ENGINEERING

TOMORROW

Installation guide

Electronic superheat controller


Type EKE 1B (PV05) English
080R9321

080R9321
Introduction
Superheat controller EKE 1B is for use where superheat must be accurately controlled,
typically in commercial air conditioning, Commercial and industrial heat pumps, Commercial
refrigeration, food retailing and industrial applications.
Compatible valves: Danfoss ETS 6 / ETS 8M (Bipolar) / ETS / ETS Colibri®, / ETS L, KVS / KVS
Colibri® and CCM / CCMT / CCMT L / CTR valves.
Reference: For details please see EKE data sheet. More info

Applications
Communication
1. Superheat controller: standalone / network

Danfoss
R64-3033.10

ETS Colibri®

S2 Pe

2. Valve driver Reference signal


Reference signal

Info for UK customers only: Danfoss Ltd., 22 Wycombe End, HP9 1NB, GB
ETS Colibri®
R64-3041.10
Danfoss

S2 Pe

CAN RJ

Dimensions in mm
EKE 1B
110
130

Danfoss
Weight: 152 gram 70 60 80G8215.11

© Danfoss | Climate Solutions | 2024.03 AN232086439422en-000806 | 1


TECHNICAL SPECIFICATIONS

POWER SUPPLY
EKE has galvanic isolation by switch-mode power supply.
24 V AC ± 20 %, 50/60 Hz. Maximum power consumption: 18 VA.
Input voltage rating (DC): 24 V DC ± 20%, 15 W.

I/O TYPE NUMBER SPECIFICATION


Max. 15 V input voltage
Do not connect voltage sources to unpowered units without limiting the current
to analog inputs (overall 80 mA).
Open circuit HW diagnostics available for voltage input on : AI4
AI3 (Pe)
Analog 0 – 5 V ratiometric,
Voltage 2
inputs AI4
0 – 5 V , 0 – 10 V
AI1 (S3, S4), AI2 (S2)
NTC 2
NTC temperature probes, 10 kΩ at 25 °C
Auxiliary 5V+
1
Supplies Sensor supply: 5 V DC / 15 mA, overload protection approximately 150 mA
DI1, DI2
Steady current minimum 1mA
Digital Voltage free
2 Cleaning current 100 mA at 15 V DC
inputs contacts
On: RIL < = 300 Ω
Off: RIH > = 3.5 k Ω

C1-NO1
Digital Normally Open: 3 A General purpose, 250 V AC, 100 k cycle
Relay 1
output Normally Open: 3 A Inductive (AC-15), 250 V AC, 100 k cycle
Normally Closed: 2 A General purpose, 250 V AC, 100 k cycle
Stepper valves: A1, A2, A3, A4
Bipolar stepper motor output:
- Danfoss ETS 8M (Bipolar) / ETS C / ETS L / KVS / KVS C / CCMT 2 – CCMT 42,
CCMT L / CTR Valves
Stepper Other Valves:
Bipolar 1
motor - speed 10 – 400 pps
- drive mode 1/8 microstep
- max. peak phase current: 1.2 A (848 mA RMS)
- max. drive voltage 40 V
- max. output power 12 W
VBATT: 18 – 24 V DC (24 V DC recommended):
Battery
1 – max. battery current: 850 mA at 18 V
backup
– battery alarm will be activated below 16 V DC and above 27 V DC
RS485
RS-485 RTU 1 Galvanic isolation
Communi- No Built-in termination
cation
CAN - RJ
CAN 1
RJ connector to directly connect and supply a MMI

