Isometer Irdh575
Isometer Irdh575
IRDH575_D00089_05_M_XXEN/01.2020 Manual EN
Table of Contents
1. Important information .................................................................................... 8
1.1 How to use this manual ................................................................................. 8
1.2 Technical support: service and support ................................................... 9
1.2.1 First level support ............................................................................................. 9
1.2.2 Repair service ..................................................................................................... 9
1.2.3 Field service ..................................................................................................... 10
1.3 Training courses ............................................................................................. 10
1.4 Delivery conditions ....................................................................................... 10
1.5 Inspection, transport and storage ........................................................... 11
1.6 Warranty and liability ................................................................................... 11
1.7 Disposal ............................................................................................................ 12
2. Safety instructions ......................................................................................... 13
2.1 General safety instructions ........................................................................ 13
2.2 Work activities on electrical installations ............................................. 13
2.3 Device-specific safety information ......................................................... 14
2.4 Use for the intended purpose ................................................................... 16
3. Function ........................................................................................................... 17
3.1 General characteristics ................................................................................ 17
3.2 Essential functions of the ISOMETER® .................................................... 17
3.3 Essential functions of the Insulation fault location system (EDS) 18
3.4 Product description ...................................................................................... 18
3.5 Function ............................................................................................................ 19
3.5.1 Current output for external measuring instrument ......................... 20
3.5.2 Real-time clock ............................................................................................... 20
3.5.3 Insulation fault location .............................................................................. 20
3.5.4 Interconnected systems ............................................................................. 21
IRDH575_D00089_05_M_XXEN/01.2020 3
Table of Contents
4 IRDH575_D00089_05_M_XXEN/01.2020
Table of Contents
IRDH575_D00089_05_M_XXEN/01.2020 5
Table of Contents
6 IRDH575_D00089_05_M_XXEN/01.2020
Table of Contents
IRDH575_D00089_05_M_XXEN/01.2020 7
1. Important information
Always keep this manual within easy reach for future reference.
To make it easier for you to understand and revisit certain sections in this man-
ual, we have used symbols to identify important instructions and information.
The meaning of these symbols is explained below:
IRDH575_D00089_05_M_XXEN/01.2020
8
Important information
Commissioning
Troubleshooting
IRDH575_D00089_05_M_XXEN/01.2020 9
Important information
products
Analysis of the electrical installation in the building (power quality test,
*Available from 7.00 a.m. to 8.00 p.m. 365 days a year (CET/UTC+1)
**Mo-Thu 7.00 a.m. - 8.00 p.m., Fr 7.00 a.m. - 13.00 p.m
10 IRDH575_D00089_05_M_XXEN/01.2020
Important information
Sale and delivery conditions can be obtained from Bender in printed or elec-
tronic format.
device.
Failure to observe the instructions in this operating manual regarding
manufacturer.
Non-observance of technical data.
IRDH575_D00089_05_M_XXEN/01.2020 11
Important information
1.7 Disposal
Abide by the national regulations and laws governing the disposal of this de-
vice. Ask your supplier if you are not sure how to dispose of the old equip-
ment.
The directive on waste electrical and electronic equipment (WEEE directive)
and the directive on the restriction of certain hazardous substances in electri-
cal and electronic equipment (RoHS directive) apply in the European Commu-
nity. In Germany, these policies are implemented through the "Electrical and
Electronic Equipment Act" (ElektroG). According to this, the following applies:
Electrical and electronic equipment are not part of household waste.
Batteries and accumulators are not part of household waste and must
be disposed of in accordance with the regulations.
Old electrical and electronic equipment from users other than private
households which was introduced to the market after 13 August 2005
must be taken back by the manufacturer and disposed of properly.
For more information on the disposal of Bender devices, refer to our
homepage at www.bender-de.com -> Service & support.
12 IRDH575_D00089_05_M_XXEN/01.2020
2. Safety instructions
If the device is used outside the Federal Republic of Germany, the applicable
local standards and regulations must be complied with. The European stan-
dard EN 50110 can be used as a guide.
IRDH575_D00089_05_M_XXEN/01.2020
13
Safety instructions
14 IRDH575_D00089_05_M_XXEN/01.2020
Safety instructions
IRDH575_D00089_05_M_XXEN/01.2020 15
Safety instructions
16 IRDH575_D00089_05_M_XXEN/01.2020
3. Function
IRDH575_D00089_05_M_XXEN/01.2020
17
Function
18 IRDH575_D00089_05_M_XXEN/01.2020
Function
3.5 Function
The IRDH575 ISOMETER® is connected between the unearthed system and the
protective conductor (PE).
The response values and other function parameters are set via the function keys.
The parameters are indicated on the LC display and are stored in a non-vola-
tile memory (EEPROM) after the setting is completed.
A microprocessor-controlled pulsating AC measuring voltage is superimpo-
sed on the system ( AMPPlus measuring principle*). The measuring cycle
consists of positive and negative pulses of the same amplitude. The period de-
pends on the respective system leakage capacitances and the insulation resis-
tance of the system to be monitored.
An insulation fault between system and earth closes the measuring circuit.
From the measured current value, the microprocessor calculates the insulati-
on resistance which is indicated on the LC display or the external kΩ measu-
ring instrument.
The measuring time is determined by the system leakage capacitances, the in-
sulation resistance, and the system-related interference disturbances. System
leakage capacitances do not influence the measuring accuracy.
If the reading is below the selected response values ALARM1/ALARM2, the as-
sociated alarm relays respond and the alarm LEDs "ALARM1/2" light up and
the measuring value is indicated on the LC display (in the event of DC insula-
tion faults, the faulty supply line is indicated). The fault indication can be
stored by bridging the terminals R1/R2 (external RESET button [NC contact])
or by setting the fault memory to "Memory:on" in the "ISO SETUP" menu.
Pressing the external or internal RESET button, resets the fault message, pro-
vided that the insulation resistance is at least 25 % above the preset value.
IRDH575_D00089_05_M_XXEN/01.2020 19
Function
20 IRDH575_D00089_05_M_XXEN/01.2020
Function
IRDH575 via the RS-485 interface (BMS protocol) and is then indicated by an
alarm LED and indicated on the display. In the Master mode (Addr. 1), this
alarm message is indicated by the alarm relay K3 as common alarm.
