Cooling Tower: User Manual
Cooling Tower: User Manual
MD cooling tower
I N STA L L AT I O N - O P E R AT I O N - M A I N T E N A N C E
Z0602117_G ISSUED 04/2019 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT
contents
This manual contains vital information for the proper installation and
Note operation of your cooling tower. Carefully read the manual before
installation or operation of the tower and follow all instructions.
Save this manual for future reference..
Overview....................................................................................................................................... 3
Tower Location............................................................................................................................ 4
Tower Shipment.......................................................................................................................... 4
Receiving Tower.......................................................................................................................... 5
Hoisting Tower............................................................................................................................. 5
Tower Installation........................................................................................................................ 6
Motor Wiring................................................................................................................................ 9
Mechanical Equipment........................................................................................................... 11
Tower Startup........................................................................................................................... 12
Tower Operation....................................................................................................................... 15
Freezing Weather Operation................................................................................................. 16
Water Quality and Blowdown............................................................................................... 19
Cooling Tower Inspection and Maintenance..................................................................... 21
Belt Tensioning......................................................................................................................... 22
Sheave Alignment.................................................................................................................... 24
Fan Motor Access and Removal.......................................................................................... 25
Cold Water Basin Access / Air Inlet Louver Removal......................................................27
Access Door Operation......................................................................................................... 28
Drift Eliminator Removal and Replacement....................................................................... 28
Distribution System Maintenance........................................................................................ 30
Schedule of Tower Maintenance.......................................................................................... 31
Seasonal Shutdown Instructions......................................................................................... 34
Maintenance Schedule............................................................................................................37
Troubleshooting........................................................................................................................ 38
2
overview
Safety First
The location and orientation of the cooling tower can affect the safety of those
responsible for installing, operating or maintaining the tower. However, since
SPX Cooling does not determine the location or orientation of the tower, we
cannot be responsible for addressing those safety issues that are affected
by the tower’s location or orientation.
3
overview
Those are only some of the safety issues that may arise in the design
process. SPX strongly recommends that you consult a safety engi-
neer to be sure that all safety considerations have been addressed.
Several options are available that may assist you in addressing some of these
personnel safety concerns, including:
— mechanical access platform and ladder
— ladder extensions (used where the base of the tower is elevated)
— safety cages for ladders
— safety gate for ladders
Tower Location
Space available around the tower should be as generous as possible to pro-
mote ease of maintenance—and to permit freedom of airflow into and through
the tower. If you have questions about the adequacy of the available space
and the intended configuration of the tower, please contact your Marley sales
representative for guidance.
Prepare a stable, level support foundation for the tower, utilizing weight, wind
load, and dimensional information appearing on appropriate Marley submittal
drawings. Supports must be level to insure proper operation of the tower.
Tower Shipment
Unless otherwise specified, MD cooling towers ship by truck on trailer(s),
which lets you receive, hoist, and install the tower in one continuous operation.
Single-cell towers ship on one truck. Multicell towers, depending on their size,
and towers with access options (i.e. factory assembled access platforms) may
require more than one truck.
Responsibility for the condition of the tower upon its arrival belongs to the
truck driver—as does the coordination of multiple shipments, if required. Each
tower has recommended tie down instructions by which they should be se-
cured to the flatbed. Drivers should follow these instructions when securing
the tower to the flat-bed.
4
receiving and hoisting
Receiving Tower
Prior to unloading the tower from the delivering carrier, inspect the shipment
for evidence of damage in transit. If damage is apparent, note the freight bill
accordingly. This will support your future recovery claim.
Find and remove the installation instruction drawings and bills of material
located in a plastic container in the cold water basin. This information should
be kept for future reference and maintenance purposes.
Hoisting Tower
All models consist of two modules per cell. Both modules have hoisting clips.
Detailed hoisting drawing are included in the literature package.
LIFTING LIFTING
SLING SLING
WIDTH WIDTH
70° MAX
BOTH MODULES
5
installation
Tower Installation
These installation instructions are intended to help you prepare
Note before your tower arrives. If discrepancies exist between these
instructions and those shipped with the tower, the instructions
shipped with the tower will govern.
6
installation
Protect adjacent areas from excessive heat and sparks during weld-
Caution ing or damage could occur.
