Although the IEEE standard recommends limits for         measured at part load values will also be acceptable.
both voltage distortion and current distortion,          To use our rock analogy, the full load fundamental
specifications that reference a 5% harmonic              current is the size of our pond and the harmonic
limitation are generally referring to current            current is the size of our rock. (See Table D.)
distortion. In most cases, if the current distortion
                                                         Table D
falls within IEEE-519 requirements, the voltage          Comparison of TDD and THD(I)
distortion will also be acceptable.
                                                          Fundamental          Harmonic         THD(I)   TDD
Determining compliance with IEEE-519 requires an          Current (rms)      Current (rms )
actual measurement of the system during operation.             1000                50             5%      5%
Predicting compliance in advance often requires a              800                43.8           5.4%    4.4%
system study that accounts for all electrical                  600                36.3           6.1%    3.6%
equipment (transformers, wires, motors, VFDs,                  400                29.7           7.4%    3.0%
etc.) in the system.
                                                               200                20.0           10%      2%
Introduction To Harmonic Terms                                 100                13.4          13.4%    1.3%
                                                         TDD - Total Demand Distortion
Total Harmonic Voltage Distortion - THD (V)              THD(I) - Total Harmonic Current Distortion
As harmonic currents flow through devices with           Short Circuit Ratio
reactance or resistance, a voltage drop is developed.
                                                         Short circuit ratio is the short circuit current value of
These harmonic voltages cause voltage distortion of
                                                         the electrical system divided by its maximum load
the fundamental voltage wave form. The total
                                                         current. Standard IEEE-519 Table 2 defines
magnitude of the voltage distortion is the THD (V).
                                                         different acceptance levels of TDD depending on
The IEEE-519 standard recommends less than 5%
                                                         the short circuit ratio in the system. Systems with
THD (V) at the point of common coupling for
                                                         small short circuit ratios have lower TDD
general systems 69 kV and under.
                                                         requirements than systems with larger short circuit
Total Harmonic Current Distortion - THD (I)              ratios. This difference accounts for the fact that
                                                         electrical systems with low short circuit ratios tend
This value (sometimes written as THID) represents        to have high impedances, creating larger voltage
the total harmonic current distortion of the wave        distortion for equivalent harmonic current levels.
form at the particular moment when the                   (See Table E.)
measurement is taken. It is the ratio of the harmonic
current to the fundamental (non-harmonic) current        Mitigating Harmonics
measured for that load point. Note that the
                                                         Some utilities now impose penalties for introducing
denominator used in this ratio changes with load.
                                                         harmonics onto their grid, providing incentives for
Total Demand Distortion - TDD                            owners to reduce harmonics. In addition, reducing
                                                         harmonic levels can prevent potential damage to
Total Demand Distortion (TDD) is the ratio of the        sensitive equipment residing on the same system.
measured harmonic current to the full load               There are many approaches to mitigating harmonics.
fundamental current. The full load fundamental           Several commonly used methods are discussed here.
current is the total amount of non-harmonic current
consumed by all of the loads on the system when the      Line Reactors
system is at peak demand. The denominator used in        Line reactors add reactance and impedance to the
this ratio does not change with load. Although TDD       circuit. Reactance and impedance act to lower the
can be measured at any operating point (full or part     current magnitude of harmonics in the system and
load), the worst case TDD will occur at full load. If    thereby lower the TDD. Line reactors also protect
the full load TDD is acceptable, then the TDD            devices from large current spikes with short rise
                                                        8
 Table E
 Table 2 - Current distortion limits for systems rated 120 V through 69 kV
                                     Maximum harmonic current distortion in percent of IL
                                         Individual harmonic order (odd harmonics)a,b
         Isc/IL          3≤h<11         11≤h<17          17≤h<23           23≤h<35          35≤h<50             TDD
         <20c               4.0            2.0              1.5               0.6              0.3              5.0
         20<50              7.0            3.5              2.5               1.0              0.5               8.0
         50<100            10.0            4.5              4.0               1.5              0.7              12.0
         100<1000          12.0            5.5              5.0               2.0              1.0              15.0
         >1000             15.0            7.0              6.0               2.5              1.4              20.0
a Even  harmonics are limited to 25% of the odd harmonic limits above.
b Current  distortions that result in a dc offset, e.g., half-wave converters, are not allowed.
c All power generation equipment is limited to these values of current distortion, regardless of actual I /I where
                                                                                                         sc L
          Isc = maximum short-circuit current at PCC
          IL = maximum demand load current (fundamental frequency component) at the PCC under normal load operating conditions.
 times. A line reactor placed between the VFD and                 upstream of the filter. These types of filters generally
 the motor would help protect the motor from current              have excellent harmonic mitigation characteristics.
 spikes. A line reactor placed between the supply and             Active filters may reduce generator size
 VFD would help protect the supply from current                   requirements.
 spikes. Line reactors are typically only used                    VFDs Using Active Front End Technology (AFE)
 between the VFD and the motor when a
 freestanding VFD is mounted more than fifty feet                 Some VFDs are manufactured with IGBT rectifiers.
 from the motor. This is done to protect the motor                The unique attributes of IGBTs allow the VFD to
 windings from voltage peaks with extremely quick                 actively control the power input, thereby lowering
 rise times.                                                      harmonics, increasing power factor and making the
                                                                  VFD far more tolerant of supply side disturbances.