During the insulation fault location process the insulation monitoring func-
tion is deactivated. If the test current falls below the value the EDS4… is capa-
ble of measuring, the insulation fault location process will be stopped by
IRDH575.
IRDH575_D00089_05_M_XXEN/01.2020 21
Function
22 IRDH575_D00089_05_M_XXEN/01.2020
Function
addr. 1 addr. 2
IT system 1 IT system 2
IT system 4 IT system 3
addr. 4 addr. 3
Example:
Let as assume, in the before-mentioned ring-type arrangement, the associa-
ted coupling switch of the Slave ISOMETER® 2 were open. The coupling swit-
ches of the BMS Master (Addr. 1) and of the Slaves 3 and 4 were closed. In this
case the ISOMETER® and EDS functions of the Master and the Slaves 3 and 4
would be deactivated. In spite of changing to the STANDBY mode, the Master
status of the device with address 1 would remain. That means, if a paramete-
rization is necessary, it has to be carried out via the IRDH575 with BMS
address 1.
IRDH575_D00089_05_M_XXEN/01.2020 23
Function
24 IRDH575_D00089_05_M_XXEN/01.2020
Function
Each ISOnet slave checks the network for an ISOnet master. If there is no mas-
ter available, the display will show the fault message “ISOnet Master?“ after
approximately 1 hour. Additionally, the LED for device errors lights and the
Relay K3 switches. With the ISOnet function activated, the function input
F1/F2 is automatically deactivated.
addr. 1 addr. 2
IT system 1 IT system 2
IT system 4 IT system 3
addr. 4 addr. 3
IRDH575_D00089_05_M_XXEN/01.2020 25
Function
This has the advantage that no auxiliary contacts of a coupling switch are re-
quired. Furthermore, this solution is recommended for IT systems coupled via
capacitances or diodes.
26 IRDH575_D00089_05_M_XXEN/01.2020
Function
Error
message Meaning Steps to taken
IRDH575_D00089_05_M_XXEN/01.2020 27
Function
3.5.8 Relay K3: device fault alarm and EDS common message
Relay K3 is intended to signal device and connection errors of the
ISOMETER®. In the Master mode with bus address 1, EDS alarm messages can
be collectively indicated by the K3 relay as well as system fault messages. Coll-
ective indication of the EDS alarms by K3 can be disabled by selecting „K3
Alarm: off“ from the "EDS Setup" menu. Refer to page 63.
K3 is permanently set to N/C operation, with the contacts 31-34 normally
closed, that means when a fault occurs, the relay deenergizes (K3: 31-32 con-
nected).
Further details are described in "Chapter 3.5.7 Self test". Even when a protocol
converter of the FTC470… series is installed in a BMS system which is tem-
porarily taking over the Master function is, the function collective EDS mes-
sage will remain. This function is directly dependent on BMS address 1, the
Master status is a secondary factor.
28 IRDH575_D00089_05_M_XXEN/01.2020
4. Connection
IRDH575_D00089_05_M_XXEN/01.2020
29
Connection
IRDH575_D00089_05_M_XXEN/01.2020 30
Connection
1 2 3 4
mA
5 6 7 8 9
RS485
ON
M+ M- T1 T2 R1 R2 F1 F2 A B 31 32 34 21 22 24 11 12 14
OFF
S2 S1
IRDH575 K3 K2 K1
A1/+ A2/- L1 L2 L3 KE
L1 L2 L3
6A 3(N) AC-System Un PE
L1
L2
L3 14
N
10 11
L1 L2 L3
AC-System
L1
Un
L2
12
L1 L2 L3
DC-System
L+
Un
L- 13
31 IRDH575_D00089_05_M_XXEN/01.2020
Connection
IRDH575_D00089_05_M_XXEN/01.2020 32
5. Commissioning flow chart
IRDH575_D00089_05_M_XXEN/01.2020
33
Commissioning flow chart
IRDH575_D00089_05_M_XXEN/01.2020 34
Commissioning flow chart
EDS460 / EDS470
35 IRDH575_D00089_05_M_XXEN/01.2020
Commissioning flow chart
Are all bus nodes available after Check the wiring and bus nodes
the completion of the test ? no (RS485 LED)
yes
yes
yes
IRDH575_D00089_05_M_XXEN/01.2020 36
Commissioning flow chart
37 IRDH575_D00089_05_M_XXEN/01.2020
6. Operation and setting
IRDH575_D00089_05_M_XXEN/01.2020
38
Operation and setting
39 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
Insulation Fa u l t 8
1
Rs=011kW . H 7
2 --EDS:on---auto--- 6
ADR:02 k03 12mA
3 4 5
6 -on---auto: EDS is in the AUTO mode and just running. Further modes
are:
- on: EDS is activated
- off: EDS is deactivated
- pos470 : Addr. and channel of the EDS have to be selected
(in the Master mode only), EDS47… only
- 1cycle : after testing all the channels, once the EDS is deactivated
IRDH575_D00089_05_M_XXEN/01.2020 40
Operation and setting
8 Messages:
- Insulation fault
- Connection system?
- Connection PE?
- Device error x
- ****STANDBY*****
41 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
Please have the details above on hand if you have a problem and if you con-
tact Bender for technical questions.
TEST RESET
Pressing the RESET key resets insulation
and fault messages of the ISOMETER®. This
function is only active after activating the fault memory in the ISO-SETUP
menu or after bridging R1/R2. Furthermore, the ISOMETER® can only be reset
when the present insulation value is 25 % higher than the preset response va-
lue.
The menu system is called up by pressing the MENU key.
MENU
IRDH575_D00089_05_M_XXEN/01.2020 42
Operation and setting
For controlling the menu system, the Up/Down keys, the ENTER key and the
ESC key are used:
Up key:
Moving up in the menu, increasing a parameter
TEST
Down key:
Moving down in the menu, decreasing a parameter
RESET
ENTER key:
Selecting a menu item or sub menu item, confirming or sto-
MENU ring a parameter change and going back to the associated sub
menu item or going to the next input area.
ESC key:
ESC
to return to the previous menu.
INFO If the menu has not been closed, the device returns to the dis-
play mode again after approximately 5 minutes.