© Danfoss | Climate Solutions | 2024.03 AN232086439422en-000806 | 2


GENERAL FEATURES AND WARNINGS

PLASTIC HOUSING FEATURES


- DIN rail mounting complying with EN 50022
- Self-extinguishing V0 according to IEC 60695-11-10 and glowing/hot wire test at 960 °C according to IEC 60695-2-12
- Ball test: 125 °C according to IEC 60730-1. Leakage current: ≥ 250 V according to IEC 60112
OTHER FEATURES
- Operating conditions CE: -20T60, 90% RH non-condensing
- Storage conditions: -30T80, 90% RH non-condensing
- To be integrated in Class I and/or II appliances
- Index of protection: IP 20 on product and IP40 only on the front cover
- Period of electric stress across insulating parts: long
- Suitable for using in a normal pollution environment
- Category of resistance to heat and fire: D
- Immunity against voltage surges: category II
- Software class and structure: class A
CE COMPLIANCE
This product is designed to comply with the following EU standards:
- Low voltage guideline: 2014/35/EU
- Electromagnetic compatibility EMC: 2014/30/EU and with the following norms:
- EN61000-6-1, EN61000-6-3 (immunity for residential, commercial and light-industrial environments)
- EN61000-6-2, EN61000-6-4 (immunity and emission standard for industrial environments)
- EN60730 (Automatic electrical controls for household and similar use)

GENERAL WARNINGS
- Every use that is not described in this manual is considered incorrect and is not authorized by the manufacturer
- Verify that the installation and operating conditions of the device respect those specified in the
manual, especially concerning the supply voltage and environmental conditions
- This device contains live electrical components. All service and maintenance operations must therefore be
performed by qualified personnel
- The device must not be used as a safety device
- Liability for injury or damage caused by the incorrect use of the device lies solely with the user
INSTALLATION WARNINGS
- Recommended mounting position: vertical
- Installation must comply with local standards and legislation
- This product is not subject to the UK PSTI regulation, as it is for supply to and use only by professionals with the necessary expertise and qualifications.
Any misuse or improper handling may result in unintended consequences. By purchasing or using this product, you acknowledge and accept the
professional-use-only nature of its application. Danfoss does not assume any liability for damages, injuries, or adverse consequences (“damage”) resulting
from the incorrect or improper use of the product and you agree to indemnify Danfoss for any such damage resulting from your incorrect or improper
use of the product.
- Before working on the electrical connections, disconnect the device from the main power supply
- Before carrying out any maintenance operations on the device, disconnect all electrical connections
- For safety reasons the appliance must be fitted inside an electrical panel with no live parts accessible
- Do not expose the device to continuous water sprays or to a relative humidity greater than 90%.
- Avoid exposure to corrosive or pollutant gases, natural elements, environments where explosives or mixes of
flammable gases are present, dust, strong vibrations or shock, large and rapid fluctuations in ambient temperature
that might cause condensation in combination with high humidity, strong magnetic and/or radio interference
(e.g. transmitting antennae)
- When connecting loads be aware of the maximum current for each relay and connector
- Use cable ends suitable for the corresponding connectors. After tightening connector screws, tug the cables gently
to check their tightness
- Use appropriate data communication cables. Refer to the EKE data sheet for the kind of cable to be used and setup
recommendations
- Minimize the length of probe and digital input cables as much as possible, and avoid spiral routes around power
devices. Separate from inductive loads and power cables to avoid possible electromagnetic noises
- Avoid touching or nearly touching the electronic components fitted on the board to avoid electrostatic discharges

PRODUCT WARNINGS
• Use a class II category transformer for 24 V AC power supply.
• Connecting any EKE inputs to mains voltage will permanently damage the controller.
• Battery Backup terminals does not generate power to recharge a device connected.
• Battery backup - the voltage will close the stepper motor valves if the controller loses its supply voltage.
• Do not connect an external power supply to the digital input DI terminals to avoid damaging the controller.
80G320.10
Danfoss

© Danfoss | Climate Solutions | 2024.03 AN232086439422en-000806 | 3


DIN rail mounting / demounting
The unit can be mounted onto a 35 mm DIN rail simply by snapping it into place and securing it with a stopper to prevent sliding.
It is demounted by gently pulling the stirrup located in the base of the housing.

