0% found this document useful (0 votes)
309 views72 pages

Data Aire Series Air Cooled, Water/Glycol Cooled 6 Through 30 Ton Dual Circuits

Data Aire's first precision cooling system was developed by data processing engineers who sought optimum environmental conditions for early computers. Data Aire is meeting today's challenge of not only the computer room but also the ever expanding telecommunications industry where precision cooling is vital to our everyday communications.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
309 views72 pages

Data Aire Series Air Cooled, Water/Glycol Cooled 6 Through 30 Ton Dual Circuits

Data Aire's first precision cooling system was developed by data processing engineers who sought optimum environmental conditions for early computers. Data Aire is meeting today's challenge of not only the computer room but also the ever expanding telecommunications industry where precision cooling is vital to our everyday communications.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 72

R-410A

Data Aire Series Air Cooled, Water/Glycol Cooled 6 through 30 ton Dual Circuits R-410A

R-410A

Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aires rst precision cooling system was developed by data processing engineers who sought optimum environmental conditions for early computers. It was clear that people comfort air conditioning system were unable to meet the environmental requirements of computers and data processing equipment. Precision environmental control equipment with high sensible cooling ratios was a necessity. Problems with paper sticking , head crash, and static electricity were eliminated. Humidity uctuation were controlled saving possible electrical and mechanical failures and more importantly Downtime. Data Aires innovative response to the challenge of eliminating problems within the computer room environment was the start of wide use precision cooling. As in the past, Data Aire is meeting todays challenge of not only the computer room but also the ever expanding telecommunications industry where precision cooling is vital to our everyday communications. Telecommunication equipment requires a controlled environment with clean and properly distributed air. As in the computer room, the environment must be precisely controlled 24 hour a day, 365 days a year. Data Aire produces solutions. We have offered environmental control solutions to meet specic needs in the smallest of places and in areas of thousands of square feet. We are prepared to assist you, your in-house engineering department, consulting engineer, or construction department in dening the proper solutions and bringing them to a predened outcome. Data Aire is committed to being the supplier of choice for environmental process cooling with exibility, reliability, and expertise required to meet our customers needs. To be successful, it is essential to be creative and use our resources to their fullest capabilities. The Data Aire goal is to benet the employees, partners, and most of all our customers with honesty and integrity. Data Aire Delivers!

DATA AIRE DX SERIES - R410-A DIRECT EXPANSION UNITS AIR COOLED, WATER COOLED, GLYCOL COOLED
(Separate brochure for Chilled Water Cooled units.)

TABLE OF CONTENTS

Design Features .................................................................................................5 System Controls ................................................................................................8 Options ............................................................................................................10 Model Number Identication ..........................................................................13 Performance Data Air Cooled......................................................................................14 Water Cooled..................................................................................20 Glycol Cooled ................................................................................26 Energy Saver ..................................................................................32 Auxiliary Chilled Water .................................................................34 Dimensional and Component Drawings 6, 8, and 10 ton...............................................................................36 13 ton .............................................................................................40 16, 20, and 26 ton...........................................................................44 30 ton .............................................................................................48 Plenum and Floorstand ..................................................................52 Heat Exchangers ............................................................................53 Standard Condenser Electrical Data................................................................59 Dimensional and Weight Information .............................................................60 Guide Specications........................................................................................61

Data Aire, Inc. reserves the right to make design changes for the purpose of product improvement or to withdraw any design without notice.

PRECISION COOLING
Data Aire Series units offer precision environmental control that brings a standard of reliable performance to meet todays market demands. Data Aire systems are designed for data centers, telecommunication sites, or anywhere process cooling is required. Data Aire Series units are available in 6 through 30 nominal tons with upow or downow air distribution either in air cooled or water/glycol cooled models. Each unit is factory run tested and put through a vigorous quality control procedure.

COMFORT
Computer rooms and other environmentally controlled spaces require air which is clean and properly distributed, with precisely controlled temperature and humidity. Building or people comfort cooling systems are not designed to meet these demands. Data Aire Series units are designed to maintain temperature and humidity with properly distributed clean air required in environmentally controlled areas.

HIGH PERFORMANCE/LOW COST


Engineered for performance and reliability, each Data Aire Series unit comes with Data Aires commitment to excellence. This commitment began with Data Aires rst process cooling unit and has continued for more than 30 years of building the industrys nest environmental control equipment.

DATA AIRE DELIVERS


Standard ship cycle is 30 days from date of order. With an optional premium quick ship units can be expedited to ship in little as one week. All units are built to your specic order and specication. Call your nearest Data Aire representative for more information. 4

DESIGN FEATURES

FRAME/CABINET
Units are constructed with heliarc welded tubular steel frames. The tubular construction provides for maximum strength and ease of access. Side and front panels can be easily removed with quarter-turn fasteners allowing full access to all unit components. All panels include 1 inch thick, 11/2 pound density insulation for protection and sound attenuation.

FILTER SECTION
Units are provided with 4 inch deep, 30% efcient (based on ASHRAE Std. 52.1-1992), pleated lters. The lter section is accessible from the top or side on downow units and the right hand side on upow units.

REHEAT
Three stage electric reheat is standard. Lowwatt density, nned, tubular sheathed coils are constructed of stainless steel and provide ample capacity to maintain room dry bulb conditions during dehumidication. Low-watt density coils eliminate ionization associated with open air electric resistance heating.

COIL SECTION
Designed for draw through application, the computer selected dual circuited A-frame coil has an interwoven surface that increases unit efciency at low load conditions. Air is drawn through both circuits of the coil at low velocity providing effective surface exposure with minimum turbulence. Air bypass is provided to prevent saturated air from being introduced into the controlled space. The coil sits in a stainless steel drain pan.

HUMIDIFICATION
Data Aire Series units include an electric steam generator humidier with quick change disposable cylinders and auto-ush cycle. The steam generator humidier with its patented control system optimizes cylinder life and energy efciency by concentrating incoming water to a predetermined conductivity much higher than that of any entering water. The control system continuously monitors the conductivity in the cylinder through its electronics which allows water to be ushed as often as is necessary to maintain the capacity at this design conductivity. The high design conductivity results in a minimum ushing of heated water which saves energy. The humidier is designed to allow all units at any voltage to produce full rated steam output capacity at an optimum low water level based on this design conductivity.

FAN SECTION
The centrifugal, forward curved, double width, double inlet blower conguration is engineered for quiet reliable operation. The dual belt driven variable pitch drive section provides adjustable air ow capability to match the load requirements of the controlled space. The draw through design insures even air distribution across the coil, low internal cabinet pressure losses and static sealing of the lter section. Motors are mounted on an adjustable slide base and have internal overload protection.

REFRIGERATION CIRCUITS

Dual refrigeration circuits include high efciency hermetic scroll type compressors. Scroll compressors represent new yet proven compressor technology. Scroll compressors offer a combination of reliability, performance, and efciency. System noise is inherently quieter with scroll compressors. Scroll compressors offer: Simplicity - Fewer parts. Two components, a xed scroll and orbiting scroll, replace approximately 15 parts required to do the same work. Improved Starting Ability - With the scroll design the internal compression components always start unloaded even if the system pressures are not balanced. Since internal compressor pressures are always balanced at start-up, low voltage characteristics are excellent for scroll compressors. Energy Efciency - Scroll compressors are at least 10% more efcient than reciprocating type compressors. The suction and discharge processes of a scroll compressor are physically separated. This reduces heat transfer between the suction and discharge gas. In a piston type compressor the cylinder is exposed to both suction and discharge gas. This results in high heat transfer reducing the compressor efciency. Scroll compressor compression and discharge processes are very smooth. Gas is compressed in approximately 11/2 revolutions compared to less than 1/2 revolution for a piston. Scrolls require no valves. Piston compressors require both suction and discharge valves. No valves, no valve losses. Durability - Signicant design effort and system cost are required to protect piston compressors from slugging and debris. Scroll compressors are designed to be more tolerant of both liquid and debris. Reliability - Scrolls contain fewer moving parts resulting in greater reliability. Proven performance means fewer maintenance calls for eld personnel. Lower Sound - Systems properly designed with scroll compressors will be inherently quieter. On average, the compressor is up to 5 decibels quieter. (Sound characteristics of a scroll compressor are different than that of a reciprocating compressor. These do not effect system performance or reliability) These durable, heavy duty compressors have no gaskets or seals, eliminating the possibility of refrigerant or oil leaking into the controlled space or environment. Each refrigeration circuit includes built-in compressor overload protection, crankcase heater, lter drier, sight glass, adjustable expansion valve with external equalizer, low pressure override timer (air cooled units), manual reset high pressure control, and anti-short cycle timer. Water/glycol cooled units include counterow condensers sized to provide the required capacity for heat rejection with minimum water/glycol ow and total pressure drop. Head pressure regulating valves control

REFRIGERATION CIRCUITS, continued

the condensing temperature and maintain required capacity at various water/glycol ow rates and temperatures. Air Cooled with Remote Outdoor Air Cooled Condenser A wide range of outdoor condensers are available with vertical air discharge. Condensers manufactured by Data Aire are sized to meet the required heat rejection and ambient conditions. The industrial duty condenser design includes an aluminum housing, aluminum nned copper tube coils, powder coated fan guards, energy efcient, thermally protected direct drive motors, and variable speed fan control on the lead motor for proper control down to -20 F. Additional fan motors are controlled with ambient thermostats. Air Cooled with Indoor Condenser A wide range of oor mounted indoor condensers with horizontal intake and discharge are available for applications where an outdoor condenser cannot be used. Finished to match the indoor evaporator section, the condenser includes a centrifugal, forward curved, double width, double inlet blower engineered for quiet and reliable operation. The belt driven variable pitch drive section provides adjustable airow. The motor has internal overload protection and is mounted on an adjustable slide base. Indoor condensers are provided with a factory mounted and piped receiver. The receiver has a head pressure control valve to maintain ooded condenser control. Air Cooled with Remote Outdoor Condensing Unit When compressors are required to be out of the controlled space, Data Aire Series units are available with a remote outdoor condensing unit. The condensing unit includes the compressors with built-in overload protection, crankcase heater, lter drier, sight glass, and condenser coil. The

condenser coil is constructed with copper tubes and aluminum ns. The housing is aluminum with vertical air discharge. The condenser is variable speed fan control on the lead motor for head pressure control down to -20 F. Additional fan motors are controlled by ambient fan thermostats. Water/Glycol Cooled with Remote Outdoor Fluid Cooler Remote outdoor dry coolers (uid coolers) are available in a variety of sizes. Each dry cooler includes an aluminum housing, aluminum nned copper tube coil, powder coated fan guards, surge tank, pump contactor, and energy efcient, thermally protected direct drive motors. Dry coolers with multiple motors have cycling control. Water/Glycol Cooled with Indoor Fluid Cooler When required a wide range of oor mounted indoor uid coolers (dry coolers) are available. The air intake and discharge are horizontal. Units are nished to match the indoor unit. The centrifugal, forward curved, double width, double inlet blower is engineered for quiet reliable operation. The belt driven variable pitch drive section provides adjustable airow. The fan motor has internal overload protection and is mounted on an adjustable slide base. The unit control panel includes a pump contactor (units can be ordered with a factory mounted pump).