For the sake of clarity, the following symbols are used for the functions ENTER,
UP/DOWN and ESCAPE in the menu diagrams of this operating manual:
ESC
43 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
IRDH575_D00089_05_M_XXEN/01.2020 44
Operation and setting
45 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
1. EXIT
2. HISTORY INFO
3. ISO SETUP
4. ISO ADVANCED
5. EDS SETUP
ESC 6. EDS 460/490
7. EDS 470
8. COM SETUP
9. PASSWORD
10. LANGUAGE
11. SERVICE
Menu
ESC item
1 ... 7
PASSWORD SERVICE
COM SETUP LANGUAGE
1. EXIT
2. Addr: 001 1. EXIT
3. ISONet: Off 2. Text: Deutsch
4. ISO Monitor
IRDH575_D00089_05_M_XXEN/01.2020 46
Operation and setting
****IT-SYSTEM****
R >010 MW
- EDS: off -- auto --
MENU
******************
1. EXIT
2. HISTORY INFO
3. ISO SETUP
4. ISO ADVANCED
5. EDS SETUP
ESC 6. EDS 460/490
7. EDS 470
8. COM SETUP
9. PASSWORD
10. LANGUAGE
11. SERVICE
Menu
item
8 ... 11 ESC
1. EXIT
2. Alarm1 040 kW
3. Alarm2 010 kW 1. EXIT
4. K1 : NO 2. EDS: auto
5. K2 : NO 3. System: 3AC
6. Memory: off 4. MaxPuls:025mA
7. M+/M-: 0-20 mA 5. K3 Alarm: on
47 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
IRDH575_D00089_05_M_XXEN/01.2020 48
Operation and setting
1. EXIT
2. HISTORY INFO
3. ISO SETUP
4. ISO ADVANCED
5. EDS SETUP
6. EDS 460/490
7. EDS 470
8. COM SETUP
9. PASSWORD
10. LANGUAGE
11. SERVICE
Nr.: 01 #Nr: 08
ESC
Power on
01.01.06 16:12
Clear all: off
Nr.: 02 #Nr: 08
Rmin: 010kW Clear all: off Clear all: on
01.01.02 17:26
Clear all: off
Nr.: 03 #Nr: 08
Alarm1: 004kW Clear all: off Clear all: on
03.01.06 10:33
Clear all: off
49 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
6.4.2 Starting the EDS system via the response values ALARM 1
and ALARM 2
The EDS system is started when the value of the insulation resistance falls
below the lowest preset response value, i.e. below both alarm values.
When setting the ISOMETER® response values, make sure that the lower value
of them is within a range which the EDS system is able to find. Therefore it is
recommended to set the ISOMETER® response value according to the respon-
se characteristic curves of the EDS system (Refer to page 102).
IRDH575_D00089_05_M_XXEN/01.2020 50
Operation and setting
K1: N.C Test = N/C operation contacts 11-12-14, with relay test
(the alarm relay is energized during normal operation)
K1: N.O Test = N/O operation contacts 11-12-14, with relay test
(the alarm relay is deenergized during normal operation)
K1: N.C = N/C operation contacts 11-12-14, without relay test
(the alarm relay is energized during normal operation)
K1: N.O = N/O operation contacts 11-12-14, without relay test
(the alarm relay is deenergized during normal operation)
K1: Flash = Flashing function contacts 11-12-14
(the alarm relay and the LED flash in the event of an alarm
message, approximately 0.5 Hz
51 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
1. EXIT
2. HISTORY INFO
3. ISO SETUP
4. ISO ADVANCED
5. EDS SETUP
6. EDS 460/490
7. EDS 470
8. COM SETUP
9. PASSWORD
10. LANGUAGE
11. SERVICE
1. Exit
2. AL1: 40 KW Alarm1 : 40 KW
3. AL2: 10 KW
4. K1 : N.O 001 KW
.
5. K2 : N.O .
6. Memory: off 10 MW
7. M+/M-: 0-20 mA Alarm2 : 10 KW
Memory: off
Memory: on
Memory: off
M+/M-: 0-20 mA
M+/M-: 0-20 mA
M+/M-: 4-20 mA
IRDH575_D00089_05_M_XXEN/01.2020 52
Operation and setting
K2: N.C Test = N/C operation contacts 21-22-24, with relay test
(the alarm relay is energized during normal operation)
K2: N.O Test = N/O operation contacts 21-22-24, with relay test
(the alarm relay is deenergized during normal operation)
K2 : N.C = N/C operation contacts 21-22-24, without relay test
(the alarm relay is energized during normal operation)
K2 : N.O = N/O operation contacts 21-22-24, without relay test
(the alarm relay is deenergized during normal operation)
K2 : Flash = Flashing function contacts 21-22-24
(the alarm relay and the LED flash in the event of an alarm
message, approximately 0.5 Hz)
53 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
IRDH575_D00089_05_M_XXEN/01.2020 54
Operation and setting
55 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
6.5.7 Specifying the starting time of the automatic self test (Test)
If the 24h self test is activated in the ISO ADVANCED menu, it is possible to set
the time (hour) when the self test is to be carried out by means of the
"TEST: 12:00" sub menu. Then the self test is automatically carried out once a
day at a given time. If the 1 hour auto test has been selected, the self test will
be carried out at every full hour.
IRDH575_D00089_05_M_XXEN/01.2020 56
Operation and setting
1. EXIT
2. HISTORY INFO
3. ISO SETUP
4. ISO ADVANCED
5. EDS SETUP
6. EDS 460/490
7. EDS 470
8. COM SETUP
9. PASSWORD
10. LANGUAGE
11. SERVICE
1. Exit
2. AGH: no
3. Ce max : 150µF Ce max : 150µF
4. Measure: AMP
Ce max : 150µF
5. Autotest: 24h
Ce max : 500µF
6. Clock: 21:09
7. Date: 01.01.01
Measure: AMP
8. Test: 12:00 DC
AMP
24h
no
01h
Autotest: 24h
Clock: 21:09
Date: 01.01.01
Test: 12:00
Test: 00:00
.
.
.
