can be used with a 230VAC or
115VAC line.
Note: Motor performance and efficiency, including brush life, may be adversely affected when using a
90 VDC motor with a 230VAC line.
Figure 2-3 Control Board
Y G R B
JOG MAX MIN ACCEL DECEL TCL CL IR

CON1
To LED Board JOG MAX MIN ACCEL DECEL TCL CL IR
I1
NTCL

2.5A

7.5A
TCL
10V

10A
5V

5A
J7

J5

I2
J4

Run Relay
To Start/Stop Switch START Output Contacts
TB4
(See Section 4.9)
COM
NO
RELAY CONTACT RATINGS
NC COM NO

STOP COM 1 Amp at 30 Volts DC


JOG NC 0.5 Amp at 125 Volts AC
0.25 Amp at 250 Volts AC
To Main Speed Potentiometer P3

P2
J1

P1
TRQ
SPD

T
T+ 90V
TB3 180V
T- J3

50V
20V/30V
7V
Two mating sockets are located
J6 ARM FUSE under R69 to install a
Plug-In Horsepower Resistor®
For Optional BC153 for motors under 2.5 Amps.
(BLU)
R69 See Note in Appendix A of
L1B J2A
the manual.
J9A 115V
L1A 230V
(BLU) J2B
(ORN) A1B 230V
J8A 115V
(RED) A1A

CON2
(WHT) A2B
J8B
(BLK) A2A
TB1 (WHT)
L2A
J9B

GROUND
F1 F2 L2B
TB2
SHUNT (WHT)
MOTORS
ONLY A1 A2 L1 L2 SCREW
Shunt Wound Motors
Connect motor armature leads to A1(+) and A2(-). See Figures 2-4 and 2-5.
a. For 90 VDC motors with 100 volt fields and 180 VDC motors with 200 volt fields.
Connect full voltage shunt field wires to F1 and F2.

MN705 2-3
b. For 90 VDC motors with 50 volt fields and 180 VDC motors with 100 volt fields.
Connect half voltage field wires to F1 and L1.
4. Select Speed Or Torque Mode.
Set J1 (factory set for speed control). to SPD for Speed control or to TRQ for torque control.
5. Set Armature Current. Jumper J4 is factory set for 10 amp motors (10A).
For motors with less armature current rating, place J4 in the proper position.
Note: The factory setting for Current Limit is 150% of the nominal current setting (e.g., if J4 is selected
for 10 amps, the actual CL setting will be 15 amps).
Figure 2-4 Full Voltage Field Connection Figure 2-5 Half Voltage Field Connection
TB2 TB1 TB2 TB1
F1 F2 A1 A2 L1 L2 F1 F2 A1 A2 L1 L2
GROUND GROUND
SCREW SCREW
+ - + - + - + -

M
FIELD M

FIELD ARMATURE AC LINE ARMATURE AC LINE


INPUT INPUT

Torque specifications are provided in Table 2-1.


Table 2-2A Field Connection (Shunt Wound Motors Only)
AC Line Voltage (VAC) Armature Voltage (VDC) Field Voltage Field
(VDC) Connections
115 90 100 F1, F2
115 90 50 F1, L1
230 180 200 F1, F2
230 180 100 F1, L1
230 90* 100 F1, L1
* Step down operation.
DC Tachometer Connection
If Tachometer feedback is required, an analog tach signal must be connected to terminal block TB3.
For location, see Figure 2-3.
To avoid erratic operation, do not bundle AC line and motor wires with potentiometer, voltage
following, enable, inhibit or other signal wiring. Use shielded cables on all signal wiring over 12 (30
cm). The shield should be grounded on the control side only.
Connect the Tachometer so that when the motor rotates the positive tach voltage lead is connected to
T+ and the negative tach lead is connected to T-. See Figure 2-6.
Figure 2-6 Tachometer Connection Diagram
TB3

T- -
T
T+ +

Torque specifications are provided in Table 2-1.


Note: For Tachometer feedback, Jumper J3 must be set to the T position, Jumper J6 must be set for
the proper tach voltage, and the IR COMP must be set to minimum (CCW) position.

