Study Guide Paper 2
Study Guide Paper 2
INSTALLATION RULES
Paper 2
V 5.4
The limitations of the voltage in the system to 50 V a.c. rms or 120 V d.c. ripple free
Give the formula to calculate the sustained current carrying capacity of a cable
The sustained current carrying capacity (I) of a cable buried directly in the ground can be calculated
by the following equation:
I = IS x F 1 x F2 x F3 x F4, where:
F2 is the soil temperature at depth of burial rating factor given in Table 6.11
F4 is the grouping of directly buried cables that are thermally interdependent rating factor given in
Table 6.13
State all the factors that will influence the Current Carrying Capacity of a cable.
Ambient temperature
Neutral imbalance
Harmonics
Consumer’s Earth Terminal (CET), terminal that is effectively and permanently earthed and to which
the earth continuity of an installation is permanently connected. The regulation states that, each
installation shall have a consumer’s earth terminal at or near the point where the supply cables to
the installation enter the building or structure. All conductive parts that are to be earthed shall be
connected to a main earthing terminal, which shall be connected to the consumer’s earth terminal
(for the purposes of carrying earth fault currents). The consumer’s earth terminal shall be earthed
by connecting it to the supply earth terminal or the protective conductor and if installed, the earth
electrode. The effectiveness of the supplier’s protective conductor shall be determined in
accordance with 8.7.5.
Tamper proof (All connections, joints are mechanically sound and shall not be tampered with
especially all bonding and earthing conductors). A main earth terminal or bar must be provided for
each installation to collect and connect together all protective and bonding conductors. It must be
possible to disconnect the earthing conductor from this terminal for test purposes, but only by the
use of a tool. This requirement is intended to prevent unauthorized or unknowing removal of
protection.
There shall be no mixed loading of circuits, except: A single phase circuit that has over-current
protection rated at not more than 20 A may supply a mixed load of:
(b) Socket-outlets and fixed appliances, or Socket-outlets, luminaries and fixed appliances
Socket-outlets rated at 16 A or more that are connected to circuits with mixed loading shall comply
with the earth leakage requirements of 6.7.5
Temporary installations for building construction site work, repairs, alterations, extensions and
similar work.
What is the maximum % volt drop for an AC and DC Supply in the RSA?
The voltage drop for a.c and d.c supply shall not exceed 5%
GPS co-ordinates of your DB may be obtained at local municipality. You may use the address and
site number
EXAMPLE 2
VOLTAGE DROP CALCULATIONS
Name FOUR different methods of how the voltage drop of a cable can be determined and give examples
for each method.
ANSWER: Suppose a balance three phase load of 100A is to be supplied by a 25mm2 copper cable over a
distance of 100m. Then calculate the Voltage Drop using FOUR known METHODS.
Given: I = 100A
Vd = (Fv x I x R x L) [Volts]
1000
Where,
Vd is the voltage drop to be calculated in volts
Where,
R = (Value of R in Ω/Km x L in meters) [Ohms]
1000
METHOD 3
(mV/A/m) = 1.5 for a 25mm2 copper (Cu) determined from Table 6.3(b) on page 105 or Table 6.4(b)
on page 107 of the regulation book – The distinction between the two tables is that Table 6.3(b)
makes provision for a 1 mm2 whereas Table 6.4(b) does not: In the exam you will most likely be
given Table 6.3(b), other than this they are similar in all aspects.
For phase to neutral: Vd = 15/√3 = 8.66 V [NB: See section 6.2.7 page 120]
METHOD 4
ADDITIONAL METHODS
Alternative Method 1:
In the case of a load with impedance, the voltage drop can be calculated from the following
The phase angle θ of the load is determined by power factor = cos θ and the reactance X may be obtained
from cable manufactures
Alternative Method 2:
Alternative Method 3:
**If the load is either inductive or capacitive, what methods would you use to determine the actual volt
drop? So if the load is either inductive or capacitive, how do we determine the actual volt drop?
Where,
1.1 With reference to FIGURE 1, on the DIAGRAM SHEET (Diagrams.pdf attached), calculate the following:
1.1.3 Test the answer in QUESTION 1.1.1 above by making use of any other method. (3)
1.2 By making use of TABLE E1 (attached) only, calculate the actual length of a 10 mm2 copper ECC
conductor if the total resistance of the conductor is 0,22 ohm. (2)
[10]
We know that the voltage drop shall not exceed 11.5V [5% of 230V] according to the code
Given:
The resistive load of 50A, 65m away from the point of control
From the Point of control to the joint we have 40m of 16mm2 copper cable
From the joint to the load we have 25m of 10mm2 copper cable
We can get R which is the resistance of the cable in ohms per kilometer (Ω/Km) from Table E1:
Vd = (Fv x I x R x L) [Volts]
1000
Where,
Vd = (Fv x I x R x L)
1000
Total Resistance of the supply cable = Resistance of a 16mm2 cable + Resistance of a 10mm2 cable
Alternative methods:
Method 1:
NB: Remember that we have to account for the voltage drop on neutral.