“Click” 3

Connection overview: EKE 1B

Modbus ANALOG
ANALOG/ DIGITAL
/ DIGITALINPUT
INPUT CAN - RJ
COM

COM

COM

CAN RJ
5V+
GND

DI2
DI1

AI4
AI3
AI2
AI1
H
L

COM

COM

COM

CAN RJ
5V+
GND

DI2
DI1

AI4
AI3
AI2
AI1
H
L

Superheat controller
EKE 1B - 080G5350
80G8287A.01
Danfoss

GND

Bat+

NO1

NC1
+/~
–/~

A1
A2

C1
B1
B2
GND

Bat+

NO1

NC1
+/~
–/~

A1
A2

C1
B1
B2

PWR 24V Vbat STEPPER VALVE


STEPPER DIGITAL OUTPUT
OUTPUT

© Danfoss | Climate Solutions | 2024.03 AN232086439422en-000806 | 4


Connection overview, EKE 1B Master controller

MMIGRS2 Display
RS485 MODBus
CAN RJ

RS485 RTU MODBus


080G0294 (optional)

NTC (S3/S4)
DI1 (ON/OFF)*

Optional
NTC (S2)

080G0075 (opt.)
AI4 (0 / 10 V)
Supervisor EKE
MMIMYK

CANBus
COM
network

DI2
Gateway
AKS Cable
1 connection
060G1034
3

Pressure transmitter
COM

COM

COM
CAN RJ
GND

5V+
DI2
DI1

DI3
AI4
AI3
AI2
AI1
e.g. AKS 32R
H
L

KoolProg
PC tool
COM

COM

COM CAN RJ
GND

5V+
DI2
DI1

DI3
AI4
AI3
AI2
AI1
H
L

* Note: If Dl1(On/Off ) switch is not


used it must be short circuited

Superheat
Superheat controller
controller
EKE 1B - 080G5350
80G318.10
Danfoss

GND

Bat+

NO1

NC1
+/~
–/~

A1
A2

C1
B1
B2

C1 NC1

Power
+/~

NO1
GND
–/~

Bat+

NC1
NO1

NC1
+/~
–/~

Power supply
C1
A1
A2

C1
B1
B2

24 V AC 24 V DC
C1 NO1
± 20% ± 20% +
– 18 V
+ Relay
Normally open or
Power
2.5 A Batt
T fuse backup normally closed
(optional) (optional)
orange

(optional)
yellow

black
red

ETS6 valve
green
white
black

Alarm
red

ON/OFF
ETS / KVS solenoid
Colibri® valve
CCMT/CTR valves

© Danfoss | Climate Solutions | 2024.03 AN232086439422en-000806 | 5


Sensor mounting: Temperature sensor
1
3 / - 5/ in.
1 2 OD 122 - 168 mm

60G496.11
3
/4 - 7/8 in.
Danfoss

OD 18 - 22 mm

84N365.11
Danfoss
Conductive 1 - 13/8 in.
paste Evaporator outlet OD
25 - 35 mm

13/8 in. and higher

84N366.12
OD 35 mm and higher

Danfoss
Important Note
• Mount the sensor on a clean
paint-free surface.
• Remember to use heat
conducting paste and insulate D f
Danfoss
84N403.10
the sensor.
• For precise measurements,
mount the sensor max. 5 cm
from the outlet of the evaporator.

Close to
Close tothe
the
Evaporator evaporator
evaporator
Pressure transmitter
• Installation of the pressure transmitter is less critical. However, the pressure transmitter should be closer to
the temperature sensor, right after the evaporator and with its head upright. It is a good practice to select
a pressure transmitter with an average load of 40 - 60% of full scale.
• 5 EKEs at maximum are allowed to share the output signal of a ratiometric pressure transmitter.
In order to get a correct acquisition on all the units all the three wires (GND, 5 V and transmitter signal
output) must be routed to every unit.

