Instruction Book Part 1 of 2
Instruction Book Part 1 of 2
Part 1 of 2
M-3425A
Generator Protection
PROTECTION
Generator Protection
M-3425A
Integrated Protection System® for Generators of All Sizes
–2–
M-3425A Generator Protection Relay
PROTECTIVE FUNCTIONS
Device Setpoint
Number Function Ranges Increment Accuracy†
Phase Distance (three-zone mho characteristic)
Circle Diameter #1,#2,#3 0.1 to 100.0 Ω 0.1 Ω 0.1 Ω or 5%
(0.5 to 500.0 Ω) ( 0.5 Ω or 5%)
Offset #1,#2,#3 –100.0 to 100.0 Ω 0.1 Ω 0.1 Ω or 5%
21 (–500.0 to 500.0 Ω) ( 0.5 Ω or 5%)
Impedance Angle #1,#2,#3 0° to 90° 1° 1°
Load Encroachment Blinder #1,#2,#3
Angle 1° to 90° 1° 1°
R Reach 0.1 to 100 Ω
Time Delay #1,#2,#3 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
Out-of-Step Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
Overcurrent Supervision 0.1 to 20 A 0.1 A 0.1 A or 2%
(0.02 to 4 A) 0.01 A 0.02 A or 2%
When out-of-step blocking on Zone 1 or Zone 2 is enabled, Zone 3 will not trip and it will be used to detect the
out-of-step condition for blocking Function 21 #1 and/or 21 #2.
Volts / Hz
Definite Time
Pickup #1, #2 100 to 200% 1% 1%
Time Delay #1, #2 30 to 8160 Cycles 1 Cycle 25 Cycles
24
Inverse Time
Pickup 100 to 200% 1% 1%
Characteristic Curves Inverse Time #1–#4 — —
Time Dial: Curve #1 1 to 100 1
Time Dial: Curves #2–#4 0.0 to 9.0 0.1
Reset Rate 1 to 999 Sec. 1 Sec. .02 Sec. or 1%
(from threshold of trip)
The percent pickup is based on nominal VT secondary voltage and nominal system frequency settings. The
pickup accuracy stated is only applicable from 10 to 80 Hz, 0 to 180 V, 100 to 150% V/Hz and a nominal voltage
setting of 120 V.
Phase Undervoltage
†
Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.
–3–
M-3425A Generator Protection Relay
†
Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.
–4–
M-3425A Generator Protection Relay
Pickup
50
BF-Ph
Phase Current 0.10 to 10.00 A 0.01 A 0.1 A or 2%
50 (0.02 to 2.00 A) ( 0.02 A or 2%)
BF 50
BF-N Neutral Current 0.10 to 10.00 A 0.01 A 0.1 A or 2%
(0.02 to 2.00 A) ( 0.02 A or 2%)
Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
50BF can be initiated from designated M-3425A output contacts or programmable control/status inputs.
Definite Time Overcurrent
–5–
M-3425A Generator Protection Relay
50 Overcurrent
Pickup 0.5 to 15.00 A 0.01 A 0.1 A or 2%
50/ (0.1 to 3.00 A) ( 0.02 A or 2%)
27
27 Undervoltage
Pickup 5 to 130 V 1V 0.5 V
Pick-up Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
Drop-out Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
Inverse Time Neutral Overcurrent
†
Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.
–6–
M-3425A Generator Protection Relay
Phase Overvoltage
Multi-purpose input that may be used for turn-to-turn stator ground protection, bus ground protection, or as an
extra Phase-Phase, or Phase-Ground voltage input.
VT Fuse-Loss Detection
A VT fuse-loss condition is detected by using the positive and negative sequence components
of the voltages and currents. VT fuse-loss output can be initiated from internally generated
60 logic, and/or from input contacts.
FL
Alarm Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
Three Phase VT
Fuse Loss Detection Enable/Disable
†
Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.
–7–
M-3425A Generator Protection Relay
Definite Time*
Pickup 0.5 to 240.0 A 0.1 A 0.1 A or 3%
(0.1 to 48.0 A) ( 0.02 A or 3%)
Time Delay 1 to 8160 Cycles 1 Cycle –1 to +3 Cycles or 1%
Inverse Time*
67N Pickup 0.25 to 12.00 A 0.01 A 0.1 A or 3%
(0.05 to 2.40 A) ( 0.02 A or 3%)
Characteristic Curve Definite Time/Inverse/Very Inverse/Extremely Inverse/IEC Curves
Moderately Inverse/Very Inverse/Extremely Inverse/IEEE Curves
Time Dial 0.5 to 11.0 0.1 3 Cycles or 5%
0.05 to 1.10 (IEC Curves) 0.01
0.5 to 11 (IEEE curves) 0.01
Directional Element
Max Sensitivity Angle (MSA) 0 to 359° 1°
Polarizing Quantity 3Vo (calculated), VN or VX
*Directional control for 67NDT or 67NIT may be disabled.
VX polarization cannot be used if 25 function is enabled.
3Vo polarization can only be used with line-ground VT configuration.
Operating current for 67N can be selected as 3Io (calculated) or IN (Residual CT).
If 87GD is enabled, 67N with IN (Residual CT) operating current will not be available.
Out of Step (mho characteristic)
†
Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.
–8–
M-3425A Generator Protection Relay
Frequency Accumulation
†
Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.
–9–
M-3425A Generator Protection Relay
IPSlogicTM
IPSlogic uses element pickups, element trip commands, control/status input state changes,
IPS output contact close signals to develop 6 programmable logic schemes.
Time Delay #1–#6 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%
Breaker Monitoring
The AUX input is provided for monitoring the integrity of the trip circuit. This input can be used for nominal trip coil
voltages of 24 V dc, 48 V dc, 125 V dc and 250 V dc.
Nominal Settings
†
Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.
–10–
M-3425A Generator Protection Relay
Sync Check
25D Dead Check
Dead Voltage Limit 0 to 60 V 1V 0.5 V or ±0.5%
Dead Time Delay 1 to 8160 Cycles 1 Cycle –1 to +3 Cycles or 1%
25S Sync Check
Phase Angle Window 0° to 90° 1° 1°
Upper Voltage Limit 60 to 140 V 1V 0.5 V or ±0.5%
25
Lower Voltage Limit 40 to 120 V 1V 0.5 V or ±0.5%
Delta Voltage Limit 1.0 to 50.0 V 0.1 V 0.5 V or ±0.5%
Delta Frequency Limit 0.001 to 0.500 Hz 0.001 Hz 0.0007 Hz or ±5%
Sync Check Time Delay 1 to 8160 Cycles 1 Cycle –1 to +3 Cycles or ±1%
Various combinations of input supervised hot/dead closing schemes may be selected. The 25 function cannot be
enabled if the 59D function with VX or 67N function with VX is enabled.
Field Ground Protection
Pickup 2 to 40 mA 1 mA 1 mA
64S Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle* or 1%
Undervoltage Inhibit 5 to 30 V 1V 0.5 V to 0.5%
External low frequency generator, band pass filter and current transformer are required for this function. 59D and
27TN function should be disabled when the 64S function is enabled. 59N may be applied when this function is
enabled.
†
Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating.
–11–
M-3425A Generator Protection Relay
Description
The M-3425A Generator Protection Relay is suitable for all generator ratings and prime movers. Typical
connection diagrams are illustrated in Figure 4, M-3425A One-Line Functional Diagram (configured for phase
differential), and Figure 5, One-Line Functional Diagram (configured for split-phase differential).
Configuration Options
The M-3425A Generator Protection Relay is available in either a Base or Comprehensive package of
protective functions. This provides the user with flexibility in selecting a protective system to best suit the
application. Additional Optional Protective Functions may be added at the time of purchase at per-function
pricing.
The Human-Machine Interface (HMI) Module, Target Module, or redundant power supply can be selected at
time of purchase.
When the Field Ground (64F) Premium Protective Function is purchased, an external coupler module
(M-3921) is provided for isolation from the dc field voltages.
When 100% Stator Ground (64S) protection using low-frequency injection is purchased, an external band
pass filter and frequency generator is provided.
Metering
The relay provides metering of voltages (phase, neutral and sequence quantities), currents (phase, neutral
and sequence quantities), real power, reactive power, power factor and impedance measurements.
Metering accuracies are:
Voltage: 0.5 V or 0.5%, whichever is greater
0.8 V or 0.75%, whichever is greater (when both RMS and Line-Ground to Line-Line are
selected)
Current: 5 A rating, 0.1 A or 3%, whichever is greater
1 A rating, 0.02 A or 3%, whichever is greater
Power: 0.01 PU or 2% of VA applied, whichever is greater
Frequency: 0.02 Hz (from 57 to 63 Hz for 60 Hz models; from 47 to 53 Hz for 50 Hz models)
0.1 Hz beyond 63 Hz for 60 Hz models, and beyond 53 Hz for 50 Hz models
Volts/Hz: 1%
Oscillographic Recorder
The oscillographic recorder provides comprehensive data recording of all monitored waveforms, storing up to
472 cycles of data. The total record length is user-configurable from 1 to 16 partitions. The sampling rate is 16
times the power system nominal frequency (50 or 60 Hz). The recorder may be triggered using either the
designated control/status inputs, trip outputs, or using serial communications. When untriggered, the recorder
continuously stores waveform data, thereby keeping the most recent data in memory. When triggered, the
recorder stores pre-trigger data, then continues to store data in memory for a user-defined, post-trigger delay
period. The data records can be stored in either Beckwith Electric format or COMTRADE format.
Target Storage
Information associated with the last 32 trips is stored. The information includes the function(s) operated, the
functions picked up, input/output status, time stamp, and phase and neutral currents at the time of trip.
–12–
M-3425A Generator Protection Relay
Calculations
Current and Voltage RMS Values: Uses Discrete Fourier Transform algorithm on sampled voltage and current
signals to extract fundamental frequency phasors for relay calculations. RMS calculation for the 50, 51N, 59
and 27 functions, and the 24 function are obtained using the time domain approach to obtain accuracy over a
wide frequency band. When the RMS option is selected, the magnitude calculation for 59 and 27 functions is
accurate over a wide frequency range (10 to 80 Hz). When the DFT option is selected, the magnitude
calculation is accurate near nominal frequency (50 Hz/60 Hz) but will degrade outside the nominal frequency.
For 50 and 51N functions the DFT is used when the frequency is 55 Hz to 65 Hz for 60 Hz (nominal) and 45 Hz
to 55Hz for 50 Hz (nominal), outside of this range RMS calculation is used.
Sensing Inputs
Five Voltage Inputs: Rated for a nominal voltage of 50 V ac to 140 V ac at 60 Hz or 50 Hz. Will withstand 240
V continuous voltage and 360 V for 10 seconds. Source voltages may be line-to-ground or line-to-line
connected. Phase sequence ABC or ACB is software selectable. Voltage transformer burden less than 0.2 VA
at 120 V ac.
Seven Current Inputs: Rated nominal current (IR) of 5.0 A or 1.0 A at 60 Hz or 50 Hz. Will withstand 3IR
continuous current and 100IR for 1 second. Current transformer burden is less than 0.5 VA at 5 A, or 0.3 VA
at 1 A.
Control/Status Inputs
The control/status inputs, INPUT1 through INPUT6, can be programmed to block any relay protective function,
to trigger the oscillograph recorder, to operate one or more outputs or can be an input into IPSlogicTM. To
provide breaker status LED indication on the front panel, the INPUT1 control/status input contact must be
connected to the 52b breaker status contact.
The optional expanded I/O includes an additional 8 programmable control/status inputs (INPUT7 through
INPUT14).
▲ CAUTION: The control/status inputs should be connected to dry contacts only, and are internally connected
(wetted) with a 24 V dc power supply.
Output Contacts
Any of the functions can be individually programmed to activate any one or more of the eight programmable
output contacts OUTPUT1 through OUTPUT8. Any output contact can also be selected as pulsed or latched.
IPSlogic can also be used to activate an output contact.
The optional expanded I/O includes an additional 15 programmable output contacts (OUTPUT9 through
OUTPUT23). These contacts are configurable only using IPScom software.
The eight output contacts (six form ‘a’ and two form ‘c’), the power supply alarm output contact (form ‘b’), the
self-test alarm output contact (form ‘c’) and the optional 15 expanded I/O output contacts (form 'a') are all rated
per ANSI/IEEE C37.90-1989 for tripping. Make 30 A for 0.2 seconds, carry 8 A, break 6 A at 120 V ac, break
0.5 A at 48 V dc; 0.3 A, 125 V dc; 0.2 A, 250 V dc with L/R=40 mSec.
–13–
M-3425A Generator Protection Relay
IPSlogic
This feature can be programmed utilizing the IPScom® Communications Software. IPSlogic takes the contact
input status and function status, and by employing (OR, AND, and NOT) boolean logic and a timer, can
activate an output or change setting profiles.
Communication
Communications ports include rear panel RS-232 and RS-485 ports, a front panel RS-232 port, a rear-panel
IRIG-B port and an Ethernet port (optional). The communications protocol implements serial, byte-oriented,
asynchronous communication, providing the following functions when used with the Windows™-compatible
M-3820D IPScom® Communications Software. MODBUS and BECO 2200 protocols are supported providing:
• Interrogation and modification of setpoints
• Time-stamped information for the 32 most recent trips
• Real-time metering of all quantities measured
• Downloading of recorded oscillographic data and Sequence of Events Recorder data.
When the optional Ethernet port is purchased it also provides MODBUS over TCP/IP and BECO2200 over
TCP/IP protocols.
IRIG-B
The M-3425A Generator Protection Relay can accept either modulated or demodulated IRIG-B time clock
synchronization signal. The IRIG-B time synchronization information is used to correct the hour, minutes,
seconds, and milliseconds information.
–14–
M-3425A Generator Protection Relay
Temperature
Controller M-3425A
R1 IN X
C Alarm/Trip
IN RTN
R2
Impulse Voltage
IEC 60255-5 5,000 V pk, +/- polarity applied to each independent circuit to earth
5,000 V pk, +/- polarity applied between each independent circuit
1.2 by 50 μs, 500 ohms impedance, three surges at 1 every 5 seconds
Insulation Resistance
IEC 60255-5 > 40 Megaohms
–15–
M-3425A Generator Protection Relay
Electrical Environment
Electrostatic Discharge Test
EN 60255-22-2 Class 4 (8 kV)—point contact discharge
EN 60255-22-2 Class 4 (15kV)–air discharge
■ NOTE: The signal is applied to the digital data circuits (RS-232, RS-485, IRIG-B, Ethernet communication
port and field ground coupling port) through capacitive coupling clamp.
Radiated Susceptibility
ANSI/IEEE 25-1000 Mhz @ 35 V/m
C37.90.2
Output Contacts
ANSI/IEEE Make 30 A for 0.2 seconds, off for 15 seconds for 2,000 operations, per Section 6.7.1, Tripping
C37.90.0 Output Performance Requirements
Atmospheric Environment
Temperature
IEC 60068-2-1 Cold, –20° C
IEC 60068-2-2 Dry Heat, +70° C
IEC 60068-2-3 Damp Heat, +40° C @ 93% RH
Mechanical Environment
Vibration
IEC 60255-21-1Vibration response Class 1, 0.5 g
Vibration endurance Class 1, 1.0 g
–16–
M-3425A Generator Protection Relay
Compliance
UL-Listed per 508 – Industrial Control Equipment
UL-Listed Component per 508A Table SA1.1 Industrial Control Panels
CSA-Certified per C22.2 No. 14-95 – Industrial Control Equipment
CE Safety Directive – EN61010-1:2001, CAT II, Pollution Degree 2 (Pending for expanded I/O option.)
Physical
Without Optional Expanded I/O
Size: 19.00" wide x 5.21" high x 10.20" deep (48.3 cm x 13.2 cm x 25.9 cm)
Mounting: The unit is a standard 19", semiflush, three-unit high, rack-mount panel design, conforming to
ANSI/EIA RS-310C and DIN 41494 Part 5 specifications. Vertical or horizontal panel-mount options are
available.
Approximate Weight: 17 lbs (7.7 kg)
Approximate Shipping Weight: 25 lbs (11.3 kg)
External Connections
M-3425A external connection points are illustrated in Figures 2 and 3.
–17–
3
2
BECKW IT H ELECT RIC CO . INC. W A RNING! CO NT A CT W IT H T ERMINA L S MA Y CA US E EL ECT RIC S HO CK MODEL: M-3425A FIRMWARE: D-0150
R
R
6 19 0 118 t h AV E NO . FO R CO NT A CT RA T INGS S EE INS T RUCT IO N MA NUA L
5 0 Hz 6 0 Hz S ERIA L NO .
8 3 F4
L A RGO , FL 3 3 7 7 3 727- 5 4 4 - 23 26
L IS T ED NRT L / C
IND.CO NT .EQ LR 8 9 4 6 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
IRIG- B COM 2
COM2 RS 2 3 2
ETHERNET 24 IN IN IN IN IN IN IN
48 - + - +
! 125
6 5 4 3 2 1 RT N
250 ! P/ S S ELF- T EST 8 7 6 5 4 3 2 1
RS 4 8 5 (5 2 b)
1 A UX COM 3 INPUTS A LA RMS OUT PUTS
V V V
A B C VN IA IB IC IN Ia Ib Ic PS 2 PS 1 PS2 PS1
! F IE L D G N D VA B VB C VC A
COUPLER + - + -
F1 F2
4
3 A MP,2 5 0 V ( 3 A B)
M-3425A Generator Protection Relay
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
64 VX 65 64S 18 - 5 6 18 - 5 6
64F 0 .0 1A NO M 85 265 85 265
F3 F4
RA T ED V O L T A GE
RAT ED CURRENT
6 0 - 14 0 V A C,5 0 / 6 0 Hz 1A ,NO M 5 A ,NO M
■ NOTES:
–18–
1. See M-3425A Instruction Book Section 2.3, Setpoints and Time Settings, subsection for 64B/F Field Ground Protection.
2. Before making connections to the Trip Circuit Monitoring input, see M-3425A Instruction Book Section 5.5, Circuit Board Switches and Jumpers,
for the information regarding setting Trip Circuit Monitoring input voltage. Connecting a voltage other than the voltage that the unit is configured
to may result in mis-operation or permanent damage to the unit.
3. 8 WARNING: ONLY DRY CONTACTS must be connected to inputs (terminals 5 through 10 with 11 common) because these contact
inputs are internally wetted. Application of external voltage on these inputs may result in damage to the units.
4. 8 WARNING: The protective grounding terminal must be connected to an earthed ground any time external connections have been
made to the unit.
BECKW IT H ELECT RIC CO . INC. W A RNING! CO NT A CT W IT H T ERMINA L S MA Y CA US E EL ECT RIC S HO CK MODEL: M-3425A FIRMWARE: D-0150
6 19 0 118 t h AV E NO .
FO R CO NT A CT RA T INGS S EE INS T RUCT IO N MA NUA L 5 0 Hz 6 0 Hz S ERIA L NO .
L A RGO , FL 3 3 7 7 3 727- 5 4 4 - 23 26
IN IN IN IN IN IN IN IN IN
RT N 14 13 12 11 10 9 8 7
R
C US 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9
83F4 INPUTS OUT PUTS
2 LIST ED
IND. CONT . EQ . 12 15 16 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
1 2 3 4 5 6 7 8 9 10 11 13 14 17 18
IRIG- B COM 2
RS 2 3 2
1 24 IN IN IN IN IN IN IN
48 - + - +
COM 2 ! 125
6 5 4 3 2 1 RT N 6 5 4 2
ETHERNET P/ S S ELF- T EST 8 7 3 1
250 RS 4 8 5 (5 2 b) !
A UX COM 3 INPUTS A LA RMS OUT PUTS
V V V PS 1
A B C VN IA IB IC IN Ia Ib Ic PS 2 PS2 PS1
! F IE L D G N D VA B VB C VC A
COUPLER + - + -
F1 F2
3 A MP,2 5 0 V ( 3 A B)
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
64 VX 65 64S 18 - 5 6 18 - 5 6
64F 0 .0 1A NO M 85 265 85 265
F3 F4
4 RA T ED V O L T A GE 3 RAT ED CURRENT
6 0 - 14 0 V A C,5 0 / 6 0 Hz 1A ,NO M 5 A ,NO M
–19–
Figure 3 External Connections (With Optional Expaned I/O)
■ NOTES:
1. See M-3425A Instruction Book Section 2.3, Setpoints and Time Settings, subsection for 64B/F Field Ground Protection.
2. Before making connections to the Trip Circuit Monitoring input, see M-3425A Instruction Book Section 5.5, Circuit Board Switches and Jumpers,
for the information regarding setting Trip Circuit Monitoring input voltage. Connecting a voltage other than the voltage that the unit is configured
to may result in mis-operation or permanent damage to the unit.
3. 8 WARNING: ONLY DRY CONTACTS must be connected to inputs (terminals 5 through 10 with 11 common and terminals 68 through
75 with 66 and 67 common) because these contact inputs are internally wetted. Application of external voltage on these inputs may
result in damage to the units.
4. 8 WARNING: The protective grounding terminal must be connected to an earthed ground any time external connections have been
made to the unit.
M-3425A Generator Protection Relay
M-3425A Generator Protection Relay
Targets CT
50 50
(Optional) BFPh DT
Integral HMI VT (Note 1)
(Optional)
CT (Residual)
Metering (Note 4)
87
Waveform Capture
25 52
VT Gen
IRIG-B
Front RS232
Communication
81R 81A 81 27 59 24 M
Rear RS232
Communication (Metering) VT (Note 1)
Rear Ethernet
Port (Optional)
Rear RS-485 (Note 3)
Communication M-3921
59X +
Multiple Setting
Groups
-
Programmable I/O
64F 64B
27
Self Diagnostics
CT (Neutral)
59D Line Side 87 50 50N 51N (Notes 2 & 5)
Voltage 27
27 GD BFN
(Software Select) 59D 64S 59N R
32
TN
R
–20–
M-3425A Generator Protection Relay
Targets CT (Residual)
(Optional) (Note 5)
Integral HMI
(Optional) 25 52
VT Gen
Metering
Waveform Capture
81R 81A 81 59 27 24 M
IRIG-B
(Metering)
50 CT (Note 3)
Front RS232 DT
Communication
Rear RS232
Communication VT (Note 1)
Rear Ethernet
Port (Optional)
(Note 2)
Rear RS-485 M-3921
Communication 59X +
Multiple Setting
Groups -
Self Diagnostics
CT
78 60FL 51V 50/27 40 32 21 50 49 46 M
Dual Power Supply
(Optional) (Metering)
Breaker
Monitoring
Trip Circuit
Monitoring 3VO (Calculated)
(Note 4)
VX
Event Log 67N
VN 67N Polarization
(Software Select)
VX 3VO (Calculated)
–21–
M-3425A Generator Protection Relay
17.48 [44.4]
ACTUAL
5.21 [13.23]
ACTUAL
Rear View
10.20 [25.91]
19.00
[48.26]
19.00 [48.26]
0.33
18.34 [46.58] [0.84]
2.35 [5.96]
1.35 [3.42]
■ NOTE: Panels for vertical mounting are available (See Figure 8).