7
installation
Side outlet sump connection: For shipping purposes, sumps are at-
tached upside down in the basin to prevent damage. Sumps are to be
installed in the square opening in the floor of the cold water basin of one
or more cells—sealed against leakage, and attached by machine bolts,
according to the installation drawing included. An appropriately sized
circular opening in the vertical face of the sump has been drilled to 125#
ANSI B16.1 flat-face flange specifications. A full faced gasket and ap-
propriately sized bolts (by others) must be used for proper distribution.
11. Attach makeup water supply piping to appropriately sized float valve con-
nection located in cold water basin. Tower drain and overflow connections
are located on the side of the collection basin. If you wish to pipe overflow
and drain water to a remote discharge point, make those connections also.
12. Attach your warm water return piping to the inlet connection.
Protect adjacent areas from excessive heat and sparks during welding
Caution or damage could occur.
8
installation
Motor Wiring
For maintenance/safety purposes, SPX recommends a lockout
Warning type disconnect switch for all mechanical equipment. In addition
to a disconnect switch, the motor should be wired to main power
supply through short circuit protection, and a magnetic starter with
overload protection.
Wire motor leads as shown on the motor nameplate matching the supply
voltage. Do not deviate from the motor nameplate wiring.
Internal space heaters may be present, depending upon the motor manufac-
turer. For space heater operation and wiring refer to the Marley “Fan Motor”
User Manual” User Manual Z0239042.
Either of following symbols may be shown on the motor nameplate –
Δ, Δ Δ, Y, or YY. These symbols represent how the motor is constructed on
the inside and in no way have anything to do with a Delta or Wye electrical
distribution system serving the motor.
When using a starter:
• Set motor overload protection to 110% of motor nameplate amps. This
setting allows the fan motor to operate during cooler weather. During
cooler weather it is common for the motor to draw 6 to 10% higher than
nameplate amps. High amps are common during tower commissioning
when the tower is dry and the ambient air temperature is cool.
Do not start the motor(s) more than four to five times per hour. Short
Note cycling the tower will cause fuses, breakers or O.L.s to operate and
will decrease motor life.
Do not start the motor more than four to five times per hour (each
Note low speed start and each high speed start count as one start).
9
installation
• Set the VFD solid state overload protection to 119% of motor nameplate
amps and set “maximum current parameter” in the VFD to motor nameplate
amps. “Maximum current parameter” will reduce fan speed and limit amp
draw to nameplate amps during cold weather operation. If furnished with
a mechanical O.L. set this at 110% over motor nameplate amps.
• Motor rotation must be the same in both VFD mode and By-pass mode.
• If cable distance between the VFD and motor is greater than 100 feet a DV/DT
output filter is recommended to avoid damage to the motor. 100 feet distance
is based on our field experience, the VFD manufacture may state different
distances and distance does vary depending on the VFD manufacture.
• Program the VFD for variable torque output.
• Do not start and stop the motor using the safety switch at the motor. If
the drive is being commanded to run and the load side is cycled ON and
OFF with the safety switch this may damage the VFD.
10
installation
Mechanical Equipment:
Always shut off electrical power to the fan motor prior to perform-
Warning ing any maintenance on the tower. Any electrical switches should
be locked out and tagged out to prevent others from turning the
power back on.
1. Spin the fan manually to assure that all fan blades properly clear the inside
of the fan cylinder. Observe the action of the sheaves and belts to be sure
that the motor is properly aligned with the fan sheave. If necessary, cor-
rect the alignment in accordance with the Belt Tensioning and Sheave
Alignment section on pages 21 and 24.
The following steps require operation of the fan motor while the access
Warning door is open. DO NOT view the fan operation from near or inside the
access door location. Fan rotation should be viewed from tower grade.
The access door should NOT be opened while the fan is operating.
Caution The fan rotation causes a negative pressure inside the cooling tower
and will abruptly pull the door open should access be attempted. Only
open the cooling tower access door when the fan is off and locked out.
2. Momentarily bump (energize) the motor and observe rotation of the fan.
The fan should rotate in a counterclockwise direction when viewed from
below. If rotation is backwards, shut off the fan and reverse two of the
three primary leads supplying power to the motor.
11
operation
3. Run the motor and observe the operation of the mechanical equipment.
Operation should be stable.
4. Check belt tension and torque on the fan and motor sheave after 10 to
60 hours of operation. See Torque Values on page 25.
