0% found this document useful (0 votes)
6 views2 pages

MCCB Ma

The LV429740 is a Compact NSX100F circuit breaker designed for motor protection with a rated current of 100 A and a breaking capacity of up to 85 kA depending on the voltage. It features a magnetic trip unit, is suitable for isolation, and complies with various international standards including IEC and UL. The product is environmentally sustainable and comes with an 18-month warranty.

Uploaded by

JW
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
6 views2 pages

MCCB Ma

The LV429740 is a Compact NSX100F circuit breaker designed for motor protection with a rated current of 100 A and a breaking capacity of up to 85 kA depending on the voltage. It features a magnetic trip unit, is suitable for isolation, and complies with various international standards including IEC and UL. The product is environmentally sustainable and comes with an 18-month warranty.

Uploaded by

JW
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Product datasheet LV429740

Characteristics circuit breaker Compact NSX100F - MA - 100 A - 3


poles 3d

Main
Range Compact
Product or component type Circuit breaker
Device short name Compact NSX100F
Circuit breaker application Motor protection
Poles description 3P
Protected poles description 3t
Network type AC
Network frequency 50/60 Hz
[In] rated current 100 A ( 40 °C )
100 A ( 65 °C )

It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand 8 kV
voltage
[Ue] rated operational voltage 690 V AC 50/60 Hz
Breaking capacity code F
Breaking capacity 10 kA at 600 V AC 50/60 Hz conforming to UL 508
20 kA at 600 V AC 50/60 Hz conforming to NEMA
AB1

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
35 kA at 480 V AC 50/60 Hz conforming to NEMA

Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
AB1
35 kA at 480 V AC 50/60 Hz conforming to UL 508
85 kA at 240 V AC 50/60 Hz conforming to NEMA
AB1
85 kA at 240 V AC 50/60 Hz conforming to UL 508
Icu 22 kA at 525 V AC 50/60 Hz conforming to IEC
60947-2
Icu 30 kA at 500 V AC 50/60 Hz conforming to IEC
60947-2
Icu 35 kA at 440 V AC 50/60 Hz conforming to IEC
60947-2
Icu 36 kA at 380/415 V AC 50/60 Hz conforming to
IEC 60947-2
Icu 8 kA at 660/690 V AC 50/60 Hz conforming to
IEC 60947-2
Icu 85 kA at 220/240 V AC 50/60 Hz conforming to
IEC 60947-2
[Ics] rated service breaking Ics 11 kA 525 V AC 50/60 Hz conforming to IEC
capacity 60947-2
Ics 35 kA 440 V AC 50/60 Hz conforming to IEC
60947-2
Ics 36 kA 380/415 V AC 50/60 Hz conforming to
IEC 60947-2
Ics 4 kA 660/690 V AC 50/60 Hz conforming to IEC
60947-2
Ics 85 kA 220/240 V AC 50/60 Hz conforming to
IEC 60947-2
Ics 12.5 kA 500 V AC 50/60 Hz conforming to IEC
60947-2
Suitability for isolation Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2
Utilisation category Category A
Trip unit name MA
Trip unit technology Magnetic
Trip unit protection functions I
Trip unit rating 100 A ( 65 °C )
Protection type Short-circuit protection (magnetic)

1/2
Pollution degree 3 conforming to IEC 60664-1

Complementary
Control type Toggle
Mounting mode Fixed
Mounting support Backplate
Upside connection Front
Downside connection Front
Mechanical durability 50000 cycles
Electrical durability 10000 cycles 690 V In conforming to IEC 60947-2
20000 cycles 690 V In/2 conforming to IEC 60947-2
30000 cycles 440 V In conforming to IEC 60947-2
50000 cycles 440 V In/2 conforming to IEC 60947-2
Connection pitch 35 mm
Local signalling Positive contact indication
Short-time pick-up adjustment type Isd Adjustable
[Isd] short-time pick-up adjustment range 9...14 x In
Height 161 mm
Width 140 mm
Depth 86 mm
Product weight 2.05 kg

Environment
Electrical shock protection class Class II
Standards EN 60947-2
IEC 60947-2
NEMA AB1
UL 508
Product certifications CSA
UL
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Ambient air temperature for operation -35...70 °C
Ambient air temperature for storage -55...85 °C

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0819 - Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Available

Contractual warranty
Period 18 months

2/2