TRIPLE WAVEBAND IR FLAME DETECTOR, EXPLOSION-PROOF /
DUST-PROOF, WITH REMOTE TEST FUNCTION                                                                                                      CR1D-EW
                                                                                    ■ Features
                                                                                    •             Capable of detecting a 0.33m x 0.33m gasoline
                                                                                                  pan fire at up to 60m
                                                                                    •             Infrared sensing technology using three
                                                                                                  wavebands for optimum false alarm immunity
                                                                                    •             Omniview 360° four-color LED indicator for
                                                                                                  visible indication of sensor operation from any
                                                                                                  angle (Alarm, Trouble, Start-up, and Testing)
                                                                                    •             Suitable for indoor and outdoor use
                                                                                    •             Dust-poof and Water-proof equivalent to IP66/
                                                                                                  IP67
                                                                                    •             Responds to flickering flames
                                                                                    •             Stylish and functional design
                                                                                    •             Current consumption approx. 6mA (standby),
                                                                                                  50mA (alarm)
                                                                                    •             Adjustable angle bracket with fine scale
                                                                                    •             Ex-proof class : Ex db II CT6Gb
■ Description
The CR1D-EW is a triple waveband infrared
flame detector ideal for indoor/outdoor hazardous
environments. Its three built-in infrared sensors can                               ■ Dimensions
detect fuel fires at long distances with a high immunity
to false alarms.
The CR1D-EW is equipped with a manual and
automatic Self-Test function to assure continued
reliable operation. Its Omniview™ indicator provides
360°visibility for easy status recognition by four types
of color illumination.                                                                                                         (76)
The CR1D-EW has the same interface to a previous
                                                                                         178.9
model of 1RB1-EW, which provides compatibility for
wiring.
Optional weather-proof hood offers an enhancement
of tolerance to the rise of temperature due to the
direct sunlight.                                                                                                [Top]
                                                                                         [Mounting Pitch]
                                                                                              100
                                                                                   120
                                                                                                                 100                     98.9            80
                                                                                                            [Mounting Pitch]                    [Side]
                                                                                                                  120
                                                                                                               [Front]                                        (mm)
       CRD-EW-14A                         CRD-EW-14B
Sunshade for CR1D-EW                View angle restriction
                                     hood for CR1D-EW
                                         NOT TO BE USED FOR INSTALLATION PURPOSES.
               Nittan reserves the right to make changes at any time without notice in prices, colours, materials,
               components, equipment, specifications and models and also to discontinue models.                                       CR1D-EW-DAT-00             Rev.0
                                                                    Page 1 of 5
■ Directional Sensitivity and Range
Directional Sensitivity and Range                                                                              Direction
                                                0°
                                                                                                                                   50°
         50°                                                                              50°
                                                                                                                              0°
                                                                                                                                                 50°
                                                                                                                            Directional Range
100%    80%      60%      40%      20%                 20%       40%        60%           80%    100%
Selectable Detector Sensitivity                                                                    Detectable Flame Size
                                                                                                                                                       1m
  Detector Sensitivity           Detection Range
       High (default)                    60 m                                                           30cm
                                                                                                                     50cm
                                                                                          10cm
          Middle                         30 m
           Low                           15 m
                                                                   (Sensitivity = High)
                                                                                                                            (N-Heptane fire on a 0.1 m2 pan)
Detector sensitivity is selectable from 3 values by a dedicated setting tool. Detection range is a detectable
distance for a 0.1 m2 n-Heptane pan fire. The CR1D-EW has a detection range of 60 m away and a wide angle
of 100 degrees toward horizontal and vertical directions.
■ Triple Wavelength IR Detecting
         Wavelength range for identifying a true fire
Fire (flame) has a characteristic peak at 4.4 µm in a spectral distribution, which is called as CO2 emission. The
CR1D-EW has 3 sensors that monitor the band of CO2 emission and two wavebands on either side respectively.
The detector avoids false alarms by the feature of frequency-fluctuation detection.
                                             NOT TO BE USED FOR INSTALLATION PURPOSES.
                   Nittan reserves the right to make changes at any time without notice in prices, colours, materials,
                   components, equipment, specifications and models and also to discontinue models.                          CR1D-EW-DAT-00                 Rev.0
                                                                        Page 2 of 5
■ OMNIVIEW™ 360° LED
The CR1D-EW has a large ring OMNIVIEW™ 360°LED indicator to see detector status easily.