Test: 23:00
57 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
IRDH575_D00089_05_M_XXEN/01.2020 58
Operation and setting
1. EXIT
2. HISTORY INFO
3. ISO SETUP
4. ISO ADVANCED
5. EDS SETUP
6. EDS 460/490
7. EDS 470
8. COM SETUP
9. PASSWORD
10. LANGUAGE
11. SERVICE
1. Exit
2. EDS: auto EDS : auto
3. System: 3AC auto
4. MaxPuls: 025mA on
off
5. K3 Alarm: on pos470
1cycle
System: 3AC
3AC
K3 Alarm: on AC
on DC
off
POSITION SETUP
ADR: 002 k: 001
no EDS/ 15mA/
>1A/ >10A
MaxPuls: 025mA
1 mA
2,5 mA
10 mA
25 mA
50 mA
59 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
1cycle
EDS47… :
As soon as the insulation resistance has fallen below the ISOMETER®
response values ALARM 1 and 2, the EDS system is automatically acti-
vated once. It remains active until every EDS47… has measured all
channels once and as long as the test current during the measure-
ments is above 1.5 mA (EDS470) or 0.15 mA (EDS473).
EDS46… / 49… :
As soon as the insulation resistance has fallen below the ISOMETER®
response values ALARM 1 and 2, the EDS system is automatically acti-
vated once. It remains active for approximately 5 minutes when the
test current during the measurement is above 1.5 mA (EDS460/
EDS490) or 0.15 mA (EDS461/EDS491).
auto
As soon as the insulation resistance has fallen below the ISOMETER®
response values ALARM 1 and 2, the EDS system is automatically acti-
vated for approximately 5 minutes and remains activated as long as the
test current is above 5 mA (0.5 mA). The EDS insulation fault location
process is cyclically interrupted for approximately 5 minutes (factory
setting), i.e. for the time the ISOMETER® is carrying out insulation fault
measurements.
6.6.3 System DC / 1 AC / 3 AC
The type of the system to be monitored are to be selected from this sub menu:
DC = DC system
1 AC = single phase AC system
3 AC = three-phase AC system
IRDH575_D00089_05_M_XXEN/01.2020 60
Operation and setting
Resulting from the type of supply system, the real test current in AC systems
is lower than the setting. The reduction factor is 0.5 in AC-Systems and 0.67 in
3AC systems. Therefore, the test current setting 1 mA for EDS473 and 10 mA
for EDS470 devices is not admissible in AC systems.
A list of possible test current settings for IRDH575 in relation to the type of
supply system and insulation fault evaluators is given in the table below:
61 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
Please note:
In supply systems to be monitored with a voltage < 40 V the
maximum test current of all IRDH575B1… versions is
limited to approximately 25 mA .
IRDH575_D00089_05_M_XXEN/01.2020 62
Operation and setting
6.6.5 K3 alarm: ON
The K3 relay can be used either for one or for two functions. It is always used
for signalling IRDH575 device errors.
K3 alarm: on
6.7.1 General
The following parameters have an effect on that device the BMS address of
which is being displayed. Set the address in order to select the appropriate de-
vice.
Memory
Use this menu option to switch the fault memory of the selected EDS46…/
EDS49… on or off. Factory setting = off.
Trigger
Use this parameter to specify whether the fault location of EDS46… / EDS49…
is to be started by an IRDH575 (Com) or if automatically and continuously all
measuring channels are measured in parallel (Auto). Factory setting = Com.
63 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
N. freq
Use this menu option to select the nominal frequency of the system to be mo-
nitored. You may select 50, 60 or 400 Hz. Factory setting = 50 Hz.
System
Use this menu option to select the type of the distribution system to be moni-
tored.
You may select:
DC = DC system
AC = single-phase AC system
3 AC = three-phase AC system
6.7.2 Channel
The following parameters have an effect on the device the BMS address and
measuring channel of which is being displayed. Set the respective address
and channel in order to select the appropriate device.
IRDH575_D00089_05_M_XXEN/01.2020 64
Operation and setting
1. Exit
2. General
3. Channel
4. Relay: N/O
5. Test/Reset
ADR: 2...90 Sw: V1.02
1. Exit
2. Memory: off on Memory: on
off
3. Trigger: Com
4. N.freq.: 50 Hz Com Trigger: Auto
see 5. System: AC Auto
next
page
DC N.freq.: 60 Hz
50 Hz
60 Hz
400 Hz
AC Systeme: 3AC
DC
3AC
2...
ResVal: 0005 mA
10mA
W/WR
WS CT: off
ADR: 2...90 CH: 1...12 P52
1. Exit P165
2. ResVal: 0004 mA P20
3. CT: W/WR off 00 s
4. T(on) :00 s 06 s T(on) : 12 s
12 s
5. T(off) :06 s 18 s T(off) : 18 s
6. CTmonitor: on 24 s
7. Inverter: off on
8. Op. mode: N/O CTmonitor: off
off
on Inverter: on
off
65 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
ResVal
Use this menu option to set the response values of the EDS device to be para-
meterized. This applies to:
EDS460 / EDS490: 2…10 mA in 1 mA steps, factory setting = 5 mA
CT: W/WR
Select the measuring current transformer type to be used from the list below:
W/WR = circular or rectangular measuring current transformer =
factory setting
WS = split-core current transformer
off = channel switched off
T(on)
Use this menu option to set a response delay of 0…24 s for the selected
EDS4…;
Factory setting = 0 s.
T(off)
Use this menu option to set a delay on release of 0…24 s for the EDS4…;
Factory setting = 6 s.
CT monitor
To enable or disable the CT monitoring. That enables the EDS… to check the
proper connection of the respective measuring current transformer. After the
test, this will be indicated on the display as described in "Chapter 6.7.4 EDS
Test". Faults are indicated by the "Alarm 1“ LED. In position "off“, this function
is deactivated.
Factory setting = on.
Inverter
Use this menu option to adapt a selected channel of the EDS46… /49… to a
circuit comprising a frequency converter; Factory setting = off.
IRDH575_D00089_05_M_XXEN/01.2020 66
Operation and setting
Op.mode
Use this menu option to determine the operating mode of the 12 channel-re-
lated alarm relays of an EDS490 / EDS491; Factory setting = N/O.
6.7.3 Relay
Use this menu to set the parameters for common alarm and system fault alarm
at the relays of EDS46… and EDS49. The following parameters have an effect
on that device the BMS address and the associated alarm relay of which are
being displayed. Set the address and the respective relay /1,2) in order to se-
lect the appropriate device.