–22–
M-3425A Generator Protection Relay
10.20
[25.9]
19.00
[48.26]
.25 X .45 SLOT [.64 X 1.14]
4 PLACES
OUTPUTS
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
COM 1
RELAY BRKR
TARGET
TARGET
4.00 OK CLOSED TARGET PS 1
RESET
[10.16]
TIME OSC. PS 2
6.96 SYNC TRIG
[17.68]
M-3425A
GENERATOR PROTECTION
R
B EC KWIT H
CO . INC .
E L EC T R IC
OUTPUTS
Made in U.S.A. EXIT ENTER OUT 1 OUT 3 OUT 5 OUT 7
1.48 OUT 2 OUT 4 OUT 6 OUT 8
3.76
0.33 18.34
[0.84] [46.58]
–23–
M-3425A Generator Protection Relay
5.65
[13.41]
0.40 [1.02] x
0.27 [0.68] 5.59
SLOT (4x) [14.20]
0.33 2.25 ACTUAL
[0.84] [5.72] 1.71
[4.34]
17.5
[44.45]
19.00
[48.26] 17.31
18.34 [43.97]
[46.58] Actual
Rear View
n NOTE: Dimensions in brackets are
in centimeters.
RECOMMENDED CUTOUT WHEN
RELAY IS A PANEL MOUNT
■ NOTES:
1. When mounted vertically, the target module will be located at the top and all front-panel text will be
horizontally aligned. Consult Beckwith Electric Co. for details.
2. Expanded I/O not avilable on vertical mount chassis model.
Figure 8 Vertical Mounting Dimensions (Without Expanded I/O)
–24–
M-3425A Generator Protection Relay
18.34
.34 [46.17]
[.86] 17.50
[44.45]
1.48
[3.76]
2.25
[5.72]
5.28
[13.40]
\U+2205.28 (4X)
RECOMMENDED CUTOUT
STANDARD 3 UNIT PANEL M-3425A
18.34
.34 [46.17]
[.86] 17.50
[44.45]
1.48
[3.76]
7.03
[17.86]
4.00
[10.16]
\U+2205.28 (4X)
RECOMMENDED CUTOUT
4 UNIT PANEL M-3425A (EXTENDED I/O)
TOLERANCE: .XX±.015
–25–
M-3425A Generator Protection Relay
PROTECTION RELAY
M-3425A
PROCESSOR
Excitation
System
Squarewave
Generator Gen.
Rotor
Signal COUPLING
Measurement NETWORK
and Processing (M-3921)
Shaft
Ground
Brush
Ground/Machine Frame
NOTES:
1. The above circuit measures insulation resistance (Rf) between rotor field winding and ground (64F).
2. Relay injects 15 V squarewave (Vout) and measures return signal (Vf) to calculate Rf.
3. The injection frequency can be set (0.1 to 1.0 Hz) based on the rotor capacitance, in order to
improve accuracy.
4. The signal rise time is analyzed to determine if shaft brushes are lifting or open (64B).
5. May also be applied on generators with brushless excitation with a grounding brush and pilot
ground fault detection brush.
Function Specification
Field/Exciter Supply Voltage Rating (Terminal (3) to (2)):
• 60 to 1200 V dc, continuous
• 1500 V dc, 1 minute
Operating Temperature: –20° to +70°, Centigrade
–26–
M-3425A Generator Protection Relay
Voltage Withstand
Isolation
4 kV ac for 1 minute, all terminals to case
Impulse Voltage
IEC 60255–5, 5,000 V pk, 1.2 by 50 μs, 0.5 J, 3 positive and 3 negative impulses at 5 second
intervals per minute
Electrical Interference
Electrostatic Discharge Test
IEC 61000-4-2 Class 4 (8 kV)—point contact discharge
Radiated Susceptibility
ANSI/IEEE 25-1000 Mhz @ 20 V/m
C37.90.2
Atmospheric Environment
IEC 60068–2–1 Cold, –20° C
IEC 60068–2–2 Dry Heat, +70° C
IEC 60068–2–3 Damp Heat, +40° C @ 93% RH
Enclosure Protection
NEMA 1, IEC IPC-65
–27–
7.87 [19.99] 2.96 REF [7.52]
BECKWIT H
CO. INC.
EL ECT RIC
Made in U.S.A.
9.06 [23.01]
3.54 [9.0]
MOUNTING PATTERN
WITHOUT TABS
2 00
0
BECKWITH ELECTRIC CO., INC.
1:
d
re
is
Re
g PHONE (727) 544-2326 • FAX (727) 546-0121
IS O
E-MAIL marketing@beckwithelectric.com
WEB PAGE www.beckwithelectric.com
– This sign warns that the area is connected to a dangerous high voltage, and you
must never touch it.
– This sign means that you should refer to the corresponding section of the operation
manual for important information before proceeding.
The following features, described in this Instruction Book, are only available for firmware version
D-0150-V01.00.33 and later:
Table of Contents
M-3425A Generator Protection
Instruction Book
Chapter 1 Introduction
1.1 Instruction Book Contents ................................................................. 1–1
1.2 M-3425A Generator Protection Relay ................................................ 1–2
1.3 Accessories ........................................................................................ 1–4
Chapter 2 Application
2.1 Configuration ...................................................................................... 2–1
Profiles ................................................................................................ 2–2
Functions ............................................................................................ 2–2
Special Considerations ........................................................................ 2–2
Relay System Setup .......................................................................... 2–3
2.2 System Diagrams ............................................................................... 2–7
2.3 Setpoints and Time Settings ........................................................... 2–13
21 Phase Distance ........................................................................... 2–14
24 Overexcitation Volts/Hz .............................................................. 2–18
25 Sync Check ................................................................................. 2–21
27 Phase Undervoltage .................................................................... 2–25
27TN Third Harmonic Undervoltage, Neutral .................................. 2–26
32 Directional Power ........................................................................ 2–30
40 Loss of Field ............................................................................... 2–35
46 Negative Sequence Overcurrent ................................................. 2–39
49 Stator Overload Protection ......................................................... 2–41
50/50N Instantaneous Overcurrent,Phase & Neutral Circuits ........ 2–44
50BF Generator Breaker Failure/HV Breaker Flashover................. 2–46
50DT Definite Time Overcurrent (for split-phase differential) ........ 2–49
50/27 Inadvertant Energizing ........................................................... 2–50
51N Inverse Time Neutral Overcurrent ............................................ 2–52
51V Inverse Time Phase Overcurrent with
Voltage Control/Restraint ................................................................. 2–53
59 Phase Overvoltage ...................................................................... 2–55
59D Third Harmonic Voltage Differential ......................................... 2–56
59N Overvoltage, Neutral Circuit or Zero Sequence ...................... 2–58
59X Multipurpose Overvoltage (Turn-to-Turn Stator Fault
or Bus Ground Protection) ............................................................... 2–59
60FL VT Fuse Loss ......................................................................... 2–61
64B/F Field Ground Protection ........................................................ 2–64
64F Field Ground Protection ............................................................ 2–64
64B Brush Lift-Off Detection ........................................................... 2–66
64S 100% Stator Ground Protection by Low Frequency
Signal Injection ................................................................................. 2–67
i
M-3425A Instruction Book
Chapter 3 Operation
3.1 Front Panel Controls ............................................................................ 3–1
Alphanumeric Display .......................................................................... 3–1
Screen Blanking .................................................................................. 3–1
Arrow Pushbuttons .............................................................................. 3–1
Exit Pushbutton ................................................................................... 3–1
Enter Pushbutton ................................................................................. 3–1
Target & Status Indicators and Controls .............................................. 3–1
Power Supply #1 (#2) LED ................................................................... 3–2
Relay OK LED ..................................................................................... 3–2
Oscillograph Recorded LED ................................................................. 3–2
Breaker Closed LED ............................................................................ 3–2
Target Indicators and Target Reset ..................................................... 3–2
Time Sync LED ................................................................................... 3–2
Diagnostic LED .................................................................................... 3–2
Accessing Screens ............................................................................. 3–2
Default Message Screens .................................................................. 3–2
3.2 Initial Setup Procedure/Settings ........................................................ 3–5
3.3 Setup Unit Data ................................................................................... 3–5
Setup Unit Data Entry .......................................................................... 3–5
Setup Unit Features That Do Not Require Data Entry .......................... 3–6
3.4 Setup System Data ............................................................................. 3–6
Configure Relay Data ........................................................................... 3–7
Setpoints and Time Settings ............................................................... 3–7
Oscillograph Recorder Data ................................................................. 3–8
Communications Settings .................................................................... 3–8
3.5 Status/Metering ................................................................................... 3–9
3.6 Target History .....................................................................................3–10
ii
Table of Contents
iii
M-3425A Instruction Book
Chapter 1
1-1 M-3925A Target Module ..................................................................... 1–3
1-2 M-3931 Human-Machine Interface (HMI) Module............................. 1–4
Chapter 2
2-1 Setup System Dialog Box ................................................................. 2–5
2-2 Selection Screen for Expanded Input ............................................... 2–6
2-3 Pulse Relay Expanded Output Screen .............................................. 2–6
2-4 Latch Relay Expanded Output Screen .............................................. 2–6
2-5 One-Line Functional Diagram ............................................................. 2–7
2-6 Alternative One-Line Functional Diagram
(configured for split-phase differential) .............................................. 2–8
2-7 Three-Line Connection Diagram ......................................................... 2–9
2-8 Function 25 Sync Check Three-Line Connection Diagram............. 2–10
2-9 Function 59X Turn-to-Turn Fault Protection Three-Line
Connection Diagram ......................................................................... 2–11
2-10 Function 67N, 59D, 59X (Bus Ground) Three-Line
Connection Diagram ......................................................................... 2–12
2-11 Selection Screen for Expanded I/O Initiate .................................... 2–13
2-12 Phase Distance (21) Coverage ........................................................ 2–15
2-13 Phase Distance (21) Function Applied for System Backup ........... 2–16
2-14 Phase Distance (21) Setpoint Ranges ............................................ 2–17
2-15 Example of Capability and Protection Curves (24) ......................... 2–19
2-16 Volts-per-Hertz (24) Setpoint Ranges .............................................. 2–20
2-17 Sync Check Logic Diagrams ........................................................... 2–23
2-18 Sync Check (25) Setpoint Ranges .................................................. 2–24
2-19 Phase Undervoltage (27) Setpoint Ranges ..................................... 2–25
2-20 Third-Harmonic Undervoltage (27TN) Protection Characteristics ... 2–27
2-21 27TN Blocking Regions .................................................................... 2–28
2-22 Third Harmonic Undervoltage, Neutral Circuit (27TN)
Setpoint Ranges ............................................................................... 2–29
2-23 Tripping on Reverse Power Flow
(Over Power with Negative Pickup) ................................................. 2–31
2-24 Tripping on Low Foward Power
(Under Power with Positive Pickup) ................................................ 2–32
2-25 Tripping on Overpower (Over Power with Positive Pickup) ........... 2–32
iv
Table of Contents
Chapter 2 (cont'd)
2-26 Tripping on Over Reactive Power with Element #3
(Over Power, Positive Pickup and Directional Power Sensing
Set to Reactive) ............................................................................... 2–33
2-27 Directional Power, 3-Phase (32) Setpoint Ranges .......................... 2–34
2-28 Loss of Field (40) Protective Approach 1 ....................................... 2–37
2-29 Loss of Field (40) Protective Approach 2 ....................................... 2–37
2-30 Loss of Field (40) Setpoint Ranges ................................................ 2–38
2-31 Negative Sequence Overcurrent Inverse Time Curves .................. 2–40
2-32 Negative Sequence Overcurrent (46) Setpoint Ranges .................. 2–40
2-33 Time Constant, Function 49 ............................................................ 2–41
2-34 49 Function Overload Curves .......................................................... 2–42
2-35 Stator Thermal Protection (49) Setpoint Ranges ............................ 2–43
2-36 Instantaneous Overcurrent (50) Setpoint Ranges ........................... 2–44
2-37 Instantaneous Neutral Overcurrent (50N) Setpoint Ranges ........... 2–45
2-38 Breaker Failure Logic Diagram ........................................................ 2–47
2-39 Breaker Failure (50BF) Setpoint Ranges ........................................ 2–48
2-40 Definite Time Overcurrent (50DT) Setpoint Ranges ....................... 2–49
2-41 Inadvertent Energizing Function Logic Diagram ............................. 2–51
2-42 Inadvertent Energizing (50/27) Setpoint Ranges ............................ 2–51
2-43 Inverse Time Neutral Overcurrent (51N) Setpoint Ranges ............. 2–52
2-44 Voltage Restraint (51VR) Characteristic ......................................... 2–54
2-45 Inverse Time Overcurrent with Voltage Control/Voltage
Restraint (51VC/VR) Setpoint Ranges ............................................ 2–54
2-46 Phase Overvoltage (59) Setpoint Ranges ....................................... 2–55
2-47 Third Harmonic Overvoltage Scheme for Generator
Ground-Fault Protection ................................................................... 2–57
2-48 Third Harmonic Voltage Differential (59D) Setpoint Ranges .......... 2–57
2-49 Overvoltage, Neutral Circuit or Zero Sequence (59N)
Setpoint Ranges ............................................................................... 2–58
2-50 Turn-to-Turn Stator Winding Fault Protection ................................. 2–59
2-51 Multipurpose Overvoltage (59X) Setpoint Ranges .......................... 2–60
2-52 Fuse Loss (60FL) Function Logic .................................................... 2–62
2-53 Fuse Loss (60FL) Setpoint Ranges ................................................. 2–63
2-54 M-3921 Field Ground Coupler .......................................................... 2–64
2-55 Field Ground Protection (64B/F) Setpoint Ranges ......................... 2–65
v
M-3425A Instruction Book
Chapter 2 (cont'd)
2-56 64S Function Component Connection Diagram .............................. 2–68
2-57 64S Function Time Delay Pickup Current Correlation .................... 2–68
2-58 100% Stator Ground Protection (64S) Setpoint Ranges ................ 2–69
2-59 Residual Directional Overcurrent (67N) Trip Characteristics .......... 2–70
2-60 Residual Directional Overcurrent (67N) Setpoint Ranges ............... 2–72
2-61 Out-of-Step Relay Characteristics ................................................... 2–74
2-62 Out-of-Step Protection Settings ....................................................... 2–74
2-63 Out-of-Step (78) Setpoint Ranges ................................................... 2–75
2-64 Example of Frequency (81) Trip Characteristics ............................ 2–77
2-65 Frequency (81) Setpoint Ranges ..................................................... 2–77
2-66 Frequency Accumulator (81A) Example Bands .............................. 2–79
2-67 Frequency Accumulator (81A) Setpoint Ranges ............................. 2–79
2-68 Rate of Change of Frequency (81R) Setpoint Ranges ................... 2–80
2-69 Differential Relay (87) Operating Characteristics............................ 2–81
2-70 Phase Differential (87) Setpoint Ranges ......................................... 2–81
2-71 Ground Differential (87GD) Setpoint Ranges .................................. 2–83
Chapter 3
3-1 M-3425A Front Panel ......................................................................... 3–3
3-2 Screen Message Menu Flow ............................................................. 3–3
3-3 Main Menu Flow ................................................................................. 3–4
vi
Table of Contents
Chapter 4
4-1 Multiple System Addressing Using
Communications Line Splitter ............................................................ 4–2
®
4-2 IPScom Menu Selections ................................................................ 4–6
4-3 IPScom Program Icon ........................................................................ 4–8
4-4 New Device Profile Dialog Box .......................................................... 4–9
4-5 Communication Dialog Box .............................................................. 4–10
4-6 Setup System Dialog Box ............................................................... 4–11
4-7 Expanded Input Active State ........................................................... 4–12
4-8 Pulse Relay Expanded Output Screen ............................................ 4–12
4-9 Latch Relay Expanded Output Screen ............................................ 4–12
4-10 Relay Setpoints Dialog Box ............................................................. 4–13
4-11 Typical Setpoint Dialog Box ............................................................ 4–13
4-12 Expanded I/O Initiate ....................................................................... 4–13
4-13 All Setpoints Table Dialog Box (Partial) ......................................... 4–14
4-14 Configure Dialog Box (Partial) ......................................................... 4–15
4-15 Configure Dialog Box Partial
(shown with Expanded Input/Outputs) ............................................. 4–16
4-16 Unit Date/Time Dialog Box .............................................................. 4–17
4-17 Target Dialog Box............................................................................. 4–18
4-18 Trigger Events Screen with Expanded I/O ..................................... 4–19
4-19 Event Log Viewer ............................................................................. 4–19
4-20 Event Download Screen ................................................................... 4–20
4-21 Setup Oscillograph Recorder ........................................................... 4–20
4-22 Retrieve Oscillograph Record Dialog ............................................... 4–20
4-23 Profile Switching Method Dialog ...................................................... 4–20
4-24 Select Active Profile ........................................................................ 4–21
4-25 Copy Active Profile .......................................................................... 4–21
4-26 About IPScom® Dialog Box ............................................................. 4–21
4-27 Primary Status Dialog Box .............................................................. 4–22
4-28 Secondary Status Dialog Box.......................................................... 4–22
4-29 Accumulator Status Screen ............................................................. 4–23
4–30 Phase Distance Dialog Box ............................................................. 4–23
4-31 Loss of Field Dialog Box ................................................................. 4–24
4-32 Out of Step Dialog Box ................................................................... 4–24
vii
M-3425A Instruction Book
Chapter 4 (cont.)
