Is Operator Guide
Is Operator Guide
InteliSys®
Modular Gen-set Controller
Operator guide for SPM, SSB, SPtM, SPI, MINT
IS-CU
June 2005
Operator guide
Default applications
There are five default applications: SPM, SSB, SPtM, MINT, MEXT.
SPM Single prime mover, no mains.
SSB Single stand-by, no synchronizing, break transfer.
SPtM Single stand-by, forward and reverse synchronizing, parallel operation, peak shaving, soft
load transfer.
SPI Single stand-by, no MCB control, forward synchronizing, parallel operation, peak shaving,
soft load transfer.
MINT Multiple parallel, forward synchronizing, load and VAR sharing, power management, soft
load transfer.
Detail documentation
For more detail please refer to corresponding User guides (where –x-x means software version):
IS-SPM-x.x.pdf WinEdit-MultiEdit-x.x.pdf
IS-SSB-x.x.pdf Communiation guide-x.x.pdf
IS-SPtM-x.x.pdf Application guide-x.x.pdf
IS-SPI-x.x.pdf Troubleshooting guide-x.x.pdf
IS-MINT-x.x.pdf
Text
PAGE (Capital letters in the frame) buttons on the front panel
Conformity declaration
Following described machine complies with the appropriate basic safety and health
requirement of the EC Low Voltage Directive No: 73/23 / EEC and EC
Electromagnetic Compatibility Directive 89/336 / EEC based on its design and type,
as brought into circulation by us.
Be aware that the binary outputs can change state during and after software
reprogramming (before the controller is used again ensure that the proper
configuration and setpoint settings are set in the controller)!!!
Switch controller to OFF mode and disconnect the Binary outputs Starter and Fuel to
avoid unexpected automatic start of gen-set and GCB closing.
Take care when disconnecting In/Im3 terminals when the gen-set is stopped.
For safety connect parallel to InteliSys In/Im3 terminals two anti parallel diodes 10A/100V.
In any case do not disconnect generator CT terminals when the gen-set is loaded.
Note:
ComAp believes that all information provided herein is correct and reliable and reserves the right to update
at any time. ComAp does not assume any responsibility for its use unless otherwise expressly undertaken.
10
8 7 6 5
16 15 14 13 12 11
Pushbuttons
1. Numeric keyboard for setpoints values adjusting, measure screen fast select
2. CLEAR Clears character left from the cursor (Back Space), Exit from MENU
3. ENTER Value confirmation (function is equal to 7.)
4. MODE→ forward through gen-set operation modes OFF -> MAN-> SEM -> AUT->TEST.
←MODE backward through gen-set operation modes OFF<- MAN<- SEM <-AUT<-TEST.
FAULT RESET Acknowledges faults and alarms.
START Starts the gen-set in MAN and SEM mode.
STOP Stops the gen-set in MAN and SEM mode.
5. GCB ON/OFF When in MAN mode, opens and closes the GCB.
6. MCB ON/OFF When in MAN mode, opens and closes the MCB.
Display handling
7. ENTER Menu, value item confirmation (function is equal to 3.)
8. MENU Switch to the InteliSys Menu screen
9. ↑, ↓,<, > Select the InteliSys Menu item
10. ALARM LIST Switch to the InteliSys Alarm screen
Three color LED status: green = operation, orange = warning, red = fail
Display menus
There are 3 display menus available: Measurements, Params and History
Each menu consists of several groups of screens, except of history.
kW RPM
0 0
3
CAN16 1000000000000000
CAN32 0000000000000000
InteliSys – Operator guide, ©ComAp – June 2005 -9-
IS-Operator guide. PDF
[2-1] Bus 1/1 [8-1] Bin inputs 1/1
Bus freq 0,0 Hz BI1 ………….. 0 BI9 ……..……….. 0
BI2 ………….. 0 BI10 …………….. 0
Bus V Ph-Ph 0 0 0V BI3 ………….. 0 BI11 …………….. 0
BI4 ………….. 0 BI12 …………….. 0
Bus V Ph-N……│…….…│… Bargraph………. BI5 ………….. 0 BI13 …………….. 0
BI6 ………….. 0 BI14 …………….. 0
BI7 ………….. 0 BI15 …………….. 0
BI8 ………….. 0 BI16 ………..….. 0
[9-1] Bin outputs 1/1
BO1 ………….. 0
BO2 ………….. 0
BO3 ………….. 0
BO4 ………….. 0
BO5 ………….. 0
BO6 ………….. 0
BO7 ………….. 0
BO8 ………….. 0
[10-1] Analog inputs 1/1
Analog input 1………………… ………….. 0 °C
Analog input 2………………… ………….. 0 °C
Analog input 3………………… ………….. 0 °C
Analog input 4………………… ………….. 0 °C
Analog input 5………………… ………….. 0 °C
Analog input 6………………… ………….. 0 °C
Analog input 7………………… ………….. 0 °C
Analog input 8………………… ………….. 0 °C
[9-1] Cylinder temps 1/2
I.
