System No. C-AJ-2109
ED
Classified by
Underwriters Laboratories, Inc.
to UL 1479 W Rating - Class 1 (See Items 2, 3 and 4)
3
3 2 2 1
A A
5
4 4
5
SECTION A-A
1. Floor or Wall Assembly — Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall
may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 12 in. (305 mm).
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufactures.
2. Steel Sleeve — (Optional) — Nom 12 in. (305 mm) diam (or smaller) Schedule 40 (or heavier) steel pipe cast or grouted into floor or wall
assembly, flush with floor or wall surfaces a max of 3 in. (76 mm) above the floor. If the steel sleeve extends above the floor, the T Rating of the
firestop system is 0 Hr and a min 1/2 in. (13 mm) annular space is required between the through penetrant (Item 3) and the periphery of the
opening. The W Rating does not apply when the steel sleeve is used.
3. Through Penetrants — One nonmetallic pipe to be installed either concentrically or eccentrically within the firestop system. For max 6 in. (152
mm) diam pipes, the annular space between the pipe and the periphery of opening shall be min 0 in. (0 mm, point contact) to max 1/2 in. (13 mm).
For nom 8 in. (203 mm) and 10 in. (254 mm) diam pipes, the annular space between the pipe and the periphery of opening shall be min 0 in. (0
mm, point contact) to max 1-1/4 in. (32 mm). If the steel sleeve extends above the floor (Item 2), a min 1/2 in. (13 mm) annular space is required
between the through penetrant (Item 3) and the periphery of the opening. Pipe to be rigidly supported on both sides of floor or wall assembly. For
systems with a W Rating, the max annular space is 1/2 in. (13 mm). The T Ratings are dependent on the size and/or type of pipe as shown in the
table below. The following types and sizes of nonmetallic pipes may be used:
A. Polyvinyl Chloride (PVC) Pipe — Nom 10 in. (254 mm) diam (or smaller) Schedule 40 solid core or cellular core PVC pipe for use in closed
(process or supply ) or vented (drain, waste or vent) piping systems. For systems with a W Rating, the nom diam of pipe shall not exceed 6 in.
(152 mm).
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 10 in. (254 mm) diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or
supply) piping systems. For systems with a W Rating, the nom diam of pipe shall not exceed 6 in. (152 mm).
C. Acrylonitrile Butadiene Styrene (ABS) Pipe — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 solid-core or cellular core ABS pipe for use
in closed (process or supply) or vented (drain, waste or vent) piping system.
D. Flame Retardant Polypropylene (FRPP) Pipe — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 FRPP pipe for use in closed (process or
supply) or vented (drain, waste or vent) piping systems.
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
July 31, 2018
Hilti Firestop Systems Page: 1 of 2
CAJ 2109
System No. C-AJ-2109
Pipe Nom Pipe F Rating
Type Diam, In. (mm) Hr
PVC, CPVC Greater than 6 (152) 2
PVC, CPVC, ABS, FRPP 6 (152) or smaller 3
Pipe Nom Pipe T Rating
Type Diam, In. (mm) Hr
PVC, CPVC, ABS, FRPP 1-1/2, 2, 3 (38, 51, 76) 2
PVC, CPVC, ABS, FRPP 4 (102) 3
PVC, CPVC, ABS+, FRPP 6 (152) 3
PVC, CPVC Greater than 6 (152) 0
ABS++ 6 (152) 0
+ Indicates solid core ABS only.
++ Indicates cellular core ABS only.
4. Fill, Void or Cavity Material* — Sealant — Min 1/2 in. (13 mm) thickness of fill material applied within the annulus, flush with top or bottom surface
of floor or both surfaces of wall. Sealant is optional for pipes having a max diam of 6 in. (152 mm) in unsleeved openings. For systems with W
Rating and/or L Rating, min 1/2 in. (13 mm) thickness of CP 601S, CFS-S SIL GG, CFS-S SIL SL (floors only) Sealant shall be applied within the
annulus, flush with top or bottom surface of floor.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE MAX Intumescent Sealant, CP 601S Sealant, CFS-S SIL GG, CFS-S SIL
SL (floors only) Sealant
4A. Packing Material — (Not Shown) — Min 1/2 in. (13 mm) thickness of 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into annular
space and recessed from the top surface of floor to accommodate the required thickness of fill material. Required only when CP 604 Sealant is
used.
5. Firestop Device* — Firestop Collar — Firestop collar shall be installed in accordance with the accompanying installation instructions. Collar to be
installed and latched around the pipe and secured to underside of floor or both sides of wall using the anchor hooks provided with the collar.
Minimum two anchor hooks for nom 1-1/2 and 2 in. (38 and 51 mm) diam pipes. Minimum three anchor hooks required for nom 3 and 4 in. (76 and
102 mm) diam pipes. Minimum four anchor hooks required for nom 6 in. (152 mm) diam pipes. Minimum ten anchor hooks required for nom 8 in
(203 mm) diam pipes. Minimum twelve anchor hooks required for nom 10 in. (254 mm) diam pipes. The anchor hooks are to be secured with min
1/4 in. (6 mm) diam by min 1-1/4 in. (32 mm) long steel expansion bolts or min 0.145 in. (3.7 mm) diam by 1-1/4 in. (32 mm) long powder actuated
fasteners utilizing a 1-7/16 in. (37 mm) diam by 1/16 in. (1.6 mm) thick steel washer. As alternates to the anchors specified above, Hilti 1/4 in. (6
mm) diam by 1-1/4 in. (32 mm) long KWIK-CON II+ concrete screw anchor, Hilti 1/4 in. (6 mm) diam by 1-3/4 in. (45 mm) long KWIK-BOLT 3 steel
expansion anchor or Hilti X-DNI 27 P8 S15 powder actuated floor pin with integral nom 9/16 in. (15 mm) diam washer may be used.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 643N 50/1.5", CP 643N 63/2", CP 643N 90/3", CP 643N 110/4", CP 643 160/6",
CP 644-200/8" US or CP 644-250/10" US Firestop Collar
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
respectively.
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
July 31, 2018