Tower Startup
Microorganisms including Legionella bacteria can exist in premise
Warning plumbing including cooling towers. The development of an effective
water management plan (WMP) and implementation of maintenance
procedures are essential to prevent the presence, dissemination and
amplification of Legionella bacteria and other waterborne contami-
nants throughout premise plumbing. Before operating the cooling
tower, the water management plan and maintenance procedures
must be in place and regularly practiced.
Water System:
1. Consult a knowledgeable water treatment professional to clean and treat
your new cooling tower prior to startup. Cooling towers must be cleaned
and disinfected regularly in accordance with ASHRAE Standard 188 and
Guideline 12.
The water conditions during the initial tower operation are crucial in pre-
venting premature corrosion of galvanized steel (white rust). For at least
the first eight weeks of operation, pH should be controlled between 6.5
12
operation
and 8.0 with hardness and alkalinity levels between 100 and 300 ppm
(expressed as CaCO3).
2. Do NOT attempt any service unless the fan motor is locked out.
3. Remove any and all accumulated debris from tower. Pay particular atten-
tion to inside areas of cold water basin, louvers and drift eliminators. Make
sure that cold water suction screens are clear and properly installed.
4. Fill the water system to an approximate depth of 7" in the depressed area
of the cold water basin at the center of the tower. This is the recommended
operating water level. Adjust the float valve so that it is 75% open at that
level. Continue filling the system until the water reaches a level approxi-
mately 1⁄8" below the lip of the overflow.
The system pumps and piping connected to the cooling tower must
Caution be configured such that the flowrate supplied to the water inlet of
each tower cell does not exceed the maximum design flowrate per
cell during startup, commissioning or operation. Overpumping will
result in elevated pressure levels in the tower’s water distribution
system - spray pressures exceeding 8.0 psi may damage the distri-
bution system.
5. Completely open all hot water flow control valves. Start your pump(s) and
observe system operation. Since the water system external to the tower
will have been filled only to the level achieved in the cold water basin, a
certain amount of “pump-down” of the basin water level will occur before
water completes the circuit and begins to fall from the fill. The amount
of initial pump-down may be insufficient to cause the float valve to open.
However, you can check its operation by pressing down on the operating
lever to which the stem of the float valve is attached.
Some trial and error adjustment of the float valve may be required to
balance the makeup water with tower operation. Ideally, the float valve
setting will be such that no water is wasted through the overflow at pump
shutdown. However, the water level after pump start-up must be deep
enough to assure positive pump suction.
13
operation
14
operation
Tower Operation
General:
The cold water temperature obtained from an operating cooling tower will vary
with the following influences:
1. Heat load With the fan in full operation, if the heat load increases, the
cold water temperature will rise. If the heat load reduces, the cold water
temperature will reduce.
Note that the number of degrees (“range”) through which the tower cools
the water is established by the system heat load and the amount of water
being circulated, in accordance with the following formula:
or — in SI units
The cooling tower establishes only the cold water temperature attainable
Heat Load (kilowatts)
Range – °C
under any operating =
circumstance.
liters/sec x 4.187
2. Air wet-bulb temperature Cold water temperature will also vary with the
wet-bulb temperature of the air entering the louvered faces of the tower.
Reduced wet-bulb temperatures will result in colder water temperatures.
However, the cold water temperature will not vary to the same extent as
the wet-bulb. For example, a 20°F reduction in wet-bulb may result in only
a 15°F reduction in cold water temperature.
3. Water flow rate Increasing the water flow rate (gpm) will cause a slight
elevation in cold water temperature, while reducing the water flow rate
will cause the cold water temperature to decrease slightly. However, at
a given heat load (see formula above), water flow reductions also cause
an increase in the incoming hot water temperature. Use care to prevent
the hot water from exceeding 125°F, in order to prevent damage to the
tower components.
4. Air flow rate Reducing air flow through the tower causes the cold wa-
ter temperature to rise. This is the approved method by which to control
leaving water temperature.
15
operation
If your tower is equipped with a two-speed motor, you will enjoy greater
opportunity for temperature control. When the water temperature becomes
too cold, switching the fan to half-speed will cause the cold water tem-
perature to rise—stabilizing at a temperature a few degrees higher than
before. With a further reduction in water temperature, the fan may be
cycled alternately from half-speed to off.
Do not start the motor more than four to five times per hour (each
Note low speed start and each high speed start count as one start).