SYSTEM CONTROL

DATA ALARM PROCESSOR-III The Data Alarm Processor-III (DAP III) offers the denitive answer for precision environmental control. The DAP-III control system not only controls and monitors temperature, humidity, airow and cleanliness, it provides component run times, alarm history and an automatic self-test of the microprocessor on system start-up. All messages are presented in a clear vernacular format and sequentially displayed on a backlit, liquid crystal display (LCD). OPERATION Highly reliable, at, sealed switches with tactile feedback allow unit on/off operation, menu selection for programming, operational information, diagnostics, and historical data. Multilevel password prevents unauthorized access. Alarm conditions are enunciated by an audible alarm. The alarm silence button will quiet the audible alarm but the display will continue to indicate the alarm condition until the problem is corrected. STANDARD FEATURES Two row, eight character, backlit LCD screen Programmed settings saved in ash memory Smooth keyboard type buttons Real time clock with back-up battery Forward and backward menu access Data base of unit and room conditions Factory calibrated humidity sensor Factory calibrated temperature sensor Power ON status contact Stand alone panel Microprocessor based Automatic self-test diagnostics USB port for software upgrades All settings from face of panel Multi-level password access Battery backup for historical data Menus factory programmed

OPERATIONAL FEATURES Automatic or manual restart Automatic reheat element rotation Adjustable mode and stage response time Chilled water energy saver coil ush cycle Compressor short cycle control on DX units Start time delay Automatic compressor rotation Hot water coil ush cycle Humidity anticipation Sequential load activation Dehumidication mode lockout

OPTIONAL FEATURES Energy saver (glycol) or auxiliary chilled water operation Periodical DX activation on Energy Saver system Supplemental compressor in Energy Saver mode Chilled water temperature sensor Four analog inputs (4-20 mA or 0-10 VDC signal) Two analog outputs (0-10 VDC signal) Underoor water detection cable Fan speed control for optional plug fan or VFD Humidier auto-ush cycle Three additional remote alarms Discharge air temperature sensor Modulating humidier control RS-485 Multi-drop network card Ethernet network card LONTALK network card

DIAGNOSTIC and SERVICE FEATURES Alarms displayed in order of occurrence Manual diagnostic program Programmable delays for optional alarms Adjustable alarm limits Programmable remote alarm contact Select alarms optional disabled Four programmable optional alarm inputs Selectable audio alarm tone Manual override for blower, cool 1/2, reheat 1, humidication and water valve 8

SYSTEM CONTROL, continued

PROTECTIVE and SAFETY FEATURES Metal shell enclosure with sealed front control panel Opto-coupler signal inputs Heavy ground planes and power foils Switching power supply Watch dog timer Protected 24VAC power input Isolation transformer Fuses on all control boards

CONDITIONS and DATA DISPLAYED Current percent of capacity utilized Current temperature Current humidity Current discharge air temperature* Current chilled water temperature* Temperature setpoint Humidity setpoint Unit or network identication number* Zone number*

Cooling stages Reheat stages Chilled water ow percentage

FUNCTIONS DISPLAYED Energy Saver* Dehumidication Humidication ALARMS

High temperature warning High humidity warning High pressure/internal overload compressor 1 High pressure/internal overload compressor 2 Under oor water detection Firestat tripped, unit shutdown Custom message (programmed by factory)* Chilled water temperature sensor problem* Low voltage warning Compressor short-cycle Humidity sensor problem Local alarm* Check humidier cylinder* No water ow* Standby pump on* HISTORICAL DATA Equipment run times High and low temperature in last 24 hours Average percent of capacity last hour

Low temperature warning Low humidity warning Low pressure compressor 1 Low pressure compressor 2 No air ow Dirty lter alarm Humidity failure Manual override Power failure restart Temperature sensor problem Maintenance required Discharge air sensor problem* Fan motor overload* Smoke detector, unit shutdown* Person to contact on alarm*

Alarm history for last ten alarms High and low humidity in last 24 hours

PROGRAMMABLE SETTINGS and SELECTIONS The user friendly Menus and Select buttons used with the 10 menu groups permit step-by-step programming of many functions. The DAP III Operation Manual provides a complete and detailed guide to the settings and selections. Refer to it for specic ranges and settings.
* - May require additional components and/or sensors.

OPTIONS

Energy Saver Coil - The Data Aire Energy Saver Coil is built into the system to provide total required capacity. Whenever the incoming water/glycol temperature is below 45o F/7.2o C, Energy Saver cooling is available. Energy Saver mode operates in the following range: return air setpoint plus deadband plus 2 degrees. The Energy Saver will operate providing there is a need for cooling. The valve will open at setpoint plus deadband. The valve will modulate as long as the space is between setpoint plus deadband plus 2 degrees. If the temperature falls below the deadband minus setpoint, the valve will close and the space is considered satised. While still in Energy Saver with the valve modulating, if the temperature goes beyond setpoint plus 2 degrees, the Energy Saver valve will close and DX cooling will begin. The Energy Saver coil includes the next size motor, 3-way pressure control valve on the condenser water circuit, and 3-way valve on the economy coil. Common piping for coil and condensers is provided. Energy Saver/Compressor Supplement - Units with Energy Saver option can be provided with compressor supplement if the Energy Saver is not sufcient as a stand alone system. When the incoming water/glycol temperature is below the setpoint of the water changeover thermostat, the Energy Saver is enabled (even if there is no call for cooling). Upon a call for cooling (setpoint plus deadband), the valve will open proportionally - 10% for each 0.1o above setpoint plus deadband. The compressor will come on at setpoint plus deadband plus 1o (the valve is 100% open at this point). The compressor will go off at setpoint plus deadband plus 0.7o. The valve will close proportionally - 10% for each 0.1o below setpoint plus deadband. An air discharge sensor is factory installed.

Auxiliary Chilled Water Coil - Where an existing chilled water loop is available, units can be tted with an auxiliary chilled water coil. Units will operate using the chilled water for cooling. Upon a loss of water ow or an increase in room temperature the system will bring on compressor (DX) cooling. The Auxiliary Chilled Water coil includes the next size motor. Separate piping is provided for the chilled water coil and refrigeration connections. Auxiliary Chilled Water Coil/Compressor Supplement - The Auxiliary Chilled Water Coil can be provided with compressor supplement for extended savings by allowing the compressor to supplement operation as needed when the chilled water is not sufcient on a stand alone basis. An air discharge sensor is factory installed. (See Energy Saver/Compressor Supplement for details)

Remote Temperature and Humidity Sensors - Temperature and humidity sensors may be ordered for remote wall mounting. Sensors are provided in a wall mount plastic case for remote sensing of temperature and humidity. 25 feet of shielded cable is provided for eld wiring. Smoke Detector - A unit mounted smoke detector will shut down the unit if smoke is sensed. The unit mounted microprocessor control will sound an alarm and display a SMOKE DETECTED message. The smoke detector is mounted in the return air stream and is provided with auxiliary contacts. Unit Mounted Disconnect - A unit mounted nonautomatic disconnect switch is installed in the high voltage electrical section. The operating mechanism (handle) protrudes through the decorative exterior panel. The operating mechanism prevents access to the high voltage electrical components by not allowing entry until switched to the OFF position.

10

OPTIONS, continued

Tandem Scroll Compressors - Units may be ordered with tandem scroll compressors when four stage compressor control is required. Units remain dual circuited. Tandem scrolls offer the inherent advantages of scroll technology: higher efciency, increased reliability, lower sound, and excellent liquid handling. Scroll tandems offer two steps of modulation so that one or both compressors (per circuit) can run depending upon the load of the system, resulting in part-load efciency equal to full load efciency. Two-step modulation is possible because of a carefully designed tubing conguration and the scrolls superior ability to tolerate liquid. The built-in discharge check valve, present in all scroll compressors, effectively prevents liquid migration in the off compressor. Oil migration is controlled with two specially designed oil and gas equalization lines. Adding this option to 30ton unit will increase cabinet size to 144. (See Supplement TS1-99: Tandem Scroll Technical Performance) Semi-Hermetic Compressors - Cast iron semihermetic compressors are available on all Data Aire Series units. Semi-hermetic compressors are mounted on vibration isolators and have builtin overload protection. The compressors also include oil sight glass, reversible oil pump for forced feed lubrication, and suction line strainer. Units with semi-hermetic compressor option also include solenoid valves and mufers. Maximum rpm is 1750. Four Step Control (Cylinder Unloading) - Units with semi-hermetic compressors may be ordered with four step control for periods of low load conditions. Cylinder unloaders on one head of each compressor reduces compressor cooling capacity. Four steps of cooling are available to meet changing room conditions. Compressor Sequence: Step 1 Lead compressor starts with unloader valve activated Step 2 Lead compressor running at full load Step 3 Lag compressor starts with unloader valve activated Step 3 Lag compressor running at full load 11

Hot Gas Bypass - Hot gas bypass is available for changing load conditions. The hot gas bypass valve is installed between the compressor discharge line and the leaving side of the expansion valve through a side outlet distributor. The system with the evaporator under full load will maintain pressure on the leaving side of the hot gas bypass valve to keep the valve port closed. Should the load on the evaporator decrease to the point where the coil is below the desired setting, the pressure on the discharge of the hot gas bypass will put pressure on the diaphragm overcoming the spring pressure of the seat and allowing some hot gas to mix with the normal liquid discharge of the expansion valve raising the evaporator pressure. This reduces the cooling capacity of the unit to match the load. The hot gas bypass valve can be adjusted to ne tune the unit to room conditions. Humidier Modulating Control - Modulating control may be added to the units steam generator humidier. Modulating control will allow the humidier to match its output to the signal from the humidity control. A self-regulating auto ush is included. Hot Water Reheat - Where hot water is available, a water coil for reheat is offered. The coil is designed for 150 psi maximum water pressure and includes a 2-way valve (a 3-way is also available). Units with the hot water reheat do not include electric reheat. Supplemental reheat may be ordered. Hot Gas Reheat - The units hot gas discharge may be used for reheat and maximum system efciency. Supplemental electric reheat may be ordered in addition to the hot gas reheat. 3-Way Water Regulating Valve - 3-way water regulating valves are available on water and glycol cooled units to replace the standard 2-way valve. The 3-way valve controls the water/glycol ow rate to maintain the required capacity under varying conditions. This option is recommended on units with dual pump applications.

OPTIONS, continued

Upow Air Discharge Plenum - Upow air discharge plenums are fully insulated with front discharge grille. Side grilles for both or one side are available. Plenums are 18 high and painted to match the units color. Floorstands - Floorstands are adjustable ( 2 inches) and may be ordered with factory installed turning vane or with seismic construction. High Efciency Filters - Standard lters are rated at 30% (per ASHRAE Std. 52-76). Higher efciency lters are available (consult factory regarding efciency percentage and unit static pressures). Condensate Pumps - Condensate pumps may be ordered factory installed or shipped loose for eld installation. Condensate pumps are complete with sump, motor, and automatic control. Pumps shipped loose are available in 115, 230, or 460 volts. Pump Ratings: 230 volt: with check valve - 40 GPH at 20 feet without check valve - 130 GPH at 40 feet 460 volt: with check valve - 50 GPH at 20 feet without check valve - 270 GPH at 40 feet Pump Package - Centrifugal pump packages are available to circulate water or water/glycol solutions. Pumps are available in various horsepower and voltages. Both 3400 and 1750 rpm pumps are available as an option. On dual pump applicatons it is recommended that a 3-way water regulating valve be used in lieu of the standard 2-way valve. Pump Enclosure - Pump enclosures are available for either single or dual pump applications. Pump enclosures are vented and weather resistant. When ordered with pumps, the pumps are factory mounted in the enclosure ready for eld piping and wiring. 12

Integral Pump Enclosures - Pumps may be factory mounted as an integral part of the dry cooler. A 30 extension is added to the dry cooler. Pumps are pre-piped and wired and includes shut-off valves. A ow switch is included with dual pumps. Pump Auto-Changeover - Dual pump packages may be provided with a pump auto-changeover control and NEMA 4 ow switch (eld installed). The pump auto-changeover control is factory wired and mounted in the dry cooler control box. The pump auto-changeover control provides automatic pump changeover in the event of a pump failure. Upon pump changeover, an audible alarm will sound at the indoor unit and a message (STANDBY PUMP ON) will be displayed on the indoor unit microprocessor display. Extended Compressor Warranty - Extended compressor warranties are available from Data Aire. Contact your local representative for one that best suites your needs.