2-4 MN705
Remote Speed Reference
The control is operated by the main potentiometer on front panel. However, the control can be
operated remotely by and external potentiometer, or an Isolated analog voltage for voltage following.
To operate from an external source remove white, orange and violet potentiometer leads from
terminals P1, P2 and P3. The leads may be taped and left in the control. The potentiometer itself
may be removed (if required). If the potentiometer is removed, a watertight seal must be installed to
prevent water entry through the cover.
Remote Potentiometer (5K)
Connect remote potentiometer wires to terminals P1, P2 and P3, so that the high side of the
potentiometer connects to P3, the wiper to P2 and the low side to P1. See Figure 2-7.
Figure 2-7 Remote Potentiometer Connection (5K)
High
P3

Wiper

P2
Low

P1

Analog Input
An isolated 0-5 or 0-10VDC analog voltage can also be used to control speed. See Figure 2-8.
Figure 2-8 Analog Voltage Connection
Isolated Voltage
Source +
0-5 P2
0 - 10
VDC -

P1

Notes:
1. If the available analog speed reference signal voltage is not isolated, an optional Signal Isolator
Board, model BC145, may be installed. Reference Instruction Manual MN1373.
2. When using an external analog signal, the main speed potentiometer must be disconnected from
terminal P1, P2, and P3. The MIN trimpot may need to be adjusted to achieve 0 output voltage.
Remote Start/Stop Switch
A remote Start/Stop Switch may be installed by disconnecting the wires from the Start, Com, and Stop
terminals, and reconnecting the terminals to a remotely mounted switch. See Figure 2-9.
Figure 2-9 Remote Start/Stop Switch Connection

START
COM

STOP

Note: The Start/Stop function may be bypassed by connecting a jumper wire across the Start and Com
terminals.

MN705 2-5
Inhibit
WARNING: When the Inhibit jumper is installed, the drive and motor will start and run when AC power is applied,
when power is restored after a momentary power loss, or after an overload or TCL fault is reset. The
user must ensure that automatic start up of the driven equipment will not cause injury to operating
personnel or damage to the driven equipment. The user is responsible for providing suitable audible or
visual alarms or other devices to indicate that the drive may start at any moment. Failure to observe
this warning could result in severe bodily injury or loss of life.
WARNING: Do not use start/stop, inhibit or enable functions as a safety disconnect. Use only an AC line
disconnect for that purpose. Failure to observe this warning could result in severe bodily injury or loss
of life.
The control can be electronically stopped and started with the Inhibit circuit. To Stop the control,
Terminals I1 and I2 must be connected as shown. See Figure 2-10.
The control can be restarted by opening the contact.
Figure 2-10 Inhibit Circuit Wiring
SWITCH OR RELAY
OPEN TO"START"
CLOSE TO "STOP"
I1

I2
Note: The Inhibit Circuit is not isolated. Do not connect common or ground leads from the remote
circuit.
Enable
The control can also be started and stopped with an Enable circuit (the Enable circuit functions
opposite to that of the inhibit circuit; open to start, close to stop, Enable: open to stop, close to start).
The Enable function is established by wiring a contact in series with the violet potentiometer lead
connected to terminal P3. The Enable circuit is not isolated. Do not connect common or ground leads
from external power sources. See Figure 2-11.
Figure 2-11 Enable Circuit Wiring

VLT VLT

P3 P3

SWITCH,RELAY OR FET A SOLID STATE RELAY CAN


OPEN TO "STOP" ALSO BE USED WITH AN
CLOSED TO "START" OPEN COLLECTOR

MAIN POTENTIOMETER MAIN POTENTIOMETER

Note: The MIN speed trimpot must not be set higher than 70% CW rotation (Approximately
2:00 o’clock position) or Enable will not function.

2-6 MN705
RUN/FAULT Relay Connection
The Run/Fault Relay, K1, Output Contacts are located at TB4 and can be used to turn on or off
equipment. See Figure 2-12.
Figure 2-12 Run/Fault Relay Connections
N.O COM N.C

TB4
N.O - Normally Open
COM - Common
N.C - Normally Closed

Torque specifications are provided in Table 2-1.