4-33 Phasor Dialog Box ........................................................................... 4–25
4-34 Sync Scope Screen ......................................................................... 4–25
4-35 Function Status Screen ................................................................... 4–26
4-36 IPSutil™ Main Menu Flow ............................................................... 4–29
4-37 Warning Message ............................................................................. 4–30
4-38 IPSutility Reset Relay Message ..................................................... 4–30
4-39 Monitor Status Screen ..................................................................... 4–31
4-40 Calibration Dialog Box ...................................................................... 4–31
4-41 Communication Dialog Box .............................................................. 4–32
4-42 Relay Comm Port Settings .............................................................. 4–32
4-43 Ethernet Settings .............................................................................. 4–32
4-44 Unit Date/Time Dialog Box .............................................................. 4–32
4-45 Change Communication Access Code Dialog Box ......................... 4–33
4-46 Change User Access Code Dialog Box .......................................... 4–33
4-47 Setup Dialog Box ................................................................................ 4–33
Chapter 1
1-1 M-3425A Device Functions ................................................................ 1–2
Chapter 2
2-1 Input Activated Profile ....................................................................... 2–3
2-2 Impedance Calculation ..................................................................... 2–17
2-3 Voltage Control Time Settings ......................................................... 2–36
2-4 Delta/Wye Transformer Voltage-Current Pairs ................................ 2–54
2-5 Typical Frequency Settings ............................................................. 2–65
2-6 Typical Brush Lift-Off Settings ........................................................... 2–66
Chapter 3
3-1 Recorder Partitions .............................................................................. 3–8
Chapter 4
4-1 Dead-Sync Time .................................................................................. 4–3
4-2 Microsoft Windows Keyboard Shortcuts ............................................. 4–28
viii
Table of Contents
Chapter 5 Installation
5.1 General Information ............................................................................ 5–1
5.2 Mechanical/Physical Dimensions ...................................................... 5–1
5.3 External Connections ......................................................................... 5–9
5.4 Commissioning Checkout ................................................................ 5–15
5.5 Circuit Board Switches and Jumpers .............................................. 5–20
Chapter 6 Testing
6.1 Equipment/Test Setup ........................................................................ 6–2
6.2 Functional Test Procedures ............................................................... 6–6
Power On Self Tests ......................................................................... 6–7
21 Phase Distance .............................................................................. 6–8
24 Volts per Hertz, Definite Time ......................................................... 6–9
24 Volts per Hertz, Inverse Time ........................................................6–10
25D Dead Check ................................................................................6–12
25S Sync Check ................................................................................6–14
27 Phase Undervoltage .......................................................................6–16
27TN Third-Harmonic Undervoltage, Neutral .......................................6–17
32 Directional Power, 3-Phase ............................................................ 6–21
40 Loss of Field ..................................................................................6–24
46 Negative Sequence Overcurrent Definite Time ..............................6–26
46 Negative Sequence Overcurrent Inverse Time ..............................6–27
49 Stator Overload Protection ......................................................... 6–28
50 Instantaneous Phase Overcurrent .............................................. 6–30
50BF/50BF-N Breaker Failure .......................................................... 6–31
50/27 Inadvertant Energizing ........................................................... 6–33
50DT Definite Time Overcurrent for Split-Phase Differential ......... 6–34
50N Instantaneous Neutral Overcurrent ......................................... 6–35
51N Inverse Time Neutral Overcurrent .......................................... 6–36
51V Inverse Time Phase Overcurrent with
Voltage Control/Restraint ................................................................. 6–37
59 RMS Overvoltage, 3-Phase ........................................................ 6–39
59D Third-Harmonic Voltage Differential ......................................... 6–40
59N Overvoltage, Neutral Circuit or Zero Sequence ...................... 6–41
59X Multipurpose Overvoltage ............................................................6–42
60FL VT Fuse Loss Detection ............................................................6–43
64F Field Ground Protection ...............................................................6–44
64B Brush Lift Off Detection...............................................................6–46
64S 100% Stator Ground Protection by Injection ...............................6–47
67N Residual Directional Overcurrent, Definite Time ..........................6–49
67N Residual Directional Overcurrent, Inverse Time ..........................6–51
78 Out of Step ....................................................................................6–53
81 Frequency ......................................................................................6–55
81A Frequency Accumulator ..............................................................6–56
81R Rate of Change of Frequency .................................................. 6–57
ix
M-3425A Instruction Book
Appendices
Appendix A: Configuration Record Forms ......................................... A–1
Appendix B: Communications............................................................ B–1
Appendix C: Self-Test Error Codes ................................................... C–1
Appendix D: Inverse Time Curves .................................................... D–1
Appendix E: Declaration of Conformity ............................................. E–1
x
Table of Contents
Chapter 5
5-1 M-3425A Mounting Dimensions – Horizontal Chassis ..................... 5–2
5-2 M-3425A Mounting Dimensions – Horizontal
Chassis (Expanded I/O) ..................................................................... 5–3
5-3 M-3425A Panel Mount Cutout Dimensions .......................................... 5–4
5-4 M-3425A Mounting Dimensions – Vertical Chassis ........................ 5–5
5-5 (H2) Mounting Dimensions ................................................................. 5–6
5-6 (H3) Mounting Dimensions for GE L-2 Cabinet ................................ 5–7
5-7 (H4) Mounting Dimensions .................................................................. 5-8
5-8 Optional Dual Power Supply .............................................................. 5–9
5-9 Expanded I/O Power Supply .............................................................. 5–9
5-10 External Connections ....................................................................... 5–10
5-11 Three-Line Connection Diagram ....................................................... 5–11
5-12 Function 25 Sync Check Three-Line Connection Diagram............. 5–12
5-13 Function 59X Turn-to-Turn Fault Protection Three-Line
Connection Diagram ......................................................................... 5–13
5-14 Function 67N, 59D, 59X (Bus Ground), Three-Line
Connection Diagram ......................................................................... 5–14
5-15 M-3425A Circuit Board ........................................................................5–22
5-16 M-3425A Circuit Board (Expanded I/O) ........................................... 5–23
Chapter 6
6-1 Voltage Inputs: Configuration V1 ......................................................... 6–3
6-2 Voltage Inputs: Configuration V2 ......................................................... 6–3
6-3 Current Inputs: Configuration C1 .......................................................... 6–4
6-4 Current Inputs: Configuration C2 .......................................................... 6–4
6-5 Current Configuration C3 ...................................................................... 6–5
6-6 64S Test Configuration ........................................................................ 6–5
6-7 Field Ground Coupler ..........................................................................6–45
6-8 Status LED Panel ...............................................................................6–70
6-9 M-3925A Target Module Panel ...........................................................6–71
6-10 M-3931 Human/Machine Interface (HMI) Module ................................6–71
6-11 COM1/COM2 Loopback Plug ..............................................................6–72
6-12 RS-485 2-Wire Testing ........................................................................6–74
6-13 Current Input Configuration .................................................................6–79
xi
M-3425A Instruction Book
Chapter 6 (cont'd)
6-14 Voltage Input Configuration ................................................................6–79
6-15 Voltage Input Configuration ................................................................6–79
6-16 Voltage Input Configuration ................................................................6–80
Appendix A
A-1 Human-Machine Interface (HMI) Module ...........................................A–6
A-2 Communication Data & Unit Setup Record Form ............................. A–7
A-3 Functional Configuration Record Form ............................................ A–10
A-4 Setpoint & Timing Record Form ...................................................... A–28
Appendix B
B-1 Null Modem Cable: M-0423 ................................................................B–2
B-2 RS-232 Fiber Optic Network .............................................................. B–3
B-3 RS-485 Network ................................................................................... B–4
B-4 COM2 Pinout for Demodulated TTL Level Signal ............................. B–4
Appendix D
D-1 Volts/Hz (24) Inverse Time Curve Family #1 (Inverse Square) .......D–2
D-2 Volts/Hz (24) Inverse Time Family Curve #2 ................................... D–3
D-3 Volts/Hz (24IT) Inverse Time Curve Family #3 ................................ D–4
D-4 Volts/Hz (24IT) Inverse Time Curve Family #4 ................................ D–5
D-5 BECO Definite Time Overcurrent Curve ...........................................D–8
D-6 BECO Inverse Time Overcurrent Curve ............................................ D–9
D-7 BECO Very Inverse Time Overcurrent Curve ................................. D–10
D-8 BECO Extremely Inverse Time Overcurrent Curve ........................ D–11
D-9 IEC Curve #1 – Inverse .................................................................. D–12
D-10 IEC Curve #2 – Very Inverse ......................................................... D–13
D-11 IEC Curve #3 – Extremely Inverse ................................................ D–14
D-12 IEC Curve #4 – Long Time Inverse .................................................. D–15
D-13 IEEE Inverse Time Overcurrent Curves ............................................ D–16
D-14 IEEE Very Inverse Time Overcurrent Curves .................................... D–17
D-15 IEEE Extremely Inverse Time Overcurrent Curves ........................... D–18
xii
Table of Contents
Chapter 5
5-1 Jumpers ............................................................................................ 5–20
5-2 Dip Switch SW-1 .............................................................................. 5–21
5-3 Trip Circuit Monitor Input Voltage Select Jumper Configuration .... 5–21
Chapter 6
6-1 Output Contacts ............................................................................... 6–68
6-2 Input Contacts .................................................................................. 6–69
Appendix A
A-1 Relay Configuration Table .................................................................. A–2
Appendix B
B-1 Communication Port Signals ............................................................. B–2
Appendix C
C-1 Self-Test Error Codes ........................................................................ C–1
Appendix D
D-1A M-3425A Inverse Time Overcurrent Relay Characteristic Curves ... D–6
Appendix E
E-1 Declaration of Conformity .................................................................. E–2
xiii
M-3425A Instruction Book
xiv
Introduction – 1
1 Introduction
This instruction book includes six chapters and five Chapter 4: Remote Operation
Appendices. Chapter 4 is designed for the person or group
responsible for the remote operation and setting of
Chapter 1: Introduction the relay using the M-3820D IPScom ®
Communications Software or other means.
Chapter One summarizes relay capabilities,
introduces the instruction book contents, and
describes accessories. Chapter 5: Installation
The person or group responsible for the installation
Chapter 2: Application of the relay will find herein all mechanical information
required for physical installation, equipment ratings,
Chapter Two is designed for the person or group and all external connections in this chapter. For
responsible for the application of the M-3425A
reference, the Three-Line Connection Diagram is
Generator Protection Relay. It includes functional
repeated from Chapter 2, Application. Further, a
and connection diagrams for a typical application of
commissioning checkout procedure is outlined using
the relay; and describes the configuration process
the HMI option to check the external CT and VT
for the unit (choosing active functions), output connections. Additional tests which may be desirable
contact assignment and input blocking designation. at the time of installation are described in Chapter
It also illustrates the definition of system quantities
6, Testing.
and equipment characteristics required by the
protective relay, and describes the individual function
settings. Chapter 6: Testing
This chapter provides step-by-step test procedures
Chapter 3: Operation for each function, as well as diagnostic mode and
autocalibration procedures for HMI-equipped units.
Chapter Three is designed for the person(s)
responsible for the operation, direct setting, and
configuration of the relay. Chapter Three provides Appendix A: Configuration Record Forms
information regarding the operation and interpretation This Appendix supplies a set of forms to record and
of the unit's front panel controls and indicators, document the settings required for the proper
including operation of the optional M-3931, Human operation of the relay.
Machine Interface (HMI) and M-3925A Target
Modules. It further describes the procedures for Appendix B: Communications
entering all required data to the relay. Included in
this chapter is a description of the process This Appendix describes port signals, protocols,
necessary for review of setpoints and timing, and various topologies, and equipment required for
monitoring function status and metering quantities, remote communication.
viewing the target history, and setup of the
oscillograph recorder.
1–1
M-3425A Instruction Book
Appendix C: Self-Test Error Codes The relay stores time-tagged target information for
This Appendix lists all the error codes and their the thirty-two most recent trips. For units equipped
definitions. with the optional M-3925A Target Module, LEDs are
used to provide a detailed visual indication of
function operation for the most recent event.
Appendix D: Inverse Time Curves
This Appendix contains a graph of the four families The unit retains up to 472 cycles of oscillograph
of Inverse Time Curves for V/Hz applications, the waveform data. This data can be downloaded and
Inverse Time Overcurrent Curves, and the IEC analyzed using the M-3801D IPSplot ® PLUS
curves. Oscillograph Analysis Software.
The unit is powered from a wide input range switch
Appendix E: Declaration of Conformity mode power supply. An optional redundant power
This Appendix contains the Beckwith Electric Co.’s supply is available for units without the Expanded
Declaration of Conformity required by ISO/IEC I/O. When expanded I/O option is selected, the unit
17050–1:2004. includes the second power supply.
The relay includes self-test, auto calibration, and
diagnostic capabilities, in addition to IRIG-B time-
1.2 M-3425A Generator
sync capability for accurate time-tagging of events.
Protection Relay
1–2
Introduction – 1
1–3
M-3425A Instruction Book
a
Figure 1-1 M-3925A Target Module
a
a
a
EXIT ENTER
1–4
Application – 2
2 Application
2–1
M-3425A Instruction Book
Control/status input IN1 is preassigned to be the The relay allows the user to designate up to six
52b breaker status contact. If a multiple breaker logic functions which perform similarly to internal
scheme is used, the control/status input IN1 must relay functions, using IPSlogicTM. These external
be the series combination of the “52b” breaker functions may be enabled or disabled, and output
contacts. Additional user-chosen control/status contacts and blocking control/status inputs are
inputs may initiate actions such as breaker failure, chosen the same as for the internal functions. The
initiate external fuse loss detection, or trigger the external functions are described in further detail in
oscillograph recorder. Section 2.3, Setpoint and Time Settings, IPSlogic
subsection.
■ NOTE: Uppercase text indicates selection.
27#1 PHASE UNDERVOLTAGE This menu designation is required for each relay function. After enabling
disable ENABLE the function, the user is presented with the two following screens:
This submenu item assigns the blocking designations (up to six, plus
27#1 BLOCK INPUT fuse-loss logic) for the enabled function. “OR” logic is used if more than
fl i6 i5 i4 i3 i2 I1 one input is selected.
This submenu item assigns the output contacts (up to eight) for the
27#1 RELAY OUTPUT particular relay function. If no output contacts are assigned, the function
o8 o7 o6 o5 o4 o3 o2 O1 will not generate any output or targets even though the function is enabled.
■ NOTE: Units with expanded I/O can only set OUT9–OUT23 and
IN7–IN14 using IPScom®.
Profiles Functions
Up to four setpoint profiles may be used. Each Configuration of the relay consists of enabling the
profile contains a complete set of function functions for use in a particular application,
configuration and settings. One of the four profiles designating the output contacts each function will
may be designated as the Active Profile, which will operate, and which control/status inputs will block
contain the settings that the relay will actively use. the function. The choices include eight programmable
output contacts (OUT1–OUT8) and six control/status
The Active Profile may be chosen manually or by inputs (IN1–IN6)/(OUT1–OUT23 and IN1–IN14 for
contact input. When the profile Switching Method is expanded I/O units) plus a block choice for fuse
set to Manual, the HMI, remote communications or loss logic operation (see Section 2.3, Setpoint and
one of the IPSlogic elements will select the Active Time Settings, 60FL Fuse Loss subsection for
Profile. When the Switching Method is set to Input details.)
Contact, the profile is selected by the input contacts.
When Input Contact is selected, only the input Control/status inputs may also initiate actions, such
contacts can switch the relay’s profile, and none of as Breaker Failure Initiate, Trigger Oscillograph
the Manual methods will switch the profile. Recorder, Switch Setpoint Profile, or initiate an
IPSlogic function. The control/status inputs and
A Copy Profile feature is available. This feature output contacts need to be chosen before configuring
copies an image of the Active Profile to any one of the individual functions. Both can be recorded on
the other three profiles. This feature can speed up the Relay Configuration Table in Appendix A, Forms.
the configuration process. Consider, for example, a
situation where a breaker will be removed from Special Considerations
service. Two profiles will be used: an “In Service” Control/status input IN1 is preassigned to be the
profile (Profile 1), and an “Out of Service” profile 52b breaker contact. IN5 and IN6 may be used to
(Profile 2). select setpoint profiles.
Profile 2 will be identical to the “In Service” profile, Outputs 1–6 and 9–23 are form “a” contacts (normally
with the exception of the overcurrent settings. open), and outputs 7 and 8 are form “c” contacts
(center tapped “a” and “b” normally closed) contacts.
Profile 1 is set to be the Active Profile, and all
Output contacts 1–4 contain special circuitry for
setpoints entered. An image of Profile 1 will then be
copied to Profile 2 with the Copy Active Profile high-speed operation and pick up 4 ms faster than
outputs 5–8. Function 87 outputs are recommended
command. Profile 2 is then selected as the Active
to be directed to OUT1 through OUT4 contacts.
Profile, and the overcurrent setpoints modified.
2–2
Application – 2
INPUT ACTIVATED PROFILES When Input Activated Profiles is disabled, the Active Profile can be
disable enable selected using HMI or remote communication. When enabled, the
Active Profile is selected by the state of Input 5 and 6 (see Table 2-1).
ACTIVE SETPOINT PROFILE This screen sets the active setpoint profile.
________
This screen initiates a copy of the Active Profile to any one of the
COPY ACTIVE PROFILE
other profiles.
TO_PROFILE_1
NOMINAL CURRENT The secondary CT current of the phase CT’s with rated generator
________ Amps current. I nom = (VA $ (Vgen rated(S3) )(CT ratio) )
This screen allows the user to select the phase rotation of the M-3425A
PHASE ROTATION
to match the generator.
a-c-b a-b-c
2–3
M-3425A Instruction Book
This screen allows the selection of RMS or DFT for the 59 and 27
59/27 MAGNITUDE SELECT
functions. The magnitude can be selected as the RMS of the total
rms dft waveform (including harmonics) or the RMS of the 60/50 Hz fundamental
component of the waveform using the Discrete Fourier Transform (DFT).
When the RMS option is selected, the magnitude calculation is accurate
over a wide frequency range (10 to 80 Hz) and the accuracy of the time
delay is +20 cycles. When the DFT option is selected, the magnitude
calculation is accurate near 50 or 60 Hz and the timer accuracy is &1
cycle. When a wider frequency response is needed, select RMS. For
generator protection applications, it is recommended to use the RMS
selection. RMS is the default when shipped from the factory. For 59
function when positive sequence voltage is selected, the calculation uses
DFT irrespective of DFT/RMS selection.
If pulse relay operation is selected, output will dropout after the seal-in
PULSE RELAY
delay expires, even if the condition which caused the relay to pick up is
o8 o7 o6 o5 o4 o3 o2 o1 still out of band. When selected, latching outputs are not available. *
If any of the outputs are selected as latched, then after tripping, this
LATCHED OUTPUTS
output will stay activated, even when the tripping condition is removed.
o8 o7 o6 o5 o4 o3 o2 o1 The Latched Output can be reset using the TARGET RESET pushbutton.
When selected, Pulse Relay is not available. *
Minimum time the output contact will remain picked up to ensure proper
RELAY SEAL-IN TIME OUT1
seal-in, regardless of the subsequent state of the initiating function. Indi-
________ Cycles vidual Seal-In settings are available for all outputs.*
ACTIVE INPUT OPEN/close This designates the “active” state for the individual status input. Program-
ming uppercase (see I6) causes the “active” or “operated” condition to be
I6 i5 i4 i3 i2 i1
initiated by the external contact opening. Otherwise, external contact clo-
sure will activate the input.*
*■ Note: Settings for expanded I/O must be made through IPScom®.
V.T. PHASE RATIO Ratio of the phase VTs. Example: 13,800 V : 120 V =13,800/120=115:1
________ : 1
V.T. NEUTRAL RATIO Ratio of the neutral VT. Example: 13,800 V : 120 V =13,800/120=115:1
________ :1
2–4
Application – 2
SETUP
SETUP SYSTEM
59/27 Mag. Select: RMS 50DT Enable Relay Seal-In Time Relay Seal-In Time Expanded
DFT
Split Phase
Phase Rotation: ABC AC B Differential: Disable OUT 1: 30 8160 OUT 9: 30 8160 30 OUT 17
cycles cycles
V.T. Phase Ratio: :1 1.0 2: 30 10: 30 30 18
1.0 6550.0
3: 30 11: 30 30 19
V.T. Neutral Ratio: 1.0 :1 1.0 6550.0
4: 30 12: 30 30 20
V.T. VX Ratio 1.0 :1 1.0 6550.0
5: 30 13: 30 30 21
C.T. Phase Ratio: 10 :1 1 65500 6: 30 14: 30 30 22
C.T. Neutral Ratio: 10 :1 1 65500 7: 30 15: 30 30 23
Pulse Relay 2 2
8: 30 cycles 16: 30 cycles
Outputs: 1 2 3 4 5 6 7 8
Latched Outputs
Outputs: 1 2 3 4 5 6 7 8 Pulse Relay Expanded Outputs
Save Cancel
COMMAND BUTTONS
Input Active When the unit is equipped with expanded I/O, this command opens the Expanded Input Active
State State screen (Figure 2-2), to allow the selection of Expanded Inputs 7 through 14.
Expanded
Pulse/Latch When the unit is equipped with expanded I/O, this command opens the Pulse/Latch
Relay screen (Figures 2-3 and 2-4) to allow the selection of expanded outputs 9 through 23.
Expanded
Outputs
Save When connected to a protection system, sends the currently displayed information to the unit.
Otherwise, saves the currently displayed information.
Cancel Returns you to the IPScom® main window; any changes to the displayed information are lost.
■ NOTE: Checking the inputs for the Active Input Open parameter designates the “operated” state established by
an opening rather than a closing external contact.
2–5
M-3425A Instruction Book
? X
Expanded Input Active State
OK
8 Open Close 12 Open Close
Cancel
9 Open Close 13 Open Close
? X
OUTPUT9 OUTPUT17
OUTPUT10 OUTPUT18
OUTPUT11 OUTPUT19
OUTPUT12 OUTPUT20 OK
OUTPUT13 OUTPUT21
Cancel
OUTPUT14 OUTPUT22
OUTPUT15 OUTPUT23
OUTPUT16
? X
OUTPUT9 OUTPUT17
OUTPUT10 OUTPUT18
OUTPUT11 OUTPUT19
OUTPUT12 OUTPUT20 OK
OUTPUT13 OUTPUT21
Cancel
OUTPUT14 OUTPUT22
OUTPUT15 OUTPUT23
OUTPUT16
2–6
Application – 2
Targets CT
50 50
(Optional) BFPh DT
Integral HMI VT (Note 1)
(Optional)
CT (Residual)
Metering (Note 4)
87
Waveform Capture
25 52
VT Gen
IRIG-B
Front RS232
Communication
81R 81A 81 27 59 24 M
Rear RS232
Communication (Metering) VT (Note 1)
Rear Ethernet
Port (Optional)
Rear RS-485 (Note 3)
Communication M-3921
59X +
Multiple Setting
Groups
-
Programmable I/O
64F 64B
27
Self Diagnostics
CT (Neutral)
59D Line Side 87 50 50N 51N (Notes 2 & 5)
Voltage 27
27 GD BFN
(Software Select) 59D 64S 59N R
32 TN
R
■ NOTES:
1. When 25 function is enabled, 59X, 59D with VX and 67N with VX are not available, and vice versa.
2. When 67N function with IN (Residual) operating current is enabled, 87GD is not available, and vice
versa.
3. The 50BFN, 50N, and 51N may utilize either the neutral current or the residual current.
4. When used as a turn-to-turn fault protection device.
5. The current input IN can be either from neutral current or residual current.
6. The 50BFN, 50N, 51N, 59D, 67N (with IN or VN) and 87GD functions are unavailable when the 64S
function has been purchased. See the M-3425A Instruction Book for connection details.
Targets CT (Residual)
(Optional) (Note 5)
Integral HMI
(Optional) 25 52
VT Gen
Metering
Waveform Capture
81R 81A 81 59 27 24 M
IRIG-B
(Metering)
50 CT (Note 3)
Front RS232 DT
Communication
Rear RS232
Communication VT (Note 1)
Rear Ethernet
Port (Optional)
(Note 2)
Rear RS-485 M-3921
Communication 59X +
Multiple Setting
Groups -
Self Diagnostics
CT
78 60FL 51V 50/27 40 32 21 50 49 46 M
Dual Power Supply
(Optional) (Metering)
Breaker
Monitoring
Trip Circuit
Monitoring 3VO (Calculated)
(Note 4)
VX
Event Log 67N
VN 67N Polarization
(Software Select)
VX 3VO (Calculated)
CT
59D Line Side CT (Neutral)
Voltage 27 50N 51N (Note 5)
(Software Select) 59D 27 64S 59N R
32
TN
R
1 Wire to split phase differential CTs for 4 Alarm output can be grouped to a single alarm
use with 50DT split phase function. at the discretion of user.
A B C
2 Required generator breaker status input 5 Available control output to service other relays
Other (52b). Contact is closed when generator for VT Fuse Loss can be designated.
Relays M-3425A
breaker is open. Use unit breaker 6 Input contact number is designated by user.
1
50 51 contact if no generator breaker present.
3 Output contact pairs designated by
1 user.
48 49
WARNING: ONLY dry contact inputs must be
M-3425A connected because these contact inputs are
1 internally wetted. Application of external
46 47
39 38 41 40 43 42 voltage on these inputs may result in
damage to the units.
NOTE : M-3425A current terminal polarity marks
( . ) indicate "entering" current direction when
A B C M-3425A
Three VT Wye-Wye primary current is "from" the generator to the
10
52 Alternate Connection system. If CT connections differ from those
52b
Gen 11
shown, adjust input terminals.