Power supply
• Power sharing is allowed in EKE controller.
• It is a good practice not to reverse the polarity of the power connection cables.
Selection of the common power supply depends on the total number of sharings and the valve in use.
EKE EKE EKE
RGND

RGND
COM

COM

COM

COM

COM

COM

CAN RJ CAN RJ
RGND

COM

COM

COM

CAN RJ
5V+

5V+
DI2
DI1

DI3

5V+

DI2
DI1

DI3
AI4
AI3
AI2

AI4
AI3
AI2
D+

D+
D–

DI2
DI1

DI3

D–
AI4
AI3
AI2
D+
D–
80G295.10
Danfoss
+/~
–/~

+/~
–/~

Superheat controller
Superheat controller Superheat
Superheatcontroller
controller Superheat controller
Superheat controller
EKE 1x - 080G5xxx EKE 1x - 080G5xxx EKE 1x - 080G5xxx
GND

Bat+

GND

Bat+
NO1

NO1
NC1

NC1
GND

Bat+

NO1
+/~

+/~
NC1
–/~

–/~
+/~
–/~
A1
A2

C1

A1
A2
B1
B2

C1
B1
B2
A1
A2

C1
B1
B2

Power supply

© Danfoss | Climate Solutions | 2024.03 AN232086439422en-000806 | 6


Relay Outputs
EKE 1B has 1 relay output:
• Type SPDT relay. Digital Output can be used to connect either a solenoid valve or an alarm.
• The relays cannot be used for the direct connection of capacitive loads such as LEDs and ON/OFF control of
EC motors. All loads with a switch-mode power supply must be connected with a suitable contactor or similar.
Cable length
EKE controller supports the following max. cable length.

Cable length Wire size min. / max.


[m] [m2]
Analog inputs (Current/Voltage) max. 10 0.14 / 1.5
Temperature sensor max. 10 *) –
Stepper valve connection max. 30 0.14 / 1.5
Power supply max. 5 0.2 / 2.5
Digital input max. 10 0.14 / 1.5
Digital output – 0.2 / 2.5
Digital MMI max. 3 over CAN RJ –
Communication bus max. 1000 0.14 / 1.5

Cable and wiring *)


• The max. cable distance between the controller and the valve depends on many factors like shielded/
unshielded cable, the wire size used in the cable, the output power for the controller and EMC.
• Keep controller and sensor wiring well separated from mains wiring.
• Connecting sensors by wires more than the specified length may decrease the accuracy of measured values.

Warning
Separate the sensor and digital input cables as much as possible (at least 10 cm) from the power cables to the
loads to avoid possible electromagnetic disturbance. Never lay power cables and probe cables in the same
conduits (including those in the electrical panels).

Connecting Modbus
• For the MODbus cable, it is best to use 24 AWG shielded twisted-pair cable with a shunt capacitance
of 16 pF/ft and 100Ω impedance.
• The controller provides an insulated RS485 communication interface which is connected to the
RS485 terminals (see connection overview).
• The max. permissible number of devices simultaneously connected to RS485 cable output is 32.
The RS485 cable is of impedance 120 Ω with maximum length of 1000 m.
• Terminal resistors 120 Ω for terminal devices are recommended at both ends.
• The EKE communication frequency (baud rate) can be one of the following: 9600, 19200 or
38400 baud, default 19200 8 E 1.
• The default unit address is 1, which can be changed using parameter “G001 Controller adr.”.
Modbus
D+
D-
Not in use
Danfoss Gnd
84N404.10

For a detailed explanation of Modbus installation and setting software parameters, see:
Data sheet for “EKE Superheat controller” and “EKD EIM Data Communication Modbus RS485 RTU”.