MODEL NUMBER IDENTIFICATION

13

AIR COOLED: Performance data at STANDARD airow

MODEL NUMBER CAPACITY in Btu/hr - Gross 80o DB/67o WB 50% RH 75o DB/62.5o WB 50% RH 75o DB/61o WB 45% RH 72o DB/60o WB 50% RH 72o DB/58.6o WB 45% RH Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible

DAAD/U-06 DAAD/U-08 DAAD/U-10 DAAD/U-13 DAAD/U-16 DAAD/U-20 DAAD/U-26 DAAD/U-30

76,800 58,300 71,600 56,300 69,500 60,200 68,400 55,100 66,900 58,600

108,600 84,900 100,500 81,600 97,100 87,200 95,700 79,700 93,000 84,600

128,400 106,400 119,300 102,400 115,800 109,600 113,900 99,900 110,600 106,300

165,600 126,600 153,500 121,800 149,300 130,300 145,900 119,000 142,000 126,100

214,900 160,300 199,700 154,700 193,800 165,000 190,600 151,400 185,400 160,200

266,500 204,900 246,800 197,200 240,400 211,100 235,000 192,500 229,700 204,700

326,900 243,400 303,700 235,100 294,300 250,400 289,800 230,100 283,300 244,100

388,200 301,700 360,600 290,700 350,100 310,900 344,000 284,100 334,400 301,400

BLOWER SECTION Airow - CFM Standard Motor - horsepower External static pressure (E.S.P.) - inches of W.G. Number of motors/fans Maximum E.S.P. (Standard motor) Maximum E.S.P. (Next Size motor) Next size motor horsepower COMPRESSORS Type: Hermetic scroll Semi-Hermetic Number Refrigerant type EVAPORATOR COIL Face area - sq. ft. Rows of coils Face velocity - FPM REHEAT SECTION Electric kW Capacity - Btu/hr Hot gas Capacity - Btu/hr Steam Capacity - Btu/hr Standard 15 51,225 Optional 26,000 Optional 105,500 60,000 Optional 70,000 34,300 Standard 15 51,225 Optional 38,000 Optional 115,000 65,000 Optional 81,000 44,800 Standard 15 51,225 Optional 42,200 Optional 121,000 69,000 Optional 86,000 47,500 Standard 15 51,225 Optional 48,000 Optional 126,000 72,000 Optional 90,000 49,400 Standard 22.5 76,835 Optional 64,000 Optional 90,000 108,000 Optional 130,000 74,200 Standard 22.5 76,835 Optional 81,000 Optional 210,000 120,000 Optional 145,000 82,000 Standard 22.5 76,835 Optional 101,000 Optional 230,000 130,000 Optional 160,000 90,700 Standard 30 102,450 Optional 126,000 N/A N/A N/A N/A N/A N/A 12.2 2 221 12.2 3 295 12.2 4 369 14.5 5 331 24.4 3 262 24.4 4 328 24.4 5 369 32.5 4 369 Downow Upow Downow Upow 2,700 2 0.5 1/1 0.8 0.7 0.9 0.9 3 3,600 2 0.5 1/1 1.0 0.9 1.5 1.5 3 4,500 3 0.5 1/1 1.2 1.0 1.5 1.0 5 4,800 3 0.5 1/1 0.7 0.6 1.5 1.5 5 6,400 3 0.5 1/2 1.0 0.9 1.4 1.3 5 8,000 5 0.5 1/2 1.2 1.1 1.5 1.5 7.5 9,000 7.5 0.5 1/2 1.5 1.5 1.5 1.5 10 12,000 3 0.5 3/3 1.5 1.5 1.5 1.5 5

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Downow Upow

Hot water Capacity - Btu/hr

Downow Upow

R-410A

14

AIR COOLED: Performance data at STANDARD airow

MODEL NUMBER HUMIDIFIER SECTION Steam generator Capacity lbs/hr (Adjustable) kW Steam grid Capacity lbs/hr at 15 psi

DAAD/U-06 DAAD/U-08 DAAD/U-10 DAAD/U-13 DAAD/U-16 DAAD/U-20

DAAD/U-26 DAAD/U-30

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

FILTER SECTION* Quantity /size Downow

(4 inch thick, 30% efcient, based on ASHRAE Std. 52-76) 3/20x25 2/20x25 3/20x25 2/20x25 3/20x25 2/20x25 2/20x25 2/16x25 3/20x25 3/20x25 2/16x25 2/20x25 2/16x25 3/20x25 2/16x25 2/20x25 2/16x25 3/20x25 2/16x25 2/20x25 2/16x25 3/20x25 4/16x25 2/20x25 4/16x25

Upow

CONNECTION SIZES Liquid line - O.D. Copper (2 per unit) 1/2 1/2 1/2 5/8 5/8 Hot gas line - O.D. Copper (2 per unit) 1/2 5/8 5/8 3/4 3/4 Suction line* - O.D. Copper (2 per unit) 7/8 7/8 1 1/8 1 1/8 1 3/8 Condensate drain 3/4 3/4 3/4 3/4 3/4 Humidier supply 1/4 1/4 1/4 1/4 1/4 NOTE: Refer to Operation and Maintenance manual for recommended pipe sizing between unit and condenser. 5/8 3/4 1 3/8 3/4 1/4 7/8 7/8 1 3/8 3/4 1/4 7/8 7/8 1 3/8 3/4 1/4

ELECTRICAL SECTION

Standard Motor

Electrical data based on STANDARD unit: electric reheat - YES, steam generator - YES and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 61/75/80 28/34/35 22/27/30 70/81/90 35/41/45 25/29/30 78/90/100 36/42/45 29/33/35 87/100/110 101/124/125 110/134/150 43/49/50 49/60/70 53/64/70 33/38/45 38/47/50 41/50/60 151/171/200 164/199/225 69/78/90 77/93/110 59/66/80 64/77/90

Electrical data based on: electric reheat - NO, steam generator - YES and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 61/71/80 28/33/35 22/25/30 70/81/90 35/41/45 25/29/30 78/90/100 36/42/45 29/33/35 87/100/110 43/49/50 33/38/45 97/112/125 110/125/150 50/58/70 55/63/70 38/44/50 41/47/50 151/171/200 165/186/225 69/78/90 79/89/110 59/66/80 68/76/90

Electrical data based on: electric reheat - YES, steam generator - NO and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 61/75/80 28/34/35 22/27/30 65/80/90 31/39/40 24/29/30 71/86/90 33/40/45 26/32/35 75/92/100 101/124/125 110/134/150 36/44/50 49/60/70 53/64/70 28/34/40 38/47/50 41/50/60 134/162/175 164/199/225 62/74/90 77/93/110 51/62/70 64/77/90

Electrical data based on: electric reheat - NO, steam generator - NO and STANDARD MOTOR. 208-230/3/60 FLA/MCA/MOP 32/36/45 41/46/60 49/55/70 58/65/90 460/3/60 FLA/MCA/MOP 15/17/20 22/25/30 23/26/35 30/33/45 575/3/60 FLA/MCA/MOP 11/12/15 15/16/20 19/20/25 23/25/30 * Only applicable when compressors are in the condensing unit rather than evaporator section. FLA - Full load amps MCA - Minimum circuit ampacity (wire sizing amps) MOP - Maximum rating of the overcurrent protective device * Units with Auxiliary Chilled Water Coils have different lter quantities as those listed in this section. Refer to dimensional data sheets. 69/76/100 38/42/50 28/31/40 81/90/110 42/47/60 31/34/45 123/135/175 137/151/200 56/62/80 66/73/100 48/53/70 57/63/80

15

R-410A

AIR COOLED: Performance data at STANDARD airow

MODEL NUMBER ELECTRICAL SECTION

DAAD/U-06 DAAD/U-08 DAAD/U-10 DAAD/U-13 DAAD/U-16 DAAD/U-20 DAAD/U-26 DAAD/U-30 Next Size Motor

Electrical data based on: electric reheat - YES, steam generator humidier - YES and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/77/80 29/35/40 23/28/30 72/83/90 36/42/45 26/30/35 84/96/110 39/44/50 31/35/40 93/106/110 107/130/150 116/140/150 161/181/225 183/218/253 45/51/60 52/63/70 56/68/70 73/82/100 84/101/110 35/40/45 40/49/50 44/53/60 60/68/80 70/83/90

Electrical data based on: electric reheat - NO, steam generator humidier - YES and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/73/80 29/34/35 22/26/30 72/83/90 36/42/45 26/30/35 84/96/110 39/44/50 31/35/40 93/106/110 103/118/125 115/130/150 161/181/225 184/205/253 45/51/60 53/60/70 59/66/80 73/82/100 86/96/110 35/40/45 40/46/50 45/50/60 60/68/80 74/82/100

Electrical data based on: electric reheat - YES, steam generator humidier - NO and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/77/80 29/35/40 23/28/30 68/83/90 33/40/45 25/30/35 77/92/100 35/42/45 28/34/35 81/98/110 107/130/150 116/140/150 144/172/200 183/218/253 38/46/50 52/63/70 56/68/70 65/78/90 84/101/110 30/36/40 40/49/50 44/53/60 53/63/70 70/83/90

Electrical data based on: electric reheat - NO, steam generator humidier - NO and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA - full load amps FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 35/38/50 16/18/20 12/13/15 44/48/60 23/26/35 16/17/20 56/61/80 26/28/35 21/22/30 65/71/90 32/35/45 25/27/35 75/82/110 40/44/60 30/33/45 87/95/125 133/145/175 155/169/225 46/50/60 60/66/80 74/80/100 34/37/50 50/55/70 63/69/90

MCA - Minimum circuit amps (wire size amps)

MOP - Maximum rating of the overcurrent protective device

COMPRESSOR 208-230/3/60 460/3/60 575/3/60

FLA -full load amps 13.1 6.1 4.4 17.6 9.6 6.1 20.5 9.6 7.6 25.0 12.8 9.6 30.1 16.7 12.2 33.3 17.9 12.8 51.3 23.1 19.9 55.8 26.9 23.7

CONDENSER

Remote air cooled outdoor

Standard selection at 95 F ambient at sea level Evaporative model DAAD/U-06 DAAD/U-08 DAAD/U-10 DAAD/U-13 DAAD/U-16 DAAD/U-20 DAAD/U-26 DAAD/U-30 Condenser model DARC-06 DARC-09 DARC-11 DARC-15 DARC-17 DARC-21 DARC-28 DARC-30 Selection at 100 F ambient at sea level Evaporative model Condenser model

DAAD/U-06 DAAD/U-08 DAAD/U-10 DAAD/U-13 DAAD/U-16 DAAD/U-20 DAAD/U-26 DAAD/U-30 DARC-07 DARC-11 DARC-15 DARC-17 DARC-21 DARC-24 DARC-30 DARC-40

Selection at 105 F ambient at sea level Evaporative model DAAD/U-06 DAAD/U-08 DAAD/U-10 DAAD/U-13 DAAD/U-16 DAAD/U-20 DAAD/U-26 DAAD/U-30 Condenser model DARC-11 DARC-15 DARC-15 DARC-21 DARC-24 DARC-30 DARC-40 DARC-50 (Note: Refer to pages 57 and 61 for electrical data on remote air cooled condensers.)