The Run/Fault Relay Contact status for various drive operating conditions is shown in Table 2-3.
Relay Contacts Ratings: 1 Amp at 30VDC, 0.5 Amps at 125VAC, and 0.25 Amps at 250VAC.
Table 2-3 Drive Operating Condition and Run/Fault Relay Contact Status
Drive Description Run Relay Operation Fault Relay Operation
Operating (J5 = NTCL Position) (Factory Setting) (J5 = TCL Position)
Condition
Normally Open Normally Closed Normally Open Normally Closed
Power Off Main Power Open Closed Open Closed
Disconnected
Run Mode1 Normal Drive Closed Open Closed Open
Operation
Stop Mode2 Selected by Open Closed Open Closed
Operator
Fault3 Drive Tripped - - Open Closed

Notes:
1. Run Mode is selected with the optional FWD-BRK-REV Switch.
2. Stop Mode is selected using the optional FWD-BRK-REV Switch.
3. TCL Fault.
Install Cover
1. Ensure the gasket is in place around the cover lip.
2. Close cover. Tighten cover screws as specified in Figure 2-1.

MN705 2-7
2-8 MN705
Chapter 3
Adjustments & Start-up
Important Application Information
Motor Type
The BC154/BCWD140 is designed for Permanent Magnet (PM), Shunt Wound and Universal
(AC/DC) motors. Use of higher voltage motors will result in reduction of available maximum (MAX)
speed (Trimpot Adjustment). Also, if motor is not an SCR rated type, the actual AC line amperage at full
load should not exceed the motor’s DC nameplate rating.
Torque Requirements
When replacing an AC induction motor with a DC motor and speed control, consideration must be
given to the maximum torque requirements. The full load torque rating of the DC motor must be equal
to, or greater than, that of the AC motor.
Acceleration Start
The BC154/BCWD140 contains an adjustable acceleration start feature that allows the motor to
smoothly accelerate from 0-full speed over a time period of 0.1 to 15 seconds.
Limitation In Use
The BC154/BCWD140 controls are designed for use on machine applications.
Setting selectable jumpers
The BC154/BCWD140 has selectable jumpers that can be set to accommodate various applications.
Jumpers must be set before the control can be used. Set the jumpers as follows:
Be certain all power is off.
J1 - Speed and torque mode
Selects Speed (SPD) or Torque (TRQ) operating modes.
Speed Mode - When Jumper J1 is placed in the “SPD” position, the drive will control motor speed as
a linear function of the main potentiometer setting, or analog voltage input. The range of output speed
can be adjusted with the MIN and MAX trimpots. The motor will maintain the preset speed as long as
the maximum load does not exceed the current limit set point. If the motor load exceeds the current
limit setting, the Overload LED will turn on and the motor will stall. See Figure 6-2, 6-3 through 6-6,
which illustrate Motor Speed and Torque Modes.
Figure 3-1 Motor Speed vs. Potentiometer Figure 3-2 Preset Motor Speed vs. Motor Load
Rotation (Speed Mode) (Speed Mode)
100 100
90 HIGHER SET SPEED
MOTOR OUTPUT SPEED (%)

90
80
MOTOR SPEED (%)

80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
0 LOWER SET SPEED
0
0 10 20 30 40 50 60 70 80 90 100 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150
POTENTIOMETER ROTATION (%) APPLIED TORQUE% CL SETPOINT

MN705 3-1
Torque Mode - When Jumper J1 is placed in the “TRQ” position, the drive will control motor torque as
a linear function of main potentiometer setting. If the motor load exceeds the torque setting, the motor
will stall, the Overload LED will light, and the drive will apply a constant preset torque based on the
potentiometer setting. The Overload LED will light when the load torque approaches the current limit
set point. The torque limits are set via jumper J4 and the CL trimpot.
Note: When operating in the Torque Mode, Jumper J5 must be in the “NTCL” position or drive will shut
down when CL Timer times out.
Figure 3-3 Motor Output Torque vs. Potentiometer Figure 3-4 Motor Speed vs. Applied Motor Load
Rotation (Torque Mode) (Torque Mode)

100 100
90 90
MOTOR OUTPUT SPEED (%)