Op.mode
Use this menu option to set the operating mode of the common relays for
alarm 1 and alarm 2. Factory setting: Relay 1 = N/O, Relay 2 = N/C.
ALARM
Use this menu option to assign an occurring EDS alarm to one or both EDS
alarm relays. Factory setting for Relay 1/2 = on.
Dev. Error
Use this menu option to assign an occurring EDS device fault alarm to one or
both EDS alarm relays. Factory setting. Relay 1 = off, Relay 2 = on.
In case of fault the following fault messages appear on the display of the
IRDH575:
no CT (measuring current transformer not connected)
67 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
Device type
Software version
CT connection
at EDS47… means:
– ok = channel switched on
– off = channel switched off
– noCT = no measuring current transformer connected
– short = measuring current transformer short-circuited
Memory behaviour of the EDS47… (Memory on/off)
If one of the tested BMS devices does not provide the required properties, no
answer is shown in the list of properties.
Factory setting = off.
IRDH575_D00089_05_M_XXEN/01.2020 68
Operation and setting
1. Exit
2. General see previous page
3. Channel
4. Relay: N/O
5. Test/Reset
N/C
ADR: 2...90 Relay: 1...2 N/O Op. mode: N/C
1. Exit
2. Op. mode: N/O
3. Alarm: off on Alarm: on
off
4. Dev. Error: on
1. Exit
2. EDS Test: off on EDS Test: on busy .... 16 s
off
3. EDS Reset: off
on EDS-Reset: on
off
69 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
Device type
Software version
CT connection
in case of EDS47… means:
– off = channel switched off
– noCT = no measuring current transformer connected
– short = measuring current transformer short-circuited
Memory behaviour of the EDS47… (Memory on/off)
IRDH575_D00089_05_M_XXEN/01.2020 70
Operation and setting
6.8.4 Details about the menu points Relay, Memory and n-peak
The parameters indicated on the IRDH575 display do not necessarily corres-
pond to the EDS47… settings. Only when a control command is sent to EDS
by pressing Return, the EDS settings of EDS47… correspond to the IRDH575
indication.
71 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
****EDS-Monitor****
Nr.: 01 #Nr.: 02
1. Exit ADR: 03 k12 20mA
2. EDS Monitor *********************
3. EDS Test: off
4. EDS Reset: off Nr: 01
5. Relay: N/O
6. Memory: on 01...50
7. CT Setup
8. n-peak: 1...255
EDS-Test: off
****CT-SETUP****
ADR: 2....90 k: 1....12
EDS-Test: on
Typ: standard/split /off on
conn.-CT: on/off off
busy .... 16 s
IRDH575_D00089_05_M_XXEN/01.2020 72
Operation and setting
6.8.6 Relay
Operating principle of the alarm relays of EDS47…:
N.C = N/C operation
6.8.7 Memory
Setting of the memory behaviour of EDS47…
The factory setting is „on“.
When the memory is in "on" position, the alarms of an EDS47… are
maintained until a RESET is carried out via the menu (IRDH575) or the
RESET key is pressed on the EDS47…
When the memory if in "off" position, the alarm stored in the EDS47…
will be deleted when the next scanning is carried out, provided that no
insulation fault exists and no insulation fault location process is run-
ning.
6.8.8 CT Setup:
Setting of the CT type and connection monitoring for EDS47…:
ADR:
Note:
When ADR:2-90 and k:1-12 are selected, the same CT type will be
set for every channel of every device address.
Type:
– standard = measuring current transformers of circular and rectan-
gular type = factory setting
– split = split-core measuring current transformers
– off = channel switched off
conn.-CT
On or off switching of the CT monitoring
Factory setting is „on“.
73 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
6.8.9 n-peak:
n-peak: 1-255
Setting of the maximum automatic elongation of the measuring time
of the connected EDS47…if disturbances are likely to occur in the sys-
tem being monitored. By default, four measurements are carried out
per channel before the EDS47… proceeds to the next channel.
If disturbances occur during the measurement due to system interfer-
ences (signalled by the "Fault"-LED at EDS47…), the number of meas-
urements per channel will automatically be increased by the preset
number n, that means 4 + n measurements per channel are carried out
in this case. The n-times elongation of the measuring time per channel
will automatically be stopped, when the fault is eliminated.
Factory setting is n = 5.
IRDH575_D00089_05_M_XXEN/01.2020 74
Operation and setting
! ! ! ! N O D ATA ! ! ! !
No data found: R= A D R: 02
I n s u l at i o n Fa u l t
Current data address 03: R= 010K W A D R: 03
75 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
6.9.3 ISOnet
Use this menu item to activate the ISOnet function of an IRDH575.
Refer to page 24 for an ISOnet description.
1. EXIT
2. HISTORY INFO
3. ISO SETUP
4. ISO ADVANCED
5. EDS SETUP
6. EDS 460/490
7. EDS 470
8. COM SETUP
9. PASSWORD
10. LANGUAGE
11. SERVICE
1. Exit
2. Addr: XXX Addr: XXX
3. ISONet: off ADR: 001
4. ISO Monitor .
.
.
ADR: 030
ISOnet : off
off
on
****IT-SYSTEM****
R >123 kW ADR: 01
IRDH575_D00089_05_M_XXEN/01.2020 76
Operation and setting
The desired password (menu item 2. Password: xxx) can be set with the UP/
DOWN keys and confirmed with the ENTER key.
The password can be activated in the menu item "3. Status: on" by clicking the
ENTER key. The factory setting is "3. Status: off", that means that the password
is deactivated.
1. EXIT
2. HISTORY INFO
3. ISO SETUP
4. ISO ADVANCED
5. EDS SETUP
6. EDS 460/490
7. EDS 470
8. COM SETUP
9. PASSWORD
10. LANGUAGE
11. SERVICE
1. Exit
2. Password: XXX Password: XXX
3. Status: off 000
.
.
.