16
operation
Slushy, transitory ice forms routinely in the colder regions of the fill
Note at low temperature. Such ice normally has no adverse effect on tower
operation, but its appearance should be a signal to the operator to
undertake ice control procedures. It is the operator's responsibil-
ity to prevent the formation of destructive (hard) ice on the cooling
tower fill and louvers. Certain guidelines should be followed:
1. Do not allow the tower’s leaving water temperature to drop below a mini-
mum allowable level—say 36°F to 40°F. If such low temperature operation
is necessary or beneficial to your process, establish the minimum allowable
level as follows:
During the coldest days of the first winter of operation, observe whether
any ice is forming on the bottom of the fill or the louvers. If hard ice is
present on either component, you must increase the allowable cold water
temperature. If the coldest possible water is beneficial to your process, ice
of a mushy consistency can be tolerated—but routine periodic observation
is advisable.
17
operation
It is recommended that you discuss your freeze prevention options with your
local Marley sales representative.
18
operation
19
operation
Blowdown:
A cooling tower cools water by continuously causing a portion of it to evaporate.
Although the water lost by evaporation is replenished by the makeup system, it
exits the tower as pure water—leaving behind its burden of dissolved solids to
concentrate in the remaining water. Given no means of control, this increasing
concentration of contaminants can reach a very high level.
In order to achieve water quality which is acceptable to the cooling tower (as
well as the remainder of your circulating water system), the selected water
treatment company must work from a relatively constant level of concentra-
tions. This stabilization of contaminant concentrations is usually accomplished
by blowdown, which is the constant discharge of a portion of the circulating
water to waste. As a rule, acceptable levels on which to base a treatment
schedule will be in the range of 2-4 concentrations. The following table shows
the minimum amount of blowdown (percent of flow) required to maintain dif-
ferent concentrations with various cooling ranges*:
Number of Concentrations
Cooling Range
1.5X 2.0X 2.5X 3.0X 4.0X 5.0X 6.0X
5° F (2.78° C) .78 .38 .25 .18 .11 .08 .06
10° F (5.56° C) 1.58 .78 .51 .38 .25 . 18 .14
15° F (8.33° C) 2.38 1.18 .78 .58 .38 . 28 .22
20° F (11.11° C) 3.18 1.58 1.05 .78 .51 .38 .30
25° F (13.89° C) 3.98 1.98 1.32 .98 .64 .48 .38
Multipliers are based on drift of 0.02% of the circulating water rate.
* Range = Difference between hot water temperature coming to tower and cold water tem-
perature leaving tower.
When water treatment chemicals are added, they should not be in-
Note troduced into the circulating water system via the cold water basin
of the cooling tower. Water velocities are lowest at that point, which
results in inadequate mixing.
20
maintenance
Do NOT attempt any service unless the fan motor is locked out.
• Consult a knowledgeable water treatment professional to clean and treat
your new cooling tower prior to startup. See Tower Startup section of this
manual.
• Cooling towers must be cleaned and disinfected regularly in accordance
with ASHRAE Standard 188 and Guideline 12.
• Workers performing decontamination procedures must wear personal
protective equipment (PPE) as directed by their facility safety officer.
• Cooling towers must be visually inspected regularly to assess signs of bacte-
rial growth, appearance of debris and scale on drift eliminators and general
operating conditions. Refer to ASHRAE Standard 188 and Guideline 12
for specific frequency recommendations.
• Replace worn or damaged components.
To minimize the presence of waterborne microorganisms, including Legionella,
follow the water management plan for your facility, perform regularly scheduled
cooling tower inspections and maintenance, and enlist the services of water
treatment professionals.
For additional technical support, contact your Marley sales represen-
tative. For help identifying the sales representative in your area, visit
spxcooling.com/replocator.
References:
ashrae.org. Search “ASHRAE Standard 188” and “ASHRAE Guideline 12.”
cdc.gov. Search “Water Management Program.”
21
maintenance
Belt Tensioning:
Always shut off electrical power to the tower fan motor prior to
Warning performing any inspections that may involve physical contact with
the mechanical or electrical equipment in or on the tower. Lock out
and tag out any electrical switches to prevent others from turning
the power back on. Service personnel must wear proper personal
protective clothing and equipment.
On the MD5006 thru MD5010, the fan motor and belt adjustment mechanism
is located outside the tower. Remove the motor protection hood by loosening
the two thumbscrews on top and hinge the hood up and out of the way. Also,
remove the motor sheave safety bracket and set aside. See the following images.
On the MD5016 thru MD5018 the motor is located inside the tower plenum.
Open the access door (see Access Door Opening Procedure) and hinge out
of the way.