* * * The following section has no reference to column headings * * *


EVAPORATOR FAN MOTOR Horsepower 208-230/3/60 460/3/60 575/3/60 1.0 3.6 1.8 1.4 FLA - full load amps 1.5 4.8 2.4 2.0 2.0 6.2 3.1 2.5 3.0 9.0 4.4 3.3 5.0 14.6 6.6 5.3 7.5 23.0 11.0 8.6 10.0 29.0 14.0 10.0

R-410A

16

AIR COOLED: Performance data at OPTIONAL airow

MODEL NUMBER CAPACITY in Btu/hr - Gross 80 F/67 WB 50% RH 75 DB/62.5 WB 50% RH 75 DB/61 WB 45% RH 72 DB/60 WB 50% RH 72 DB/58.6 WB 45% RH Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible

DAAD/U-06

DAAD/U-08 DAAD/U-10 DAAD/U-13 DAAD/U-16 DAAD/U-20 DAAD/U-26 DAAD/U-30

79,900 65,000 74,200 62,500 71,900 67,100 70,800 61,000 68,800 64,900

111,700 94,900 103900 91,100 100,600 97,900 99,200 88,900 96,300 94,700

132,500 119,700 122,800 114,900 118,800 118,600 117,000 112,000 113,300 112,700

169,500 138,100 157,300 132,700 152,400 142,200 150,000 129,500 146,000 137,800

222,900 180,800 207,200 173,900 201,300 186,600 197,700 169,700 194,000 181,300

271,700 218,900 251,800 210,300 245,600 226,000 239,800 205,100 234,500 218,600

333,200 258,200 309,800 248,900 300,400 266,000 295,700 243,400 289,100 258,700

397,900 329,300 369,300 316,300 357,900 339,400 352,200 308,500 343,800 329,000

BLOWER SECTION Airow - CFM Standard motor - horsepower External static pressure (E.S.P.) - inches of W.G. Number of motors/fans Maximum E.S.P. (Standard Motor) Maximum E.S.P. (Next Size Motor) Next size motor - horsepower Downow Upow Downow Upow 3,300 3 0.5 1/1 0.9 0.7 1.5 1.5 5 4,400 3 0.5 1/1 1.2 0.9 1.5 1.5 5 5,500 5 0.5 1/1 1.2 1.0 1.2 0.9 7.5 5,600 5 0.5 1/1 1.1 0.6 1.1 1.0 7.5 8,000 5 0.5 1/2 1.2 0.9 1.5 1.5 7.5 9,000 7.5 0.5 1/2 1.5 1.1 1.5 1.5 10 10,000 7.5 0.5 1/2 1.0 1.6 1.5 1.5 10 14,000 3 0.5 3/3 0.6 0.5 1.5 1.5 5

COMPRESSORS Type: Hermetic scroll Semi-hermetic Number Refrigerant type

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

EVAPORATOR COIL Face area - sq ft Rows of coils Face velocity - fpm . 12.2 2 271 12.2 3 361 12.2 4 451 14.5 5 386 24.4 3 328 24.4 4 369 24.4 5 410 32.5 4 431

REHEAT SECTION Electric kW Capacity - Btu/hr Hot gas Capacity - Btu/hr Steam Capacity - Btu/hr Hot water Capacity - Btu/hr Downow Upow Downow Upow Standard 15 51,225 Optional 26,000 Optional 105,500 60,000 Optional 70,000 34,300 Standard 15 51,225 Optional 38,000 Optional 115,000 65,000 Optional 81,000 44,800 Standard 15 51,225 Optional 42,200 Optional 121,000 69,000 Optional 86,000 47,500 Standard 15 51,225 Optional 48,000 Optional 126,000 72,000 Optional 90,000 49,400 Standard 22.5 76,835 Optional 64,000 Optional 190,000 108,000 Optional 130,000 74,200 Standard 22.5 76,835 Optional 81,000 Optional 210,000 120,000 Optional 145,000 82,000 Standard 22.5 76,835 Optional 101,000 Optional 230,000 130,000 Optional 160,000 90,700 Standard 30 102,450 Optional 126,000 N/A N/A N/A N/A N/A N/A

17

R-410A

AIR COOLED: Performance data at OPTIONAL airow

MODEL NUMBER HUMIDIFIER SECTION Steam generator Capacity - lb/hr (Adjustable) kW Steam grid Capacity - lb/hr at 15 psi

DAAD/U-06 DAAD/U-08 DAAD/U-10 DAAD/U-13 DAAD/U-16 DAAD/U-20 DAAD/U-26 DAAD/U-30

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

FILTER SECTION Quantity/Size Downow

(4 inch thick, 30% efcient, based on ASHRAE Std. 52-76) 3/20x25 2/20x25 3/20x25 2/20x25 3/20x25 2/20x25 2/20x25 2/16x25 3/20x25 3/20x25 2/16x25 2/20x25 2/16x25 3/20x25 2/16x25 2/20x25 2/16x25 3/20x25 2/16x25 2/20x25 2/16x25 3/20x25 4/16x25 2/20x25 4/16x25

Upow

CONNECTION SIZES Liquid line - O.D. Copper (2 per unit) 1/2 1/2 1/2 5/8 5/8 Hot gas line - O.D. Copper (2 per unit) 1/2 5/8 5/8 3/4 3/4 Suction line* - O.D. Copper (2 per unit) 7/8 7/8 1 1/8 1 1/8 1 3/8 Condensate drain 3/4 3/4 3/4 3/4 3/4 Humidier supply 1/4 1/4 1/4 1/4 1/4 (Note: Refer to Operation and Maintenance manual for recommended pipe sizing between unit and condenser.) 5/8 3/4 1 3/8 3/4 1/4 7/8 7/8 1 3/8 3/4 1/4 7/8 7/8 1 3/8 3/4 1/4

ELECTRICAL SECTION

Standard Motor

Electrical data based on STANDARD unit: electric reheat - YES, steam generator humidier - YES, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/77/80 29/35/40 23/28/30 72/83/90 36/42/45 26/30/35 84/96/110 39/44/50 31/35/40 93/106/110 107/130/150 116/140/150 151/171/200 164/199/225 45/51/60 52/63/70 56/68/70 69/78/90 77/93/110 35/40/45 40/49/50 44/53/60 59/66/80 64/77/90

Electrical data based on: electrical reheat -NO, steam generator humidier - YES, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/73/80 29/34/35 22/26/30 72/83/90 36/42/45 26/30/35 84/96/110 39/44/50 31/35/40 93/106/110 103/118/125 115/130/150 151/171/200 165/186/225 45/51/60 53/60/70 59/66/80 69/78/90 79/89/110 35/40/45 40/46/50 45/50/60 59/66/80 68/76/90

Electrical data based on: electrical reheat -YES, steam generator humidier - NO, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/77/80 29/35/40 23/28/30 68/83/90 33/40/45 25/30/35 77/92/100 35/42/45 28/34/35 81/98/110 107/130/150 116/140/150 134/162/175 164/199/225 38/46/50 52/63/70 56/68/70 62/74/90 77/93/110 30/36/40 40/49/50 44/53/60 51/62/70 64/77/90

Electrical data based on: electrical reheat -NO, steam generator humidier - NO, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 35/38/50 16/18/20 12/13/15 44/48/60 23/26/35 16/17/20 56/61/80 26/28/35 21/22/30 65/71/90 32/35/45 25/27/35 75/82/110 40/44/60 30/33/45 87/95/125 123/135/175 137/151/200 46/50/60 56/62/80 66/73/100 34/37/50 48/53/70 57/63/80

* Only applicable when compressors are in the condensing unit rather than the evaporator section. FLA - Full load amps MCA - Minimum circuit amps (wire sizing amps) MOP - Maximum rating of the overcurrent protective device

R-410A

18

AIR COOLED: Performance data at OPTIONAL airow

MODEL NUMBER ELECTRICAL SECTION

DAAD/U-06 DAAD/U-08 DAAD/U-10 DAAD/U-13 DAAD/U-16 DAAD/U-20 DAAD/U-26 DAAD/U-30 Next Size Motor

Electrical data based on: electric reheat - YES, steam generator humidier - YES, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 69/83/90 32/38/40 25/30/35 78/90/100 39/44/50 28/32/35 92/105/110 101/115/125 116/139/150 125/149/150 151/171/200 164/199/225 43/49/50 49/56/60 56/67/70 60/72/80 69/78/90 77/93/110 34/39/40 38/43/50 43/52/60 45/54/60 59/66/80 64/77/90

Electrical data based on: electrical reheat -NO, steam generator humidier - YES, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 69/80/90 32/36/40 24/28/30 78/90/100 39/44/50 28/32/35 92/105/110 101/115/125 112/126/150 125/139/150 151/171/200 165/186/225 43/49/50 49/56/60 57/65/70 63/70/80 69/78/90 79/89/110 34/39/40 38/43/50 43/49/50 46/52/60 59/66/80 68/76/90

Electrical data based on: electrical reheat -YES, steam generator humidier - NO, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 69/83/90 32/38/70 25/30/35 74/89/90 35/42/45 27/32/35 85/101/110 39/47/50 31/37/40 90/106/110 116/139/150 125/149/150 134/162/175 164/199/225 43/51/60 56/67/70 60/72/80 62/74/90 77/93/110 33/39/45 43/52/60 45/54/60 51/62/70 64/77/90

Electrical data based on: electrical reheat -NO, steam generator humidier - NO, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA - full load amps FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 41/44/50 19/20/25 14/15/20 50/54/70 26/28/35 18/19/25 64/69/90 30/33/40 24/26/30 73/79/100 37/40/50 28/30/40 83/91/110 44/49/60 33/36/45 96/104/125 123/135/175 137/151/200 50/54/70 56/62/80 66/73/100 36/39/50 48/53/70 57/63/80

MCA - Minimum circuit amps (wire size amps)

MOP - Maximum rating of the overcurrent protective device

COMPRESSOR 208-230/3/60 460/3/60 575/3/60

FLA - full load amps 13.1 6.1 4.4 17.6 9.6 6.1 20.5 9.6 7.6 25.0 12.8 9.6 30.1 16.7 12.2 33.3 17.9 12.8 51.3 23.1 19.9 55.8 26.9 23.7

CONDENSER

Remote air cooled outdoor

Standard selection at 95 F ambient and sea level Evaporator model DAAD/U-06 DAAD/U-08 DAAD/U-10 DAAD/U-13 DAAD/U-16 DAAD/U-20 DAAD/U-26 DAAD/U-30 Condenser model DARC-06 DARC-09 DARC-11 DARC-15 DARC-17 DARC-21 DARC-28 DARC-30 Selection at 100 F ambient and sea level Evaporator model Condenser model

DAAD/U-06 DAAD/U-08 DAAD/U-10 DAAD/U-13 DAAD/U-16 DAAD/U-20 DAAD/U-26 DAAD/U-30 DARC-07 DARC-11 DARC-15 DARC-17 DARC-21 DARC-24 DARC-30 DARC-40

Selection at 105 F ambient and sea level Evaporator model DAAD/U-06 DAAD/U-08 DAAD/U-10 DAAD/U-13 DAAD/U-16 DAAD/U-20 DAAD/U-26 DAAD/U-30 Condenser model DARC-11 DARC-15 DARC-15 DARC-21 DARC-24 DARC-30 DARC-40 DARC-50 (NOTE: Refer to pages 57 and 61 for electrical data on remote air cooled condensers.)