A A
B B
C C
42 43 40 41 38 39 42 43 40 41 38 39
Generator
M-3921 a b c a b c
Field Ground
Coupler Module Other Other
Relays M-3425A Relays M-3425A
Other
a b c Relays M-3425A 59 58 59 58
58 59
57 56 57 56
56 57
OR OR
55 54 55 54
54 55
M-3425A M-3425A
45 44 52 53
R OR
High Impedance Grounding R Low Impedance Grounding
2–9
M-3425A Instruction Book
M-3425A
65 Used when Generator
VX
Side VTs are connected
Line-Ground.
64
65
VX Used when Generator Side VTs
64 are connected Line-Line
A B C M-3425A
10
52
52b
Gen 11
A B C
M-3425A
39
Three VT Wye-Wye
38 Connection
41
40
43
42
OR
M-3425A
42
A B C
43 Two VT Open-Delta
Connection
40
41
38
39
Generator
■ NOTE: When VX is connected for Sync Check function (25), turn-to-turn fault protection (59X) is not
available.
2–10
Application – 2
A B C M-3425A
52 10
52b
Gen
11
A B C
M-3425A
VX
65
R
64
Generator
a b c
Line to Neutral
Voltage Rated
Cable
M-3425A
M-3425A
52 53
OR R
45 44
■ NOTE: When VX is connected for turn-to-turn fault protection, 59X and 25 functions are not available.
Figure 2-9 Function 59X Turn to Turn Fault Protection Three-Line Connection Diagram
2–11
M-3425A Instruction Book
Bus Section
A
M-3425A
53
R Residual CT I N input can be connected
52 either at Neutral or as Residual.
M-3425A
67N
65 64 Connection
59X A B C M-3425A
Bus Ground
52 10
52b
Gen
11
A B C
M-3425A
VX
65
R
64
67N, 59D
Connection
a b c
M-3425A
I N input can be connected
52 53
either at Neutral or as Residual.
OR
M-3425A
45 44
R
■ NOTE: When VX is connected for bus ground protection (59X, 67N, or 59D) , 25 function is not available.
Figure 2-10 Function 67N, 59D, 59X (Bus Ground) Three-Line Connection Diagram
2–12
Application – 2
The individual protective functions, along with their magnitude and timing settings are described in the
following pages. Settings for disabled functions do not apply. Some menu and setting screens do not appear
for functions that are disabled or not purchased. Menu screens are as they would appear on units equipped
with the M-3931 HMI Module. The same setting may be entered using M-3820D IPScom Communications
Software.
For those units equipped with Expanded I/O, setting of Expanded Inputs and Outputs is accomplished by
selecting “Expanded I/O” from the individual function screen. IPScom® will display the Expanded I/O
Initiate dialog screen (Figure 2-11).
? X
Expanded Input
Expanded Output Initiate Initiate
OUTPUT9 OUTPUT17 Input 7
OUTPUT16 Input 14
2–13
M-3425A Instruction Book
21 Phase Distance
The Phase Distance function (21) is designed for When the generator is connected to the system
system phase fault backup protection and is through a delta/wye transformer, proper voltages
implemented as a three-zone mho characteristic. and currents (equivalent to the high side of the
transformer) must be used in order for the relay to
Three separate distance elements are used to detect see correct impedances for system faults. By
AB, BC, and CA fault types. The ranges and enabling the Delta-Y Transform feature (see Section
increments are shown in Figure 2-14. The diameter, 2.1, Configuration, Relay System Setup), the relay
offset, system impedance angle (relay characteristic can internally consider the 30° phase shift (30° lead
angle), and definite time delay need to be selected delta-ab or 30° lag delta-ac) through the delta/wye
for each zone for coordination with the system transformer, saving auxiliary VTs. Impedance
relaying in the specific application. calculations for various VT connections are shown
in Table 2-2. All impedance settings are secondary
Zone 1, Zone 2 and Zone 3 may be used for backup
relay quantities and can be derived from the following
protection for unit transformer and transmission
faults. Zone 3 in conjunction with Zone 2 can be formula:
used to detect an Out of Step condition and it can Z SEC = ZPRI x (RC ÷ RV)
be programmed to block Function 21 #1 and/or 21
#2. If Zone 3 is being used for out-of-step blocking, where ZSEC = secondary reflected impedance, ZPRI
= primary impedance, RC = current transformer
it does not trip.
ratio, and RV = voltage transformer ratio.
If Zone 1 is not set to see the transmission system,
out-of-step blocking is not recommended. The minimum current sensitivity depends on the
programmed reach (diameter and offset). If the
When Zone 3 is used for Out-of-step blocking, the current is below the minimum sensitivity current,
out of step delay is used for the detection of the the impedance calculated will saturate, and not be
transit time of the swing between Zone 3 and Zone accurate. This will not cause any relay misoperation.
2 impedances.
An overcurrent supervision feature can be enabled,
The load encroachment blinder function can be set which will block the 21 function when all three
with a reach and an angle as shown in Figure 2-13. phase currents are below the pickup value.
When enabled, this feature will block the 21 Function
from misoperating during high load conditions.
2–14
Application – 2
21 #1 OC SUPERVISION
________ Amps
21 #1 OUT OF STEP BLOCK When enabled the 21 Function is blocked on the detection of an
disable enable out-of-step condition.
The time delays are set to coordinate with the primary protection of
21 #1 DELAY those overreached zones and, when applicable, with the breaker
________ Cycles failure schemes associated with those protective zones.
21 #3 OUT OF STEP DELAY In Zone #3 when out-of-step blocking is enabled for Zone #1 or #2.
________ Cycles
+X
Protected Range Zone 2
–X
3
52 52 52
Bus
M-3425A
21
■ NOTE: The reach settings of the distance elements (21) should not include generator impedance since
the distance measurement starts at the VT location. However, since the neutral side CTs are
used for this function, backup protection for generator Phase-to-Phase faults is also provided
2–15
M-3425A Instruction Book
+jX
ZONE 3
Transmission Line
ZONE 2
Circle
Diameters ZONE 1
Unit Transformer
R2
Block
R1
Θ
Block
δ2 δ1
–R +R
–jX
2–16
Application – 2
? X
#1 #2 #3
(21) PHASE DISTANCE
Circle Diameter: 0.1 Ohm 100.0 Ohm(s)
Enable
Overcurrent SV: 0.1 A 20 A
Disable
Save Cancel
Transformer Direct
Connected Transformer Delta-AC Connected Transformer Delta-AB Connected
L-L or L-G to L-L L-G L-L or L-G to L-L L-G L-L or L-G to L-L L-G
2–17
M-3425A Instruction Book
24 Overexcitation Volts/Hz
The Volts-Per-Hertz function (24) provides Setting this relay function involves determining the
overexcitation protection for the generator and unit- desired protection levels and operating times. The
connected transformers. This function incorporates first step is to plot the combined generator and
two definite time elements which can be used to associated unit transformer overexcitation capability
realize traditional two-step overexcitation protection. limits. This data is typically available from the
In addition, the relay includes an inverse time manufacturer and should be plotted on the same
element that provides superior protection by closely voltage base. Depending on the resulting
approximating the combined generator/unit characteristic, one of the four families of inverse
transformer overexcitation curve. Industry standard time curves (as shown in Appendix D, Inverse
inverse time curves may be selected along with a Time Curves) can be matched to provide the
linear reset rate which may be programmed to protection. The two definite time elements can be
match specific machine cooling characteristics. used to further shape the protection curve or provide
The percent pickup is based on the Nominal Voltage an alarm.
setting and the nominal frequency. The V/Hz function
provides reliable measurements of V/Hz up to 200% Figure 2-15 illustrates a composite graph of generator
for a frequency range of 2–80 Hz. The ranges and and transformer limits, a chosen inverse time curve
increments are presented in Figure 2-16. and pickup, and a definite time pickup and delay.
24DT #1 PICKUP Definite time setpoint #1 establishes the V/Hz level above which the
________ % protection operating time will be fixed at the definite time delay #1.
24DT #1 DELAY Delay time #1 establishes the operation time of the protection for all
________ Cycles V/Hz values above the level set by definite time setpoint #1.
24DT #2 PICKUP Definite time setpoint #2 could be programmed to alarm, alerting the
________ % operator to take proper control action to possibly avoid tripping.
24DT #2 DELAY Time to operation at any V/Hz value exceeding Definite time setting
________ Cycles #2.
24IT PICKUP The pickup value is the V/Hz value at which the chosen inverse
curve begins protective operation. Typical value is 105%.
________ %
24IT CURVE Allows the user to designate the appropriate curve family for this
crv#1 crv#2 crv#3 crv#4 protection application. These curves are shown in Appendix D, Inverse
Time Curves.
24IT TIME DIAL The appropriate curve in the family is designated by the associated
________ “K” value of the curve.
24IT RESET RATE The value entered here should be the time needed for the unit to
________ Seconds cool to normal operating temperature if the V/Hz excursion time
was just under the trip time.
2–18
Application – 2
M-3425A Firmware Versions D-0114VXX.XX.XX After any V/Hz excursion, cooling time must also
and Earlier be taken into account. If the unit should again be
■ NOTE: When the inverse time element is subjected to high V/Hz before it has cooled to
enabled, the definite time element #1 normal operating levels, damage could be caused
must be enabled which will provide before the V/Hz trip point is reached. For this
definite minimum time setting for the reason, a linear reset characteristic, adjustable to
inverse time curve. take into account the cooling rate of the unit, is
provided. If a subsequent V/Hz excursion occurs
The following steps must be followed when setting before the reset characteristic has timed out, the
the inverse time element and definite time element time delay will pick up from the equivalent point (as
#1: a %) on the curve. The Reset Rate setting entered
1. The pickup of the inverse time element should be time needed for the unit to cool to normal
must be less than the pickup of the operating temperature if the V/Hz excursion time
definite time element #1 was just under the trip point.
1000
100
Transformer Limit Curve
on Generator Base
A2
0.1 Definite Time Delay (A1)
0.01
100 105 110 115 120 125 130 135 140 145 150
Percentage Volts/Hz
2–19
M-3425A Instruction Book
? X
F24
(24) - VOLTS/HZ
Curves: #1 #2 #3 #4
Time Dial: 1 100
Reset Rate: 1 Sec 999 Secs
Save Cancel
2–20
Application – 2
25 Sync Check
■ NOTE: The 25 function cannot be enabled under Dead Line/Dead Bus Check
any one of the following conditions:
The Dead Volt Limit defines the Hot/Dead voltage
• 67N (Residual Directional Overcurrent) level used in Deadline/Dead Bus closing schemes.
is enabled and the polarizing quantity When the measured VX voltage is equal to or below
has been set to VX. the Dead Volt Limit, VX is considered dead. When
• 59D is enabled and the line side voltage the measured VX is above the Dead Volt Limit, VX
is set to VX. is considered hot. The opposite side of the breaker
uses the positive sequence voltage measurement
• 59X is connected for turn-to-turn fault
(V1) for 3-phase consideration in determining hot/
protection or bus ground protection.
dead detection. Different combinations of hot line/
The Synchronism (Sync) Check function (25) is dead bus closings may be selected, depending on
used to ensure that the voltage magnitude, phase how the buses are referenced. A logic diagram of
angle and frequency of the generator (V1) and the the Deadline/Dead Bus scheme is presented in
utility system (VX) are within acceptable limits before Figure 2-17.
the generator is synchronized with the system.
The Dead V1, Dead VX, and Dead V1 & VX enable
Generator voltage (V1) can be selected as A, B, or
are software switches used to enable the dead
C (line-to-ground and line-ground to line-line) or AB,
line/dead bus logic. Further conditioning can be
BC, or CA (line-to-line).
performed on the dead detection logic by selecting
The sync check function includes phase angle, one or more input contacts (Dead Input Enable) to
delta frequency, and delta voltage checks. control the enabled dead detection element. For
example, if INPUT2 (I2) is selected under the
Dead Input Enable screen, and both the Dead V1
Phase Angle Check and Dead VX elements are enabled, the dead check
The phase angle is considered acceptable when timer will start when INPUT2 is activated, and
the selected sync phase voltage (V1) and system either V1 dead/VX hot or V1 hot/VX dead. This
voltage (VX) are within the Upper Volt Limit and allows for external control of the desired dead
Lower Volt Limit window and the measured phase closing scheme. Dead Input Enable selections are
angle is within the phase angle window. common to all dead detection elements. If no
inputs are selected under the Dead Input Enable
Phase angle window is defined as twice the Phase
screen, and any dead element is enabled, the
Angle Limit setting. For example, if the Phase
dead check timer will start immediately when the
Angle Limit is set at 10 degrees, a phase angle
dead condition exists.
window of 20 degrees exists between –10 degrees
and +10 degrees. The logic diagram of the phase The 25S and 25D can be programmed to be sent to
angle check is shown in Figure 2-17. two different contacts, if desired.
■ NOTE: The 25 function does not produce a
Delta Voltage and Delta Frequency Check
target or LED and is accompanied by
Delta Voltage and Delta Frequency elements may the HMI message “F25 Function
be individually enabled or disabled, as desired. The Operated”.
Delta Voltage check will compare the absolute
difference between the selected sync phase voltage
(V1) and the measured system voltage (VX) with
the Delta Voltage Limit setting. Likewise, the Delta
Frequency measures the frequency difference
between V1 and VX voltage signals. The Phase
Angle Check, Delta Voltage and Delta Frequency
Check all combine through an appropriate timer
with the output directed to the programmed 25S
output contact. A logic diagram representing this
logic is presented in Figure 2-17.
2–21
M-3425A Instruction Book
25S LOWER VOLT LIMIT Lower voltage limit for voltage acceptance.
________ Volts
25S SYNC-CHECK PHASE Selects the phase voltage on the generator side for Sync Check func-
a b c tions (A, B, or C for line-to-ground and line-ground to line-line, and AB,
BC, CA for line-to-line)
25D DEAD VOLT LIMIT Voltage less than this setting is defined as “DEAD”; above this setting
________ Volts as “HOT”.
25D DEAD INPUT ENABLE Externally controlled dead closing. Inputs IN7–IN14 must be set using
i6 i5 i4 I3 i2 i1 IPScom.
2–22
Application – 2
AND
Dead V X Hot V1 Enabled
2–23
M-3425A Instruction Book
? X
F25
(25) - SYNC CHECK
Phase Angle Window: 0o 90o 25S
Upper Voltage Limit: 60 V 140 V
Enable Disable
Enable Disable
Save Cancel
2–24
Application – 2
27 Phase Undervoltage
The Phase Undervoltage function (27) may be used Magnitude measurement depends on the 59/27
to detect any condition causing long- or short-term Magnitude Select setting. (See Section 2.1,
undervoltage. This is a true three-phase function in Configuration, Relay System Setup.) When the RMS
that each phase has an independent timing element. calculation is selected, the magnitude calculation is
The ranges and increments are presented in Figure accurate over a wide frequency range (10 to 80 Hz)
2-19. and the accuracy of the time delay is +20 cycles. If
DFT calculation is selected, the magnitude
calculation is accurate near 50 or 60 Hz, and the
timer accuracy is &1 cycle.
27 #1 DELAY
________ Cycles
? X
F27
Pickup: 5V 180 V #1
Delay: 1 Cycle 8160 Cycles
Pickup: 5V 180 V #2
Delay: 1 Cycle 8160 Cycles
Pickup: 5V 180 V #3
Delay: 1 Cycle 8160 Cycles
Save Cancel
2–25
M-3425A Instruction Book
27TN #1 PICKUP Relay volts are equal to the primary neutral voltage divided by the
________ Volts grounding transformer ratio. Generally set for approximately 50%
of the minimum third harmonic voltage observed during various loading
conditions.
27TN #1 POS SEQ VOLT BLK
disable ENABLE 27TH #1 REV POWER BLK
disable ENABLE
2–26
Application – 2
27TN Setpoint
Pre-fault fundamental neutral voltage level
59N Setpoint (typically 5V)
Neutral End of Terminal End
Generator of Generator
0% 50% 100%
Fault Position
(% of stator winding measured
27TN from neutral end of generator)
Protection
provided by: 59N
5% - 10%
0-30%
Figure 2-20 Third Harmonic Undervoltage (27TN) Protection Characteristics
2–27
M-3425A Instruction Book
-P +P
Reverse Block Forward Block High Band
Power Power Forward
Block Block Power Block
-Q
Figure 2-21 27TN Blocking Regions
2–28
Application – 2
#1 #2
(27TN) - THIRD HARMONIC UNDERVOLTAGE, NEUTRAL
Lead Power Factor Block: 0.01 Lead 1.00 Lead Enable Disable
Save Cancel
Figure 2-22 Third Harmonic Undervoltage, Neutral Circuit (27TN) Setpoint Ranges
2–29
M-3425A Instruction Book
32 Directional Power
The Directional Power function (32) can provide valves are closed. In this case the Over/Under
protection against both generator motoring and power setting is set to Under and a positive pickup
overload. It provides three power setpoints, each setting is chosen. The relay will trip when the
with a magnitude setting and a time delay. The measured forward power is less than the pickup
Forward Power direction (power flow to system) is value. The function should be blocked when the
automatically chosen when the pickup setting is generator breaker is open (using contact input
positive and the Reverse Power direction (power blocking) otherwise the function will trip and prevent
flow to generator) is automatically chosen when the the generator from being brought online.
pickup setting is negative. The range, as shown is
from –3.000 PU to 3.000 PU where 1.0 PU is equal Protection from Generator Overload
to the generator MVA rating. Normalized PU power
flow measurements are based on Nominal Voltage Protection from generator overload is provided by
and Nominal Current setting, as shown in Section selecting a positive pickup setting with Over/Under
2.1, Configuration, Relay System Setup. Power setting set to Over. The relay will operate
when the measured real power is greater than the
pickup setting.
Protection from Generator Motoring
Protection against motoring is provided by selecting Protection from Excessive Reactive Power
a negative pickup with Over/Under power set to
Over. The relay will operate when the measured The directional power element #3 can be set to
real power is greater (more negative) than the pickup operate on either real power or reactive power.
setting in the reverse direction. When protection from excessive reactive power is
required the element #3 can be set to operate on
In some steam generator applications it is desirable reactive power. The relay will operate when the
to trip the generator when the forward power is less measured reactive power exceeds the pickup
than a small value. This is due to the fact that the setting.
trapped steam will cause the generator to supply a
small amount of power even though the steam Figures 2-23 through 2-26 show reverse power, low
forward power, over power, and over reactive power
applications.
32 #1 PICKUP The reverse power pickup setting should be based on the type of
________ PU prime mover and the losses when the generator is motoring.
32 #1 DELAY Reverse power relays should always be applied with a time delay in
________ Cycles order to prevent mis-operation during power swing conditions. Typical
time delay settings are 20 to 30 seconds.
32 #1 TARGET LED Target LED for the 32 Function elements can be individually enabled
disable enable or disabled.
32#1 UNDER/OVER POWER When Low Forward Power protection is desired, set this to Under
over under with a positive pickup setting. The relay will trip when the real power
measurement is less than or equal to the pickup setpoint.
2–30
Application – 2
32 #2 TARGET LED
disable enable
32 #3 PICKUP
________ PU
32 #3 DELAY
________ Cycles
32 #3 TARGET LED
disable enable
Reverse
Power Flow Forward
Power Flow
PU
-1.0 PU 1.0 PU
TRIP
Pickup
Figure 2-23 Tripping on Reverse Power Flow (Over Power with Negative Pickup)
2–31
M-3425A Instruction Book
Reverse Forward
Power Flow Power Flow
PU
-1.0 PU 1.0 PU
TRIP
Pickup
Figure 2-24 Tripping on Low Forward Power (Under Power with Positive Pickup)
Reverse Forward
Power Flow Power Flow
PU
-1.0 PU 1.0 PU
TRIP
Pickup
2–32
Application – 2
Reactive Power
Into System
TRIP
Pickup
Reverse Forward
Power Flow Power Flow
PU
-1.0 PU 1.0 PU
Reactive Power
Into Generator
Figure 2-26 Tripping on Over Reactive Power with Element #3 (Over Power, Positive Pickup and
Directional Power Sensing Set to Reactive)
2–33
M-3425A Instruction Book
? X
F32
Save Cancel
2–34
Application – 2
40 Loss of Field
The Loss-of-Field function (40) provides protection not required). The directional unit’s angle setting
for a partial or complete loss of field. A variety of (ΘD) can be set from 0° to 20°.
possible settings make the M-3425A Generator
Protection Relay very flexible when applied to loss- The settings of the offset mho elements should be
of-field protection. Ranges and increments are such that the relay detects the loss-of-field condition
presented in Figure 2-30. for any loading while not mis-operating during power
swings and fault conditions. Two approaches are
The loss-of-field function is implemented with two widely used in the industry, both of which are
offset mho elements, an undervoltage element, supported by the M-3425A relay. Both approaches
and a directional element. The setting for each mho require knowledge of the reactances and other
element, diameter, offset, and time delay, are parameters of the generator. They are described in
adjusted individually. Each element has two time Figure 2-28, Loss of Field (40) — Protective
delay settings. The second time delay (delay with Approach I and Figure 2-29, Loss of Field (40) —
VC) is applicable with voltage control, and the timer Protective Approach II.
only starts if the positive sequence voltage is
below the voltage control setting. The function with Positive sequence impedance measurements are
voltage control and without voltage control can be used for the loss of field functions. All impedance
programmed to send to two different output contacts, settings are secondary relay quantities and can be
if desired. The delay with voltage control may be derived from the following formula:
enabled on each element but the voltage level Z SEC = ZPRI x (RC ÷ RV)
setting is common. The voltage control allows for
faster tripping when low voltage may be caused by where ZSEC = secondary reflected impedance, ZPRI
the VAr intake by the machine with loss of = primary impedance, RC = current transformer
excitation. A common directional unit is provided to ratio, and RV = voltage transformer ratio.
block the relay operation during slightly underexcited
conditions (since approach #1 with negative offset
is inherently directional, the directional element is
2–35
M-3425A Instruction Book
Zone 1 Zone 2
80 to 90% of
Voltage Control Setting N/A
Nominal Voltage
2–36
Application – 2
+X
1.0 pu Underexcited
Xd
Loss of Excitation
Final Impedance
Locus
Machine Capability
X
Figure 2-28 Loss of Field (40)—Protective Approach 1
Directional Element +X
Block Direction
Heavy Load Light Load
Trip Direction
QD XT
R +R
Directional X'd
Element Angle 2
Setting
Underexcited
1.1 Xd
Loss of Excitation
Final Impedance
Locus
Machine Capability
X
Figure 2-29 Loss of Field (40)—Protective Approach 2
2–37
M-3425A Instruction Book
F40
(40) - LOSS OF FIELD
Save Cancel
■ NOTE: Out of Step Block Enable is not available for this release, and will appear greyed-out in display.