HIGHER TORQUE SETTING

MOTOR SPEED (%)


80 80
70 70
60 60
50 50
40
40
30
20 30
10 20
0 10
0 10 20 30 40 50 60 70 80 90 100 0 LOWER TORQUE SETTING
POTENTIOMETER ROTATION (%) Note: S1 and S2 .= Speed Setting

J2 - Input AC line voltage


Selects the AC line voltage source connected to the drive (115/230VAC).
J2A and J2B in the correct corresponding positions, “115V” or “230V”, see Figure 3-5.
Figure 3-5 Setting AC Line Voltage with Jumper J2A and J2B
Set to 230 VAC
(Factory Setting) Set to 115 VAC

115V 115V

230V 230V

J2A J2A

230V 230V

115V 115V

J2B J2B

3-2 MN705
J3 - Armature Voltage Output and Tachometer Feedback
Select the required armature voltage by placing J3 in the proper position “90V” for 90-130VDC motors
and “180V” for 180-220VDC motors. For 115VAC line input, J3 must be set to “90V”. See Figure 3-6.
Figure 3-6 Setting Armature Voltage with Jumper J3
Set for 180VDC
Set for 90VDC
(Factory Setting)

T T
90V
90V
180V
180V
J3 J3

For 230VAC line input, the Armature voltage is normally set to “180V”. It is possible to operate in a
Step-Down Mode (90-180VDC motor with a 230VAC line) by setting J3 to “90”. However, reduced
performance may result.
If tachometer feedback is to be used, J3 must be placed in the “T” position and an external DC
tachometer must be installed.
Table 3-1 Relationship of AC Line Input and Motor Voltage with Jumper J2 and J3 Position
AC Input Voltage J2A, J2B Position J3 Position** Motor Voltage
115 115 90 90
230 230 180 180
230 230 90* 90*
* A 90VDC motor can be used with a 230VAC line. However, speed range may be reduced and motor derating
may be required.
** Set J3 to “T” if tachometer feedback is used.
J4 - Armature Current
Select the J4 position (2.5A, 5A, 7.5A, 10A) closest to the rated motor current. Note that the output
is factory set to 150% of the J4 position (e.g. 15 amps in the 10A position and 11 amps in the 7.5
position, etc.). This setting can be readjusted using the CL trimpot.
Note: For subfractional horsepower motors with current ratings below 2.5 amps, the drive can be
modified. Refer to Appendix A.
Table 3-2 Jumper J4 Setting vs. Motor Horsepower

Motor Horsepower
Jumper J4 Range
Factory Setting
90VDC 180VDC
1 2
10A
7.5A
3/4 1-1/2
5A 1/3 - 1/2 3/4 - 1
2.5A
1/6 - 1/4 1/3 - 1/2

MN705 3-3
J5 - Current Limit Mode J5
(Factory set for TCL). This control contains electronic current limiting which
limits the maximum DC current to the motor (the current limit set point is TCL NTCL
established with the selection of the J5 position and the setting of the CL
trimpot). See Figure 6-8. Two modes of current limit operation are provided:
Timed Current Limit “TCL”
In this mode the drive will turn off after being in current limit for a preset time. The time period is
adjustable with the TCL trimpot from 0.5-15 seconds and is factory set for approximately seven (7)
seconds. TCL provides electronic motor overload protection.
After the control times out in TCL, it can be reset by placing the front panel Start Switch to the “STOP”
position and then to “START”, or by cycling the AC power. If the Start Switch is jumpered out, the
control can be restarted after timing out in TCL, by cycling AC power OFF and ON.
Note: The Overload lamp will remain lighted until the control is reset.
Non-Timed Current Limit “NTCL”
In this mode the drive will reach the preset current limit during overload and stay at that level until a
fuse blows or the drive is manually turned off. If non-timed CL operation is desired, move jumper J5
from the factory set “TCL” position to the “NTCL” position.
The NTCL position must be used when operating in the Torque Mode.
J6 – Tachometer Voltage 50V
Note: Selection of this jumper position is not required if tachometer
feedback is not used. 20/30V
If a tachometer feedback is used, select the J6 position that corresponds
to the tachometer voltage in Volts/1000 RPM. The selection of J6 position 7V
is based on a maximum motor speed of 1800 RPM. If other than standard
tachometer voltages and motor speeds are used, an external resistor (RT) may be used (1/2 watt
rating).
Factory setting is 7V.
Calculate the value of RT as follows:
RT = [(1.64 x VT x S) - 20,000] ohms
where: RT = Calibration resistor value (ohms)
VT = Tach Voltage in Volts/1000 RPM
S = Base speed of motor in RPM
Install resistor (RT) in series with either tachometer lead.
Note: For tachometer feedback Jumper J3 must be in the “T” position.
J7 - Signal Input Voltage 10V 5V
The output of this control is normally controlled with the main speed
adjust potentiometer. However, an isolated analog voltage may also J7
be used in place of a potentiometer. The control can be scaled for
either a 0-5VDC or 0-10VDC by placing J7 in the appropriate position
“5V” or “10V”. The scaling can be further adjusted with the “MAX” trimpot.

