QSF-QC-07

Conductor Test Report Ver:01, Rev:00

PO No 757404 Sample No: 5


Test Date 13-07-25 Tested By: Adex Engineering Ltd.
Supplier: Meghna Star

Sample Details:
Length 1000 mm Conductor Size 30 X 5 mm
Insulation Thickness (mm) N/A Temperature 32 °C
Conductor Type Rectangular Copper Bar

Test Data: The following test were conducted as per IEC-60851-5:2008 standard.
Parameter At Ambient Temperature At 20 °C At 75 °C
Resistance
143 136.26 167.17
(μΩ)
Resistivity
2.04E-05 2.51E-05
(Ω-mm )
% IACS
84.35
Conductivity

Insulation Breakdown Voltage (KV) Leakage Current (mA)


N/A N/A

Summary:
Parameter Required Measured
Conductor Size (mm) 30 X 5 30 X 5
Covered Conductor Size (mm) N/A X N/A N/A X N/A
Insulation Thickness (mm) N/A N/A
Resistivity at 20°C (Ω-mm) N/A 2.04384E-05
IACS Conductivity (%) ≥ 99 84.35
Insulation Breakdown Voltage (KV) N/A N/A

Observations: IACS Conductivity of this sample copper is fair and below standard requirements.

_______________ _____________________________
Test By: Approved By:
MD. Islam Hossain
Asst. Manager-QA/QC & Testing
Adex Engineering Ltd.