 Passive Filters                                                  The AFE VFDs have ultra low harmonics capable of
                                                                  meeting IEEE-519 standards without any external
 Trap Filters are devices that include an electrical              filters or line reactors. This significantly reduces
 circuit consisting of inductors, reactors, and                   installation cost and generator size requirements.
 capacitors designed to provide a low impedance path              An AFE drive provides the best way to take
 to ground at the targeted frequency. Since current               advantage of VFD benefits and minimize harmonics.
 will travel through the lowest impedance path, this
 prevents the harmonic current at the targeted                    Multi-Pulse VFDs (Cancellation)
 frequency from propagating through the system.
 Filters can be mounted inside the drive cabinet or as            There are a minimum of six rectifiers for a three-
 free standing devices. Trap filters are typically                phase AC VFD. There can be more, however.
 quoted to meet a THD(I) value that would result in               Manufacturers offer 12, 18, 24, and 30 pulse drives.
 compliance with IEEE-519 requirements if the                     A standard six-pulse drive has six rectifiers, a 12-
 system were otherwise already in compliance.                     pulse drive has two sets of six rectifiers, an 18-pulse
                                                                  drive has three sets of six rectifiers and so on. If the
 Active Filters                                                   power connected to each set of rectifiers is phase
                                                                  shifted, then some of the harmonics produced by one
 Some devices measure harmonic currents and                       set of rectifiers will be opposite in polarity from the
 quickly create opposite current harmonic wave                    harmonics produced by the other set of rectifiers.
 forms. The two wave forms then cancel out,
 preventing harmonic currents from being observed
                                                            9
The two wave forms effectively cancel each             REFERENCES
other out. In order to use phase shifting, a           IEEE Standard 519-2014. “IEEE Recommended
special transformer with multiple secondary                 Practices and Requirements of Harmonic
windings must be used. For example, with a                  Control in Electrical Power Systems.”
12-pulse VFD, a Delta/Delta-Wye transformer
with each of the secondary phases shifted by           Rockwell Automation. “Dealing with line
30 degrees would be used.                                  harmonics from PWM variable frequency
                                                           drives.”
CONCLUSION                                             John F. Hibbard, Michael Z. Lowenstein.
                                                             “Meeting IEEE 519-1992 Harmonic
• VFDs provide the most energy efficient
                                                             Limits Using Harmonic Guard Passive
  means of capacity control.
                                                             Filters”
• VFDs have the lowest starting current of                   (TRANS-COIL, INC)
  any starter type.
                                                       Tony Hoevenaars, P. Eng, Kurt LeDoux, P.E.,
• VFDs reduce thermal and mechanical                        Matt Colosina. 2003. “Interpreting
  stresses on motors and belts.                             IEEE Std 519 and Meeting its
• VFD installation is as simple as connecting               Harmonic Limits in VFD
  the power supply to the VFD.                              Applications.”
                                                            (IEEE paper No. PCIC-2003-XX).
• VFDs with AFE technology can meet even
  the most stringent harmonic standards and            Gary Rockis, Glen Mazur, American Technical
  reduce backup generator sizing.                           Publishers, Inc. 1997. “Electrical Motor
                                                            Controls.”
• VFDs provide high power factor,
  eliminating the need for external power              Richard H. Smith, P.E., Pure Power. 1999.
  factor correction capacitors.                             “Power Quality Vista Looks Good
                                                            Thanks to IGBTs.”
• VFDs provide lower KVA, helping
  alleviate voltage sags and power
  outages.                                             FURTHER READING FROM CARRIER
NOTE: It is the responsibility of the user to          Carrier. 1993. Harmonics: A Brief Introduction.
evaluate the accuracy, completeness or                 Carrier. 1999. 19XRV Marketing Guide.
usefulness of any content in this paper. Neither
Carrier nor its affiliates          make      any      Carrier. 2005. Carrier Introduces Rotary
representations or warranties regarding the            Chillers with Liquiflo2 Variable Speed Drive.
content contained in this paper. Neither Carrier       Carrier. 2005. Carrier Variable Speed Screw
nor its affiliates will be liable to any user or       White Paper
anyone else for any inaccuracy, error or omission,
regardless of cause, or for any damages resulting
from any use, reliance or reference to the content
in this paper.
Copyright 2005 Carrier Corporation   www.carrier.com   Printed in U.S.A.      Rev 7-18     Replaces: New