© Danfoss | Climate Solutions | 2024.03 AN232086439422en-000806 | 7


Stepper Motor Output
• All valves are driven in a bipolar mode with a 24 V supply chopped to control the current (Current driver).
• The stepper motor is connected to the “Stepper Valve” terminals (see terminal assignment) with a standard M12
connection cable.
• To configure stepper motor valves other than Danfoss stepper motor valves, the correct valve parameters must
be set as described in the Valve configuration section (see manual for details).
• The default valve setting in EKE 1B is: none.
• The correct valve must be defined in “Valve configuration”, i.e. parameter I067. An overview of valve types is
given in the “Parameter identification” section.

Valve Cable Connection

ETS/KVS/CCM/ CCMT/CTR/ CCMT L


Stepper valve connector ETS 8M Bipolar ETS 6
(Using Danfoss M12 Cable)

A1 White Orange Orange


A2 Black Yellow Yellow

B1 Red Red Red

B2 Green Black Black


Not connected - - Grey

• All valves are driven in a bipolar mode with a 24 V supply chopped to control the current (Current driver).
• The stepper motor is connected to the “Stepper Valve” terminals (see terminal assignment) with a
standard M12 connection cable.
• To configure stepper motor valves other than Danfoss stepper motor valves, the correct valve parameters
must be set as described in the Valve configuration section by selecting user defined valve.

Guideline for long M12 cables on Danfoss stepper motor valves


• Long cables will lead to degradation of performance.
• You can overcome this degradation by changing the settings for the valve driver. This guideline is based on
the cable type being the same type as the standard Danfoss stepper motor cable.

Recommended wire size and cable distance between EKE controller and stepper motor valve
Cable length 1 m – 15 m 15 m – 30 m
0.52 / 0.33 mm2 0.33 mm2
Wire diameter
(20 / 22 AWG) (20 AWG)

© Danfoss | Climate Solutions | 2024.03 AN232086439422en-000806 | 8


LED indication

(A) Two status LEDs to indicate operational status


• Steady green = power ON
• Flashing green = data transmission / initialization
• Flashing red = alarm / error condition

(B) Two status LEDs to indicate valve operation


• Flashing red = valve closing
• Steady red = valve fully closed
(A) (B) • Flashing green = valve opening
• Steady green = valve fully open
• Both green and red flashing = valve-related alarm

USER INTERFACE
EKE 1B can be setup using one of the following user interfaces:
1. Danfoss KoolProg software
2. Danfoss MMIGRS2 external display
3. Communication bus: Modbus RS485 RTU

KoolProg
KoolProg is a software tool for quickly and easily configuring EKE controllers. It enables you
to make online changes to parameter configuration, copy settings to multiple controllers,
monitor the live status of input/outputs, and quickly analyze controller behavior and
program patterns with a graphical trending tool.
KoolProg Software is available for download free of charge at http://koolprog.danfoss.com.
KoolProg requires a Gateway (code 080G9711) to connect to the PC.
Always use latest KoolProg version and User must check the software version of EKE and
create configuration file in KoolProg for that version. Configuration made with the different
software version should not be copied to controller.

CANRJ

EKE

Power supply Cable holder


80G296B.10

USB
Danfoss

Gateway
Important note!
To guarantee a reliable USB connection to a host device (e.g. industrial PC), you must:
• Connect terminals R and H on MMIMYK CAN port using a termination wire.
• Place cable holder close to MMIMYK to keep USB connector firmly in place.
• Keep USB cable length < 1 m.
• Place MMIMYK and route USB cable far from noise sources (inverter, motors, contactors etc.)
© Danfoss | Climate Solutions | 2023.10 AN232086439422en-000806 | 9
Danfoss MMIGRS2 display ACCCBI080G0075

CAN RJ

Connecting external MMIGRS2 display

COM

COM

COM
CAN RJ

5V+
DI2
DI1

DI3
AI4
AI3
AI2
MMIGRS2 display can be used to set up EKE 1B. The display
can be used not only for setting up the necessary param-
eters, but also as an external display during operation to MMIGRS2
show important parameters, e.g. degree of opening of
valve, superheat, etc.
Superheat
Superheat controller
controller
EKE 1B - 080G5350
Important note:
• Max. distance between controller and display is
3 m over CAN RJ.