SAFETY
BRACKET
Belt tension on all models is adjusted by turning a large threaded rod(s) that
drives the motor mounting plate away from (or toward) the fan centerline.
22
maintenance
23
maintenance
early failure. Specific tools are made to measure the tension of a V-belt drive
system. A Dodge® V-Belt Tension Tester, Browning® Belt Tension Checker
or equivalent an alternative should be used for tensioning V-belts. Check with
you local belt supplier.
Belt tension is measured by applying a force perpendicular to the belt at the
center point between motor and fan sheaves. The belt should deflect 1⁄64 of
the entire span, (measured sheave centerline to sheave centerline) when the
pressure shown in the table below is applied. Because belt tension is a func-
tion of the motor sheave diameter, it is necessary to inspect the motor sheave
to determine the diameter. If diameter markings are unreadable, measure the
sheave diameter at the bottom of the sheave grooves.
New belts (operating less than 8 hours) should be tensioned to the maximum
value. Tension after this period should use no less than the minimum value. If
the belt span was measured in inches, then use the pounds of force values.
If the belt span was measured in centimeters, then use the kilograms of force
values. If specific tensioning instructions are provided with your tensioning
tool, those instructions should be used instead.
Sheave Alignment:
Motor Sheave Used V-Belt New V-Belt
diameter minimum maximum
3.4" - 4.2" 4.9 lb 7.2 lb
85cm - 105cm 2.2 kg 3.3 kg
4.4" - 5.6" 7.1 lb 10.5 lb
106cm - 140cm 3.2 kg 4.8 kg
5.8" - 8.6" 8.5 lb 12.6 l
141cm - 220 cm 3.9 kg 5.7 kg
Always shut off electrical power to the tower fan motor prior to
Warning performing any inspections that may involve physical contact with
the mechanical or electrical equipment in or on the tower. Lock out
and tag out any electrical switches to prevent others from turning
the power back on. Service personnel must wear proper personal
protective clothing and equipment.
• The motor sheave is to be positioned as close as possible to the motor
in order to minimize torque on the motor bushings.
• The motor and fan sheaves may have grooves that are not used. The bot-
tom surface of the motor and fan sheaves must be aligned within 1⁄8" of
24
maintenance
each other and level within 1⁄2° (1⁄8" in 12") in order to not adversely affect
belt and sheave life.
Sheave Assembly Bolt Torque
• Alignment can be achieved by placing a straight edge across the top of
Busing Type ft·lbƒ N·m
the sheaves making sure that it is level and measuring down to the bottom
SD 5 10 surface of both sheaves at four points. See photo.
SK 15 20
• The number of grooves on the motor and fan sheaves may not match
SF 25 30
each other, or the number of grooves on the belt. Always install the belts
E 35 50
on the highest grooves on the fan sheave. Doing so will reduce the force
on the fan shaft bearings, thus increasing their life.
25
maintenance
MD5006 through MD5010 models’ fan motors are oriented with the shaft up.
The motor may be hoisted by threading an eye bolt into the motor shaft and
lifting with a hoist. To remove the motor fastener hardware, lift on the motor
slightly with the hoist to remove the weight from the fasteners, then loosen
and remove motor fasteners.
On MD5016 through MD5018 models, the fan motor is located inside the
plenum of the cooling tower. The motor can be accessed through the mechani-
cal access panel. See the Access Door Operation section for instruction on
opening the access panel. Remove the drive belt by following the instructions
in the Belt Tensioning section.
HINGE MOTOR MOUNT
HARDWARE RETAINING BOLTS
JACKING SCREW
ACCESS PANEL
OPENING
INSIDE VIEW
Motor inside plenum models are equipped with either a hinged or sliding
motor plate. For hinged motor plate models, loosen the motor mount system
retaining bolts shown in the image. It is not necessary to loosen any hard-
ware other than what is indicated. Hinge the motor mounting system 90° out
through the access panel. Attach a hoist to the motor with straps or chains.
Lift on the motor slightly with the hoist to remove the weight from the motor
fasteners, then loosen and remove motor fasteners.
For sliding motor plate models, the motor may be hoisted out through the fan
cylinder opening. Turn the adjustment rod(s) counterclockwise to slide the
motor toward the interior of the cooling tower. Remove the portion of the fan
guard nearest the motor location. It may be necessary to de-pitch or remove
one or more fan blades —consult the fan manual accompanying the cooling
tower. Attach a hoist to the motor with straps or chains. Lift on the motor
26
maintenance
slightly with the hoist to remove the weight from the motor fasteners, then
loosen and remove motor fasteners.