2–38
Application – 2
46IT MAX DELAY The maximum trip time is used to reduce the
________ Cycles longer trip times associated with low to moder-
ate imbalances to a preset time.
2–39
M-3425A Instruction Book
400
200
Definite Maximum
100
Time Setting Range
80
60
40
Time (Seconds)
20
10
8
6 I22t=K
4
K
95
1 50
25
0.6
10
0.4 5
2
Definite 1
* 0.2 Minimum
Time
0.1
4 5 6 8 10 20 40 60 80 100 150 200 300 400 500 600 800 1000 1000 2000 3000 4000
■ NOTE: When the phase current exceeds 3X I nominal, the operating times will be greater than those
shown.
* 0.24 seconds for 50 Hz units.
Figure 2-31 Negative Sequence Overcurrent Inverse Time Curves
? X
F46
Time Dial: 1 95
Maximum Time: 600 Cycles 65500 Cycles
Reset Time: 1 Second 600 Seconds
Save Cancel
2–40
Application – 2
Current-Square
IL2
I2PL
Imax2
IL2
IL2
I2PL
t
t
Tripped Not Tripped
Figure 2-33 Time Constant, Function 49
49#1 MAX OVERLOAD CURR Selects the maximum allowed continuous overload
________ Amps current.
2–41
M-3425A Instruction Book
49 - Overload Curves
10
0.1
t/t
P=0.0
P=0.5
P=0.6 0.01
P=0.7
P=0.8
P=0.9
P=0.99
0.001
1 2 3 4 5 6 7 8 9
IL/Imax
IPL
where: P=
Imax
Figure 2-34 49 Function Overload Curves
2–42
Application – 2
? X
F49
Time Constant: #1
1.0 min 999.9 min
1.00 A 10.00 A
Max. Overload Current:
Time Constant: #2
1.0 min 999.9 min
1.00 A 10.00 A
Max. Overload Current:
Save Cancel
2–43
M-3425A Instruction Book
The relay current (IR) is equal to the primary current (Ip) divided by
50#1 PICKUP
the appropriate CT ratio. These screens are repeated for 50#2 ele-
________ Amps
ment.
50#1 DELAY
________ Cycles
50N PICKUP
________ Amps
50N DELAY
________ Cycles
? X
F50
Save Cancel
2–44
Application – 2
? X
F50N
Save Cancel
2–45
M-3425A Instruction Book
2–46
Application – 2
50BF PHASE ELEMENT If generator breaker failure function is used in this application, ENABLE
disable enable here.
50BF NEUTRAL ELEMENT If the breaker flashover protection is to be used with the generator
disable enable breaker failure function of the relay, set ENABLE (enable phase
element also for this application.)
50BF INPUT INITIATE Designate the status inputs which will initiate the breaker failure
i6 i5 i4 i3 i2 i1 timer. Inputs IN7–IN14 must be set using IPScom®.
50BF OUTPUT INITIATE Designate the outputs that will initiate the breaker failure timer. Outputs
o8 o7 o6 o5 o4 o3 o2 o1 OUT9–OUT23 must be set using IPScom.
50BF DELAY For generator breaker failure protection, the time delay should be set to
________ Cycles allow for breaker operating time plus margin.
50BF-Ph
Overcurrent
I>P.U. AND
OR
Phase Initiate Enable
IN1 (52b)
NOT
Logic high when breaker closed
Logic high
when breaker open
50BF-N
Overcurrent
I>P.U.
AND
Programmed
Neutral Initiate Enable
OR
AND DELAY
TIME
Output
Contacts
Output Initiate
Input Initiate
2–47
M-3425A Instruction Book
? X
F50BF
Save Cancel
2–48
Application – 2
? X
F50DT
Save Cancel
2–49
M-3425A Instruction Book
50/27 PICKUP Typical pickup setting is 0.5 amps. No coordination is required with other
________ Amps protection since this function is only operational when the generator is
off-line.
50/27 VOLTAGE CONTROL The purpose of the undervoltage detector is to determine whether the unit
________ Volts is connected to the system. The voltage level during this accidental
energization depends on the system strength. Typical setting is 50%–
70% of rated voltage (in some cases, it may be set as low as 20%.)
50/27 PICKUP DELAY The pickup time delay is the time for the undervoltage unit to operate to
________ Cycles arm the protection. It must coordinate with other protection for conditions
which cause low voltages (typically longer than 21 and 51V time delay
settings.)
The dropout time delay is the time for the unit to operate to disarm the
50/27 DROPOUT DELAY
protection when the voltage is increased above the pickup value or the
________ Cycles
generator is brought on-line.
2–50
Application – 2
50
Overcurrent
I>PU
Programmed
Timer AND Output
Contacts
Pickup
27 Delay
Undervoltage*
V<PU Dropout
Delay
? X
F50/27
(27) - UNDERVOLTAGE
Pickup: 5V 130 V
Save Cancel
2–51
M-3425A Instruction Book
51N PICKUP The relay current (IR) is equal to the primary current (IP) divided by the
________ Amps appropriate CT ratio. IR = IP ÷ CT ratio
? X
F51N
#1
Pickup: 0.25 A 12.00 A
Curves
Beco Definite Time Beco Inverse Beco Very Inverse Beco Extremely Inverse
Save Cancel
2–52
Application – 2
51V Inverse Time Phase Overcurrent with 51V is a true three-phase function, in that the relay
Voltage Control/Restraint incorporates separate integrating timers on each
Time-overcurrent relays, one per phase, are used phase.
to trip circuits selectively and to time-coordinate
with other up- or downstream relays. For this The inverse time overcurrent function can be voltage
function, eight complete series of inverse time controlled (VC), voltage restrained (VR), or neither.
tripping characteristics are included. The same For voltage-controlled operation, the function is not
descriptions and nomenclature which are traditionally active unless the voltage is below the voltage
used with electromechanical relays are used in the control setpoint. This philosophy is used to confirm
relay. Thus, user may choose from four BECO that the overcurrent is due to system fault. When
curves (BEDEF, BEINV, BEVINV, and BEEINV), applied, most users will set voltage control limits in
four IEC curves (IECI, IECVI, IECEI, and IECLT), the range of 0.7 to 0.9 per unit RMS voltage. When
and three IEEE curves (MINV, VINV, EINV.) Within voltage restraint is selected (See Figure 2-44,
each family, the operator selects time dial setting Voltage Restraint (51VR) Characteristic), the pickup
and pickup (tap) setting, just as with setting is continuously modified in proportion to the
electromechanical relays. Ranges and increments collapsing terminal voltage. The voltage restraint
are presented in Figure 2-45. function is well-suited to small generators with
relatively short time constants.
The curves available for use are shown in Appendix
D, Inverse Time Curves. They cover a range from ■ NOTE: The 51V function should be blocked by
1.5 to 20 times the pickup setting. An additional fuse loss if in the voltage control mode
one cycle time delay should be added to these only. Fuse loss blocking is not desirable
for voltage restraint mode because the
curves in order to obtain the relay operating time.
pickup is automatically held at 100%
Inverse time curves saturate beyond 20 times
pickup during fuse loss conditions, and
pickup. For currents in excess of 20 times pickup, operation will continue as normal.
operating times are fixed at the 20 time pickup
level. The particular settings will be made by The internally derived voltage used to realize the
information from short-circuit fault studies and voltage control or restraint feature depends on the
knowledge of the coordination requirements with configured VT configuration and the Delta-Y
other devices in the system that respond to time Transform setting (see Section 2.1, Configuration,
overcurrent. Relay System Setup). Table 2-4, Delta/Wye
Transformer Voltage-Current Pairs describes the
calculation for the various system VT configurations.
51V VOLTAGE CONTROL Disable if neither voltage control nor voltage restraint is desired. If
disable V_CNTL v_rstrnt voltage restraint is designated, the tap setting is modified as shown in
Figure 2-43. If voltage control is designated, the 51V will only operate
when the voltage is less than the 51V voltage control setting specified
51V VOLTAGE CONTROL below. When applied, the voltage control is usually set in the range of
________ Volts 70% to 90% of the nominal voltage.
2–53
M-3425A Instruction Book
100
75
Tap Setting as %
of Tap Setting at 50
Rated Voltage
25
0 25 50 75 100
? X
F51V
#1
Pickup: 0.50 A 12.00 A
Time Dial: 0.5 11.0
Curves
Beco Definite Time Beco Inverse Beco Very Inverse Beco Extremely Inverse
Save Cancel
Figure 2-45 Inverse Time Overcurrent with Voltage Control/Voltage Restraint (51VC/VR)
Setpoint Ranges
2–54
Application – 2
59 Phase Overvoltage
The Phase Overvoltage function (59) may be used Magnitude measurement depends on the 59/27
to provide overvoltage protection for the generator. Magnitude Select setting (See Section 2.1,
The relay provides overvoltage protection functions Configuration, Relay System Setup). When the
with three voltage levels and three definite-time RMS option is selected, the magnitude calculation
setpoints, any one or more of which can be is accurate over a wide frequency range (10 to 80
programmed to trip the unit or send an alarm. This Hz) and the accuracy of the time delay is +20
is a true 3-phase function in that each phase has an cycles. If DFT option is selected, the magnitude
independent timing element. calculation is accurate near 50 or 60 Hz, and the
timer accuracy is &1 cycle. When the input voltage
The 59 function can be programmed to use phase select is set to positive sequence voltage, the 59
voltage (any one of the three phases) or positive functions uses DFT to measure the positive
sequence voltage as input. sequence voltage, irrespective of DFT/RMS
selection. Ranges and increments are presented in
Figure 2-46.
59 #1 PICKUP
________ Volts
59 #1 DELAY
________ Cycles
? X
F59
(59) - PHASE OVERVOLTAGE
Pickup: 5V 180 V
Delay: 1 Cycle 8160 Cycles
Pickup: 5V 180 V
Save Cancel
59D RATIO The ratio (or third harmonic) voltage measured at the generator
________ terminals to the third harmonic voltage measured at neutral. This
setting requires field measurements of third-harmonic voltage. Take
measurements at various loadings and use smallest ratio:
V3N
= Ratio
V3X
Ratio/2 = Setpoint (50% margin)
59D DELAY
________ Cycles
2–56
Application – 2
M-3425A
V 3N V 3X
Figure 2-47 Third Harmonic Voltage Differential (Ratio) Scheme for Generator Ground Fault
Protection
? X
F59D
Enable Disable
Save Cancel
2–57
M-3425A Instruction Book
? X
59N
Save Cancel
Figure 2-49 Overvoltage, Neutral Circuit or Zero Sequence (59N) Setpoint Ranges
2–58
Application – 2
59X #1 PICKUP When used for Turn-to-Turn fault protection the pickup should be set
________ Volts above the normal zero sequence voltage level. Typically the pickup
is set to 5 V.
When used for Bus Ground protection it is again set above the normal
zero sequence voltage seen at the bus. Typical setting is between 10
and 20 Volts to provide sensitive protection.
The Time Delay for Turn-to-Turn faults should be set to approximately
59X #1 DELAY
5 cycles. For bus ground fault protection application the time delay
________ Cycles
should coordinate with other ground fault relaying and VT fuses.
59X #2 screens are identical to 59X #1.
GENERATOR
R 3V 0
59X
■ NOTE: Installation requires the cable from the neutral of the VT to generator neutral be insulated for the
system line-to-ground voltage.
2–59
M-3425A Instruction Book
? X
F59X
Pickup: 5V 180 V #1
Delay: 1 Cycle 8160 Cycles
Pickup: 5V 180 V #2
Delay: 1 Cycle 8160 Cycles
Save Cancel
2–60
Application – 2
60FL INPUT INITIATE The initiating control/status inputs are user-designated. The clos-
FL i6 i5 i4 i3 i2 i1 ing of any of the externally connected contacts (across these in-
puts) will start the associated time delay to the 60FL function op-
60FL 3 PHASE DETECT eration. In order to use internal fuse loss logic for 60FL function,
disable enable “FL” must be checked. Externally initiated fuse loss detection may
be input to other status inputs. Inputs IN7–IN14 must be set using
IPScom®.
60FL DELAY The time delay is set to coordinate for conditions which may appear
________ Cycles as a fuse loss but will be corrected by other protection (such as a
secondary VT circuit fault which will be cleared by local low voltage
circuit action). This delay does not affect internal FL blocking op-
tion.
2–61
2–62
External Fuse
INx Loss Function Protection Function Block
External
Signal by INx from External FL
"FL" Function
Internal 60FL Logic: 1 & 2 Phase Loss of Potential FL Protection Function Block
M-3425A Instruction Book
Disable Enable
AND
IA > 1.25 IN
I1 Verifies On-line condition
OR AND
IB > 1.25 IN OR VA,B,C Indication of 3-phase loss of potential
IA,B,C Prevents operation during faults
IC > 1.25 IN
Seal-in circuit ensures logic doesn't produce an
output during 3-phase fault when current decays
VA < 0.05 VN below1.25IN
VC < 0.05 VN
Internal 60FL Logic: 3 Phase Loss of Potential
? X
F60FL
Input Initiate
Expanded Input Initiate
FL 6 5 4 3 2 1
Save Cancel
2–63
M-3425A Instruction Book
64B/F Field Ground Protection cabling between the coupler and relay exceeds 100
64F Field Ground Detection feet, provisions should be made for in circuit
A typical connection diagram for Field Ground calibration to nullify the effects of cabling
Protection is given in Figure 2-54. This function capacitance. See Section 6.4, Auto Calibration, for
requires the connection of an external coupler calibration procedure.
(M-3921). To improve accuracy and minimize the The Field Ground function provides detection of
effects of stray capacitance, the M-3921 Field insulation breakdown between the excitation field
Ground Coupler should be mounted close to the winding and the ground. There are two pickup and
exciter. Connections from the coupler to the relay time delay settings, and one adjustable injection
should use low capacitance shielded cable, and be frequency setting for the 64F function. The adjustable
as short as possible. Cable shield should be frequency is provided to compensate for the amount
terminated at the relay end to the Relay Ground of capacitance across the field winding and the
Stud (See Figure 5-9, External Connections). If ground so that the function accuracy is improved.
Ranges and increments are presented in Figure
2-55.
64F #1 PICKUP
________ kOhm
64F #1 DELAY
________ Cycles
64F #2 PICKUP
________ kOhm
64F #2 DELAY
________ Cycles
PROTECTION RELAY
M-3425A
PROCESSOR
SUPPLY
VOLTAGE
Rear Terminal
Field Ground Block Pin No.
Brushes
Detection
TB3
Squarewave Vout
Generator 37 TB5 Gen.
Rotor
35 TB4 TB2
Signal COUPLING
Measurement Vf NETWORK Rf.Cf
and Processing (M-3921)
Shaft
36 TB1 TB1 Ground
Shield Brush
2–64
Application – 2
The following Table gives typical frequency settings 8 WARNING: Machine should be off-line and
based on the rotor capacitance. The rotor field excitation should be off during the
capacitance can be measured with a capacitance capacitance measurement.
meter by connecting the meter across the field
winding to ground. ■ NOTE: Field breaker should be closed for the
capacitance measurements.
Fie ld Winding to
Typical Fre que ncy Se tting
Ground Capacitance
1 to 2 µF 0.52 Hz
2 to 3 µF 0.49 Hz
3 to 4 µF 0.46 Hz
4 to 5 µF 0.43 Hz
5 to 6 µF 0.39 Hz
6 to 7 µF 0.35 Hz
7 to 8 µF 0.32 Hz
8 to 9 µF 0.30 Hz
9 to 10 µF 0.28 Hz
>10 µF 0.26 Hz
? X
F64F/B
Save Cancel
2–65
M-3425A Instruction Book
64B PICKUP
________ mV
64B DELAY
________ cycles
0.05~0.25 µF 2500 mV
2–66
Application – 2
64S 100% Stator Ground Protection by Low The expected 20 Hz current during no fault condition
Frequency Signal Injection is given by:
■ NOTE: The Stator Ground Protection function
(64S) must be selected when the V20 • N2
INF =
M-3425A is initially ordered.
XCS
The 100% stator ground fault protection is provided
Where V20 is the 20 Hz voltage measured across
by injecting an external 20 Hz signal into the neutral
the load resistor RL and XCS is the capacitive
of the generator. The protection is provided when
reactance of the gnereator stator winding and unit
the machine is on-line as well as off-line (provided
transformer referred to the grounding transformer
that the 20 Hz generator and relay are powered on.)
secondary. N is the turn ratio of the grounded
This scheme requires the following external
transformer. The pickup setting should be based on
components in addition to M-3425A protection
the required insulation resistance setting. In order
system:
to detect a fault of 5,000 Ohms on the generator
• 20 Hz Signal-generator (BECO Part No. stator, the pickup current should be set at:
430-00426)
• Band-pass filter. (BECO Part No.
430-00427) V20 N2
IPICKUP =
• 20 Hz Measuring Current Transformer, 50002 + XCS2
400/5 A CT (BECO Part No. 430-00428)
20 Hz CT Ratio
The voltage signal generated by the 20 Hz signal-
generator is injected into the secondary of the When the generator is operating normally (no ground
generator neutral grounding transformer through a fault) only a small amount of 20 Hz current will flow
band-pass filter. The band-pass filter passes the 20 as a result of the stator capacitance to ground.
Hz signal and rejects out-of-band signals. The output When a ground fault occurs anywhere on the
of the 20 Hz band-pass filter is connected to the VN generator stator windings the 20 Hz current will
input of the M-3425A relay through a suitable voltage increase. The 64S function will issue a trip signal
divider, that limits the M-3425A to O 200 V ac (the after a set time delay when the measured 20 Hz
voltage generator may be bypassed if the expected current exceeds the pickup current as illustrated in
50/60 Hz voltage during a phase-to-ground fault of Figure 2-57.
the generator is O 200 V.) The 20Hz current is also
connected to the IN input of the M-3425A, through The 64S protection can be blocked by Undervoltage
the 20Hz current transformer. Inhibit. If the 20 Hz voltage (nominal 25 V) is less
than the Undervoltage Inhibit setting (and
Undervoltage Inhibit is enabled), the 64S function
64S PICKUP will be blocked. For cases where the Load Resistor
mAmps (RL) is small, the Undervoltage Inhibit should not
be enabled, as the voltage will be small.
64S VOLT INHIBIT The 59N function (90 to 95%) should also be used
disable ENABLE in conjunction with 64S protection to provide backup.
▲ CAUTION: Dangerous high voltages may be
64S VOLT INHIBIT present at the generator terminals if the 20 Hz
injection voltage is not removed when the generator
________ Volts
is taken out of service.
If the 20 Hz injection voltage generator receives
64S DELAY power from the generator terminal voltage, then the
________ Cycles 20 Hz injection voltage generator will be
automatically switched off whenever the generator
terminal voltage is not present.
2–67
M-3425A Instruction Book
20 Hz
Supply
Generator Voltage
20 Hz DC AC
Band Pass 430- 1A1 +V Aux V A(L1)
1A3 V C(L3)
1B1 1B4 4A1
2A1
430-00427 Bl
External
2A3 Block
1A1
3A2 Device
Neutral 400A
RL 59N 1A3 1A4 Wiring Operative
Grounding 5A 3A3
L K Shielded
Transformer 4A3 3A1
l k High
400/5 A Voltage
430-00428 20 Hz CT
M-3425A
Low Max. 200 V
Voltage 44 45
V N
52 53
I N
140 %
64S
Pickup
Current
TRIP
I20
60 %
0V 5V 10 V 15 V 20 V 25 V 30 V 35 V 40 V 45 V
20 Hz Injection Voltage
2–68
Application – 2
? X
F64S
#1
Pickup: 2 mA 40 mA
Save Cancel
2–69
M-3425A Instruction Book
2–70
Application – 2
67NDT DIR ELEMENT Directional discrimination enable. When disabled, this function
disable ENABLE will work like a 50N.
67NIT DIR ELEMENT Directional discrimination enabled. When disabled, this function
disable ENABLE will operate like 51N.
67N MAX SENSITIVITY ANGLE See Figure 2-59 for Max Sensitivity Angle (MSA) settings.
________ Degrees
67N POLARIZING QUANTITY Select the polarization voltage. If 3V0 is selected, VT configura-
3V0 vn vx tion must be set to Line-Ground.
2–71
M-3425A Instruction Book
? X
F67N
(67N) - RESIDUAL DIRECTIONAL OVERCURRENT
Pickup: 0.5 A 240.0 A
Def. Time
Delay: 1 Cycle 8160 Cycles
Curves
BECO Definite Time BECO Inverse BECO Very Inverse BECO Extremely Inverse IECI IECVI
IECEI IECLTI IEEE Moderately Inv. IEEE Very Inverse IEEE Extremely InverseI
Save Cancel
2–72
Application – 2
78 Out-of-Step
The Out-of-Step function (78) is used to protect the Consider, for example, Figure 2-62. If the Out-of-
generator from out-of-step or pole slip conditions. step swing progresses to impedance Z0(t0), the
This function uses one set of blinders, along with a MHO element and the blinder A element will both
supervisory MHO element. Ranges and increments pick up. As the swing proceeds and crosses blinder
are presented in Figure 2-63. B at Z1(t1), blinder B will pick up. When the swing
reaches Z2(t2), blinder A will drop out. If TRIP ON
The pickup area is restricted to the shaded area in MHO EXIT option is disabled and the timer has
Figure 2-61, Out-of-Step Relay Characteristics, expired (t2–t1>time delay), then the trip circuit is
defined by the inner region of the MHO circle, the complete. If the TRIP ON MHO EXIT option is
region to the right of the blinder A and the region to enabled and the timer has expired, then for the trip
the left of blinder B. For operation of the blinder to occur the swing must progress and cross the
scheme, the operating point (positive sequence MHO circle at Z3(t3) where the MHO element drops
impedance) must originate outside either blinder A out. Note the timer is active only in the pickup
or B, and swing through the pickup area for a time region (shaded area). If the TRIP ON MHO EXIT
greater than or equal to the time delay setting and option is enabled, a more favorable tripping angle is
progress to the opposite blinder from where the achieved, which reduces the breaker tripping duty.
swing had originated. When this scenario happens, The relay can also be set with a Pole Slip Counter.
the tripping logic is complete. The contact will The relay will operate when the number of pole slips
remain closed for the amount of time set by the are greater than the setting, provided the Pole Slip
seal-in timer delay. Reset Time was not expired. Typically, the Pole
XT = Transformer Reactance Slip Counter is set to 1, in which case the Pole Slip
Reset Time is not applicable.