999
Status : off
off
on
77 IRDH575_D00089_05_M_XXEN/01.2020
Operation and setting
1. EXIT
2. HISTORY INFO
3. ISO SETUP
4. ISO ADVANCED
5. EDS SETUP
6. EDS 460/490
7. EDS 470
8. COM SETUP
9. PASSWORD
10. LANGUAGE
11. SERVICE
1. Exit
2. Text: Deutsch Text: Deutsch
Deutsch
English
IRDH575_D00089_05_M_XXEN/01.2020 78
Operation and setting
mA)
Maximum system leakage capacitance (150 µF or 500 µF)
EDS mode (on, off, auto, 1 cycle), start and stop conditions for the EDS
systems
EDS type of system (DC, AC, 3 AC)
requested)
EDS Position Mode channel (BMS channel of the EDS47… to be
requested)
79 IRDH575_D00089_05_M_XXEN/01.2020
7. Serial interfaces
IRDH575_D00089_05_M_XXEN/01.2020
80
Serial interfaces
7.2.3 Wiring
A suitable type of cable for the wiring of the RS-485 network is:
screened cable, core diameter ≥ 0.6 mm
(e.g. J-Y(St)Y 2x0.6), screen on one side connected to earth (PE).
Connection to the terminals A and B.
The number of bus nodes is restricted to 32 devices. When more devices are
to be connected, Bender recommends to use an RS-485 repeater DI1.
81 IRDH575_D00089_05_M_XXEN/01.2020
Serial interfaces
33 64
1 32
DI1
IRDH575_D00089_05_M_XXEN/01.2020 82
Serial interfaces
Master receives no answer from five subsequent addresses, the scanning cyc-
le is started again. If the Master recognizes incorrect answers from a slave, the
fault message "Fault RS485" is issued by the Master.
Fa u l t R S 4 8 5
Rs=011kW . H
--EDS:on---auto---
******************
Faults may be caused when:
Addresses are assigned twice
7.3.2 BMS-Slave
In a BMS network for each slave an individual address between 2 and 30 has
to be selected. There may be no gaps of more than five subsequent addres-
ses, so that all slaves can be scanned by the Master. For IRDH575 a BMS
address can be selected from the address range 1…30. When assigning the
addresses, also other devices such as the EDS4… must be considered.
The correct reception of BMS data is indicated by a flashing point on the dis-
play on the right of the measuring pulse indication.
au t S 85
Rs=011kW . H Flashing point:
--EDS:on---auto--- BMS data re-
ceived
83 IRDH575_D00089_05_M_XXEN/01.2020
Serial interfaces
BMS bus
Fault messages of all SLAVE devices connected to the BMS bus
IRDH575_D00089_05_M_XXEN/01.2020 84
Serial interfaces
The following table gives an overview about essential alarm messages and
the assignment of the messages indicated on the display or operator panels,
e.g. PRC1470.
85 IRDH575_D00089_05_M_XXEN/01.2020
Serial interfaces
Un: 3(N)AC, AC
L1
L2
L3
N
PE
measuring
current
Us transformer
see name plate
to the
load
F F
6A 6A
A1 A2 L1 L2 L3 A1 A2 k1 l k2
IRDH575 EDS460
KE A B A B
PE
IRDH575_D00089_05_M_XXEN/01.2020 86
Serial interfaces
The following operating manuals are available when using the IRDH575 in
combination with EDS systems for other applications:
Manual for EDS470 application:
87 IRDH575_D00089_05_M_XXEN/01.2020
Serial interfaces
IRDH575_D00089_05_M_XXEN/01.2020 88
8. Factory settings
IRDH575_D00089_05_M_XXEN/01.2020
89
Factory settings
Please check if the basic setting of the ISOMETER® complies with the require-
ments of the system to be monitored.
IRDH575_D00089_05_M_XXEN/01.2020 90
9. Technical data IRDH575
IRDH575_D00089_05_M_XXEN/01.2020
91
Technical data IRDH575
IRDH575_D00089_05_M_XXEN/01.2020 92
Technical data IRDH575
Serial interface
Interface/protocol ...................................................................................................................................... RS-485/BMS
Cable length ................................................................................................................................................. ≤ 1,200 m
Recommended cable (screened, screen on one side connected to PE)................................................. J-Y(St)Y 2x0,6
Terminating resistor................................................................................................................................. 120 Ω (0,5 W)
Switching elements
Switching components............................................................... 3 changeover contacts: K1 (Alarm 1), K2 (Alarm2),
...................................................................................................... K3 (device fault, additionally selectable EDS Alarm)
Operating principle K1, K2............................................................................................................ N/O or N/C operation
Factory setting (Alarm1/Alarm2)............................................................................................................ N/O operation
Operating principle K3.............................................................................................................................. N/C operation
Electrical endurance.................................................................................................................................. 12, 000 cycles
Contact class.............................................................................................................................. IIB (DIN IEC 60255-23)
Rated contact voltage ...................................................................................................................... AC 250 V/DC 300 V
Protected separation up to ....................................................................................................................... AC/DC 150 V
Making capacity.............................................................................................................................................. AC/DC 5 A
Breaking capacity ............................................................................................................. 2 A, AC 230 V, cos phi = 0.4
.......................................................................................................................................... 0.2 A, DC 220 V, L/R = 0.04s
Contact current at DC 24 V................................................................................................................. ≥ 2 mA (50 mW)
General data
EMC ................................................................................................................. acc. to IEC 61326-2-4:2006-06 Ed. 1.0
Shock resistance acc. to IEC 60068-2-27..................................................................................................... 15 g/11 ms
Bumping acc. to IEC 60068-2-29................................................................................................................... 40 g/6 ms