80G319.10
• CANbus requires termination in both ends of the cable

Danfoss
by a 120 Ohm resistor to ensure reliable communication.

GND

Bat+

NO1

NC1
+/~
• External power for MMIGRS2 is not needed while using

–/~

A1
A2

C1
B1
B2
CAN RJ connector

MMIGRS2 (Back view)

For cable <3 metre


RJ CAN connector
Termination Jumper
between R and H

For cable >3 metre (only EKE 1C)


34G306.11
Danfoss

2-way screen connector for power supply


4-way screen connector for CANbus network

MMIGRS2 (Front view) Up

Escape / cancel

Right
Left
Enter
Down

Navigation help
Homescreen
Controller name Alarm indicator

Primary readout Reference


point
Operating status
Evap. temperature S2 – S4
Evap. pressure Media
Valve OD temperature

Note: Setup and service menu requires login with the default password 100 ( daily use),
200 (service use) or 300 (commissioning use). Long press Enter key to access login menu.
© Danfoss | Climate Solutions | 2024.03 AN232086439422en-000806 | 10
Setup wizard via MMIGRS2 display
When all connections to the controller have been made, after the power is switched on, the Danfoss logo will appear
for 5 seconds, then the Home screen will be displayed.
To access the Wizard: press and hold enter to access the Login screen, the commissioning password is 300, scroll down
the Setup and service menu and select “Setup wizard”.

The Wizard workflow is: a. Language selection; b. Application selection; c. Input configuration; and d.
Output configuration.
When using the Setup Wizard, repeat the following sequence for all parameter settings:
a. From Setup wizard, select relevant parameters.
b. Press ENTER to highlight 1st option
c. Scroll with UP / DOWN to your desired option
d. If the selected default value is acceptable, press DOWN to get to the next settings. Otherwise,
press ENTER to set your choice
e. Scroll with DOWN to the next parameter (repeat sequence a. to e.)
Note:
• If you do not have sufficient information to complete the Wizard, leave settings on their default values. To generate
the requested info, you can use Danfoss Coolselector2 software to calculate operating conditions and valve OD for the
same operating point.
• Setup Wizard only covers the most important parameters. If other features are to be enabled
(e.g. Alarm settings, MOP/LOP, etc.), they must be configured separately once the Setup Wizard is done.
Setup Wizard is also available in KoolProg PC tool.
The workflow process is the same as that described above for MMIGRS2 display.
For details, please refer to EKE data sheet.

1
Power on

3 Login
PW:
2 Commissioning 300
Service 200
Press and Daily 100
hold enter

5
Esc

Status menu Setup and service


Reference
QR code Control
Controller info Defrost
Detailed status
Alarm configuration
SH trend 25 min IO config
Display Display
Communication
Service
4
Home menu Setup wizard
Controller name

Danfoss
80G294.20

© Danfoss | Climate Solutions | 2024.03 AN232086439422en-000806 | 11


Quick guide for parameter selection

Apart from wizard setup, users can also use the following section which describes quick parameter
settings for general applications.

Driver Controller

Start : Main switch= Off Make sure that main switch is OFF before changing
the settings. The setting will depend on the system
requirement.
Parameter: R012 Main Switch

Select valve type Select predefined Danfoss valve type ETS, ETS C, KVS,
KVS C, CCM, CCMT, CTR, or user defined.
Parameter: I067 Valve configuration

Application mode Select how you want to use EKE: driver or superheat
Driver- Controller controller.
Parameter: R102 Operation mode

Analog signal type e.g Select the predefined refrigerant .