400
350
400
450
400
350
400
450
T Cyl I. Aver 400 °C
[9-2] Cylinder temps 2/2
I.
0
-50
0
50
0
-50
0
50
T Cyl I. Aver 400 °C
Hint:
Additional screens are automatically generated when external units are configured.
Screens [8.1] up to [8.7] are inputs of extension units IS-BIN16/8.
Screens [9.1] up to [9.4] are outputs of extension units IS-BIN16/8.
Screens [10.1] up to [10.8] are analog inputs of extension units IS-AIN8.
Screens [9.1] up to [9.4] are cylinder temperature indication based on IS-AIN8 analog inputs.
OFF mode
• No start of the gen-set is possible. Outputs STARTER, GCB CLOSE/OPEN and FUEL SOLENOID are
not energized.
• No reaction if buttons START,STOP,GCB ON/OFF are pressed.
• When power-cut comes, MCB CLOSE/OPEN opens. After mains returns, MCB CLOSE/OPEN closes
with MCB close del.
MAN mode
1) To start the gen-set press START.
2) When the generator voltage is within limits (adjusted in the setpoints group Generator protections)
GCB green LED on the front panel lights.
3) Press GCB ON/OFF to close the GCB. If the generator voltage is out of the limits, controller does not to
respond to the GCB ON/OFF .
a) If controller detects dead bus, immediately closes GCB OPEN/CLOSE output.
b) If controller detects voltage on the bus, starts synchronizing.
4) To stop the engine press STOP
a) controller unloads the gen-set, opens GCB CLOSE/OPEN. Unloading is active only when binary
input MCB feedback is closed or other gen-set is connected to bus. In other case GCB CLOSE/OPEN
opens immediately.
b) Gen-set is cooled and stopped.
Hint:
Controller does not respond to the binary input SYS START/STOP. The gen-set is fully in manual control;
there is no automatic way to stop it (except protections). The gen-set stays running until STOP button is
pressed.
Controller does not take place in Power management in MINT, MEXT application
SEM mode
START. button starts the gen-set.
• Controller closes GCB to dead bus.
When Mains is within limits and MCB is ON, Controller starts synchronizing and closes GCB when
synchronizing conditions are met. Gen-set remains running in parallel.
• When Mains failure is recognized during parallel operation - Controller opens MCB.
• After mains recovers Controller synchronizes MCB and returns to parallel operation
In case of mains failure the gen-set starts automatically. After mains recovery stops automatically (MCB
synchro, soft transfer). This AMF function is the same as described below in AUT mode.
Other automatic starts/stops (peak start/stop, binary input Rem Start/stop) are not active.
Load control options are the same as in AUT mode.
Hint:
InteliSys does not respond to GCB ON/OFF , MCB ON/OFF buttons.
Remote start/stop
Genset starts automatically, when binary input REM START/STOP is closed and stops by opening it.
Peak shaving
Genset can start and stop automatically according to consumption from the mains (object). IE measurement
must not be set to NONE and ProcessControl:PeakAutS/S del must be greater than 0.
If Mains import value exceeds for more than ProcessControl:PeakAutS/S del
ProcessControl:PeakLevelStart, engine starts automatically.
If Load consumption (Mains import + Genset power) drops for more than ProcessControl:PeakAutS/S del
below ProcessControl:PeakLevelStop, engine stops.
Hint:
Engine does not stop, if other condition for automatic starts are active.
Example: If peak stop condition occurs, but REMOTE START/STOP is active, engine stays running.
InteliSys does not respond to GCB ON/OFF , MCB ON/OFF , STOP, START buttons and corresponding
remote WinEdit or Modbus commands.
Set Basic setting: FltRes GoToMAN = ENABLED to avoid automatic engine start when pressing FAULT
RESET after Shut down or Slow stop alarm.
Engine can start automatically without warning when pressing FAULT RESET after shut down alarm.
Overheat protection
Function is active when ProcessControl:Overheat prot = ENABLED
Analog input: LdCtrl:TbyPwr
Setpoints: Same as described in previous paragraph ( temperature by power control)
The function is similar to the Temp by Power. But in this case the requested load can vary between Mim
Power PtM and Baseload (if Load control = BASELOAD).
Hint:
Requested temperature should be set a bit higher as operational temperature.