* * * The following section has no reference to column headings * * *


EVAPORATOR FAN MOTOR Horsepower 208-230/3/60 460/3/60 575/3/60 1.0 3.6 1.8 1.4 FLA - full load amps 1.5 4.8 2.4 2.0 2.0 6.2 3.1 2.5 3.0 9.0 4.4 3.3 5.0 14.6 6.6 5.3 7.5 23.0 11.0 8.6 10.0 29.0 14.0 10.0

19

R-410A

WATER COOLED: Performance data at STANDARD airow

MODEL NUMBER CAPACITY in BTU/hr - Gross 80 F/67 WB 50% RH 75 DB/62.5WB 50% RH 75 DB/61 WB 45% RH 72 DB/60 WB 50% RH 72 DB/58.6 WB 45% RH Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible

DAWD/U-06 DAWD/U-08 DAWD/U-10 DAWD/U-13 DAWD/U-16 DAWD/U-20 DAWD/U-26 DAWD/U-30

86,600 62,200 80,600 60,100 78,100 64,000 77,000 58,900 74,900 62,300

121,200 89,800 112,800 86,800 109,200 92,500 107,700 85,000 104,300 89,700

143,900 112,500 134,200 108,600 130,700 116,400 128,400 106,300 124,700 112,700

184,100 134,000 171,400 129,700 166,300 138,000 163,700 127,100 159,700 134,400

238,500 169,700 221,200 164,000 215,300 174,700 210,800 160,600 206,100 169,900

298,200 217,500 277,500 210,400 269,700 224,200 265,000 206,100 258,000 217,800

365,900 259,400 339,700 251,000 329,600 266,600 324,000 245,900 315,200 259,200

430,800 318,500 401,400 308,200 389,100 328,200 383,800 302,000 374,400 319,800

BLOWER SECTION Airow - CFM Standard motor - horsepower External static pressure (E.S.P.) - inches of W.G. Number of motors/fans Maximum E.S.P. (Standard Motor) Maximum E.S.P. (Next Size Motor) Next size motor - horsepower Downow Upow Downow Upow 2,700 2 0.5 1/1 0.8 0.7 0.9 0.9 3 3,600 2 0.5 1/1 1.0 0.9 1.5 1.5 3 4,500 3 0.5 1/1 1.2 1.0 1.5 1.5 5 4,800 3 0.5 1/1 0.7 0.6 1.5 1.5 5 6,400 3 0.5 1/2 1.0 0.9 1.4 1.3 5 8,000 5 0.5 1/2 1.2 1.1 1.5 1.5 7.5 9,000 7.5 0.5 1/2 1.5 1.5 1.5 1.5 10 12,000 3 0.5 3/3 1.5 1.5 1.5 1.5 5

COMPRESSORS Type: Hermetic Scroll Semi-Hermetic Number Refrigerant type Standard N/A 2 R-410A Standard N/A 2 R-410A Standard N/A 2 R-410A Standard N/A 2 R-410A Standard N/A 2 R-410A Standard N/A 2 R-410A Standard N/A 2 R-410A Standard N/A 2 R-410A

EVAPORATOR COIL Face area - sq ft Rows of coils Face velocity - fpm 12.2 2 221 12.2 3 295 12.2 4 369 14.5 5 331 24.4 3 262 24.4 4 328 24.4 5 369 32.5 4 369

REHEAT SECTION Electric kW Capacity - Btu/hr Hot gas Capacity - Btu/hr Steam Capacity - Btu/hr Hot water Capacity - Btu/hr Downow Upow Downow Upow Standard 15 51,225 Optional 26,000 Optional 105,500 60,000 Optional 70,000 34,300 Standard 15 51,225 Optional 38,000 Optional 115,000 65,000 Optional 81,000 44,800 Standard 15 51,225 Optional 42,200 Optional 121,000 69,000 Optional 86,000 47,500 Standard 15 51,225 Optional 48,000 Optional 126,000 72,000 Optional 90,000 49,400 Standard 22.5 76,835 Optional 64,000 Optional 190,000 108,000 Optional 130,000 74,200 Standard 22.5 76,835 Optional 81,000 Optional 210,000 120,000 Optional 145,000 82,000 Standard 22.5 76,835 Optional 101,000 Optional 230,000 130,000 Optional 160,000 90,700 Standard 30 102,450 Optional 126,000 N/A N/A N/A N/A N/A N/A

R-410A

20

WATER COOLED: Performance data at STANDARD airow

MODEL NUMBER HUMIDIFIER SECTION Steam generator Capacity in lb/hr (Adjustable) kW Steam grid Capacity in lb/hr at 15 psi

DAWD/U-06 DAWD/U-08 DAWD/U-10 DAWD/U-13 DAWD/U-16 DAWD/U-20 DAWD/U-26 DAWD/U-30

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

FILTER SECTION Quantity/size Downow

(4 inch thick, 30% efcient, based on ASHRAE Std. 52-76) 3/20x25 2/20x25 3/20x25 2/20x25 3/20x25 2/20x25 2/20x25 2/16x25 3/20x25 3/20x25 2/16x25 2/20x25 2/16x25 3/20x25 2/16x25 2/20x25 2/16x25 3/20x25 2/16x25 2/20x25 2/16x25 3/20x25 4/16x25 2/20x25 4/16x25

Upow

CONDENSER WATER REQMNTS Using 65F EWT GPM/P in psi Using 75 F EWT GPM/P in psi Using 85F EWT GPM/P in psi`

(Maximum design water pressure 150 psi - high pressure valves optional.) 7.1/2.0 11.1/3.0 15.8/4.0 9.5/3.0 14.8/3.5 21.0/4.0 11.9/3.5 18.6/4.0 26.2/5.0 19.0/4.0 29.7/4.5 42.0/7.0 19.0/4.0 29.7/4.5 42.0/7.0 23.8/4.0 37.1/4.5 52.5/7.0 29.7/6.0 46.4/7.0 62.6/10.5 35.0/6.5 52.0/8.0 72.0/12.0

CONNECTION SIZES Condenser water supply Condenser water return Condensate drain Humidier supply 1-5/8 1-5/8 3/4 1/4 1-5/8 1-5/8 3/4 1/4 1-5/8 1-5/8 3/4 1/4 1-5/8 1-5/8 3/4 1/4 2-1/8 2-1/8 3/4 1/4 2-1/8 2-1/8 3/4 1/4 2-1/8 2-1/8 3/4 1/4 2-1/8 2-1/8 3/4 1/4

ELECTRICAL SECTION

Standard Motor

Electrical data based on STANDARD UNIT: electric reheat - YES, steam generator humidier - YES, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 61/75/80 28/34/35 22/27/30 70/81/90 35/41/45 25/29/30 78/90/100 36/42/45 29/33/35 87/100/110 101/124/125 110/134/150 151/171/200 164/199/225 43/49/50 49/60/70 53/64/70 69/78/90 77/93/110 33/38/45 38/47/50 41/50/60 59/66/80 64/77/90

Electrical data based on: electric reheat - NO, steam generator humidier - YES, and STANDARD MOTOR. 208-230/3/60 FLA/MCA/MOP 61/71/80 70/81/90 78/90/100 87/100/110 97/112/125 110/125/150 151/171/200 165/186/225 460/3/60 FLA/MCA/MOP 28/33/35 35/41/45 36/42/45 43/49/50 50/58/70 55/63/70 69/78/90 79/89/110 575/3/60 FLA/MCA/MOP 22/25/30 25/29/30 29/33/35 33/38/45 38/44/50 41/47/50 59/66/80 68/76/90 Electrical data based on: electric reheat - YES, steam generator humidier - NO, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 61/75/80 28/34/35 22/27/30 65/80/90 31/39/40 24/29/30 71/86/90 33/40/45 26/32/35 75/92/100 101/124/125 110/134/150 134/162/175 164/199/225 36/44/50 49/60/70 53/64/70 62/74/90 77/93/110 28/34/40 38/47/50 41/50/60 51/62/70 64/77/90

Electrical data based on: electric reheat - NO, steam generator humidier - NO, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA - Full load amps FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 32/36/45 15/17/20 11/12/15 41/46/60 22/25/30 15/16/20 49/55/70 23/26/35 19/20/25 58/65/90 30/33/45 23/25/30 69/76/100 38/42/50 28/31/40 81/90/110 123/135/175 137/151/200 42/47/60 56/62/80 66/73/100 31/34/45 48/53/70 57/63/80

MCA - Minimum circuit amps (wire sizing amps)

MOP - Maximum rating of the overcurrent protective device

21

R-410A

WATER COOLED: Performance data at STANDARD airow

MODEL NUMBER ELECTRICAL SECTION

DAWD/U-06 DAWD/U-08 DAWD/U-10 DAWD/U-13 DAWD/U-16 DAWD/U-20 DAWD/U-26 DAWD/U-30 Next Size Motor

Electrical data based on: electric reheat - YES, steam generator humidier - YES, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/77/80 29/35/40 23/28/30 72/83/90 36/42/45 26/30/35 84/96/110 39/44/50 31/35/40 93/106/110 107/130/150 116/140/150 161/181/225 183/218/253 45/51/60 52/63/70 56/68/70 73/82/100 84/101/110 35/40/45 40/49/50 44/53/60 60/68/80 70/83/90

Electrical data based on: electric reheat - NO, steam generator humidier - YES, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/73/80 29/34/35 22/26/30 72/83/90 36/42/45 26/30/35 84/96/110 39/44/50 31/35/40 93/106/110 103/118/125 115/130/150 161/181/225 184/205/253 45/51/60 53/60/70 59/66/80 73/82/100 86/96/110 35/40/45 40/46/50 45/50/60 60/68/80 74/82/100

Electrical data based on: electric reheat - YES, steam generator humidier - NO, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/77/80 29/35/40 23/28/30 68/83/90 33/40/45 25/30/35 77/92/100 35/42/45 28/34/35 81/98/110 107/130/150 116/140/150 144/172/200 183/218/253 38/46/50 52/63/70 56/68/70 65/78/90 84/101/110 30/36/40 40/49/50 44/53/60 53/63/70 70/83/90

Electrical data based on: electric reheat - NO, steam generator humidier - NO, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 35/38/50 16/18/20 12/13/15 44/48/60 23/26/35 16/17/20 56/61/80 26/28/35 21/22/30 65/71/90 32/35/45 25/27/35 75/82/110 40/44/60 30/33/45 87/95/125 133/145/175 155/169/225 46/50/60 60/66/80 74/80/100 34/37/50 50/55/70 63/69/90

FLA - Full load amps MCA - Minimum circuit amps (wire sizing amps) MOP - Maximum rating of the overcurrent protective device

COMPRESSOR 208-230/3/60 460/3/60 575/3/60 13.1 6.1 4.4

FLA - full load amps 17.6 9.6 6.1 20.5 9.6 7.6 25.0 12.8 9.6 30.1 16.7 12.2 33.3 17.9 12.8 51.3 23.1 19.9 55.8 26.9 23.7

* * * The following section has no reference to column headings * * *

EVAPORATOR FAN MOTOR Horsepower 208-230/3/60 460/3/60 575/3/60 1.0 3.6 1.8 1.4

FLA - full load amps 1.5 4.8 2.4 2.0 2.0 6.2 3.1 2.5 3.0 9.0 4.4 3.3 5.0 14.6 6.6 5.3 7.5 23.0 11.0 8.6 10.0 29.0 14.0 10.0

* Units with Energy Saver or Auxiliary Chilled Water Coils have different lter quantities as those listed in this section. Refer to dimensional data sheets.