Select Refrigerant
1-5V / 0-20 mA Parameter: O030 Refrigerant
EKE 1B Parameters
Driver reference Select Temperature sensor type: EKS, ACCPBT, MBT,
I091
configuration
Ext.ref. Select Temperature sensor Sensata 112CP, Bus shared
I034 Parameter: I081 - S2 sensor configuration.
voltage,low
Ext.ref. Check parameter list for other sensors.
I035
voltage,high
Ext.ref. –
current,low
Ext.ref. – Select Pressure transmitter type –AKS 32R, Sensata
current,high
Select Pressure transmitter 112CP, OEM Ratio, NSK, AKS 32 1 - 5 V, DST P110
OEM Voltage, Bus shared
Parameter: I085 - Pe transmitter configuration.
Check parameter list for other sensors.

Define min and max Pressure transmitter in barg.


Define Min/Max Pressure Parameter: O020 - Pe min., O021 Pe max., Check
parameter list for other sensors.

Select Superheat Control Select application control type SH control. 1: MSS,


2: LoadAp, 3: Fixed, 4: Delta SH.
Parameter: N021 SH reference mode.

Set the value for the selected control min./max.


Set Min/Max Ref value superheat reference.
Parameter N009 SH max., N010 - SH min.

Select Other features Optional – Force start up, MOP, LOP, Alarm,
Thermostat function.
Check parameter list for details.

Finish: main switch = ON Remember to turn on main switch to start ‘ON’ .


Parameter R012 Main switch.

Dl1=ON ON=Regulation start


Parameter O002: 0 = Bus->Start/Stop | 1 = Main Switch
IF Dl1 is not used make a short circuit with a wire
between Dl1 and COM.

© Danfoss | Climate Solutions | 2024.03 AN232086439422en-000806 | 12


EKE 1B – Commonly used parameter identification
PNU - equivalent to the Modbus register no. (Modbus address +1).
Actual value are read/written as 16-bit integer values without decimals. This is the default value as read via Modbus.

Parameter PNU Default Description


R012 Main switch 3001 0 0 = regulation Off | 1 = regulation On
R102 Operation mode 3002 0 0 = Superheat control | 1 = Valve driver
O002 Dl1 configuration 3101 1 0 = Bus->Start/Stop | 1 = Main Switch
I091 Driver reference 3282 0 0 = Voltage to OD | 1 = Modbus to OD | 2 = Modbus to steps
configuration
I034 Ext ref. voltage low 3130 0 Range 0 – 10 V. To be used with l091
I035 Ext ref. voltage high 3129 10 Range 0 – 10 V. To be used with l091
0 = no valve, 1 = UserDef
2 = ETS 12C, 3 = ETS 24C, 4 = ETS 25C, 5 = ETS 50C, 6 = ETC 100C
7 = ETS 6, 8 = ETS 12.5, 9 = ETS 25, 10 = ETS 50, 11 = ETS 100,
12 = ETS 250, 13 = ETS 400
14 = KVS 2C, 15 = KVS 3C, 16 = KVS 5C
17 = KVS 15, 18 = KVS 42
19 = CCMT 0, 20 = CCMT 1
I067 Valve configuration 3132 0 21 = CCMT 2, 22 = CCMT 4, 23 = CCMT 8, 24 = CCMT 16, 25 = CCMT 24,
26 = CCMT 30, 27 = CCMT 42
28 = CCM 10, 29 = CCM 20, 30 = CCM 30, 31 = CCM 40
32 = CTR 20 ,
33 = CCMT 3L, 34 = CCMT 5L, 35 = CCMT 8L, 36 = CCMT 10L,
37 = ETS 175L, 38 = ETS 175L OFHT, 39 = ETS 250L,
40 = ETS 250L OFHT, 41 = ETS 400L, 42 = ETS 400L OFHT,
43 = ETS 500L, 44 = ETS 500L OFHT, 45 = ETS 8M Bipolar
0 = Undef 10 = R503 20 = R407C 30 = R417A 40 = 448A
1 = R12 11 = R114 21 = R407A 31 = R422A 41 = 449A
2 = R22 12 = R142b 22 = R407B 32 = R413A 42 = 452A
3 = R134A 13 = R User 23 = R410A 33 = R422D 43 = R450A
4 = R502 14 = R32 24 = R170 34 = 427A 44 = R452B
5 = R717 15 = R227 25 = R290 35 = R438A 45 = R454B
O030 Refrigerant 3017 0
6 = R13 16 = R401A 26 = R600 36 = R513A 46 = R1233zdE
7 = R13b1 17 = R507 27 = R600a 37 = R407F 47 = R1234zeZ
8 = R23 18 = R402A 28 = R744 38 = R1234ze 48 = R449B
9 = R500 19 = R404A 29 = R1270 39 = R1234yf 49 = R407H
50 = R469A