Note: If an Isolated input signal is not available, an accessory Signal Isolator Model BC145 can be
installed. The BC154/BCWD140 accepts a wide range of signal voltage and current. An installation
kit (BC158) containing Auto/ Man Switch and required connections are also available.

3-4 MN705
Start-Up
When jumpers are set to the desired positions, and the electrical connections have been completed,
the drive is ready for start-up.
First Time Start-up
Check of Electrical Items
1. Verify AC line voltage at source matches control rating.
2. Inspect all power connections for accuracy, workmanship and tightness and compliance to codes.
3. Verify control and motor are grounded to each other and the control is connected to earth ground.
4. Check all signal wiring for accuracy.
5. Be certain all brake coils, contactors and relay coils have noise suppression.
This should be an R-C filter for AC coils and reverse polarity diodes for DC coils. MOV type transient
suppression is not adequate.
Check of Motor and Coupling
1. Verify freedom of motion of motor shaft.
2. Disconnect the load from the motor shaft. Verify operation of the drive and motor before the load is
attached.
Procedure
1. Before starting, be sure the main speed adjust potentiometer is fully CCW.
2. Apply AC power.
3. Observe the Power “ON” LED and the “STOP” LED indicators are illuminated.
4. To start the control, move the START/STOP switch to the “START” position.
The “STOP” LED should extinguish.
5. Rotate the main speed adjust potentiometer clockwise. Motor speed should increase as
potentiometer is rotated.
6. Verify the motor shaft is rotating in the desired “forward” direction.
If the direction of rotation is wrong, stop the drive and disconnect AC power.
Reverse the A1 and A2 motor lead connections.
If a tachometer is connected, the leads may also need to be switched for correct signal polarity.
Resume the procedure at step 1.
7. When steps 1-6 operation is correct, stop the drive and disconnect AC power.
Couple the load to the motor shaft, verify the connection is secure.
8. Repeat Procedure steps 1-6 with the load coupled to the motor shaft.