If the motor is removed from the mounting plate, it should be reinstalled at the
torques specified—do not lubricate the bolts.
Motor Mounting Bolt Torque
Machine Bolt Galvanized Stainless
Size ft·lbƒ N·m ft·lbƒ N·m
10mm 15 20 30 40
12mm 25 35 50 65
16mm 65 85 120 160
20mm 125 170 230 315
Collection basin floor has uneven surfaces and has the potential to
Caution be slippery. Care should be taken if entering the basin.
Louver edges can be very sharp and could cut skin if proper protec-
tion is not used. Always wear gloves and sleeves when handling
louver packs.
27
maintenance
Always shut off electrical power to the tower fan motor prior to
Warning performing any inspections that may involve physical contact with
the mechanical or electrical equipment in or on the tower. Lock out
and tag out any electrical switches to prevent others from turning
the power back on. Service personnel must wear proper personal
protective clothing and equipment.
Eliminator edges can be very sharp and could cut skin if proper
Caution protection is not used. Always wear gloves and sleeves when han-
dling eliminator packs.
28
maintenance
To remove the eliminator, stand inside the access panel and lift with two hands
on an eliminator section, this will indicate where one section stops and another
starts. Lift the eliminators at that intersection, removing two packs at one time
(see image). Once the first two packs are removed, the remaining packs should
be easily removed. Pay close attention to the orientation and placement, they
are not symmetrical. Each pack should be replaced at the location which it
was removed. Repeat this process for the second half of the tower.
29
maintenance
Distribution System Maintenance:
To keep your MD cooling tower operating at peak performance, it may be
necessary to clear the spray system of debris or sediment. To access the spray
system, remove the drift eliminators as explained in the previous section. Ob-
serve the spray system with full flow on the unit. Each nozzle should produce
a cone pattern spray which overlaps the adjacent nozzle patterns—see image.
30
maintenance
It may also be necessary to remove an entire branch arm from the spray sys-
tem. Each arm is held in place with a retention strap bolted to the branch arm
supports. Remove the bolts attaching the strap to the support and pull sharply
on the branch arm to disengage from the header box. It may be necessary to
rotate the branch arm while pulling out from the header box.
When branch arms are removed, access to the interior of the spray header
box is available to clean and remove any debris or sediment. A drain nozzle
at the centerline of the header box is intended to drain water from the system
at shutdown, as well as be removed to wash out the header box if necessary.
Be sure to replace this nozzle if removed.
Reinstall the branch arms to the header, engaging them far enough to align
the bolts of the tie down strap to the spray system supports. It may be neces-
sary to wet the rubber grommet and pipe to facilitate assembly. Ensure that
all nozzles are aligned to the bottom of the branch arm.
Included with this instruction packet are separate User Manuals on each ma-
jor operating component of the tower, and it is recommended that you read
them thoroughly. Where discrepancies may exist, the separate User Manuals
will take precedence. The following is recommended as a minimum routine
of scheduled maintenance:
31
maintenance
Always shut off electrical power to the tower fan motor prior to
Warning performing any inspections that may involve physical contact with
the mechanical or electrical equipment in or on the tower. Lock out
and tag out any electrical switches to prevent others from turning
the power back on. Service personnel must wear proper personal
protective clothing and equipment.
32
maintenance
Inspect the spray system and nozzles for any blockage. Nozzles can be re-
moved from the grommet by pulling sharply down on the nozzles. To replace
the nozzles, wet the surface of the nozzle and grommet and push nozzle back
into place.
33
maintenance
To the extent that the galvanizing (zinc coating) still exists, paint
Note will not adhere to it readily. Contact the manufacturer of the coating
you intend to use for instructions.
The motor should be operated for three hours at least once a month. This
serves to dry out windings and lubricate bearing surfaces (refer to Marley
“Fan Motor” User Manual User Manual Z0239042.
At start of new operating season, make sure bearings are adequately lubricated
before returning motor to service. Does not apply to motors with sealed bearings.
34
maintenance
Prolonged Shutdown:
If shutdown period is longer than seasonal, contact your Marley sales repre-
sentative for additional information.