0 = Not defined | 1 = EKS 221 | 2 = ACCPBT NTC10K | 3 = MBT 153 10K |


I081 S2 sensor configuration 3266 0
4 = 112CP | 5 = Bus Shared
0 = Not defined | 1 = EKS 221 | 2 = ACCPBT NTC10K | 3 = MBT 153 10K |
I083 S3 sensor configuration 3264 0
4 = 112CP | 5 = Bus Shared
0 = Not defined | 1 = EKS 221 | 2 = ACCPBT NTC10K | 3 = MBT 153 10K |
I084 S4 sensor configuration 3262 0
4 = 112CP | 5 = Bus Shared
0 = Not defined | 1 = AKS 32R | 2 = ACCPBP Ratio | 3 = 112CP | 4 = OEM Ratio|
I085 Pe transmitter configuration 3270 0
5 = NSK | 6 = AKS 32 1-5V | 7 = OEM Voltage | 8 = Bus shared | 9 =DST P110
O020 Pe transmitter min. (in bar g) 3115 -1 Define pressure range in bar gauge
O021 Pe transmitter max. (in bar g) 3116 12 Define pressure range in bar gauge

© Danfoss | Climate Solutions | 2024.03 AN232086439422en-000806 | 13


N021 SH reference mode 3027 2 0 = Fixed SH | 1 = Loadap | 2 = MSS | 3 = Delta temp
N107 SH fixed setpoint ( K) 3028 7 Range 2 – 40 K
N009 SH max. ( K) 3029 9 Range 4 – 40 K
N010 SH min. ( K) 3030 4 Range 2 – 9 K
N116 SH ref. delta temp. factor ( %) 3035 65 Range 20 – 100

For a detailed parameter list and explanation, please check the EKE data sheet.

© Danfoss | Climate Solutions | 2024.03 AN232086439422en-000806 | 14


Related products
MMIGRS2 Display Power Supply MMIMYK Gateway

User interface module MMIGRS2 Display AK-PS MMIMYK device is used as a gateway
Input: 100 – 240 V AC, 45 – 65 Hz to connect EKEs and the PC tool i.e
Output: 24 V DC: available with 18 VA, 36 KoolProg software for parameter
VA and 60 VA setting or data logging.
ACCTRD
Input: 230 V AC, 50 – 60 Hz
Output: 24 V AC, available with 12 VA,
22 VA and 35 VA

Pressure Transducer Temperature Sensor

AKS Pressure Tranducer PT 1000


Available with ratiometric and 4 – 20 mA. AKS is a High precision temp. sensor
AKS 11 (preferred), AKS 12, AKS 21
NSK ACCPBT PT1000
Ratiometric pressure probe
NTC sensors
XSK EKS 221 ( NTC-10 Kohm) MBT 153
Pressure probe 4 – 20 mA ACCPBT
NTC Temp probe (IP 67 /68)

ACCCBI Cable Stepper motor valves M12 cable

ACCCBI cables for MMI display and gateway. EKE is compatible with Danfoss stepper M12 Angle cable to connect
motor valves i.e Danfoss ETS 6, ETS, KVS, Danfoss stepper motor valve and
ETS Colibri®, KVS colibri®, CTR, CCMT EKE controller

© Danfoss | Climate Solutions | 2024.03 AN232086439422en-000806 | 15

You might also like