   Red                                                                                 Yellow
    Alarm                                                                               Trouble
                                                                                       Green
                                                                                         Startup
                                                                                         Blue
                                                                                    Remote-Test
■ Self-Test Function
The CR1D-EW has self-test function that checking lens condition or device status either automatically or manually
to detect trouble condition. That is effective in preventing false alarms. The automatic self-test cycle is adjustable
to either every 1 hr, 12 hrs or 1 week to meet with peripheral environment.
                            Lens(sensor)
                                                         Yellow light indicating when lens or device has trouble
                                           Normal                               Dust                          Water                 Condensation
LED indication for each status
       Test Function               Detector Status                Output Signal                                         LED Indicator
                                         Normal                          Fire                                           Red (steady)
        Manual Test                   Lens Stains                     Trouble                              Yellow (Flashes every 4 seconds)
  (By remote test switch)
                                    Circuit Trouble                   Trouble                         Yellow (Flashes 2 times every 4 seconds)
                                         Normal                            -                                                 Off
       Automatic Test                 Lens Stains                     Trouble                              Yellow (Flashes every 4 seconds)
                                    Circuit Trouble                   Trouble                         Yellow (Flashes 2 times every 4 seconds)
Selectable Self-Test Cycle
            Self-Test Cycle
               Every 1 hr
              Every 12 hrs
             Every 1 week
                   Off
*Selectable by a dedicated setting tool.
 Default setting is 12 hrs.
                                            NOT TO BE USED FOR INSTALLATION PURPOSES.
                  Nittan reserves the right to make changes at any time without notice in prices, colours, materials,
                  components, equipment, specifications and models and also to discontinue models.                                      CR1D-EW-DAT-00   Rev.0
                                                                       Page 3 of 5
■ Typical Wiring
Dedicated Control Panel
                                                                          Fire     L                                     White
                                                                      Common       C                                     Black
                                                             Zone 1    Trouble     K                                     Green
                                                                      24 VDC+      I+                                    Red
                                                                          Test     T                                     Yellow
                                                                                                                         Brown
                                                                                                 *1                      Blue
                                                                                                                                  Y X T I+ K C L
                                                                                                                                              *2
                                                                                                                                           CR1D-EW
                                                                          Fire     L
                                                                      Common       C
                                                             Zone 2    Trouble     K
                                                                      24 VDC+      I+
                                                                          Test     T
                                                                                                 *1
                                                       Dedicated fire alarm panel
                                                                                                      Junction                    Y X T I+ K C L
                                                       1PV-FLD Series.                                  Box                                   *2
                                                                                                                                           CR1D-EW
                                                      *1 Install a wire jumper between the terminals connected to Brown and Blue wires.
                                                      *2 The CR1D-EW has a built-in End-of-Line device (CRE) in its enclosure.
                                                         Thus, the number of connectable detector is one per each zone.
Typical Conventional Control Panel
                                  1PM3, etc.                                             LP06                                           CR1D-EW
                                                                                                   L1                                   L (White)
                                                                                                   K1                                   K (Green)
                                                                                                   C                                    C (Black)
                                                 Ln                                 Lin            I+                                   I+ (Red)
                                  Zone n                                            Cin
                                                 C (-)                                             T                                    T (Yellow)
                                                                                    Lout           X1                                   X (Brown)
                                                                                    Cout           Y1                                   Y (Blue)
                                Typical conventional
                                                                                                                                        CR1D-EW
                                fire alarm control panels,                                         L2                                   L (White)
                                such as 1PM3, 1PV0.                                                K2                                   K (Green)
                                                                                                                                        C (Black)
                                                                 +    -                                                                 I+ (Red)
                                                                                                                                        T (Yellow)
                                                              To Next LP06
                                                                or EOL*1                          X2                                    X (Brown)
                                                                                                  Y2                                    Y (Blue)
                                                                                       +24V     24G
                                                                                       +24V    GND
                                                                                 24 VDC External Power Supply
                                                                                 Isolated, Regulated and Power
                                                                                 limited
                                *1 A CRE End-of-Line Device must be installed at the last LP06 in the Ln and C circuit.