35
additional information
36
maintenance schedule
Maintenance Service Monthly Semi-annually Seasonal Startup or Annually
Inspect General Condition and Operation x x
Air inlet x x
Nozzles x x
Collection basin x x
Check:
Blowdown–adjust as required x x
Change oil R
Belt drive:
Fan shaft bearing lubrication (every 3 mo.) every 3 months every 3 months
Fan:
Motor:
Structure:
37
troubleshooting
Motor will not start Wrong connections Check motor and control connections against wiring diagrams.
Check nameplate voltage against power supply. Check voltage at
Low voltage
motor terminals.
Open circuit in motor winding Check stator windings for open circuits.
Disconnect motor from load and check motor and Geareducer for
Fan drive stuck
cause of problem.
Rotor defective Look for broken bars or rings.
Stop motor and attempt to start it. Motor will not start if single phased.
Motor running single-phase
Check wiring, controls and motor.
Motor leads connected incorrectly Check motor connections against wiring diagram on motor.
Bad bearings Check lubrication. Replace bad bearings.
Unusual motor noise
Electrical unbalance Check voltages and currents of all three lines. Correct if required.
Air gap not uniform Check and correct bracket fits or bearing.
Rotor unbalance Rebalance.
Cooling fan hitting end bell-guard Reinstall or replace fan
Wrong voltage or unbalanced Check voltage and current of all three lines against nameplate values.
voltage
Check fan blade pitch. See Fan User Manual. Check for drag in fan
Overload
drivetrain as from damaged bearings.
Check nameplate against power supply. Check RPM of motor and gear
Wrong motor RPM
ratio.
Remove grease reliefs. Run motor up to speed to purge excessive
Bearings over greased
grease. Does not apply to motors with sealed bearings.
Wrong lubrication in bearings Change to proper lubricant. See motor manufacturer’s instructions.
Stop motor and attempt to start it. Motor will not start if single phased.
One phase open
Check wiring controls and motor
Motor runs hot Clean motor and check ventilation openings. Allow ample ventilation
Poor ventilation
around motor.
Winding fault Check with Ohmmeter.
Bent motor shaft Straighten or replace shaft.
Remove plugs and regrease bearings. Does not apply to motors with
Insufficient grease
sealed bearings.
Limit cumulative acceleration time to a total of 30 seconds per hour.
Too frequent starting or speed
Set on/off or speed change set-points farther apart. Consider installing
changes
a Marley VFD for fine temperature control.
Deterioration of grease or foreign Flush bearings and relubricate. Does not apply to motors with sealed
material in grease bearings.
Bearings damaged Replace bearings.
38
troubleshooting
Unusual fan drive vibration Make certain all blades are as far from center of fan as safety devices
Fan permit. All blades must be pitched the same. See Fan User Manual.
Clean off deposit build-up on blades
Worn Geareducer bearings Check fan and pinion shaft endplay. Replace bearings as necessary.
Disconnect load and operate motor. If motor still vibrates, rebalance
Unbalanced motor
motor.
Bent Geareducer shaft Check fan and pinion shaft with dial indicator. Replace if necessary.
Blade rubbing inside of fan
Adjust cylinder to provide blade tip clearance.
Fan noise cylinder
Loose bolts in blade clamps Check and tighten if necessary
Insufficient blowdown See “Water Treatment” section of this manual.
Scale or foreign substance in
circulating water system Consult competent water treating specialist. See “Water Treatment”
Water treatment deficiency
section of this manual.
Check to see if local heat sources are affecting tower. See if
Entering wet-bulb temperature
surrounding structures are causing recircuation of tower discharge air.
is above design
Discuss remedy with Marley representative.
Design wet-bulb temperature May have to increase tower size. Discuss remedy with Marley
was too low representative.
Cold-water temperature too
Actual process load greater May have to increase tower size. Discuss remedy with Marley
warm
than design representative.
(see “Tower Operation”)
Overpumping Reduce water flow over tower to design conditions.
Check motor current and voltage to be sure of correct contract power.
Repitch fan blades if necessary. Clean louvers, fill and eliminators.
Tower starved for air
Check to see if nearby structure or enclosing walls are obstructing
normal airflow to tower. Discuss remedy with Marley representative.
Spray system malfunction Inspect spray system for proper operation. Correct as necessary.
Excessive drift exiting tower Check to see that the eliminators are clean, free of debris and installed correctly.
Faulty drift elimination
Clean if necessary. Replace damaged or worn out components.
39
MD cooling tower
U S E R M A N UA L