Vibration resistance acc. to IEC 60068-2-6 (device in operation)..................................................... 1 g/10…150 Hz
Vibration resistance acc. to IEC 60068-2-6 (during transport)......................................................... 2 g/10…150 Hz
Ambient temperature, during operation ........................................................................................... -10 °C…+55 °C
Storage temperature range ................................................................................................................ -40 °C…+70 °C
Climatic class according to IEC 60721-3-3 .............................................................................................................. 3K5
Operating mode............................................................................................................................ continuous operation
Mounting.............................................................................................................................. as indicated on the display
Distance to adjacent devices............................................................................................................................ ≥ 30 mm
Connection .......................................................................................................................................... plug-in terminals
Connection, rigid/flexible .............................................................................................. 0.2…4 mm2/0.2…2.5 mm2
Connection, flexible with connector sleeve, without/with plastic sleeve......................................... 0.25…2.5 mm2
93 IRDH575_D00089_05_M_XXEN/01.2020
Technical data IRDH575
IRDH575_D00089_05_M_XXEN/01.2020 94
Technical data IRDH575
95 IRDH575_D00089_05_M_XXEN/01.2020
Technical data IRDH575
RF
100
≥ 0 kΩ
10
1
1 10 100 1000
Ce [µF]
IRDH575_D00089_05_M_XXEN/01.2020 96
Technical data IRDH575
Un [V]
1000 IRDH575B2
760 V
IRDH575B1
575 V
100
0,1 0,3 1 10 100
fn [Hz]
97 IRDH575_D00089_05_M_XXEN/01.2020
Technical data IRDH575
RF [kW]
10 000
1000
100
10
1
0 5 10 15 20 25
I [mA]
Ω
Ω
RF = Insulation fault in kΩ
I = Current output in mA
IRDH575_D00089_05_M_XXEN/01.2020 98
Technical data IRDH575
RF [kW]
10 000
1000
100
10
1
0 5 10 15 20 25
I [mA]
Ω
Ω
RF = Insulation fault in kΩ
I = Current output in mA
99 IRDH575_D00089_05_M_XXEN/01.2020
Technical data IRDH575
100
90
80
70
2 mA
60 5 mA
10 mA
50
40
30
20
10
0
24 48 110 230 400
Un [V]
250
200
2 mA
150 5 mA
10 mA
100
50
0
24 48 110 230 400 500 690
Un [V]
IRDH575_D00089_05_M_XXEN/01.2020 100
Technical data IRDH575
50
40
30
2 mA
5 mA
20 10 mA
10
0
24 48 110 230
Un [V]
101 IRDH575_D00089_05_M_XXEN/01.2020
Technical data IRDH575
30
AC
RF 25
3AC
(kW) 20
DC
15
10
5
0
24 48 110 230 U n (V)
Curve 1a:
Allowable response values in relation to the system voltage to be monitored
for a maximum system leakage capacitance Ce as shown by curve 2a
In order to start automatic insulation fault location, the resistance values to be
selected for ALARM 1 and ALARM 2 must be sufficiently low at a given nominal
voltage. Otherwise, the EDS test current is not sufficient to localise the insula-
tion fault. Determine the suitable values by means of the characteristic curves.
IRDH575_D00089_05_M_XXEN/01.2020 102
Technical data IRDH575
90
80
70
60
AC
RF 50
3AC
(kW) 40
DC
30
20
10
0
U n (V)
230 400 500 690 1000
Curve 1b:
Allowable response values in relation to the system voltage to be monitored
for a maximum system leakage capacitance Ce as shown in curve 2b.
103 IRDH575_D00089_05_M_XXEN/01.2020
Technical data IRDH575
Curve 2a:
Maximum allowable system leakage capacitance in relation to the system vol-
tage to be monitored. Up to this limiting value of the system leakage capaci-
tance, the EDS system has the sensitivity illustrated in curve 1a.
5
4,5
4
3,5
3 AC
C e 2,5 3AC
(µF) 2 DC
1,5
1
0,5
0
230 400 500 690 1000 U n (V)
Curve 2b:
Maximum allowable system leakage capacitance in relation to the system vol-
tage to be monitored. Up to this limiting value of the system leakage capaci-
tance, the EDS470 system has the sensitivity shown in curve 1b.
IRDH575_D00089_05_M_XXEN/01.2020 104
Technical data IRDH575
120
100
80
R F max
(%)
60
40
20
Curve 3:
A reduction of the response sensitivity at system leakage capacitances greater
than the maximum permissible value of Ce taken from the curves 2a and 2b.
The indication of the test current on the IRDH575 display in case of high sys-
tem leakage capacitance also changes.
When considering the curves, a point to be taken into account is that the sum
of the pre-capacitances upstream the measuring current transformer must
amount to at least 50 % of the total capacitance. Otherwise it may result in
wrong alarm messages.
A value of 20 000µFV/400 V = 50µF is taken for the system leakage capaci-
tance. Exceeding the limiting value may result in false trippings.
105 IRDH575_D00089_05_M_XXEN/01.2020
Technical data IRDH575
700
600
500
400
RF (k)
AC
DC
300
200
100
0
0 50 100 150 200 250 300 350
Un (V)
Curve 4:
Allowable response values in relation to the system voltage to be monitored
at a maximum system leakage capacitance Ce as shown by curve 5.
DC: set a test current of 1 or 2.5 mA.
AC: set a test current of 2.5 mA.
The EDS473 system is suitable for nominal voltages of AC 265 V and DC 308 V.
IRDH575_D00089_05_M_XXEN/01.2020 106
Technical data IRDH575
5
Ce (μF)
AC
4
DC
0
0 100 200 300 400
Un (V)
Curve 5:
Maximum allowable system leakage capacitance in relation to the system vol-
tage to be monitored.
DC: the test current is to be set to 1 or 2.5.
AC: the test current is to be set to 2.5 mA.
107 IRDH575_D00089_05_M_XXEN/01.2020
Technical data IRDH575
120
100
80
RF max [%]
60
40
20
0
0 0,5 1 1,5 2 2,5 3 3,5
x Ce max [P F]
Curve 6:
When the system leakage capacitances are greater than the maximum per-
missible value for Ce, as shown in curve 5, the response sensitivity decreases.
The indication of the test current on the IRDH575 display in case of high sys-
tem leakage capacitance also changes.
When considering the curves, a point to be taken into account is that the sum
of the pre-capacitances upstream of the individual measuring current trans-
former must amount to at least 50 % of the maximum total capacitance.
Otherwise, it may result in wrong alarm messages.
A value of 300 µFV/230 V = 1.3 µF is taken to be the maximum system leakage
capacitance value. When the limiting value is exceeded, false tripping may
occur.