Method 2:
NB: Remember that we have to account for the voltage drop on neutral.
**Please note that neither Table 6.3(b) nor Table 6.4(b) was given in the exam, so we would not be able
to use this method to authenticate our answer, but it is given here to prove that our answer is indeed
right.
Recall that resistance in Ohms can also be expressed in the following form:
If we are given resistance of 0.22 ohms and we have to calculate the actual length of a 10 mm2 (2.2 Ω/Km)
ECC, we can apply the above formula where the only unknown is L in meters:
Given:
Red Phase = 160 Amps White Phase = 90 Amps Blue Phase = 110 Amps AND L = 120m
The total voltage drop shall not exceed 5% of 400V = 20V according to the code.
Neutral current (IN) =√ (R2 + W2 + B2) - (RW+RB+WB) ………. See Page 305
= √ (1602+902+1102)-(160*90+160*110+90*110)
= 62.45 A
METHOD 1:
Vd = (mV/A/m x A x L) [Volts]
1000
= 1.042
From Table 6.3(b) or Table 6.4(b) 1.042 is somewhere between a 35mm2 cable and a 50mm2 cable (taking
from the z column – always use the z values).
For a 35mm2 cable mV/A/m is 1.10 For a 50mm2 cable mV/A/m is 0.81
Vd (Neutral) = mV/A/m x A x L Vd (Neutral) = mV/A/m x A x L
1000 1000
= 8.2434V = 6.070V
= 1.10 x 160 x 30 + 1.10 x 100 x 50 + 1.10 x 20 x 70 = 0.81 x 160 x 30 + 0.81 x 100 x 50 + 0.81 x 20 x 70
1000 1000 1000 1000 1000 1000
= 12.32V = 9.072V
From Table 6.8 on page 114, a 50mm2 cable can handle 169 Amps and thus is selected. To confirm correct
cable size, calculate Voltage Drop (Red Phase and Neutral)
= √ (1602+902+1102)-(160*90+160*110+90*110)
= 62.45 A
For 50mm2 mV/A/m = 0.81 (taking from the z column – always use the z value)
Vd (Neutral) = mV/A/m x A x L
1000
= 6.070V
= 9.072V
Total Voltage Drop = 15.14V which is less than 5% of 400V = 20V, it is within limits. So main cable size of
50mm2 4 Core copper cable is correct.
The problem with the second method is that Table 6.8 is not normally given in the exam and that we
normally not given the method of installation; therefore it will be difficult to use this method in the exam.
2. Maximum volt drop at load (E).
Vd (Neutral) = mV/A/m x A x L
1000
= 0.81 x 62.45 x 70
1000
= 3.5409V
= 0.81 x 20 x 70
1000
= 1.1340V
From Table E1 page 306 R ECC for 50mm2 is 0.44 Ω/Km L = 30m and ICB = 160 Amps
Z = L x √ (0.076)2 + (0.44)2
1000
= (120 x 0.44652)/1000 = 0.05435 Ohms
1. The minimum main cable size if Voltage drop L2 not to exceed 2%.
Given:
Load Moment = 2 x I x L
Load Moment = 2 x I x L2
2090.88 = 2 x I x 20m
1. The minimum main cable size if Voltage drop L2 not to exceed 2%.
Minimum main cable size (that is L1) if voltage drop L2 is not to exceed 2%
Total voltage drop shall not exceed 5% of 250V = 12.5V according to the code, that is Voltage drop (A to
B) + Voltage drop (B to Load) shall be less than or equal to 12.5V.
Vd (A to B) + 5V =12.5V
mV/A/m = 3.188845
3.18845 is between 10mm2 and 16mm2 from Table 6.3(b) (Two-core, single phase a.c. column)
From the above Table 16mm2 minimum main cable size is selected
For a 6mm2 cable we have 3.6Ω/Km For a 4mm2 cable we have 5.5Ω/Km
I=60A and L=65m I=60A and L=65m
R = (Value of R in Ω/Km x L in meters) [Ohms] R = (Value of R in Ω/Km x L in meters) [Ohms]
1000 1000
R = 3.6Ω/Km x 65m = 0.234Ω R = 5.5Ω/Km x 65m = 0.3575Ω
1000m 1000m
T. V. = 2 x ICB x RECC T. V. = 2 x ICB x RECC
= 2 x 60A x 0.234 Ω = 2 x 60A x 0.3575 Ω
=28.08V =42.90V
28.08V is less than 30V maximum allowed T.V. 42.90V is greater than 30V maximum allowed T.V.
Therefore the minimum area of the ECC is 6mm2
Another way of answering this question is to proceed like this:
Touch Voltage = 2 x ICB x RECC = 2 x 60 x (2.2/1000) x 65 = 17.16V acceptable which is less than 30V
Touch Voltage = 2 x ICB x RECC = 2 x 60 x (3.6/1000) x 65 = 28.08V acceptable which is less than 30V
Touch Voltage = 2 x ICB x RECC = 2 x 60 x (5.5/1000) x 65 = 42.9V which is greater than 30V
To confirm that the selected cable size is correct, calculate the actual Touch Voltage
Length = 100m
Vd at F = mV/A/m x A x L
1000
= 14.30 Volts
For a 16mm2 cable we have 1.4Ω/Km For a 25mm2 cable we have 0.88Ω/Km
I=160A and L=100m I=160A and L=100m
44.80V is greater than 30V maximum allowed T.V. 28.160V is less than 30V maximum allowed T.V.