MN705 3-5
TRIMPOT ADJUSTMENTS
The control contains trimpots that are factory set for most applications. Figure 2-3 shows the location
of the trimpots and their approximate calibrated positions. Some applications may require adjustment
of the trimpot values.
To adjust the trim pots, be sure the First Time Start-up procedure was successful and that power is
applied to the control and the drive is ready for operation.
Minimum Speed (MIN)
The MIN trimpot sets the minimum speed of the motor as a % of full range.
Adjust the MIN trimpot as follows:
1. Rotate Main Potentiometer to minimum speed position (full counterclockwise).
2. Increase setting of MIN trimpot so that motor runs at desired minimum speed.
Maximum Speed (MAX)
The MAX trimpot sets the maximum speed of the motor.
Adjust the MAX trimpot as follows:
1. Rotate Main Potentiometer to maximum speed position (full clockwise).
2. Adjust MAX trimpot setting to desired setting of motor speed.
Acceleration (ACCEL)
The ACCEL trimpot sets the amount of time for the control voltage to reach full output.
The acceleration circuit operates when rapidly rotating the main speed potentiometer to full clockwise
position, or when starting the control when the main speed potentiometer is already at speed position.
The trimpot is factory set to 1 second. If more rapid acceleration is desired, rotate the trimpot
counterclockwise. Clockwise for longer accel time.
Note: Rapid ACCEL setting may cause the current limit circuit to activate which will extend the
acceleration time. For a longer acceleration time, rotate ACCEL trimpot clockwise. 50% rotation
represents approximately seven (7) seconds and full rotation is approximately fifteen (15) seconds.
Deceleration (DECEL)
The DECEL trimpot sets the amount of time for the control voltage to reach minimum speed. The
deceleration circuit operates when rapidly rotating the main speed potentiometer to full counter
clockwise position, or when stopping the control when the motor is already at speed. It does not
operate when power is removed.
The trimpot is factory set to one (1) second. If more rapid decel is desired, rotate the trimpot
counterclockwise. Clockwise for longer decel time.
Note: For high inertial loads, a rapid DECEL setting may cause the motor to coast to a stop slower than
the DECEL setting. To increase deceleration time, rotate DECEL trimpot clockwise. 50% rotation
represents approximately seven (7) seconds and full rotation is approximately fifteen (15) seconds.
Current Limit (CL)
The CL trimpot sets the maximum amount of DC current that the motor can draw.
The amount of DC current determines the amount of maximum motor torque in both the Speed
Control Mode and Torque Mode. These CL trimpot is factory set at 150% of the motor current.
The value can be reduced by adjustment of the CL trimpot. Some applications require a lower torque
limiting value to prevent damage to the process material or the drive train.
Caution: Adjusting the current limit above 150% of the motor nameplate rating can cause overheating and
demagnetization of the PM motor.

3-6 MN705
IR Compensation (IR)
The IR Comp circuit is used to stabilize motor speed under varying loads. Factory set to 4/8 VDC for
Controls with 90/180 VDC Output.
Note: If control is in Tach Feedback mode, the IR trimpot should be set to minimum (fully CCW).
Adjust the IR trimpot as follows:
1. Run motor at approximately 30-50% of rated speed under no load and measure actual speed.
2. Load motor to rated current. Rotate IR trimpot so that the fully loaded speed is the same as the
unloaded speed measured in the previous step.
IR compensated is set so that minimal speed change will occur over a wide range of motor load.
Note: Too much IR Comp will cause unstable (oscillatory) operation.
Timed Current Limit (TCL)
Jumper J5 must be in the “TCL” position for Timed Current Limit to be operational.
This trimpot determines the approximate time the drive will stay in Current Limit before tripping.
The trimpot is adjustable over a time range of 0.5-15 seconds and is factory set to seven (7) seconds.
Rotating the trimpot clockwise increases the trip time.
This function provides motor overload protection.
Jog Speed (JOG)
This trimpot is operational only when the optional RUNSTOP-JOG Switch (BC157) is installed.
In the JOG position, the JOG trimpot can be adjusted to the JOG speed.