XS = System Reactance
Xd’= Transient Reactance of the Generator
78 DELAY The time delay should be set based on the stability study. In
________ Cycles the absence of such a study, it can be set between 3 and 6
cycles.
2–73
M-3425A Instruction Book
A B
Z3(t3)
Z0(t0)
Z1(t1)
Z2(t2)
D
A B
SYSTEM
XS
O
1.5 X T
TRANS
XT
P G
N δ F R
M
H
d SWING
LOCUS
GEN
(X 'd) MHO
ELEMENT
2X d'
BLINDER
ELEMENTS
2–74
Application – 2
? X
F78
Save Cancel
2–75
M-3425A Instruction Book
81 Frequency
The Frequency function (81) provides either Sample settings of the 81 function are shown in
overfrequency or underfrequency protection of the Figure 2-64. The frequency functions are
generator. It has four independent pickup and time automatically disabled when the input voltage
delay settings. The overfrequency mode is (positive sequence) is very low (typically between
automatically selected when the frequency setpoint 2.5 V and 15 V, based on the frequency.)
is programmed higher than the base frequency (50
or 60 Hz), and the underfrequency mode selected The 81 function should be disabled using breaker
when the setpoint is programmed below the base contact when the unit is offline.
frequency. Ranges and increments are presented
in Figure 2-65.
The steam turbine is usually considered to be more
restrictive than the generator at reduced frequencies
because of possible natural mechanical resonance
in the many stages of the turbine blades. If the
generator speed is close to the natural frequency of
any of the blades, there will be an increase in
vibration. Cumulative damage due to this vibration
can lead to cracking of the blade structure.
81 #1 PICKUP These magnitude and time settings describe a curve (as shown in
________ Hz Figure 2-64, Example of Frequency (81) Trip Characteristics) which is
to be coordinated with the capability curves of the turbine and
generator as well as the system underfrequency load-shedding
81 #1 DELAY program. These capabilities are given by a description of areas of
________ Cycles prohibited operation, restricted time operation, and continuous
allowable operation.
The underfrequency function is usually connected to trip the machine
81 #2 PICKUP whereas the overfrequency function is generally connected to an
________ Hz alarm.
In order to prevent mis–operation during switching transients, the
81 #2 DELAY time delay should be set to greater than five (5) cycles.
________ Cycles
81 #3 PICKUP
________ Hz
81 #3 DELAY
________ Cycles
81 #4 PICKUP
________ Hz
81 #4 DELAY
________ Cycles
2–76
Application – 2
Over Frequency
Magnitude #1 Trip
61.0
Over Frequency (Hz) 60.8
60.6
81
59.8
Under Frequency
Magnitude #3
59.6
81
59.4
59.2
Under Frequency
59.0
Magnitude #4 Trip
? X
F81
(81) - FREQUENCY
Save Cancel
2–77
M-3425A Instruction Book
81A Frequency Accumulator for the next band, i.e., Low Band #2 is the upper
Frequency Accumulation feature (81A) provides an limit for Band #3, and so forth. Frequency bands
indication of the amount of off frequency operation must be used in sequential order, 1 to 6. Band #1
accumulated. must be enabled to use Bands #2–#6. If any band is
disabled, all following bands are disabled.
Turbine blades are designed and tuned to operate at
rated frequencies, operating at frequencies different When frequency is within an enabled band limit,
than rated can result in blade resonance and fatigue accumulation time starts (there is an internal ten
damage. In 60 Hz machines, the typical operating cycle delay prior to accumulation), this allows the
frequency range for 18 to 25 inch blades is 58.5 to underfrequency blade resonance to be established
61.5 Hz and for 25 to 44 inch blades is between 59.5 to avoid unnecessary accumulation of time. When
and 60.5 Hz. Accumulated operation, for the life of accumulated duration is greater than set delay,
the machine, of not more than 10 minutes for then the 81A function operated the programmed
frequencies between 56 and 58.5 Hz and not more output contact. The contact can be used to alert the
than 60 minutes for frequencies between 58.5 and operator or trip the machine.
59.5 Hz is acceptable on typical machines.
The accumulator status can be set to preserve the
The 81A function can be configured to track off accumulated information from previous devices.
nominal frequency operation by either set point or This allows the relay to begin accumulating
when the frequency is within a frequency band. information at a pre-defined value. This setpoint is
only available through IPScom® Communications
When using multiple frequency bands, the lower Software.
limit of the previous band becomes the upper limit
81A #1 DELAY
81A #5 LOW BAND PICKUP
________ Cycles
________ Hz
81A #2 DELAY
81A #6 LOW BAND PICKUP
________ Cycles
________ Hz
81A #3 DELAY
________ Cycles
2–78
Application – 2
Example- Band
Fn
81-1 HB
#1 Band
81-1 LB
#2 Band
81-2 LB
#3 Band
81-3 LB
#4 Band
81-4 LB
#5 Band
0 5 10 15
Time (mins)
? X
F81A
High Pickup: #2
50.00 Hz 67.00 Hz #1
Low Pickup: 50.00 Hz 67.00 Hz
Low Pickup: 50.00 Hz 67.00 Hz Delay: 3 Cycles 360000 Cycles
Delay: 3 Cycles 360000 Cycles Reset Reset
Acc. Status: 0 Cycle 360000 Cycles
Acc. Status: 0 Cycle 360000 Cycles
OUTPUTS @ Blocking Inputs Expanded I/O’s OUTPUTS @ Blocking Inputs Expanded I/O’s
8 7 6 5 4 3 2 1 FL 6 5 4 3 2 1 8 7 6 5 4 3 2 1 FL 6 5 4 3 2 1
Save Cancel
2–79
M-3425A Instruction Book
81R #1 DELAY
________ Cycles
81R #2 PICKUP
________ Hz/s
81R #2 DELAY
________ Cycles
? X
F81R
Neg Seq.
Volt Inhibit: 0% 99%
Save Cancel
2–80
Application – 2
87 Phase Differential
The Phase Differential function (87) is a percentage For very high currents in large generators, the
differential with an adjustable slope of 1–100%. proximity of CTs and leads in different phases can
Although this protection is used to protect the cause unbalanced currents to flow in the
machine from all internal winding faults, single- secondaries. These currents must be less than the
phase to ground faults in machines with high minimum sensitivity of the relay.
impedance grounding may have currents less than
the sensitivity of the differential relay (typically There are two elements in this function. Element #2
between 3 and 30 primary amps). Ranges and is intended to provide phase differential protection
increments are presented in Figure 2-70. for SFC (Static Frequency Converter) starting gas
turbine generator applications. Element #1 should
Turn-to-turn faults are not detected by differential be disabled with a contact blocking input during a
relays because the current into the generator equals converter start operation (generator off-line), since
the current out (see functions 50DT and 59X for the current is carried by only neutral side CTs and
turn-to-turn fault protection.) Even though the the resulting differential current may mis-operate
percentage differential relay is more tolerant of CT 87#1 function. The 87#2 element, which is set with
errors, all CTs should have the same characteristics a higher current pickup, will still provide protection
and accuracies. for this condition.
To provide restraint for CT saturation at high offset
currents, the slope is automatically adjusted (at a
restraining current equal to two times nominal
current) to four times the slope setting, see Figure
2-69.
87 #2 DELAY
________ Cycles
If line side and neutral side CTs do not have the same ratio, the ratio
87 PHASE CT CORRECTION error can be corrected (the line side measured current is multiplied by
________ the phase CT correction settings.)
2–81
M-3425A Instruction Book
SLOPE
TRIP (4xset)
((IA x CTC)-Ia),
((IB x CTC)-Ib),
((IC x CTC)-Ic) BLOCK
SLOPE
(set)
MIN PU @ IRES=2xINOM
Restraint Current
((IA x CTC)+Ia)/2, ((IB x CTC)+Ib)/2, ((IC x CTC)+Ic)/2
Where IA and Ia are generator high side and neutral side currents respectively, and CTC is the
CT Phase correction.
Figure 2-69 Differential Relay (87) Operating Characteristics
? X
F87
#2
Save Cancel
2–82
Application – 2
87GD Ground (Zero Sequence) Differential The advantage of directional supervision is the
The Zero Sequence Differential function (87GD) security against ratio errors and CT saturation during
provides ground fault protection for low impedance faults external to the protected generator.
grounded generator applications. High sensitivity
The directional element is inoperative if the residual
and fast operation can be obtained using this
current (3I0 ) is approximately less than 0.2 A, in
function. Ranges and increments are presented in
which case the algorithm automatically disables the
Figure 2-71.
directional element and the 87GD function becomes
The relay provides a CT Ratio Correction Factor non-directional differential. The pickup quantity is
(RC) which removes the need for auxiliary CTs when then calculated as the difference between the
the phase and neutral CT ratios are different. corrected triple zero-sequence current (RC3I0) and
the neutral current (IN). The magnitude of the
When the system can supply zero sequence current difference (RC3I0–IN) is compared to the relay pickup.
to the ground fault (such as when several generators
are bussed together), the 87GD function operates For security purposes during external high phase-
directionally. The directional element calculates the fault currents causing CT saturation, this function is
product (–3I0INCosØ) for directional indication. The disabled any time the value of IN is less than
relay will operate only if I0 (Zero sequence current approximately 0.20 amps.
derived from phase CTs) and IN (Neutral current
from Neutral CT) have the opposite polarity, which ■ NOTE: When 87GD is enabled, 67N function is
is the case for internal generator faults. not available.
? X
F87GD
0.20 A 10.00 A #1
Pickup:
Delay: 1 Cycle 8160 Cycles
CT Ratio Corr: 0.10 7.99
Save Cancel
2–83
M-3425A Instruction Book
Breaker Monitoring
The Breaker Monitoring feature calculates an estimate the relay can operate a programmable output contact.
of the per-phase wear on the breaker contacts by The accumulated value for each phase can be
measuring and integrating the current (IT) or current displayed as an actual value. The accumulation starts
squared (I2T) passing through the breaker contacts after a set time delay from the trip initiate command to
during the interruption period. The per-phase values account for the time it takes for the breaker to start
are added to an accumulated total for each phase, opening its contacts. The accumulation continues
and then compared to a user-programmed threshold until the current drops below 10% of the nominal
value. When the threshold is exceeded in any phase, current setting or 10 cycles, whichever occurs first.
BM INPUT INITIATE Expanded Inputs IN7–IN14 (if equipped) must be set us-
i6 i5 i4 i3 i2 i1 ing IPScom.
BM DELAY
________ Cycles
BM TIMING METHOD
it i2t
? X
FBM
#1
Pickup: 0 KA 50000 KA
Save Cancel
2–84
Application – 2
Trip Circuit Monitoring no current flows and the Trip Circuit Monitoring
External connections for the Trip Circuit Monitoring Input is deactivated. An Output Contact that is
function are shown in Figure 2-73. The default Trip welded closed would also cause the Trip Circuit
Circuit Monitor input voltage is 250 V dc. See Monitoring Input to deactivate, indicating failure of
Section 5.5, Circuit Board Switches and Jumpers, the Output Contact.
Table 5-3 for other available trip circuit input voltage
When the Output Contact is closed, no current
selections. flows in the Trip Circuit Monitoring Input. If the
This function should be programmed to block when M-3425A has issued a trip command to close the
the breaker is open, as indicated by 52b contact Output Contact and Trip Circuit Monitoring Input
input (IN1). If the TCM is monitoring a lockout remains activated, this is an indication that the
relay, a 86 contact input (INx) should be used to Output Contact failed to close.
block when the lockout relay is tripped. The output of the Trip Circuit Monitoring function
When the Output Contact is open, and continuity can be programmed as an alarm to alert
exists in the Trip Circuit, a small current flows that maintenance personnel.
activates the Trip Circuit Monitoring Input. If the
Trip Circuit is open, and the output contact is open,
TCM DELAY
________ Cycles
M-3425A
52b or 86
Station
2 Battery
Trip Circuit
+
Monitoring Input 1 Aux Input
Output Other
Contact Contacts
52a
52 or 86
Trip Coil
-
Figure 2-73 Trip Circuit Monitoring Input
2–85
M-3425A Instruction Book
? X
FTC
TC
Delay: 1 Cycle 8160 Cycles
Save Cancel
2–86
Application – 2
IPSlogic™
The relay provides six logic functions and associated Programming the IPSlogic can only be implemented
IPSlogic. The logic functions can be used to allow through IPScom® Communications Software. The
external devices to trip through the relay, providing IPSlogic cannot be programmed using the Human-
additional target information for the external device. Machine Interface (HMI).
More importantly, these functions can be used in
conjunction with IPSlogic to expand the capability
of the relay by allowing the user to define customized
operating logic.
IPS LOGIC
USE IPSCOM TO CONFIGURE
2–87
2–88
Initiating Outputs
This section of the IPSlogic
used to activate the desired Output
Programmable This section of the IPSlogic
Outputs 1-8 initiates the Function Output
* Outputs 9-23
Picked Up Programmed
Programmed
Outputs 1-8
Time Delay
*Outputs 9-23
Selectable And/Or/Nor/Nand
Selectable And/Or
1-65,500 cycles
Initiating Inputs (1091sec)
Programmable
Inputs 1-6 Log Target
* 7 -14
Selectable And/Or
Initiate Via
Communication
Point IPSlogic
Activated
Blocking Inputs
This section of the IPSlogic used
to Block the Function Output
Programmable
Inputs 1-6 Log Pickup
* 7 -14
Selectable And/Or
Block Via
Communication
Point
Settings and Logic Applicable when The IPSlogic Function can be programmed to
IPSlogic™ Function(s) programmed using perform any or all of the following tasks:
IPScom®
• Change the Active Setting Profile
There are four initiating input sources: Initiating
Outputs, Initiating Function Trips, Function Pickup • Close an Output Contact
(including the IPSlogic Functions themselves), • Be activated for use as an input to another
Initiating Inputs, and initiation using the External Function
Communication Port. The only limitation is that an
IPSlogic Function may not be used to initiate itself. Since there are six IPSlogic Functions per setting
There are two blocking input sources: Blocking profile, depending on the number of different relay
Inputs and blocking using the Communication Port. settings defined, the scheme may provide up to 24
The activation state of the input function selected different logic schemes. The IPScom IPSlogic
in the Initiating Function can be either timeout Function programming screen is shown in Figure
(Trip) or pickup. The desired time delay for security 2-76.
considerations can be obtained in the IPSlogic
Function time delay setting.
(IPS) IPSLogic ? X
#1 #2 #3 #4 #5 #6
Initiating Outputs
8 7 6 5 4 3 2 1
1 #1
OR
Expanded Initiating Outputs OR
Initiating Function Timeout 2
OR
Initiating Function Pickup
Initiate via Communication Point OR
Profile
Delay: 1 Cycle 8160 Cycles NA #1 #2 #3 #4
IPS #1
DO/RST Delay: 0 Cycle 65500 Cycles Activated
Dropout (DO) Timer Reset (RST) Timer
OUTPUTS @
@ : WARNING, You have not selected an output! Expanded Outputs 8 7 6 5 4 3 2 1
Save Cancel
Notes:
1. This logic gate may be selected as either AND or OR.
2. This logic gate may be selected as AND, OR, NOR, or NAND.
Figure 2-76 IPSlogic Function Programing
2–89
M-3425A Instruction Book
2–90
Application – 2
25 35
Cycles
IPSlogic Functions (1 - 6)
PU Status
PU Time Delay
Setting (30) Seal in Delay
Seal in Delay E
PU Time Delay Timing Dropout Delay
B
Output
A C D
IPSlogic Functions (1 - 6) D
C F
PU Status
Reset Delay
10 Cycles B Reset
Delay
Reset
Delay
PU Time Delay
Setting (30)
A G
Seal In
PU Time Delay Timing Timer
E
Output
2–91
M-3425A Instruction Book
2–92
Operation – 3
3 Operation
3–1
M-3425A Instruction Book
3–2
Operation – 3
Self-Tests
POWER ON SELFTESTS
XXXXXXXX TARGET
BECKWITH ELECTRIC CO.
01-Jan-2003 01:05:20.000
53rd St. Substation
Software Version
Serial Number
ENTER ACCESS CODE ACCESS DENIED!
5-minute
Beckwith Electric Co. 0
access
SERIAL NUMBER 137 lockout
and Status Screens VOLT curr freq v/hz Þ pwr lof fuse...
Power-On
27 PHASE UNDERVOLTAGE
PHASE_UNDER ÞÞ nutrl_under phase_over...
27 #1 PICKUP
108 Volts
Main Menu Flow
Local Mode
3–3
M-3425A Instruction Book
3–5
M-3425A Instruction Book
The relay can accept a modulated IRIG-B signal 2. Press the right arrow pushbutton until
using the rear panel BNC connector, or a SETUP SYSTEM is displayed on the
demodulated TTL level signal using extra pins on top line of the screen.
the rear panel COM2 RS-232 interface connector 3. Press the ENTER pushbutton to access
(see Figure B-4 for COM2 pinout.) If the TTL signal the SETUP SYSTEM menu and begin
is to be used, then Jumper 5 will be required to be the data input.
positioned (see Section 5.5, Circuit Board Switches
System setup data is required for proper operation
and Jumpers).
of the relay. Information needed to complete this
section includes: Nominal Voltage, Nominal Current,
Setup Unit Features That Do Not Require Data VT Configuration, and other system-related
Entry information. See Section 2.1, Configuration, Relay
The Setup Unit menu categories that provide the System Setup subsection for a more detailed
user with read only information are Software description of the settings required.
Version, Serial Number and Ethernet Firmware
Ver..
The Setup Unit menu also contains features that
provide the user with the ability to Clear Output
Counters, Clear Alarm Counter, Clear Error
Codes and access the Diagnostic Mode. The error
codes are described in Appendix C, Self Test Error
Codes. Note that while the relay is in Diagnostic
Mode, all protective functions are inoperative.
3–6
Operation – 3
After enabling a function/element, the user is Settings should be programmed based on system
presented with two additional screens for selection analysis as described in Chapter 2, Application. A
of input blocking and output contact designations. complete description of the individual function as
Any combination of the control/status inputs or the well as guidelines for settings are explained therein.
internally generated VT fuse loss logic can be
selected to dynamically block the enabled function.
“OR” logic is used if more than one input is selected.
Outputs 1–6 (OUT9–OUT23 for units with expanded
I/O, set through IPScom only) are form “a” contacts
(normally open) and outputs 7 and 8 are form “c”
contacts (center tapped “a” and “b” contacts). Output
contacts 1–4 contain special circuitry for high-speed
operation and pick up approximately 4 ms faster
than other contacts.
See Section 2.1, Configuration, for more information.
3–7
M-3425A Instruction Book
3–8
Operation – 3
3. Press the ENTER pushbutton to access 3. Press the ENTER pushbutton to access
the COMMUNICATION menu and begin the STATUS menu.
the data entry.
STATUS
COMMUNICATION config sys STAT
targets osc_rec COMM
■ NOTE: Some menus are dynamic, and do not
The general information required to complete the appear if the function is not purchased
communications settings entry of this section or is unavailable.
include:
• Baud rate for COM1 and COM2 4. Press the ENTER pushbutton to move
communication ports. The COM3 port does down within the STATUS menu to the
not have a separate baud rate setting but desired category. To exit a specific
uses the setting of COM2 (or COM1: see category and continue to the next menu
Section 5.5 Circuit Board Switches and category, press the EXIT pushbutton.
Jumpers).
The menu categories for monitored values are:
• Communications address is used to
access multiple relays using a multidrop • Voltage Status: phase voltages, neutral
or network communication line. voltage, positive sequence voltage,
negative sequence voltage, zero sequence
• Communications access code is used for
voltage, third harmonic neutral voltage,
communication system security (entering
field ground measurement circuit, stator
an access code of 9999 disables the low frequency injection voltage
communication security).
• Current Status: phase currents (A–B–C/
• Communication protocol and dead sync
a-b-c), differential current, neutral current,
time for COM2 and COM3.
ground differential current, positive
• Parity for COM2 or COM3 if MODBUS or sequence current, negative sequence
MODBUS over TCP/IP protocol is used. current, zero sequence current, stator low
• Response Time Delay frequency injection current
• IP Address, Net Mask and Gateway • Frequency Status: frequency, rate of
Address are required if the ethernet port is change of frequency
utilized and the network does not support • Volts/Hz Status: volts per hertz
the DHCP protocol. • Power Status: real power, reactive power,
Detailed information concerning setup and operation apparent power, power factor
of the communication ports is described in Chapter • Impedance Status: impedance (Zab, Zbc,
4, Remote Operation. Zca), positive sequence impedance, field
ground resistance
• Sync Check Status: 25S Sync Check
3.5 Status/Metering and 25D Dead Volt
• BRKR Monitor
Monitor Status/Metering
• 81A Accum. Status
■ NOTE: Please see Figure 3-3, Main Menu Flow,
for a list of submenus associated with • IN/OUT Status: Status of input and output
the STATUS menu. contacts
• Timer: 51V Delay Timer, 51N Delay Timer,
To access the STATUS menu and begin monitoring, 46IT Delay Timer, 24IT Delay Timer
proceed as follows: • Relay Temperature
1. Press the ENTER pushbutton to display • Counters: output, alarm counter
the main menu. • Time of Last Power up
2. Press the right arrow pushbutton until • Error Codes
STATUS is displayed on the top line of • Checksums: setpoints, calibration, ROM
the screen.