Touch Voltage = 2 x ICB x RECC = 2 x 160 x (0.88/1000) x 100 = 28.16V acceptable which is less than 30V
Touch Voltage = 2 x ICB x RECC = 2 x 160 x (1.4/1000) x 65 = 44.80V acceptable which is less than 30V
Touch Voltage = 2 x ICB x RECC = 2 x 160 x (2.2/1000) x 100 = 70.4V which is greater than 30V
R = pL/A
Get the values of R and X from Table E1 on page 307 for a 35mm2 cable
PSCC = VLine
2 x ZLine
= 400 V
2 x 0.0634567
= 3.1518 kA
4. PSCC at L1.
According to the code the total voltage drop at the furthest point of consumption (L2) shall not exceed 5%
of 230V which is in this case 11.5V
Vd = mV/A/m x A x L
1000
11.5V = mV/A/m x A x L
1000
mV/A/m = 0.8556547
0.8556547 is between 50mm2 and 70mm2 from Table 6.3(b) (Two-core, single phase a.c. column)
= 12.6336 V = 8.736 V
From the above Table 70mm2 minimum cable size for the loads is selected
2. Volt drop at L1, L2 and L3
At L3: I = 20A
L = 95m but we use 96m the total length of ECC
4. PSCC at L1.
TABLE 8.1 of the Code refers to the maximum resistance of the earth continuity conductor, with reference
to a known protective device. Derive from basic principles the approximate resistance value for the
following protective devices:
1. 100 amps
2. 20 amps
3. 10 amps
4. 1 amp
For questions like this, remember that the maximum allowed touch voltage (TV) according to the code is
30V. Use this formula:
Touch Voltage = 2 x ICB x RECC
Where,
ICB is the value of the protective device (Circuit Breaker or Fuse) = the value given in amps
RECC is the resistance value of the Earth Continuity Conductor =?
Touch Voltage (TV) = 30V
1.
ICB = 100A
Substituting values we have, T. V. = 2 x ICB x RECC
30V = 2 x 100A x RECC
RECC = 30V/200A = 0.15Ω
2.
ICB = 20A
Substituting values we have, T. V. = 2 x ICB x RECC
30V = 2 x 20A x RECC
RECC = 30V/40A = 0.75Ω
3.
ICB = 10A
Substituting values we have, T. V. = 2 x ICB x RECC
30V = 2 x 10A x RECC
RECC = 30V/20A = 1.50Ω
4.
ICB = 1A
Substituting values we have, T. V. = 2 x ICB x RECC
30V = 2 x 1A x RECC
RECC = 30V/2A = 15Ω
EXAMPLE 9
GENERAL CALCULATIONS
1. Calculate the maximum value of the protection device if the following is given: 100 meters of copper
ECC 4mm2.
2. Calculate from basic principles the maximum value of the protection device, if the following is given:
the length of ECC (earth continuity conductor) is 69 meters of copper with an area of 6mm2.
3. Calculate from first principles, the actual maximum length of the ECC (earth continuity conductor) if
the main protection is 63A using a 6 mm2 copper conductor. What is the actual resistance value for
the above length?
4. Calculate from basic principles the actual length of a 10 mm2 earth continuity conductor, if the main
protection device is 60 amps and the touch voltage not to exceed 30V. What is the actual touch
voltage at the load for this conductor?
5. Calculate from basic principles the aerial area of the ECC conductor if the protection rating is 60A
and the total length is 150 meters.
6. Table 6.28 refers to the minimum size and maximum length of copper earth continuity conductors
with reference to the rated protective device. Calculate, from basic principles the minimum size of
the earth continuity conductor if the main protection is 63A and the total length is 66,66 meters.
Use any other alternative method to calculate the minimum size of the ECC conductor.
For questions like this, remember two facts: the first is that the maximum allowed touch voltage (TV)
according to the code is 30V. Use this formula:
Touch Voltage = 2 x ICB x RECC
Where,
ICB is the value of the protective device (Circuit Breaker or Fuse) = the value given in amps
RECC is the resistance value of the Earth Continuity Conductor =?
Touch Voltage (TV) = 30V
The second fact: if you can recall from the previous discussion that the resistance in Ohms can also be
expressed in the following form:
Please remember to use Table E1 for the value of R in Ω/Km for each given case.
1.
ICB =?
The value of R in Ω/Km for 4mm2= 5.5 Ω/Km [From Table E1]
L = 100m
2.
ICB =?
The value of R in Ω/Km for 6mm2= 3.6 Ω/Km [From Table E1]
L = 69m
3.
ICB =63A
The value of R in Ω/Km for 6mm2= 3.6 Ω/Km
L=?