MN705 3-7
3-8 MN705
Chapter 4
Troubleshooting
LED Indications
The front cover has three LEDs that indicate the control’s operational status.
1. Power On Indicator (ON) - This LED is Green when AC power is applied to the control.
2. Stop Indicator (STOP) - This LED is Yellow in the stop mode (start/stop switch=stop).
This indicator remains off if the control was running and inhibit is asserted or enable is opened.
3. Overload Indicator (OL) - When the motor is loaded to the current limit setpoint, this LED will glow
Red. If the control is allowed to stay in CL and then trips out in TCL (Timed Current Limit), the OL
LED will remain Red until the control is stopped and restarted with the start/stop switch.
If the OL LED remains illuminated during control operation, a fault condition may exist.
Possible causes and solutions for these conditions may be found in Table 4-1.
Note: In some applications, especially those requiring the motor to cycle on and off or, changing from one
speed to another, the OL indicator may blink indicating a transient overload. This may be a normal
condition for the application.
Table 4-1 Troubleshooting Guide
Indication Possible Cause Corrective Action
Motor is not running and Start/stop switch is in the stop position. Move the switch to the start position.
Stop LED is on.
The main speed potentiometer is set to Set the main speed potentiometer for the
zero speed. desired speed.
The main speed potentiometer, signal Verify main speed potentiometer, signal input,
input, or motor connections are open. or motor connections.
Motor is not running and Inhibit is asserted or enable is opened. Remove the inhibit signal or enable the drive.
Stop LED is not on.
Motor runs then stops Drive is tripped. Drive is overloaded. Restart drive by cycling AC power. Reduce load.
after a short time or, the
drive trips due to overload
(TCL Fault).
Line fuse blows or circuit The fuse or breaker is the incorrect Install correct size fuse or breaker.
breaker trips. rating.
OL LED indicator is on. Motor is overloaded. Check motor amps with DC ammeter in series
with armature. (If motor is shunt type, field
may be open or not receiving proper voltage.)
Correct problem.
Check motor for shorts or grounds. Motor may be defective. Replace motor.
Check position of CL trimpot. Adjust CL trimpot if set too low.
Rapid Acceleration caused OL trip. Verify Accel trim pot setting. Cycle power.
Power ON LED is not on. Verify AC power is available. Correct AC input power problem.
Replace fuse or reset breaker.
Motor runs at high speed Check position of Jumper, J3. Set J3 correctly.
and does not respond to
the main adjust pot or If tach is connected, verify signal polarity.
remote speed signal.

MN705 4-1
4-2 MN705
Appendix A
Modification for Subfractional HP Motors
Note: Before making this modification you must have a .05 ohm Plug-in Horsepower Resistor
(Baldor P/N WD3007A07).
Turn off all power.
Carefully clip out the large power resistor R69 on the printed circuit board.
The resistor location is shown in Figure 1-3.
Insert the .05 ohm Plug-in Horsepower Resistor into the two (2) pins located under the resistor, R69.
Each of the current selection values are now divided by 10. See Table A-1.
Table A-1 Current Limit Settings with .05 ohm Plug-in Horsepower Resistor Installed
Original J4 New J4 New CL Trimpot New CL Trimpot
Selections Selections Range Factory Setting
10.0 Amps 1.0 Amps 0 - 2.0 Amps 1.50 Amps
7.5 Amps 0.75 Amps 0 - 1.5 Amps 1.13 Amps
5.0 Amps 0.5 Amps 0 - 1.0 Amps 0.75 Amps
2.5 Amps 0.25 Amps 0 - 0.5 Amps 0.38 Amps