3–9
M-3425A Instruction Book
3–10
Operation – 3
VIEW TARGET HISTORY This screen gives access to the target history, and also allows
TRGT clear the user to clear the target history record from memory.
TARGET 1 This screen gives the date and time tag of the selected target.
01-JAN-2001 12:27:35.125
TARGET 1 The following screens display the timed out or “operate” func-
-OPERATE TARGETS- tions.
TARGET 1 This screen displays the specific function which timed out and
27#1 PHASE UNDERVOLTAGE triggered the target.
TARGET 1 This screen displays the phase information for the displayed
PHASE A=X B= C= function at time out.
TARGET 1
27#1 PHASE UNDERVOLTAGE
TARGET 1 This display gives the phase pickup information for the specific
PHASE A=X B=X C=X function.
TARGET 1
-CURRENT STATUS-
TARGET 1 This screen displays the phase current at the time the target
a=0.02 b=0.03 c=0.04 operated.
TARGET 1 This screen displays the neutral current at the time the target
N=0.50 AMPS operated.
3–11
M-3425A Instruction Book
3–12
Remote Operation – 4
4 Remote Operation
1
4.1 Remote Operation ...................................................................... 4–1
®
4.2 Installation and Setup (IPScom ) ............................................. 4–8
This chapter is designed for the person or group Serial Port (RS-485)
3
responsible for the remote operation and setting of COM3 located on the rear terminal block of the
the relay using the M-3820D IPScom M-3425A is an RS-485, 2-wire connection. Appendix
Communications Software or other means. B, Figure B-3 illustrates a 2-wire RS-485 network.
Individual remote addressing also allows for
4.1 Remote Operation communications through a serial multidrop network.
Up to 32 relays can be connected using the same
The M-3425A Generator Protection Relay provides
three serial communication ports and one ethernet
2-wire RS-485 communications line.
A
port. Optional Ethernet Port
The M-3425A when equipped with the optional
Serial Ports (RS-232) Ethernet Port can be accessed from a local network.
Two serial interface ports, COM1 and COM2, are When the ethernet port is enabled the COM2 serial
standard 9-pin, RS-232, DTE-configured ports. The port (RS-232) is unavailable for use. Although the
front-panel port, COM1, can be used to locally set ethernet connection speed is faster than the RS-232
and interrogate the relay using a temporary
connection to a PC or laptop computer. The second
RS-232 port, COM2, is provided at the rear of the
port (can be up to 10 Mbps), the ethernet module
connects internally through the COM2 serial
connection and is therefore limited to connection
B
unit. COM2 is unavailable for use when the optional speeds up to 9600 bps.
ethernet port is enabled.
The individual addressing capability of IPScom and Either COM2, COM3 or Ethernet port may be used
the relay allows multiple systems to share a direct to remotely set and interrogate the relay using a
or modem connection when connected through local area network, modem or other direct serial
COM2 using a communications-line splitter (see connection. Equipment such as RTU’s, data
Figure 4-1). One such device enables 2 to 6 units to
share one communications line. Appendix B, Figure
concentrators, modems, or computers can be
interfaced for direct, on-line, real time data
acquisition and control. Generally, all data available
C
B-2 illustrates a setup of RS-232 Fiber Optic network.
to the operator through the front panel of the relay
with the optional M-3931 HMI module is accessible
remotely through the BECO 2200, MODBUS, BECO
2200 over TCP/IP or MODBUS over TCP/IP data
exchange protocols.
4–1
M-3425A Instruction Book
The communication protocols are used to fulfill the When fabricating communication cables, every effort
following communications functions: should be made to keep cabling as short as possible.
• Real-time monitoring of line status Low capacitance cable is recommended. The RS-232
standard specifies a maximum cable length of 50
• Interrogation and modification of setpoints
1 • Downloading of recorded oscillograph data
• Reconfiguration of all relay functions
feet for RS-232 connections. If over 50 feet of cable
length is required, other technologies should be
investigated.
Protocol documents are available directly from Other communication topologies are possible using
Beckwith Electric or from our website the M-3425A Generator Protection Relay. An
www.beckwithelectric.com. Application Note, “Serial Communication with
Direct Connection
Beckwith Electric’s Integrated Protection System
Relays” is available from the factory or from our
In order for IPScom to communicate with the relay website at www.beckwithelectric.com.
using direct serial connection, a serial “null modem”
cable is required, with a 9-pin connector (DB9P) for
the system, and an applicable connector for the
computer (usually DB9S or DB25S). Pin-outs for a
null modem adapter are provided in Appendix B,
Communications.
An optional 10 foot null modem cable (M-0423) is
available from the factory, for direct connection
between a PC and the relay’s front panel COM port,
3 or the rear COM2 port.
IBM-Compatible PC
B Master Port
Communications-Line Splitter
C Address 6
Address 5
Address 4
Address 1
Address 3 Up to six controls
Integrated Protection can be used with a
System Address 2 communications-line splitter.
4–2
Remote Operation – 4
Setting Up the M-3425A Generator Protection Communication Access Code: If additional link
Relay for Communication security is desired, a communication access code
The initial setup of the relay for communication can be programmed. Like the user access codes, if
must be completed by utilizing the optional M-3931 the communication access code is set to 9999
HMI Module or using direct serial connection.
For units shipped without the optional HMI Module,
(default), communication security is disabled.
Individual relay communication addresses should
1
the communication parameters may be altered by be between 1 and 200. The dead sync time, while
first establishing communication using the default not critical for most communication networks, should
parameters and the IPSutil™ program. be programmed to match the communications
channels baud rate (see Table 4-1, below).
IPSutil is an auxiliary program shipped on the same
disk with the IPScom ® program. It is used
exclusively for altering communication and setup
parameters on units shipped without the M-3931 Baud Rate De ad-Sync Time
HMI Module.
9600 4 ms
Serial Communication Settings 4800 8 ms
The following parameters must be set for proper
serial communication: 2400 16 ms
COM1 Baud Rate: Standard baud rates from 300 to
9600 are available. 1200 32 ms
COM2 Baud Rate: Standard baud rates from 300 to
9600 are available. COM2 and COM3 share the
Table 4-1 Dead-Sync Time 3
same baud rate (see Section 5.5, Circuit Board Ethernet Communication Settings
Switches and Jumpers).
The RJ45 ethernet port can be enabled utilizing
COM2 Dead Sync Time: This delay establishes either IPSutil™ from the Ethernet Settings menu or
the line idle time to re-sync packet communication. from the HMI Communication menu. When the
Dead sync time should be programmed based on ethernet port is enabled the COM2 Serial Port is not
the channel’s baud rate. available for use.
COM2 Protocol: BECO 2200 or MODBUS protocol
is supported on COM2.
The following parameters must be set for proper
ethernet communication:
A
COM2 Parity: None, odd or even parity is available DHCP Protocol
if MODBUS protocol is selected.
ENABLE: If the network server supports the DHCP
COM2 Stop Bits: One or two stop bits available if protocol the network server will assign the IP
MODBUS protocol is selected.
Address, Net Mask and Gateway Address.
COM3 Dead Sync Time: This delay establishes
the line idle time to re-sync packet communication.
Dead sync time should be programmed based on
the channel’s baud rate.
DISABLE: If the network server does not support
the DHCP protocol or the user chooses to manually
input ethernet settings, then obtain the IP Address,
B
Net Mask and Gateway address from the Network
COM3 Protocol: BECO 2200 or MODBUS protocol Administrator and enter the settings.
is supported on COM3.
COM3 Parity: None, odd or even parity is available ETHERNET Protocols
if MODBUS protocol is selected. SERCONV:To utilize the BECO2200 protocol over
a TCP/IP connection select the SERCONV
COM3 Stop Bits: One or two stop bits available if
MODBUS protocol is selected.
(BECO2200 TCP/IP) protocol. The IP Address of
the relay must be entered in the IPScom
Communication screen. Also, ensure that the COM2
C
Communications Address: For multidrop networks,
protocol is selected to BECO2200 and the baud
each device must have a unique address.
rate is set to 9600 bps.
Response Time Delay: The extra time delay may
be added while the relay is sending the response. If
set to 0, the response of the relay will be equal to
the time required to process the incoming packet
(usually 20–80 ms.)
4–3
M-3425A Instruction Book
The Standard Port Number for the BECO2200 over 6. Ensure that TCP is selected (Upper Case).
TCP/IP protocol is 8800. The master device may
If TCP is not selected (Upper Case), then
require the entry of the Standard Port Number.
use the Right/Left arrow pushbuttons to
MODBUS:To utilize the MODBUS protocol over a select TCP.
1 TCP/IP connection select the MODBUS (MODBUS
over TCP/IP) protocol. The IP Address of the relay
7. Press ENTER, the following will be
displayed:
must be entered in the IPScom® Communication
screen. Also, ensure that the COM2 protocol is DHCP PROTOCOL
selected to MODBUS, baud rate is set to 9600 bps, DISABLE enable
1 stop bit and no parity selected.
8. If the network does not support the DHCP
The Standard Port Number for the MODBUS over
protocol, then go to Manual Configuration
TCP/IP protocol is 502. The master device may
of Ethernet Board (following page) to
require the entry of the Standard Port Number. manually configure the ethernet board.
9. If the DHCP Protocol is to be enabled, then
Ethernet Port Setup
use the Right/Left arrow pushbutton to select
Enabling the ethernet port and selecting the required ENABLE (Upper Case), then press ENTER,
support settings can be accomplished using either the following will be displayed:
the HMI or IPSutil™. Both methods are presented
below. TCP/IP SETTINGS
TCP prot
HMI Ethernet Port Setup
4–4
Remote Operation – 4
Then the display will return to the following: 8. Use the Right/Left arrow pushbuttons to
select the desired protocol (Upper Case),
ETHERNET SETUP
then press ENTER, the following will be
access ETH eth_ip displayed:
4–5
M-3425A Instruction Book
IPScom
File Comm Relay Window Help
A:1 M-3425
Setup System
Relay Setpoints
Set Date/Time
Primary Status
A Display
Reset LED
Secondary Status
Accumulator Status
Phase Distance
Setup Clear History Loss of Field
Retrieve Out of Step
Trigger Switching Method
Phasor Diagram
Clear Active Profile
Sync Scope
Setup Copy Profile
Function Status
Retrieve
B View
Clear
■ NOTE: Greyed-out menu items are for future release, and are not currently available.
4–6
Remote Operation – 4
3. From the Ethernet Settings screen select b. The modem must be attached to (if
Ethernet Enable. external) or assigned to (if internal) the
same serial port as assigned in IPScom.
4. Select DHCP Protocol Disable. While IPScom can use any of the four
5. Enter values for IP Address, Net Mask and
Gateway.
serial ports (COM1 through COM4),
most computers support only COM1
and COM2.
1
6. Select the desired protocol.
c. Connect the modem to the telephone
7. Select Save, IPSutil will respond with the line and power up.
Advance Setup dialog box stating “It will
take about 15 seconds to reset Ethernet 2. Connecting the Modem to the Relay:
board to allow the menu of the unit to Setup of the modem attached to the relay
reflect the change.” may be slightly complicated. It involves
programming the parameters (using the AT
8. Select OK, IPSutil will configure the ethernet command set), and storing this profile in
board, then close the Ethernet Settings the modem’s nonvolatile memory.
screen. The ethernet board is now
configured for use and may be accessed After programming, the modem will power
through a network. up in the proper state for communicating
with the relay. Programming may be
accomplished by using “Hyperterminal” or
Installing the Modems
other terminal software. Refer to your modem
Using IPScom to interrogate, set or monitor the manual for further information.
relay using a modem requires both a remote modem
connected at the relay location and a local modem
connected to the computer with IPScom installed.
■ NOTE: The relay does not issue or understand
any modem commands. It will not adjust
the baud rate and should be considered
3
In order to use IPScom to communicate with the a “dumb” peripheral. It communicates
relay using a modem, the following must be provided with 1 start, 8 data, and 1 stop bit.
with the unit:
a. Connect the unit to an external modem
• An external modem (1200 baud or higher), by attaching a standard RS-232 modem
capable of understanding standard AT cable to the appropriate serial
commands. communications port on both the unit
• Serial modem cable with 9-pin connector
for the unit and the applicable connector
for the modem.
b.
and the modem.
Connect the modem to the telephone
line and power up.
A
■ NOTE: Any compatible modem may be used; The modem attached to the unit must have the
however, the unit only communicates at following AT command configuration:
1200 to 9600 baud.
E0 No Echo
Similarly, the computer running IPScom must also Q1 Don’t return result code
have access to an internal or external compatible &D3 On to OFF DTR, hang-up and reset
modem.
The local modem can be initialized, using IPScom,
&S0
&C1
DSR always on
DCD ON when detected
B
by connecting the modem to the computer, and S0=2 Answer on second ring
selecting the COMM menu in IPScom. Select
MODEM, enter the required information, and finally The following commands may also be required at
select INITIALIZE from the expanded the modem:
Communications dialog box. The following steps
outline the initialized modem setup procedure. &Q6 Constant DTE to DCE
N0 Answer only at specified speed
1. Connecting the modem to the computer:
a. If the computer has an external modem,
use a standard straight-through RS-232
W
\Q3
Disable serial data rate adjust
Bi-directional RTS/CTS relay
C
modem cable to connect the computer &B1 Fixed serial port rate
and modem (M-3933). If the computer S37 Desired line connection speed
has an internal modem, refer to the
modem’s instruction book to determine There are some variations in the AT commands
which communications port should be supported by modem manufacturers. Refer to the
selected. hardware user documentation for a list of supported
AT commands and direction on issuing these
commands.
4–7
M-3425A Instruction Book
4–8
Remote Operation – 4
Nominal Frequency: 50 Hz 60 Hz
OK
C
C.T. Secondary Rating: 1A 5A Cancel
4–9
M-3425A Instruction Book
Address
9600
TCP IP
Modem
Delete
Save
Deletes a selected entry.
Saves any changes to the displayed
Cancel
information
Open TCP_IP
TCP IP ADDRESS: Initialize Allows the user to send special setup or
Close TCP_IP other AT commands directly to the
Modem
modem.
Bring up terminal window after dialing
Phone Number: Dial Dials the entry selected from the
directory.
Delete
Relay Menu
Save
Setup
3 Figure 4-5
Path: Comm menu
Communication Dialog Box
Monitor
Target
A TCP_IP
or modem communication.
Opens the ethernet applicable
communication screen selections to
The Relay menu provides access to the windows
used to set, monitor, or interrogate the relay. Six
submenus are provided: Setup, Monitor, Target ,
allow user to enter a TCP_IP address (if Sequence of Events, Oscillograph and Profile
necessary), and opening and closing as well as two commands, Write File to Relay, and
communication with the target relay.
Read Data From Relay.
Modem Displays the expanded Communication
dialog box.
Relay
Cancel Returns you to the IPScom main window;
4–10
Remote Operation – 4
SETUP
SETUP SYSTEM
59/27 Mag. Select: RMS 50DT Enable Relay Seal-In Time Relay Seal-In Time Expanded
DFT
Split Phase
Phase Rotation: ABC AC B Differential: Disable OUT 1: 30 8160 OUT 9: 30 8160 30 OUT 17
cycles cycles
V.T. Phase Ratio: :1 1.0 2: 30 10: 30 30 18
1.0 6550.0
3: 30 11: 30 30 19
V.T. Neutral Ratio: 1.0 :1 1.0 6550.0
4: 30 12: 30 30 20
V.T. VX Ratio 1.0 :1 1.0 6550.0
5: 30 13: 30 30 21
C.T. Phase Ratio: 10 :1 1 65500 6: 30 14: 30 30 22
C.T. Neutral Ratio: 10 :1 1 65500 7: 30 15: 30 30 23
2 2
Pulse Relay
Outputs: 1
Latched Outputs
Outputs: 1
2 3
2
4
3
5
4 5
6
6
7
7
8
8
8: 30 cycles
Save Cancel A
Figure 4-6 Setup System Dialog Box
COMMAND BUTTONS
Input Active When the unit is equipped with expanded I/O, this command opens the Expanded Input Active
State
Expanded
State screen (Figure 4-7), to allow the selection of Expanded Inputs 7 through 14. B
Pulse/Latch When the unit is equipped with expanded I/O, this command opens the Pulse/Latch
Relay screen (Figures 4-8 and 4-9) to allow the selection of expanded outputs 9 through 23.
Expanded
Outputs
Save When connected to a protection system, sends the currently displayed information to the unit.
Otherwise, saves the currently displayed information.
Cancel Returns you to the IPScom® main window; any changes to the displayed information are lost.
■ NOTE: Checking the inputs for the Active Input Open parameter designates the “operated” state established by
an opening rather than a closing external contact.
C
4–11
M-3425A Instruction Book
? X
Expanded Input Active State
1 7
8
Open
Open
Close
Close
11
12
Open
Open
Close
Close
OK
Cancel
9 Open Close 13 Open Close
? X
OUTPUT9 OUTPUT17
OUTPUT10 OUTPUT18
OUTPUT11 OUTPUT19
3 OUTPUT12
OUTPUT13
OUTPUT20
OUTPUT21
OK
Cancel
OUTPUT14 OUTPUT22
OUTPUT15 OUTPUT23
OUTPUT16
? X
OUTPUT9 OUTPUT17
OUTPUT10 OUTPUT18
B OUTPUT11
OUTPUT12
OUTPUT19
OUTPUT20 OK
OUTPUT13 OUTPUT21
Cancel
OUTPUT14 OUTPUT22
OUTPUT15 OUTPUT23
OUTPUT16
C
Figure 4-9 Latch Relay Expanded Output Screen
4–12
Remote Operation – 4
The Setpoints command displays the Relay feature hotspots which allows the user to jump from
Setpoints dialog box (see Figure 4-10) from which a scrolling dialog box to an individual relay function
the individual relay function dialog boxes can be dialog box and return to the scrolling dialog box
accessed. Choosing a Relay function button will again. All available parameters can be reviewed or
display the corresponding function dialog box (see
Figure 4-11 for example).
changed when jumping to a relay configuration dialog
box from either scrolling dialog box. 1
? X
3
46 51V 67N TC
Neg. Seq. Inv. Time Residual Dir. Trip Circuit command button OR 46 jump hotspot within All Setpoints
Overcurrent Monitor
Overcurrent Overcurrent Table or Configure dialog box
FUNCTIONS FUNCTIONS
21 -- 51V 59 -- TC
COMMAND BUTTONS
Configure Configure
Save When connected to a protection system,
OUTPUTS 1-8 OUTPUTS 9-23
Exit
sends the currently displayed
INPUTS 1-FL INPUTS 7-14 information to the unit. Otherwise, saves
the currently displayed information and
Figure 4-10 Relay Setpoints Dialog Box returns you to the Relay Setpoints, All
Setpoints Table, or Configure dialog
Path:
COMMAND BUTTONS
Relay menu / Setup submenu / Setpoints window
Cancel
box.
Returns the user to the Relay Setpoints,
A
All Setpoints Table, or Configure dialog
Functions Opens the All Setpoints Table dialog box box; any changes to the displayed
for the specified range of functions. information are lost.
Configure Opens the Configure dialog box. Expanded When the unit is equipped with expanded
I/O’s I/O, this selection allows the user to select
Exit Saves the currently displayed expanded outputs 9–23 and expanded
information and returns you to the inputs 7–14.
IPScom® main window.
The Relay Setpoints dialog box gives access to two
additional dialog boxes: All Setpoints Table and
? X B
Expanded Output Initiate Expanded Input
Configure. Initiate
OUTPUT9 OUTPUT17 Input 7
settings for each relay within a single window to OUTPUT14 OUTPUT22 Input 12
Input 14 C
which contains a chart of programmed input and
output contacts, in order to allow scrolling through Figure 4-12 Expanded I/O Initiate
all relay output and blocking input configurations.
Both dialog boxes (All Setpoint Table and Configure),
4–13
M-3425A Instruction Book
3 Delay #1:
Pickup #2:
Time Dial:
Curves #:
25S Lower Volt Limit:
Sync Check Delay:
Delta Voltage:
25D
Hot V1 Dead V2:
Dead V1 Dead V2:
Dead Delay:
Delay #2: Reset Rate: Delta Frequency: Input Initiate:
25S Sync Check:
Delay #2:
JUMP HOTSPOTS
This window provides you with jump hotspots, identified by the hand icon, that take you to each relay dialog box and
B the Setup Relay dialog box. Exiting any of these dialog boxes will return you to the All Setpoints Table dialog box.
CONTROL MENU
Close Returns you to the Relay Setpoints dialog box.
Move Allows you to reposition the dialog box.
4–14
Remote Operation – 4
Configure X
O U T P U T S Blocking Inputs
8 7 6 5 4 3 2 1 FL 6 5 4 3 2 1
1
#1
21 #2
#3
Def. Time #1
24 Def. Time #2
Inverse Time
25 Sync
Dead
27TN #1
#2
#1
27 #2
#3
32
#1 3
#2
#3
#1
40 #2
VC#1
VC#2
46
Def. Time
Inv. Time
A
50BF
#1
50
#2
50N
50DT
#1
#2 B
Figure 4-14 Configure Dialog Box (partial)
Path: Relay menu / Setup submenu / Setpoints window/ Configure command button
JUMP HOTSPOTS
This window provides you with jump hotspots, identified by the hand icon, that take you to each relay dialog box.
Exiting any of these dialog boxes will return you to the Configure dialog box.
CONTROL MENU
C
Close Returns you to the Relay Setpoints dialog box.
Move Allows you to reposition the dialog box.
4–15
M-3425A Instruction Book
Configure X
Def. Time #1
24 Def. Time #2
Inverse Time
25 Sync
Dead
27TN #1
#2
#1
27 #2
#3
#1
32 #2
#3
3 40
#1
#2
VC#1
VC#2
Def. Time
46
Inv. Time
50BF
#1
50
#2
A 50N
50DT
#1
#2
Path: Relay menu / Setup submenu / Setpoints window/ Configure command button
JUMP HOTSPOTS
B This window provides you with jump hotspots, identified by the hand icon, that take you to each relay dialog box.
Exiting any of these dialog boxes will return you to the Configure dialog box.