IRDH575_D00089_05_M_XXEN/01.2020 108
Value of the respective number
109
Position of
numbers
0= 1= 2= 3= 4=
from the
left
1 K1: N/O operation Test K1: N/C operation Test K1: flashing function K1: N/O operation K1: N/C operation
Status number
2 K2: N/O operation Test K2: N/C operation Test K2: flashing function K2: N/O operation K2: N/C operation
3 no external coupling
4 Cemax 1 µF ** Cemax 10 µF ** Cemax 150 µF Cemax 500 µF
5
6 Self test every 24 hours Self test every hour no periodic self test
IRDH575_D00089_05_M_XXEN/01.2020
Technical data IRDH575
Technical data IRDH575
All dimensions in mm
Panel cut out 138 x 90 mm
IRDH575_D00089_05_M_XXEN/01.2020 110
Technical data IRDH575
DC 20…575 V DC 19.2…72 V
DC 20…575 V DC 77…286 V
DC 20…150 V DC 19.2…72 V
DC 20…150 V DC 77…286 V
DC 340…575 V DC 77…286 V
Device with ending "W" provide improved shock and vibration resistance. A
special varnish of the electronics provides higher resistance against mechani-
cal stress and moisture. This makes the devices suitable for use in ships, on rol-
ling stock and in seismic environment.
111 IRDH575_D00089_05_M_XXEN/01.2020
Technical data IRDH575
Transparent cover,
degree of protection 144 x 96 mm B98060007
IP65
Measuring
Type Dimensions Art. No.
range
IRDH575_D00089_05_M_XXEN/01.2020 112
Technical data IRDH575
113 IRDH575_D00089_05_M_XXEN/01.2020
INDEX
A - Allowable system leakage
Alarm LED 1 39 capacitance in relation to the system
Alarm LED 2 39 voltage 104
Alarm messages 85 - Reduction of the response sensitivity
Alarm relays, operating principle setting 51 in relation to Cemax 105
Automatic self test, repetition time 55 Characteristic curves, EDS473
Automatic self test, starting time 56 - Allowable response values insulation
fault in relation to nominal voltage
B 106
BMS bus, address ranges 88 - Allowable system leakage
BMS Master 82 capacitance in relation to the system
BMS protocol 82 voltage 107
BMS Slave 83 - Reduction of the response sensitivity
in relation to Cemax 108
C Characteristic curves, IRDH575
Changing the measuring principle 55 - Current output 0...20 mA 98
Characteristic curves, EDS46... /EDS49... - Current output 4...20 mA 99
- Allowable response values for 3 AC - Max. AC voltage between system and
systems 100 earth 97
- Allowable response values for 3AC - Response time in relation to system
systems 100 leakage capacitances 96
- Allowable response values for AC sys- Checking all BMS bus nodes 70
tems 100 Combination with EDS46... devices 86
- Allowable response values for DC sys- Commissioning flow chart IRDH575 33
tems 101 Commissioning of a BMS network 87
Characteristic curves, EDS470 Current output 0/4...20 mA 99
- Allowable response values insulation
fault in relation to nominal voltage
102
IRDH575_D00089_05_M_XXEN/01.2020 114
D alarm 2 (Relay/op.mode) 67
Dimension diagram enclosure 110 - Setting the response delay, T(on) 66
Display in the menu mode 41 - Setting the system coupling (DC/1
AC/3 AC) 64
E - Starting the EDS with IRDH575 or
EDS4... continuous EDS mode (Trigger) 63
- Common message 28 - To enable or disable the CT monito-
- Max. test current, setting 60 ring (CT monitor) 66
- Start and stop conditions, setting - EDS470/473
auto, on, off, pos, 1cycle 58 - CT Setup 73
- Type of the system, setting (DC/1AC/ - EDS monitor - indication of all de-
3AC) 60 tected insulation faults 70
EDS46.../49... - Elongation of the measuring time 74
- Adapting frequency converters to the - Memory behaviour of EDS4...-12,
system being monitored (inverter) setting 73
66 - On or off switching of the CT monito-
- Assigning an EDS Alarm to one or ring 73
both common relays (Alarm - Operating principle of the alarm re-
on/off) 67 lays of EDS47..., setting 73
- EDS test (test of all BMS bus nodes) - Reset 70
68 - Test of all BMS bus nodes 70
- Setting delay on response, T(off) 66 Essential functions, ISOMETER 17
- Setting response values (ResVal) 66 External coupling devices 55
- Setting the CT type (CT-W/WR) 66 External RESET button 32
- Setting the memory behaviour of an External TEST button 32
EDS. 63
- Setting the nominal frequency 64 F
- Setting the operating mode of the 12 Factory settings 89
channel-related alarm relays Fault messages, language setting 78
(Channel/Op.mode, only EDS490/ Flashing point 83
491) 67 Function 19
- Setting the operating mode of the Function input F1/F2 22
common alarm relays alarm1 and
115 IRDH575_D00089_05_M_XXEN/01.2020
H O
How to use this manual 8 Operating features and displays IRDH575
38
I Option "W" 17
INFO button 38
Insulation fault evaluator (EDS) 18 P
Insulation fault location 18 Parameter setting via Internet 79
Interconnected systems 21 Product description 18
ISO Monitor 75
ISOnet function R
- activate, deactivate 76 Real-time clock 20
- description 24 Relay K3 28
RESET button 19, 38
M Response values Alarm 1 and Alarm 2 set-
Measuring instruments 112 ting 50
Memory database 48 RS-485 interface 80
Menu RS-485 network
- COM SETUP 75 - correct arrangement 81
- EDS 460/490 63 - wrong arrangement 81
- EDS 470 70 RS-485, termination 32
- EDS SETUP 58
- HISTORY INFO 49 S
- ISO ADVANCED 55 Self test, ISOMETER 38
- ISO SETUP 50 Service 9
- LANGUAGE 78 Setting the BMS bus address of the IRDH575
- PASSWORD 77 75
- SERVICE 79 Setting the date 56
- structure 46 Setting the maximum test current 60
Monitor Setting the real-time clock 55
- EDS Function 70 Specify allowable response values
- of the insulation fault evaluator
EDS46.../EDS49... 100
- of the insulation fault evaluator
IRDH575_D00089_05_M_XXEN/01.2020 116
EDS470 102
- of the insulation fault evaluator
EDS473 106
- see characteristic curves 96
Standards 95
Status number 109
Support 9
System leakage capacity, adaptation 55
T
Technical data 91
Terminating resistor 80
TEST button 38
Test current 20, 61
Test of all bus nodes, EDS test 68
Topology RS-485 81
Training courses 10
W
Wiring 81
Wiring diagram 32
Work activities on electrical installations 13
workshops 10
117 IRDH575_D00089_05_M_XXEN/01.2020