MN705 A-1
A-2 MN705
Baldor District Offices
UNITED STATES ILLINOIS NEW YORK TENNESSEE
CHICAGO AUBURN MEMPHIS
ARIZONA 340 REMINGTON BLVD. ONE ELLIS DRIVE 4000 WINCHESTER ROAD
PHOENIX BOLINGBROOK, IL 60440 AUBURN, NY 13021 MEMPHIS, TN 38118
4211 S 43RD PLACE PHONE: 630-296-1400 PHONE: 315-255-3403 PHONE: 901-365-2020
PHOENIX, AZ 85040 FAX: 630-226-9420 FAX: 315-253-9923 FAX: 901-365-3914
PHONE: 602-470-0407
FAX: 602-470-0464 INDIANA NORTH CAROLINA TEXAS
INDIANAPOLIS GREENSBORO DALLAS
ARKANSAS 5525 W. MINNESOTA STREET 1220 ROTHERWOOD ROAD 2920 114TH STREET SUITE 100
CLARKSVILLE INDIANAPOLIS, IN 46241 GREENSBORO, NC 27406 GRAND PRAIRIE, TX 75050
706 WEST MAIN STREET PHONE: 317-246-5100 PHONE: 336-272-6104 PHONE: 214-634-7271
CLARKSVILLE, AR 72830 FAX: 317-246-5110 FAX: 336-273-6628 FAX: 214-634-8874
PHONE: 479-754-9108
FAX: 479-754-9205 IOWA OHIO HOUSTON
DES MOINES CINCINNATI 10355 W. LITTLE YORK ROAD
CALIFORNIA 1943 HULL AVENUE 2929 CRESCENTVILLE ROAD SUITE 300
LOS ANGELES DES MOINES, IA 50313 WEST CHESTER, OH 45069 HOUSTON, TX 77041
6480 FLOTILLA STREET PHONE: 515-263-6929 PHONE: 513-771-2600 PHONE: 281-977-6500
COMMERCE, CA 90040 FAX: 515-263-6515 FAX: 513-772-2219 FAX: 281-977-6510
PHONE: 323-724-6771
FAX: 323-721-5859 MARYLAND OHIO (Continued) UTAH
BALTIMORE CLEVELAND SALT LAKE CITY
HAYWARD 7071A DORSEY RUN RD 8929 FREEWAY DRIVE 2230 SOUTH MAIN STREET
21056 FORBES STREET ELKRIDGE, MD 21075 MACEDONIA, OH 44056 SALT LAKE CITY, UT 84115
HAYWARD, CA 94545 PHONE: 410-579-2135 PHONE: 330-468-4777 PHONE: 801-832-0127
PHONE: 510-785-9900 FAX: 410-579-2677 FAX: 330-468-4778 FAX: 801-832-8911
FAX: 510-785-9910
MASSACHUSETTS OKLAHOMA WISCONSIN
COLORADO BOSTON TULSA MILWAUKEE
DENVER 6 PULLMAN STREET 5555 E. 71ST ST., SUITE 9100 1960 SOUTH CALHOUN ROAD
3855 FOREST STREET WORCESTER, MA 01606 TULSA, OK 74136 NEW BERLIN, WI 53151
DENVER, CO 80207 PHONE: 508-854-0708 PHONE: 918-366-9320 PHONE: 262-784-5940
PHONE: 303-623-0127 FAX: 508-854-0291 FAX: 918-366-9338 FAX: 262-784-1215
FAX: 303-595-3772
MICHIGAN OREGON INTERNATIONAL SALES
CONNECTICUT DETROIT PORTLAND FORT SMITH, AR
WALLINGFORD 5993 PROGRESS DRIVE 16201 SE 98TH AVENUE P.O. BOX 2400
65 SOUTH TURNPIKE ROAD STERLING HEIGHTS, MI 48312 CLACKAMAS, OR 97015 FORT SMITH, AR 72902
WALLINGFORD, CT 06492 PHONE: 586-978-9800 PHONE: 503-691-9010 PHONE: 479-646-4711
PHONE: 203-269-1354 FAX: 586-978-9969 FAX: 503-691-9012 FAX: 479-648-5895
FAX: 203-269-5485
MINNESOTA PENNSYLVANIA
FLORIDA MINNEAPOLIS PHILADELPHIA
TAMPA/PUERTO RICO/ 13098 GEORGE WEBER DR, 103 CENTRAL AVENUE
VIRGIN ISLANDS SUITE 400 SUITE 400B
3906 EAST 11TH AVENUE ROGERS, MN 55374 MOUNT LAUREL, NJ 08054
TAMPA, FL 33605 PHONE: 763-428-3633 PHONE: 856-840-8011
PHONE: 813-248-5078 FAX: 763-428-4551 FAX: 856-840-0811
FAX: 813-241-9514
MISSOURI PITTSBURGH
GEORGIA ST LOUIS 159 PROMINENCE DRIVE
ATLANTA 13678 LAKEFRONT DRIVE NEW KENSINGTON, PA 15068
62 TECHNOLOGY DRIVE EARTH CITY, MO 63045 PHONE: 724-889-0092
ALPHARETTA, GA 30005 PHONE: 314-373-3032 FAX: 724-889-0094
PHONE: 770-772-7000 FAX: 314-373-3038
FAX: 770-772-7200
KANSAS CITY
9810 INDUSTRIAL BLVD.
LENEXA, KS 66215
PHONE: 816-587-0272
FAX: 816-587-3735
MN705-0615

Baldor Electric Company


P.O. Box 2400, Fort Smith, AR 72902-2400 U.S.A., Ph: (1) 479.646.4711, Fax (1) 479.648.5792, International Fax (1) 479.648.5895
www.baldor.com
© Baldor Electric Company All Rights Reserved. Printed in USA.
MN705 6/15

You might also like