R-410A

22

WATER COOLED: Performance data at OPTIONAL airow

MODEL NUMBER CAPACITY in Btu/hr - Gross 80 F/67 WB 50% RH 75 DB/62.5 WB 50% RH 75 DB/61 WB 45% RH 72 DB/60 WB 50% RH 72 DB/58.6WB 45% RH Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible

DAWD/U-06 DAWD/U-08 DAWD/U-10 DAWD/U-13 DAWD/U-16 DAWD/U-20 DAWD/U-26 DAWD/U-30

89,100 68,500 83,300 66,200 80,600 70,700 79,800 64,800 77,800 68,900

125,100 99,900 116,400 96,200 113,000 103,100 111,200 94,000 108,200 99,900

148,700 126,300 138,100 121,200 134,000 130,300 131,800 118,200 128,800 126,300

188,700 145,600 175,800 140,500 170,700 150,200 168,100 137,500 164,000 146,000

248,600 190,600 231,200 183,900 224,100 196,400 220,800 179,800 214,600 190,500

302,500 230,800 282,200 223,100 274,300 238,500 270,100 218,500 263,800 231,900

373,200 274,100 347,000 265,000 337,200 282,500 331,200 259,500 324,000 274,900

444,100 347,000 413,500 334,600 401,300 357,900 395,100 327,200 384,500 347,200

BLOWER SECTION Airow - CFM Standard motor - horsepower External static pressure (E.S.P.) - inches of W.G. Number of motors/fans Maximum E.S.P. (Standard motor) Maximum E.S.P. (Next Size Motor) Next size motor - horsepower Downow Upow Downow Upow 3,300 3 0.5 1/1 0.9 0.7 1.5 1.5 5 4,400 3 0.5 1/1 1.2 0.9 1.5 1.5 5 5,500 5 0.5 1/1 1.2 1.0 1.2 0.9 7.5 5,600 5 0.5 1/1 1.1 0.6 1.1 1.0 7.5 8,000 5 0.5 1/2 1.2 0.9 1.5 1.5 7.5 9,000 7.5 0.5 1/2 1.5 1.1 1.5 1.5 10 10,000 7.5 0.5 1/2 1.0 1.6 1.5 1.5 10 14,000 3 0.5 3/3 0.6 0.5 1.5 1.5 5

COMPRESSORS Type: Hermetic Scroll Semi-Hermetic Number Refrigerant type

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

EVAPORATOR COIL Face area in sq ft Rows of coils Face velocity in fpm 12.2 2 271 12.2 3 361 12.2 4 451 14.5 5 386 24.4 3 328 24.4 4 369 24.4 5 410 32.5 4 431

REHEAT SECTION Electrical kW Capacity - Btu/hr Hot gas Capacity - Btu/hr Steam Capacity - Btu/hr Hot water Capacity - Btu/hr Downow Upow Downow Upow Standard 15 51,225 Optional 26,000 Optional 105,500 60,000 Optional 70,000 34,300 Standard 15 51,225 Optional 38,000 Optional 115,000 65,000 Optional 81,000 44,800 Standard 15 51,225 Optional 42,200 Optional 121,000 69,000 Optional 86,000 47,500 Standard 15 51,225 Optional 48,000 Optional 126,000 72,000 Optional 90,000 49,400 Standard 22.5 76,835 Optional 64,000 Optional 190,000 108,000 Optional 130,000 74,200 Standard 22.5 76,835 Optional 81,000 Optional 210,000 120,000 Optional 145,00 82,000 Standard 22.5 76,835 Optional 101,000 Optional 230,000 130,000 Optional 160,000 90,700 Standard 30 102,450 Optional 126,000 N/A N/A N/A N/A N/A N/A

23

R-410A

WATER COOLED: Performance data at OPTIONAL airow

MODEL NUMBER HUMIDIFIER SECTION Steam generator Capacity in lb/hr (Adjustable) kW Steam grid Capacity in lb/hr at 15 psi

DAWD/U-06 DAWD/U-08 DAWD/U-10 DAWD/U-13 DAWD/U-16 DAWD/U-20 DAWD/U-26 DAWD/U-30

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

FILTER SECTION Quantity/Size Downow

(4 inch thick, 30% efcient, based on ASHRAE Std. 52-76) 3/20x25 2/20x25 3/20x25 2/20x25 3/20x25 2/20x25 2/20x25 2/16x25 3/20x25 3/20x25 2/16x25 2/20x25 2/16x25 3/20x25 2/16x25 2/20x25 2/16x25 3/20x25 2/16x25 2/20x25 2/16x25 3/20x25 4/16x25 2/20x25 4/16x25

Upow

CONDENSER WATER Using 65 F EWT GPM/P in psi Using 75 F EWT GPM/P in psi Using 85 F EWT GPM/P in psi

Requirements (Maximum design water pressure 150 psi - high pressure valves optional.) 7.1/2.0 11.1/3.0 15.8/4.0 9.5/3.0 14.8/3.5 21.0/4.0 11.9/3.5 18.6/4.0 26.2/5.0 19.0/4.0 29.7/4.5 42.0/7.0 19.0/4.0 29.7/4.5 42.0/7.0 23.8/4 37.1/4.5 52.5/7.0 29.7/6.0 46.4/7.0 62.6/10.5 35.0/6.5 52.0/8.0 72.0/12.0

CONNECTION SIZES Condenser water supply Condenser water return Condensate drain Humidier supply 1-5/8 1-5/8 3/4 1/4 1-5/8 1-5/8 3/4 1/4 1-5/8 1-5/8 3/4 1/4 1-5/8 1-5/8 3/4 1/4 2-1/8 2-1/8 3/4 1/4 2-1/8 2-1/8 3/4 1/4 2-1/8 2-1/8 3/4 1/4 2-1/8 2-1/8 3/4 1/4

ELECTRICAL SECTION

Standard Motor

Electrical data based on STANDARD unit: electric reheat - YES, steam generator humidier - YES, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/77/80 29/35/40 23/28/30 72/83/90 36/42/45 26/30/35 84/96/110 39/44/50 31/35/40 93/106/110 107/130/150 116/140/150 151/171/200 164/199/225 45/51/60 52/63/70 56/68/70 69/78/90 77/93/110 35/40/45 40/49/50 44/53/60 59/66/80 64/77/90

Electrical data based on: electric reheat - NO, steam generator humidier - YES, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/73/80 29/34/35 22/26/30 72/83/90 36/42/45 26/30/35 84/96/110 39 44/50 31/35/40 93/106/110 103/118/125 115/130/150 151/171/200 165/186/225 45/51/60 53/60/70 59/66/80 69/78/90 79/89/110 35/40/45 40/46/50 45/50/60 59/66/80 68/76/90

Electrical data based on: electric reheat - YES, steam generator humidier - NO, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/77/80 29/35/40 23/28/30 68/83/90 33/40/45 25/30/35 77/92/100 35/42/45 28/34/35 81/98/110 107/130/150 116/140/150 134/162/175 164/199/225 38/46/50 52/63/70 56/68/70 62/74/90 77/93/110 30/36/40 40/49/50 44/53/60 51/62/70 64/77/90

Electrical data based on: electric reheat - NO, steam generator humidier - NO, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA - Full load amps FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 35/38/50 16/18/20 12/13/15 44/48/60 23/26/35 16/17/20 56/61/80 26/28/35 21/22/30 65/71/90 32/35/45 25/27/35 75/82/110 40/44/60 30/33/45 87/95/125 123/135/175 137/151/200 46/50/60 56/62/80 66/73/100 34/37/50 48/53/70 57/63/80

MCA - Minimum circuit amps (wire size amps)

MOP - Maximum rating of the overcurrent protective device

R-410A

24

WATER COOLED: Performance data at OPTIONAL airow

MODEL NUMBER ELECTRICAL SECTION

DAWD/U-06 DAWD/U-08 DAWD/U-10 DAWD/U-13 DAWD/U-16 DAWD/U-20 DAWD/U-26 DAWD/U-30 Next Size Motor

Electrical data based on STANDARD unit: electric reheat - YES, steam generator humidier - YES, and NEXT SIZE MOTOR. 208-230/3/60 FLA/MCA/MOP 69/83/90 78/90/100 92/105/110 101/115/125 116/139/150 125/149/150 151/171/200 164/199/225 460/3/60 FLA/MCA/MOP 32/38/40 39/44/80 43/49/50 49/56/60 56/67/70 60/72/80 69/78/90 77/93/110 575/3/60 FLA/MCA/MOP 23/28/30 28/32/35 34/39/40 38/43/50 43/52/60 45/54/60 59/66/80 64/77/90

Electrical data based on: electric reheat - NO, steam generator humidier - YES, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 69/80/90 32/36/40 22/26/30 78/90/100 39/44/50 28/32/35 92/105/110 101/115/125 112/126/150 124/139/150 151/171/200 165/186/225 43/49/50 49/56/60 57/65/70 63/70/80 69/78/90 79/89/110 34/39/40 38/43/50 43/49/50 46/52/60 59/66/80 68/76/90

Electrical data based on: electric reheat - YES, steam generator humidier - NO, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 69/83/90 32/38/40 23/28/30 74/89/90 35/42/45 27/32/35 85/101/110 39/47/50 31/37/40 90/106/110 43/51/60 33/39/45 116/13/150 125/149/150 134/162/175 164/199/225 56/67/70 60/72/80 62/74/90 77/93/110 43/52/60 45/54/60 51/62/70 64/77/90

Electrical data based on: electric reheat - NO, steam generator humidier - NO, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA - full load amps FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 41/44/50 19/20/25 19/20/25 50/54/70 26/28/35 18/19/25 64/69/90 30/33/40 24/26/40 73/79/100 37/40/50 28/30/40 83/91/110 44/49/60 33/36/45 96/104/125 123/135/175 137/151/200 50/54/70 56/62/80 66/73/100 36/39/50 48/53/70 57/63/80

MCA - Minimum circuit amps (wire size amps)

MOP - Maximum rating of the overcurrent protective device

COMPRESSOR 208-230/3/60 460/3/60 575/3/60

FLA - full load amps 13.1 6.1 4.4 17.6 7.6 6.1 20.5 9.6 7.6 25.0 12.8 9.6 30.1 16.7 12.2 33.3 17.9 12.8 51.3 23.1 19.9 55.8 26.9 23.7

* * * The following section has no reference to column headings * * *


EVAPORATOR Horsepower 208-230/3/60 460/3/60 575/3/60 1.0 3.6 1.8 1.4 Fan motor FLA - full load amp 1.5 4.8 2.4 2.0 2.0 6.2 3.1 2.5 3.0 9.0 4.4 3.3 5.0 14.6 6.6 5.3 7.5 23.0 11.0 8.6 10.0 29.0 14.0 10.0

* Units with Energy Saver or Auxiliary Chilled Water Coils have different lter quantities as those listed in this section. Refer to dimensional data sheets.

25

R-410A

GLYCOL COOLED: Performance data at STANDARD airow

MODEL NUMBER CAPACITY in Btu/hr - Gross 80 F/67 WB 50% RH 75 DB/62.5 WB 50% RH 75 DB/61 WB 45% RH 72 DB/60 WB 50% RH 72 DB/58.6 WB 45% RH Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible

DAGD/U-06 DAGD/U-08 DAGD/U-10 DAGD/U-13 DAGD/U-16 DAGD/U-20 DAGD/U-26 DAGD/U-30

74,600 57,500 69,400 55,400 66,700 59,000 66,300 54,200 64,600 57,600

104,800 83,400 97,300 80,300 94,200 85,800 92,800 78,400 90,100 83,200

124,400 105,000 115,400 100,800 111,600 108,000 110,000 98,300 107,300 104,900

159,700 124,200 148,400 119,800 144,200 128,100 141,700 117,100 138,200 124,400

208,600 157,800 193,400 152,000 187,500 162,200 184,300 148,600 180,000 157,700

258,100 201,600 239,100 193,900 231,400 207,100 227,800 189,300 220,800 200,600

317,000 239,500 294,500 231,100 285,300 246,400 281,000 226,100 274,500 240,000

375,400 296,800 348,800 285,800 338,100 305,700 332,800 279,200 323,500 296,400

BLOWER SECTION Airow - CFM Standard motor - horsepower External static pressure (E.S.P.) - inches of W.G. Number of motors/fans Maximum E.S.P. (Standard motor) Maximum E.S.P. (Next Size Motor) Next size motor - horsepower Downow Upow Downow Upow 2,700 2 0.5 1/1 0.8 0.7 0.9 0.9 3 3,600 2 0.5 1/1 1.0 0.9 1.5 1.5 3 4,500 3 0.5 1/1 1.2 1.0 1.5 1.5 5 4,800 3 0.5 1/1 0.7 0.6 1.5 1.5 5 6,400 3 0.5 1/2 1.0 0.9 1.4 1.3 5 8,000 5 0.5 1/2 1.2 1.1 1.5 1.5 7.5 9,000 7.5 0.5 1/2 1.5 1.5 1.5 1.5 10 12,000 3 0.5 3/3 1.5 1.5 1.5 1.5 5