NFU-7000 Addressable Control Panel
                                                       EVA-ZMU-SCI                                         LP06                                      CR1D-EW
                                                                                                                      L1                             L (White)
                                 From Panel                                                                           K1                             K (Green)
                             or Previous Device
                                                                                                                      C                              C (Black)
                                    Loop                                 A+                             Lin           I+                             I+ (Red)
                                   +    -                                A-                             Cin           T                              T (Yellow)
                                                                                                        Lout          X1                             X (Brown)
                                                         Lin+                                           Cout          Y1                             Y (Blue)
                                                         Lin-
                                                         Lout+                                                                                       CR1D-EW
                                                         Lout-                                                        L2                             L (White)
                                                                                                                      K2                             K (Green)
                                                                                                                                                     C (Black)
                                   +    -                                           +    -                                                           I+ (Red)
                                    Loop                                                                                                             T (Yellow)
                                                                                 To Next LP06
                               To Next Device                                      or EOL*1                          X2                              X (Brown)
                                                                                                                     Y2                              Y (Blue)
                                                                                                        +24V       24G
                                                                                                        +24V      GND
                                                                                                  UL listed 24 VDC Power Supply
                                                                                                  Isolated, Regulated, Power limited,
                                                                                                  Listed for Battery Backup
                                *1 A 10 kΩ End-of-Line Resister must be installed at the last LP06 in the A+ and A- circuit.
                                       NOT TO BE USED FOR INSTALLATION PURPOSES.
          Nittan reserves the right to make changes at any time without notice in prices, colours, materials,
          components, equipment, specifications and models and also to discontinue models.                                                                        CR1D-EW-DAT-00   Rev.0
                                                               Page 4 of 5
     ■ Example of Applications
              Applications                             Solutions
                                          Fire monitoring for the place where
             Ironworks plant                  may become hot by motors
                                        Fire monitoring for the large printing
             Printing factory           machine which uses organic solvent
                                          Monitoring for waste which may fire
        Waste incineration plant           spontaneously in waste storage
                                          (Correspond to high-ceiling place)
                                          Monitoring for waste storage which
            Chemical factory                   may fire spontaneously
     ■ Specifications
                 Specifications                        CR1D-EW-A03                           CR1D-EW-A04                          CR1D-EW-A05
           Detection Response Time            Normal                                Fast                                Fast
                      EOL                     Equipped                              Equipped                            Not epuipped
             Explosion-proof class            Ex db II CT6 Gb
                 Rated Voltage                24 VDC
               Operating Voltage              19.2 VDC to 33.6 VDC
                 Rated Current                L-C        : 50 mA (Max.)
                                              K-C        : 50 mA (Max.)
                                              I+ - C     : 6 mA (standby), 40 mA (alarm)
               Operating Current              L-C        : 10 μA and less
                                              K-C        : 10 μA and less
         Sensitivity / Detection Range        High       : 60 m (default)
                                              Middle     : 30 m
        (for 0.1 m2 n-Heptane pan fire)       Low        : 15 m
                  Field of View               100° (±50°)
                                              Alarm                                   : Red                (steady)
                                              Trouble                                 : Yellow             (steady or flashing)
                 LED Indicator                Remote Test                             : Blue               (flashing)
                                              Startup                                 : Green              (flashing)
                                              Normal                                  : Off
                                              Power supply voltage drops              : Red                (flashing)
                                              0.5mm² Flexible copper 8 core cable
                                              L(white), C(Black), K(Green), I+( Red), T(Yellow), X(Brown), Y(Blue)
                                              0.75mm² Flexible copper 1 core cable
               Accessory Cables               G(Yellow / Green)
                                              Length                            : 5m
                                              Sheath Outer Diameter(mm)        : 6.6mm
        Conditions for detecting lens dirt    Infrared transmittance lever: less than 50%
            Operating Temperature             -20°C to +60°C
                Exclosure Rating              IP66 (Dust-proof, Water-proof / IP67 (Dust-proof, Submersion-proof)
                                              Body    : Stainless steel
                    Material                  Window : Sapphire
                                              Bracket : Stainless steel
              Dimensions / Weight             120m(H) x 100m(W) x 179mm(D) / 2.7kg (with Mounting Bracket)
         Connectable Fire Alarm Panel         With LP-06               : 1PF, 1PK, 1PM, 1PN, 1PQ, 1PS, 1PV, etc.
                                              With ZMU and LP-06       : NFU-7000, NFU-7000-L
                                              MTE3-RD           : Flame Detector Testing Device
              Optional Accessory              CRD-EW-14A        : Sunshade for CR1D-EW
                                              CRD-EW-14B        : View angle restriction hood for CR1D-EW