InteliSys – Operator guide, ©ComAp – June 2005 - 13 -
IS-Operator guide. PDF
Export protection
Function is active when ProcessControl:Export prot = ENABLED.
Process control: IE measurement must not be set to NONE!
This function limits the requested gen-set power to keep Import power higher or equal to the setpoint
Import load.
Genset warming
Engine warming period starts after GCB is closed to parallel operation. The required gen-set load (e.g.
Baseload) is reduced to Engine params: Warming load.
Engine warming is finished when Engine params: Warming temp is reached but latest after Engine
params: Max warm time. Warming temperature is measured on Analog input Warming temp.
Genset Load is increased to Baseload (or to different value due to Import/Export function) after Warming is
finished.
Power derating
This function linearly decreases gen-set nominal power according to analog input value.
Gen-set power starts decreasing when temperature measured by Analog input Derating temp exceeds
DeratingStart value.
Gen-set power is at DeratedPower value when temperature measured by Analog input Derating temp is
equal or higher than DeratingEnd value.
Each active alarm is recorded to history and indicated on Alarm list screen. Detection of each binary input
alarm is fix 1 sec time delayed. Analog input Alarm detection is usually based on two levels (e.g. wrn and
sd). The Sensor fail activates or does not activate binary output common Alarm depends on configuration.
Use WinEdit to modify binary or analog inputs configuration.
Warning (Wrn)
When a warning occurs, only alarm outputs and common warning output are closed, no other action is
performed.
See List of possible events in chapter Remote control and data logging
Off load
When Off load protection is active GCB is opened immediately but the engine does not go to cooling state –
stays running for 60 second and then, if in AUT mode, the gen-set is stopped. Alarm outputs and common
unl output are closed. Active Off load protection disables start respectively GCB closing.
When Off load protection is not active (Binary input is opened) the gen-set starts again and GCB closes
again without Fault reset (in AUT, if a request for run – e.g. REM START/STOP – is still active).
Protection
delay Engine running only, SD, Slow stop, Wrn
Gen>V, Gen<V, Gen>f, Gen<f,
Volt unbal, Curr unbal, Reverse
power, Unload protection, Load surge
All the time & Overspeed protections & Ig IDMT, Ig unbal, IG short
Mains >V, Mains <V, Mains >f, Mains <f, MVolt unbal
Ready
Cranking Starting Running Loaded Loaded
RPM=0
GCB opened
Starter OFF
GCB closed
Unloading
Cooling
Start
Stop
Idle
or
Alarms indication
There can be following actions when Alarm is active (depends on Alarm type and configuration):
• Alarm list record
• History list record
• Active call (when is enabled and modem is installed)
• Controller front panel LED indication
• Binary output ALARM is closed when Alarm is active or when was deactivated and FAULT RESET
button was not pressed to confirm.
Binary output ALARM opens when Alarm was deactivated (no other Alarm is active) and FAULT RESET
button was pressed to confirm.
• Binary output HORN is closed for adjustable time when any new Alarm occurs.
• Corresponding value reading (binary input state, analog input value, generator voltage, .. ) is inverse
(e.g. 100 ) on Controller screen when value is out of limits (binary input protection is active).
PC software - WinEdit
On the PC (for direct or modem connection) has to be installed the ComAp’s software package WinEdit.
(based on Windows 95 or newer platform)
WinEdit enables:
read the quantities,
adjust all set points,
read the history,
control the engine,
configure the controller,
select software configuration,
modify alarm inputs and outputs,
direct or modem communication,
receive active calls.
History file
InteliSys stores a record of each important event into the history file. The history file contains several
hunderds records. When the history file is full, the oldest records are removed. History record structure
depends on local configuration.
Modem connection
Open WinEdit, Type connection = Modem. During modem connection are available all functions like from
direct connection.
Active calls
If the function is enabled and selected alarm comes up, the controller opens a connection to the remote PC
(selected phone number) automatically and send an aig archive file containing, among others the history file,
to the PC.
Operating conditions
Operating temperature -10..+60oC
Storage temperature -30..+80oC
Flash memory data retention time 10 years
Protection front panel IP65
Humidity 95% without condensation
Standard conformity
Low Voltage Directive EN 61010-1:95 +A1:97
Electromagnetic Compatibility EN 50081-1:94 (EN 61000-6-3)
EN 50081-2:96 (EN 61000-6-4)
EN 50082-1:99 (EN 61000-6-1)
EN 50082-2:97 (EN 61000-6-2)
Vibration 5 - 25 Hz, ±1,6mm
25 - 100 Hz, a = 4 g
Shocks a = 200 m/s2