COMPRESSORS Type: Hermetic Scroll Semi-Hermetic Number Refrigerant type

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/Al 2 R-410A

Standard N/Al 2 R-410A

Standard N/A 2 R-410A

EVAPORATOR COIL Face are - sq ft Rows of coils Face velocity - fpm 12.2 2 221 12.2 3 295 12.2 4 369 14.5 5 331 24.4 3 262 24.4 4 328 24.4 5 369 32.5 4 369

REHEAT SECTION Electric kW Capacity - Btu/hr Hot gas Capacity - Btu/hr Steam Capacity - Btu/hr Hot Water Capacity - Btu/hr Downow Upow Downow Upow Standard 15 51,225 Optional 26,000 Optional 105,500 60,000 Optional 70,000 34,300 Standard 15 51,225 Optional 38,000 Optional 115,000 65,000 Optional 81,000 44,800 Standard 15 51,225 Optional 42,200 Optional 121,000 69,000 Optional 86,000 47,500 Standard 15 51,225 Optional 48,000 Optional 126,000 72,000 Optional 90,000 49,400 Standard 22.5 76,835 Optional 64,000 Optional 190,000 108,000 Optional 130,000 74,200 Standard 22.5 76,835 Optional 81,000 Optional 210,000 120,000 Optional 145,000 82,000 Standard 22.5 76,835 Optional 101,000 Optional 230,000 130,000 Optional 160,000 90,700 Standard 30 102,450 Optional 126,000 N/A N/A N/A N/A N/A N/A

R-410A

26

GLYCOL COOLED: Performance data at STANDARD airow

MODEL NUMBER HUMIDIFIER SECTION Steam generator Capacity - lb/hr (Adjustable) kW Steam grid Capacity - lb/hr at 15 psi

DAGD/U-06 DAGD/U-08 DAGD/U-10 DAGD/U-13 DAGD/U-16 DAGD/U-20 DAGD/U-26 DAGD/U-30

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

FILTER SECTION Quantity/Size Downow

(4 inch thick, 30% efcient, based on ASHRAE Std. 52-76) 3/20x25 2/20x25 3/20x25 2/20x25 3/20x25 2/20x25 2/20x25 2/16x25 3/20x25 3/20x25 2/16x25 2/20x25 2/16x25 3/20x25 2/16x25 2/20x25 2/16x25 3/20x25 2/16x25 2/20x25 2/16x25 3/20x25 4/16x25 2/20x25 4/16x25

Upow

CONDENSER WATER Using 65 F EGT GPM/P in psi Using 75F EGT GPM/P in psi Using 85 F EGT GPM/P in psi Using uid cooler GPM/P in psi

Requirements: (Maximum design water pressure 150 psi - high pressure valves optional.) 7.1/2.0 11.1/3.0 15.8/4.0 21.0/5.7 9.5/3.0 14.8/3.5 21.0/4.0 28.0/7.0 11.9/3.5 18.6/4.0 26.2/5.0 35.0/7.5 19.0/4.0 29.7/4.5 42.0/7.0 56.0/9.0 19.0/4.0 29.7/4.5 42.0/7.0 56.0/9.0 23.8/4.0 37.1/4.5 52.5/7.0 70.0/10.0 29.7/6.0 46.4/7.0 62.6/10.5 87.5/14.0 35.0/6.5 52.0/8.0 72.0/12.0 98.0/16.0

CONNECTION SIZES Condensate water supply Condensate water return Condensate drain Humidier supply 1-5/8 1-5/8 3/4 1/4 1-5/8 1-5/8 3/4 1/4 1-5/8 1-5/8 3/4 1/4 1-5/8 1-5/8 3/4 1/4 2-1/8 2-1/8 3/4 1/4 2-1/8 2-1/8 3/4 1/4 2-1/8 2-1/8 3/4 1/4 2-1/8 2-1/8 3/4 1/4

ELECTRICAL SECTION

Standard Motor

Electrical data based on STANDARD UNIT, electric reheat - YES, steam generator humidier - YES, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 61/75/80 28/34/35 22/27/30 70/81/90 35/41/45 25/29/30 78/90/100 36/42/45 29/33/35 87/100/110 101/124/125 110/134/150 151/171/200 164/199/225 43/49/50 49/60/70 53/64/70 69/78/90 77/93/110 33/38/45 38/47/50 41/50/60 59/66/80 64/77/90

Electrical data based on: electric reheat - NO, steam generator humidier - YES, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 61/71/80 28/33/35 22/25/30 70/81/90 35/41/45 25/29/30 78/90/100 36/42/45 29/33/35 87/100/110 43/49/50 33/38/45 97/112/125 110/125/150 151/171/200 165/186/225 50/58/70 55/63/70 69/78/90 79/89/110 38/44/50 41/47/50 59/66/80 68/76/90

Electrical data based on: electric reheat - YES, steam generator humidier - NO, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 61/75/80 28/34/35 22/27/30 65/80/90 31/39/40 24/29/30 71/86/90 33/40/45 26/32/35 75/92/100 101/124/125 110/134/150 134/162/175 164/199/225 36/44/50 49/60/70 53/64/70 62/74/90 77/93/110 28/34/40 38/47/50 41/50/60 51/62/70 64/77/90

Electrical data based on: electric reheat - NO, steam generator humidier - NO, and STANDARD MOTOR. 208-230/3/60 FLA/MCA/MOP 32/36/45 41/46/60 49/55/70 58/65/90 69/76/100 81/90/110 123/135/175 137/151/200 460/3/60 FLA/MCA/MOP 15/17/20 22/25/30 23/26/35 30/33/45 38/42/50 42/47/60 56/62/80 66/73/100 575/3/60 FLA/MCA/MOP 11/12/15 15/16/20 19/20/25 23/25/30 28/31/40 31/34/45 48/53/70 57/63/80 FLA - Full load amps MCA - Minimum circuit amps (wire sizing amps) MOP - Maximum rating of the overcurrent protective device

27

R-410A

GLYCOL COOLED: Performance data at STANDARD airow

MODEL NUMBER ELECTRICAL SECTION

DAGD/U-06 DAGD/U-08 DAGD/U-10 DAGD/U-13 DAGD/U-16 DAGD/U-20 DAGD/U-26 DAGD/U-30 Next Size Motor

Electrical data based on: electric reheat - YES, steam generator humidier - YES, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/77/80 29/35/40 23/28/30 72/83/90 36/42/45 26/30/35 84/96/110 38/44/50 31/35/40 93/106/110 107/130/150 116/140/150 161/181/225 183/218/253 45/51/60 52/63/70 56/68/70 73/82/100 84/101/110 35/40/45 40/49/50 44/53/60 60/68/80 70/83/90

Electrical data based on: electric reheat - NO, steam generator humidier - YES, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/73/80 29/34/35 22/26/30 72/83/90 36/42/45 26/30/35 84/96/110 39/44/50 31/35/40 93/106/110 103/118/125 115/130/150 161/181/225 184/205/253 45/51/60 53/60/70 59/66/80 73/82/100 86/96/110 35/40/45 40/46/50 45/50/60 60/68/80 74/82/100

Electrical data based on: electric reheat - YES, steam generator humidier - NO, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/77/80 29/36/40 23/28/30 68/83/90 33/40/45 25/30/35 77/92/100 35/42/45 28/34/35 81/98/110 107/130/150 116/140/150 144/172/200 183/218/253 38/46/50 52/63/70 56/68/70 65/78/90 84/101/110 30/36/40 40/49/50 44/53/60 53/63/70 70/83/90

Electrical data based on: electric reheat - NO, steam generator humidier - NO, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA - Full load amps FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 35/38/50 16/18/20 12/13/15 44/48/60 23/26/35 16/17/20 56/61/80 26/28/35 21/22/30 65/71/90 32/35/45 25/27/35 75/82/110 40/44/60 30/33/45 87/95/125 133/145/175 155/169/225 46/50/60 60/66/80 74/80/100 34/37/50 50/55/70 63/69/90

MCA - Minimum circuit amps (wire sizing amps)

MOP - Maximum rating of the overcurrent protective device

COMPRESSOR 208-230/3/60 460/3/60 575/3/60

FLA - full load amps 13.1 6.1 4.4 17.6 9.6 6.1 20.5 9.6 7.6 25.0 12.8 9.6 30.1 16.7 12.2 33.3 17.9 12.8 51.3 23.1 19.9 55.8 26.9 23.7

OUTDOOR FLUID COOLER Standard selection at 95 F ambient and sea level Evaporative model DAGD/U-06 DAGD/U-08 DAGD/U-10 DAGD/U-13 DAGD/U-16 DAGD/U-20 DAGD/U-26 DAGD/U-30 Fluid cooler model DAFC-11 DAFC-17 DAFC-17 DAFC-21 DAFC-24 DAFC-37 DAFC-40 DAFC-50 Selection at 100 F ambient and sea level Evaporative model Fluid cooler model

DAGD/U-06 DAGD/U-08 DAGD/U-10 DAGD/U-13 DAGD/U-16 DAGD/U-20 DAGD/U-26 DAGD/U-30 DAFC-17 DAFC-21 DAFC-21 DAFC-30 DAFC-30 DAFC-40 DAFC-50 DAFC-61

(NOTE: Refer to pages 59 and 62 for electrical data on uid coolers.)

* * * The following section has no reference to column headings * * *


EVAPORATOR Horsepower 208-230/3/60 460/3/60 575/3/60 1.0 3.6 1.8 1.4 FAN MOTOR - FLA - full load amps 1.5 4.8 2.4 2.0 2.0 6.2 3.1 2.5 3.0 9.0 4.4 3.3 5.0 14.6 6.6 5.3 7.5 23.0 11.0 8.6 10.0 29.0 14.0 10.0

* Units with Energy Saver or Auxiliary Chilled Water Coils have different lter quantities as those listed in this section. Refer to dimensional data sheets.