CONTROL MENU
Close Returns you to the Relay Setpoints dialog box.
Move Allows you to reposition the dialog box.
4–16
Remote Operation – 4
The Set Date/Time command (see Figure 4-16) The Monitor submenu provides access for reviewing
allows the system date and time to be set, or the present status of the relay's measured and
system clock to be stopped. This dialog box also calculated values, other real-time parameters and
displays an LED mimic to identify when the Time conditions as well as examining real-time and
Sync is in use (preventing date/time from being
changed by user).
historical demand metering information (see Section
4.4, Checkout Status/Metering). A cascading menu
appears, providing several command options as
1
shown below.
■ NOTE: Displayed parameters in status screens
will vary depending on unit configuration.
Relay
Setup
Monitor Primary Status
Target Secondary Status
Sequence of Events Accumulator Status
Oscillograph Phase Distance
Profile Loss of Field
3
Sync Scope
Figure 4-16 Unit Date/Time Dialog Box Function Status
Setup
B
Monitor
Target Display
COMMAND BUTTONS
Sequence of Events Reset LED
Stop Clock This toggles between start/stop, the relay Oscillograph Clear History
clock. ‘Stop’ pauses, ‘Start’ resumes.
Profile
Save Saves Time and Date settings to the
C
Write File to Relay
relay when applicable.
Read Data From Relay
Cancel Returns you to the IPScom ® main
window. Any changes to the displayed
information is lost.
The Clear History command clears all stored target
data.
4–17
M-3425A Instruction Book
1
Expanded Inputs:
Outputs: 8 7 6 5 4 3 2 1
16 15 14 13 12 11 10 9
Expanded Outputs
23 22 21 20 19 18 17
Function # Status
COMMAND BUTTONS
Comment Opens comment dialog box for annotation.
Print Prints out selected target information, with comment.
Save Saves selected target information, with comment, as a text file.
Close Exits the currently displayed dialog box.
A Sequence of Events
The Sequence of Events function provides a time View the pararmeters captured at the time of the
stamped history of the Pickup (PU), Trip (TR) or event and Clear the event recorder.
Dropout (DR) for each element, input or output
selected in the Event Trigger Setup screen. The Setup menu item displays the Event Trigger
Setup screen Figure 4-18. Protective function Pickup,
During each event the voltage, current, impedance, Trip, Dropout and/or Output/Input Pickup or Dropout
frequency, input and output status and Volts/Hz are are selected to trigger the Sequence of Events
recorded. Up to 512 events are logged before the Recorder.
buffer begins to write over the oldest event. If multiple
B events occur, then the log entries are recorded with
one millisecond resolution within each event.
The Retrieve command downloads the events from
the currently connected relay (events must be
retrieved from the relay and stored in a file in order to
view them.)
Relay
Profile
View (20 Hz), and Istator (20 Hz) which are displayed in
Clear
the Event Log Viewer screen Figure 4-19.
Write File to Relay
Read Data From Relay The event log viewer screen includes the commands
Open, Close, Print Summary, and Print Detail.
The Sequence of Events submenu allows the user Open opens a saved sequence of events file. Close
to Setup the events that trigger the Sequence of closes the print file. Print Summary prints an event
Events recorder, Retrieve events from the relay, summary, and Print Detail prints the detailed event
report. Clear deletes event history from the control.
4–18
Remote Operation – 4
Pickup Drop
1
Functions
PU TR DR PU TR DR PU TR DR PU TR DR PU TR DR o input7 o input7
o o o F21 #1 o o o F32 #3 o o o F50N o o o F64F #2 o o o F81r #1 o input8 o input8
o o o F21 #2 o o o F40 #1 o o o F51N o o o F64S o o o F81R #2 o input9 o input9
o o o F21 #3 o o o F40 #2 o o o F51V o o o F67NDT o o o F87 #1 o input10 o input10
o input11 o input11
o o o F24DT #1 o o o F40VC #1 o o o F59 #1 o o o F67NIT o o o F87 #2
o input12 o input12
o o o F24DT #2 o o o F40VC #2 o o o F59 #2 o o o F78 o o o F87GD
o input13 o input13
o o o F24IT o o o F46DT o o o F59 #3 o o o F81 #1 o o o FBM o input14
o input14
o o o F25S o o o F46IT o o o F59D o o o F81 #2 o o o FTC o output9 o output9
o o o F25D o o o F49 #1 o o o F59N #1 o o o F81 #3 o o o IPSL #1 o output10 o output10
o o o F27 #1 o o o F49 #2 o o o F59N #2 o o o F81 #4 o o o IPSL #2 o output11 o output11
o o o F27 #2 o o o F50 #1 o o o F59N #3 o o o F81A #1 o o o IPSL #3 o output13 o output13
o o o F27 #3 o o o F50 #2 o o o F59X #1 o o o F81A #2 o o o IPSL #4 o output14 o output14
o output15 o output15
o o o F27TN #1 o o o F50/27 o o o F59X #2 o o o F81A #3 o o o IPSL #5
o output16 o output16
o o o F27TN #2 o o o F50BF o o o F60FL o o o F81A #4 o o o IPSL #6
o output17 o output17
o o o F32 #1 o o o F50DT #1 o o o F64B o o o F81A #5 o output18
o output18
o o o F32 #2 o o o F50DT #2 o o o F64F #1 o o o F81A #6 o output19 o output19
o output20 o output20
o output21 o output21
Outputs Inputs o output22
o output22
Expanded IO<<
PU 1 2 3 4 5 6 7 8 PU 1 2 3 4 5 6 o output23 o output23
DR 1 2 3 4 5 6 7 8 DR 1 2 3 4 5 6
Event Record 1
No. Event Summary
Voltages (V) Impedance (Ohm)
1 09/01/2004, 15:01:33.007
F27 #1: Pickup [A ]/Trip [A ] VA 99.9 VB 120.5 VC 119.9 Rab 110.68 Xab 5.04
2 09/01/2004, 15:02:55.507
F27 #1: Pickup [A ]/Trip [A ] VN 119.7 VX 119.7 3rdH 1.63 Rbc 120.18 Xbc -0.76
F50 #2: Pickup [A ]/Trip [A ]
3 09/01/2004, 15:02:55.615 VPS 113.3 VNS 6.7 VZS 6.7 Rca 110.48 Xca -6.62
4
F27 #1: Pickup [A ]/Trip [A
F32 #1: Pickup/Trip
F50 #2: Pickup [A ]/Trip [A
09/01/2004, 15:05:03.624
F21 #2: Pickup
]
] Currents (A)
IA 0. 996 IB 1.005 IC 0.997
Others
V/Hz (%) 99.9
B
F27 #1: Pickup [A ]/Trip [A ]
F32 #1: Pickup/Trip Ia 0. 994 Ib 1.003 Ic 0.997 Frequency (Hz) 99.9
F21 #3: Pickup [A C]
F50 #2: Pickup ]A ]/Trip [A ] IPS 0.996 INS 0.002 IN 0.997 Current Profile 1
Input
PU 1 2 3 4 5 6
Items Value Unit
Expanded Real Power 0.97 W
IO >>
DR 1 2 3 4 5 6 Reactive Power -0.007 Var
IZS 0.003 A
Output Ia diff 1.01 A
PU
DR
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Ib diff
Ic diff
Delta V
Delta F
1.01
1.01
0.1
0.000
A
A
V
Hz
C
Voltages, Currents and I/O Status
4–19
M-3425A Instruction Book
Total Event Number: Download Record #4: Cleared Record #12: Cleared
Cancel
File Format: Beco (.OSC) COMTRADE (Binary.cfg, .dat)
Retrieve Cancel
Setup
Monitor Relay
Target Setup
Sequence of Events Monitor
Oscillograph Setup Target
Profile Retrieve Sequence of Events
Trigger Oscillograph
Write File to Relay Switching Method
Clear Profile Active Profile
Read Data From Relay
Copy Profile
later time. The Setup command allows the user to The Profile submenu provides three command
set the number of partitions and triggering options: Switching Method, Active Profile, and
designations to be made (see Table 3-1, Recorder Copy Profile.
Particitions). The Retrieve command downloads
and stores collected data to a file; Trigger allows Switching Method command allows selection of
the manual triggering of the recorder; Clear erases either Manual or Input contact. Active Profile allows
user to designate active profile. Copy Profile copies
A the existing records. Run the optional M-3801D
IPSplot® PLUS Oscillograph Analysis Software
program to view the downloaded oscillograph files.
active profile to one of four profiles (user should
allow approximately 2 minutes for copying.)
▲ CAUTION: Switching the active profile when the
Setup Oscillograph Recorder
relay is on-line may cause unexpected operation if
Number of Records
1 2 3 4 5 6 7 8
the wrong profile is selected.
9 10 11 12 13 14 15 16
B
Cancel
Trigger Inputs
Manual Input Contact
6 5 4 8 7 6 5
3 2
Trigger Outputs
1 4 3 2 1 Active Profile
Trigger Inputs Expanded Trigger Outputs Expanded
14 13 12 11 23 22 21 20 19 18 17 16 P1 P2 P3 P4
10 9 8 7 15 14 13 12 11 10 9
OK Cancel
4–20
Remote Operation – 4
Active Profile
P1 P2 P3 P4
1
The Window menu enables the positioning and
arrangement of all IPScom® windows so that there
OK Cancel
is better access to available functions. This feature
allows the display of several windows at the same
time. Clicking on an inactive window activates that
Figure 4-24 Select Active Profile window.
Help
OK Cancel
Setup
Monitor
required to view this document.
The M-3425A Instruction Book has been indexed to
A
Target its table of contents. By selecting the “Navigator
Sequence of Events pane’ in Adobe Acrobat Reader, the user can directly
Oscillograph
access selected topics. The About command
Profile
displays IPScom version and development
information. Profile Info displays user infromation
Write File to Relay for input and editing.
Read Data From Relay
About IPScom
IPScoms OK
X
B
Integrated Protection System
Version: D-0133V02.00.15
Copyright 1997-2002 Beckwith Electric Co., Inc.
Unit Information
ID M-3425A
BECKWITH ELECTRIC CO
M-3425A
Serial Number
Software Version
Communication Address
1
V02.00.22
1
C
Control Number 1
Setpoint Checksum 13
Calibration Checksum 3E
4–21
M-3425A Instruction Book
Primary Status - X
1 0.00
Phase A
(v)
0.00
Phase B (v)
0.00
Phase C (v)
0.00
Neutral
(v)
0.00
Pos Seq
(v)
VOLTAGE
0.00
Neg Seq
(v)
0.00
Zero Seq (v)
0.00
3rd Harm
(v)
0.00
VX
(v)
CURRENT
POWER
Hz % Hz/S
CLOSED
8 7 6 5 4 3 2 1 FL 6 5 4 3 2 1
3 16 15 14 13 12 11 10 9 13 12 11 10 9 8 7
23 22 21 20 19 18 17 14
A Secondary Status - X
VOLTAGE
0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.0
Phase A Phase B Phase C Neutral VX Pos Seq Neg Seq Zero Seq Low F Inj. Brush (mV)
CURRENT
B Phase a
0.000
Phase b
0.000
POWER
Phase c
0.000 0.000
A-a diff B-b diff
0.000
C-c diff
0.000 0.000
I diff G
0.000
49#1 49#2
0.000
IMPEDANCE
R 0.00 X 0.00 R 0.00 X 0.00 R 0.00 X 0.00 R 0.00 X 0.00 R <5 k ohm
OUTPUTS BREAKER
INPUTS
C 8 7 6
EXPANDED OUTPUTS
5 4 3 2 1 FL 6 5 4
EXPANDED INPUTS
3 2 1
CLOSED
16 15 14 13 12 11 10 9 13 12 11 10 9 8 7
23 22 21 20 19 18 17 14
4–22
Remote Operation – 4
Startup Time:
Accumulator #1 Cycles
1
Accumulator #2 Cycles
Accumulator #3 Cycles
Accumulator #4 Cycles
Accumulator #5 Cycles
Accumulator #6 Cycles
3
Figure 4-29 Accumulator Status Screen
Phase Distance X
Circle Diameter
X 1.00
70
Circle Offset
A
0.10
60
40
30 Phase Impedances:
AB: Ω
20
BC: Ω
10 CA: Ω
4–23
M-3425A Instruction Book
Loss of Field X
Circle Diameter:
X
10 Circle Offset:
1
-0.80 -0.30 -20 -10 10 20 30 40
Directional Element
-10
-20
Positive Sequence
Impedance :
-30
-40
-50
-60
-70
CONTROL BUTTONS
Zoom In
3 Move up the scope window
Move down the scope window Zoom Out
Out of Step X
Circle Diameter
A
X 20.0 W
40
Circle Offset
15.0 W
35
25
Blinder Impedance
20 5.0 W
B
10
ENABLED
5
-0.80 -0.60 -0.40 -0.20 -10 0.20 0.40 0.60 0.80
C CONTROL BUTTONS
Move up the scope window Move the scope window to the right
4–24
Remote Operation – 4
CONTROL BUTTONS
3
p Voltage Toggle & display voltage channel information
p Currents (A) Toggle & display current channel information.
p Freeze Toggle & update information
Sync Scope X
SLOW
0
FAST
A
330 30
o
Phase Angle: 23.1
270 90
B
240 120
210 150
180
4–25
M-3425A Instruction Book
Function Status X
P T P: Pickup T:Tripped T P
(21) #1 Phase Distance (59N) #1 Neutral Overvoltage
3
(50) #1 Phase Overcurrent (87) #1 Phase Differential Current
(50) #2 Phase Overcurrent (87) #2 Phase Differential Current
(50N) Instant. Neutral Overcurrent (87GD) Ground Differential Current
(50DT) #1 Time Overcurrent (IPSL) #1 IPS LOGIC
(50DT) #2 Time Overcurrent (IPSL) #2 IPS LOGIC
(50/27) Inadvertent Energizing (IPSL) #3 IPS LOGIC
(51N) Inv. Time Neu. Overcurrent (IPSL) #4 IPS LOGIC
(51V) Inv. Time Phase Overcurrent (IPSL) #5 IPS LOGIC
(59) #1 Phase Overvoltage (IPSL) #6 IPS LOGIC
(59) #2 Phase Overvoltage (BM) Breaker Monitor
(59) #3 Phase Overvoltage (TC) Trip Circuit Monitor
(59D) Third Harmonic Voltage Differential
B OUTPUT 8 OUTPUT 16
C COMMAND BUTTONS
OK Exits the currently displayed dialog box.
The Profile Info command will allow the user to view or make notations for the relay setpoint data files.
4–26
Remote Operation – 4
4.5 Cautions
4–27
M-3425A Instruction Book
1
Keyboard Shortcuts
SYSTEM KEYS
These keys can be used within Microsoft Windows® and IPScom®.
Alt-Tab To switch between applications.
Ctrl-Esc To open Task List dialog box. Opens Start Menu (Win 95/98).
3 MENU KEYS
These keys enable you to select menus and choose commands.
Alt or F10 To select or cancel selection of the Setup menu on the menu bar.
A A character key To choose the menu or command. The underlined character matches
the one you type.
Esc To cancel the selected menu name, or to close the open menu.
B Alt-a character key To move to the option or group whose underlined letter or number
matches the one you type.
C Enter
Esc or Alt-F4
To carry out a command.
4–28
Remote Operation – 4
Setup
Monitor Status
RelayComm Ethernet Calibration
Comm Help
Connect About...
Exit Alt+F4
3
Clock
Security
A
Change Comm Access Code
Change Access Level Code
B
M-3890 IPSutil Installation and Setup
The M-3890 IPSutil Communication software package IPSutil runs with the Microsoft® Windows 95 operating
provides communication with the Beckwith Integrated system or above. Hardware requirements are the
Protection System® (IPS) for setting up the relays. same as those stated for IPScom®.
Its main purpose is to aid in setting up IPS relays
that are ordered without the optional front panel HMI
interface.
C
4–29
M-3425A Instruction Book
Overview
The Exit submenu allows you to quit IPSutil. If the
IPSutil helps in setting up IPS relays which were relay was connected, this submenu disconnects
ordered without the optional front panel HMI interface. the relay. When the relay was connected, if you
Units delivered without HMI’s are shipped with a set have made any changes for some parameters (for
of factory default settings for various parameters example, baud rate, phase rotation) the following
that the end user may wish to change. While the message window appears.
utility program is directed to users that do not have
HMI, users of HMI-provided relays can also use IPSUTILITY X
OK Cancel
WARNING X
IPSutility should NOT be used to set up the relay which is on-line because some
parameter’s modifications may result in unexpected operations. It is only for off-line relay
setup. Figure 4-38 IPSutility Reset Relay Message
OK
Relay Comm Command
A Figure 4-37 Warning Message When Relay Comm command is selected, the
Relay Comm Port Settings dialog box appears (See
Figure 4-42). It allows you to set the relay
After the user accepts the warning, the user can
access the IPSutil main menu. The following sections communication ports COM1 or COM2/COM3 baud
describe each IPSutil menu items. rate. For COM2/COM3, it allows you to set the
protocol and dead synch time. Additionally, for
COM2 and COM3, if you select MODBUS protocol,
Comm Menu
the dialog box allows you to enable the parity
Comm option.
B Connect
Exit Alt+F4
■ NOTE: If COM1 baud rate is changed and the
relay is reset, the new baud rate must be
used to communicate with COM1
The Comm menu allows the user to make
connections to the relay. This is the first command Ethernet Command
the user must use to access the unit. After the user
selects the Connect submenu item, the When the Ethernet command is selected, the
Communications dialog box appears (See Figure Ethernet Settings dialog box appears (see Figure
4-41). 4-43.) This command allows the user to enable or
Security Clear
1
Last Selftest-1: 28
OUT4: 0 OUT16: 0
Last Selftest-3: 0
The Security Menu allows you to set the Last Comm: 4112
OUT5: 18 OUT17:
0
Calibration
4–31
M-3425A Instruction Book
1
DHCP Protocol: Enable Disable
Save Cancel
PC Port Baud Rate Open COM
COM1
300 600
Access Code
1200 2400 Close COM
Figure 4-43 Ethernet Settings
4800 9600
Cancel
COMMAND BUTTONS
Ethernet Enable/Disable: Allows user to enable
Figure 4-41 Communication Dialog and disable the Ehternet Port.
DHCP Protocol Enable/Disable: Allows the user
COMMAND BUTTONS to enable or disable the DHCP protocol. When
Open COM Initiates communication with the DHCP protocol is enabled the the IP Address portion
3 protective system by direct serial
communication.
of the screen is grayed out. When DHCP protocol is
disabled the IP Address can be manually entered.
Close COM Discontinues communication with the
EGD Protocol Enable/Disable: Not available.
protective system.
Cancel Returns you to the IPSutil main window. Protocol Selection MODBUS/Serconv: Provides
Any changes to the displayed the user with the ability to select either MODBUS
information are lost. over TCP/IP or Serconv (BECO2200 over TCP\IP)
protocol.
Relay Comm Port Settings X
Communication Address:
9600
1
COM2 Baud Rate: 9600
Save
Cancel
Saves values to the relay.
Returns you to the IPSutil main window.
Any changes to the displayed
COM2 COM3
Beco 2200 MODBUS Beco 2200 MODBUS
information are lost.
Dead Sync Time: 50 ms Dead Sync Time: 50 ms
1 ms 3000 ms 1 ms 3000 ms
B Figure 4-42
OK Cancel
TIME SYNC
Stop Clock
COMMAND BUTTONS
Date: 12 / 15 / 98
OK Sends the currently displayed
information to the relay.
Cancel Returns you to the IPSutil main window. Time: 20 : 01 : 01
4–32
Remote Operation – 4
1
New User Access Code: xxxx xxxx xxxx
in the relay.
Save When connected to the protection Confirm New User Access Code: xxxx xxxx xxxx
system, the date and time information
on the display is sent to the relay.
Cancel Returns you to the IPSutil™ main OK Cancel
window. Any changes to the displayed
information are lost.
There is a blue Time Sync LED mimic on the Set Date/
Time dialog box (the LED is displayed as different
Figure 4-46 Change User Access Code
shading on a monochrome monitor). When this LED is Dialog Box
blue, the relay is synchronized with the IRIG-B signal
and the Time field is grayed out, indicating that this field
can’t be changed. But the Date field can be changed COMMAND BUTTONS
(by editing and pressing Save). When the LED is not
OK Sends the currently displayed
blue, the relay is not time-synchronized and therefore,
information to the relay.
both the Date and Time fields can be changed. The
time field in the dialog box is not updated continuously. Cancel Returns you to the IPSutil main window.
The time at which the dialog box was opened is the Any changes to the displayed
time that is displayed and remains as such. This is true information are lost.
whether the relay is synchronized with the IRIG-B signal
or not. Setup
User Logo
X 3
Line1: BECKWITH ELECTRIC CO.
Change Comm Access Code X
Line2: M-3425A
A
Output Test (Relay) Extended
23 22 21 20 19 18 17 16 15 14 13 12 11 10 9
OFF
ON
OK Cancel
User Control Number: 1
4–33
M-3425A Instruction Book
3
This Page Left Intentionally Blank
4–34
Legal Information
Patent Indemnification
The Seller shall not be liable for any property
The units described in this manual are covered by damages whatsoever or for any loss or damage
U.S. Patents, with other patents pending. arising out of, connected with, or resulting from
Buyer shall hold harmless and indemnify the Seller, this contract, or from the performance or breach
its directors, officers, agents, and employees from thereof, or from all services covered by or furnished
any and all costs and expense, damage or loss, under this contract.
resulting from any alleged infringementof United In no event shall the Seller be liable for special,
States Letters Patent or rights accruing thereform or incidental, exemplary, or consequential damages,
trademarks, whether federal, state, or common law, including but not limited to, loss of profits or
arising from the Seller’s compliance with Buyer’s revenue, loss of use of the equipment or any
designs, specifications, or instructions. associated equipment, cost of capital, cost of
purchased power, cost of substitute equipment,
facilities or services, downtime costs, or claims or
All rights reserved by Beckwith Electric Co., Inc. No reproduction may be made without prior written approval
of the Company.
0
2 00
1:
d
re
0
te
90
g is
Re
IS O