R-410A

28

GLYCOL COOLED: Performance data at OPTIONAL airow

MODEL NUMBER CAPACITY in Btu/hr - Gross 80 DB/67 WB 50% RH 75 DB/62.5 WB 50% RH 75 DB/61 WB 45% RH 72 DB/60 WB 50% RH 72 DB/58.6 WB 45% RH Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible

DAGD/U-06 DAGD/U-08 DAGD/U-10 DAGD/U-13 DAGD/U-16 DAGD/U-20 DAGD/U-26 DAGD/U-30

77,300 64,100 71,600 61,500 69,200 65,900 68,200 59,900 66,700 64,000

107,900 93,600 100,300 89,700 97,200 96,300 95,700 87,400 92,900 92,500

127,300 117,100 118,100 112,900 115,100 114,700 112,600 110,300 110,500 110,000

163,600 135,800 152,100 130,600 146,600 139,800 145,200 127,400 141,700 135,900

215,900 178,200 200,900 171,300 194,700 183,800 191,800 167,200 187,500 178,400

264,500 216,100 243,800 207,000 237,500 222,500 231,400 201,500 226,600 215,100

322,900 254,100 300,300 244,900 290,700 261,800 286,800 239,400 279,400 254,300

384,500 324,200 357,500 311,400 346,900 334,700 341,300 303,800 331,600 323,600

BLOWER SECTION Airow - CFM Standard motor - horsepower External static pressure (E.S.P.) - inches of W.G. Number of motors/fans Maximum E.S.P (Standard motor) Maximum E.S.P. (Next size motor) Next size motor - horsepower Downow Upow Downow Upow 3,300 3 0.5 1/1 0.9 0.7 1.5 1.5 5 4,400 3 0.5 1/1 1.2 0.9 1.5 1.5 5 5,500 5 0.5 1/1 1.2 1.0 1.2 0.9 7.5 5,600 5 0.5 1/1 1.1 0.6 1.1 1.0 7.5 8,000 5 0.5 1/2 1.2 0.9 1.5 1.5 7.5 9,000 7.5 0.5 1/2 1.5 1.1 1.5 1.5 10 10,000 7.5 0.5 1/2 1.0 1.5 1.5 1.5 10 14,000 3 0.5 3/3 0.6 0.5 1.5 1.5 5

COMPRESSORS Type: Hermetic Scroll Semi-Hermetic Number Refrigerant type

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

Standard N/Al 2 R-410A

Standard N/A 2 R-410A

Standard N/A 2 R-410A

EVAPORATOR COIL Face area - sq ft Rows of coils Face velocity - fpm 12.2 2 271 12.2 3 361 12.2 4 451 14.5 5 386 24.4 3 328 24.4 4 369 24.4 5 410 32.5 4 431

REHEAT SECTION Electric kW Capacity - Btu/hr Hot gas Capacity - Btu/hr Steam Capacity - Btu/hr Hot water Capacity - Btu/hr Downow Upow Downow Upow Standard 15 51,225 Optional 26,000 Optional 105,500 60,000 Optional 70,000 34,300 Standard 15 51,225 Optional 38,000 Optional 115,000 65,000 Optional 81,000 44,800 Standard 15 51,225 Optional 42,200 Optional 121,000 69,000 Optional 86,000 47,500 Standard 15 51,225 Optional 48,000 Optional 126,000 72,000 Optional 90,000 49,400 Standard 22.5 76,835 Optional 64,000 Optional 190,000 108,000 Optional 130,000 74,200 Standard 22.5 76,835 Optional 81,000 Optional 210,000 120,000 Optional 145,000 82,000 Standard 22.5 76,835 Optional 101,000 Optional 230,000 130,000 Optional 160,000 90,700 Standard 30 102,450 Optional 126,000 N/A N/A N/A N/A N/A N/A

29

R-410A

GLYCOL COOLED: Performance data at OPTIONAL airow

MODEL NUMBER HUMIDIFIER SECTION Steam generator Capacity in lb/hr (Adjustable) kW Steam grid Capacity in lb/hr at 15 psi

DAGD/U-06 DAGD/U-08 DAGD/U-10 DAGD/U-13 DAGD/U-16 DAGD/U-20 DAGD/U-26 DAGD/U-30

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

Standard 10-30 3.3-10.2 Optional 31

FILTER SECTION Quantity/size Downow

(4 inch thick, 30% efcient, based onn ASHRAE Std. 52-76) 3/20x25 2/20x25 3/20x25 2/20x25 3/20x25 2/20x25 2/20x25 2/16x25 3/20x25 3/20x25 2/16x25 2/20x25 2/16x25 3/20x25 2/16x25 2/20x25 2/16x25 3/20x25 2/16x25 2/20x25 2/16x25 3/20x25 4/16x25 2/20x25 4/16x25

Upow

CONDENSER WATER Using 65 F EGT GPM/P in psi Using 75 F EGT GPM/P in psi Using 85 F EGT GPM/P in psi Using uid cooler GPM/P in psi

Requirements (Maximum design water pressure 150 psi - high pressure valves optional.) 7.1/2.0 11.1/3.0 15.8/4.0 21.0/5.7 9.5/3.0 14.8/3.5 21.0/4.0 28.0/7.0 11.9/3.5 18.6/4.0 26.2/5.0 35.0/7.5 19.0/4.0 29.7/4.5 42.0/7.0 56.0/9.0 19.0/4.0 29.7/4.5 42.0/7.0 56.0/9.0 23.8/4.0 37.1/4.5 52.5/7.0 70.0/10.0 29.7/6.0 46.4/7.0 62.6/10.5 87.5/14.0 35.0/6.5 52.0/8.0 72.0/12.0 98.0/16.0

CONNECTION SIZES Condenser water supply Condenser water return Condensate drain Humidier supply 1-5/8 1-5/8 3/4 1/4 1-5/8 1-5/8 3/4 1/4 1-5/8 1-5/8 3/4 1/4 1-5/8 1-5/8 3/4 1/4 2-1/8 2-1/8 3/4 1/4 2-1/8 2-1/8 3/4 1/4 2-1/8 2-1/8 3/4 1/4 2-1/8 2-1/8 3/4 1/4

ELECTRICAL SECTION

Standard Motor

Electrical data based on STANDARD unit, electric reheat - YES, steam generator humidier - YES, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/77/80 29/35/40 23/28/30 72/83/90 36/42/45 26/30/35 84/96/110 39/44/50 31/35/40 93/106/110 107/130/150 116/140/150 151/171/200 164/199/225 45/51/60 52/63/70 56/68/70 69/78/90 77/93/110 35/40/45 40/49/50 44/53/60 59/66/80 64/77/90

Electrical data based on, electric reheat - NO, steam generator humidier - YES, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/73/80 29/34/35 22/26/30 72/83/90 36/42/45 26/30/35 84/96/110 39/44/50 31/35/40 93/106/110 103/118/125 115/130/150 151/171/200 165/186/225 45/51/60 53/60/70 59/66/80 69/78/90 79/89/110 35/40/45 40/46/50 45/50/60 59/66/80 68/76/90

Electrical data based on, electric reheat - YES, steam generator humidier - NO, and STANDARD MOTOR. 208-230/3/60 FLA/MCA/MOP 63/77/80 68/83/90 77/92/100 81/98/110 107/130/150 116/140/150 134/162/175 164/199/225 460/3/60 FLA/MCA/MOP 29/35/40 33/40/45 35/42/45 38/46/50 52/63/70 56/68/70 62/74/90 77/93/110 575/3/60 FLA/MCA/MOP 23/28/30 25/30/35 28/34/35 30/36/40 40/49/50 44/53/60 51/62/70 64/77/90 Electrical data based on, electric reheat - NO, steam generator humidier - NO, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA - Full load amps FLA/MCA/MOP 35/38/50 44/48/60 56/61/80 65/71/90 75/82/110 87/95/125 123/135/175 137/151/200 FLA/MCA/MOP 16/18/20 23/26/35 26/28/35 32/35/45 40/44/60 46/50/60 56/62/80 66/73/100 FLA/MCA/MOP 12/13/15 16/17/20 21/22/30 25/27/35 30/33/45 34/37/50 48/53/70 57/63/80 MCA - Minimum circuit amps (wire sizing amps) MOP - Maximum rating of the overcurrent protective device

R-410A

30

GLYCOL COOLED: Performance data at OPTIONAL airow

MODEL NUMBER ELECTRICAL SECTION

DAGD/U-06 DAGD/U-08 DAGD/U-10 DAGD/U-13 DAGD/U-16 DAGD/U-20 DAGD/U-26 DAGD/U-30 Next size motor

Electrical data based on STANDARD unit, electric reheat - YES, steam generator humidier - YES, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 69/83/90 32/38/40 25/30/35 78/90/100 39/44/50 28/32/35 92/105/110 101/115/125 116/139/150 125/149/150 151/171/200 164/199/225 43/46/50 49/56/60 56/67/70 60/72/80 69/78/90 77/93/110 34/39/40 38/43/50 43/52/60 45/54/60 59/66/80 64/77/90

Electrical data based on, electric reheat - NO, steam generator humidier - YES, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 69/80/90 32/38/40 24/28/30 78/90/100 39/44/50 28/32/35 92/105/110 101/115/125 112/126/150 124/139/150 151/171/200 165/186/225 43/49/50 49/56/60 57/65/70 46/52/60 69/78/90 79/89/110 34/39/40 38/43/50 43/49/50 45/50/60 59/66/80 68/76/90

Electrical data based on, electric reheat - YES, steam generator humidier - NO, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 69/83/90 32/38/40 25/30/35 74/89/90 35/42/50 27/32/35 85/101/110 39/47/50 31/37/40 90/106/110 116/139/150 125/149/150 134/162/175 164/199/225 43/51/60 56/67/70 60/72/80 62/74/90 77/93/110 33/39/45 43/52/60 45/54/60 51/62/70 64/77/90

Electrical data based on, electric reheat - NO, steam generator humidier - NO, and NEXT SIZE MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA - Full load amps FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 41/44/50 19/20/25 14/15/20 50/54/70 26/28/35 18/19/25 61/69/90 30/33/40 24/26/30 73/79/100 37/40/50 28/30/40 83/91/110 44/49/60 33/36/45 96/104/125 123/135/175 137/151/200 50/54/70 56/62/80 66/73/100 36/39/50 48/53/70 57/63/80

MCA - Minimum circuit amps (wire sizing amps)

MOP - Maximum rating of the overcurrent protective device

COMPRESSOR 208-230/3/60 460/3/60 575/3/60

FLA - full load amps 13.1 6.1 4.4 17.6 9.6 6.1 20.5 9.6 7.6 25.0 12.8 9.6 30.1 16.7 12.2 33.3 17.9 12.8 51.3 23.1 19.9 55.8 26.9 23.7

OUTDOOR FLUID COOLER Standard selection at 95 F ambient at sea level Evaporator model Fluid cooler model Selection at 100 F ambient at sea level Evaporator model Fluid cooler model DAGD/U-06 DAGD/U-08 DAGD/U-10 DAGD/U-13 DAGD/U-16 DAGD/U-20 DAGD/U-26 DAGD/U-30 DAFC-17 DAFC-21 DAFC-21 DAFC-30 DAFC-30 DAFC-40 DAFC-50 DAFC-61 DAGD/U-06 DAGD/U-08 DAGD/U-10 DAGD/U-13 DAGD/U-16 DAGD/U-20 DAGD/U-26 DAGD/U-30 DAFC-11 DAFC-17 DAFC-17 DAFC-21 DAFC-24 DAFC-37 DAFC-40 DAFC-50

(NOTE: Refer to pages 59 and 62 for electrical data on uid coolers.)

* * * The following section has no reference to column headings * * *


EVAPORATOR Horsepower 208-230/3/60 460/3/60 575/3/60 1.0 3.6 1.8 1.4 Fan motor FLA - full load amps 1.5 4.8 2.4 2.0 2.0 6.2 3.1 2.5 3.0 9.0 4.4 3.3 5.0 14.6 6.6 5.3 7.5 23.0 11.0 8.6 10.0 29.0 14.0 10.0

* Units with Energy Saver or Auxiliary Chilled Water Coils have different lter quantities as those listed in this section. Refer to dimensional data sheets.

31

R-410A

ENERGY SAVER-GLYCOL COOLED: Performance data at STANDARD airow

CAPACITY in Btu/hr - Gross MODEL NUMBER 75 DB/62.5 WB 50% RH 72 DB/60 WB 50% RH Rows of Coil GPM Pressure drop - psi Total Sensible Total Sensible

(based on 45 F entering uid temperature with 40% glycol solution) DAGU/D-06 DAGU/D-08 DAGU/D-10 DAGU/D-13 DAGU/D-16 DAGU/D-20 DAGU/D-26 DAGU/D-30 69,400 55,400 66,300 54,200 4 21.0 3.8 97,300 80,300 92,800 78,400 4 29.0 6.8 115,400 100,800 110,000 98,300 4 35.0 10.3 148,400 119,800 141,700 117,100 3 45 .5 21.2 193,400 152,000 184,300 148,600 4 56.0 14.7 239,100 193,900 227,800 189,300 4 70.0 22.4 294,500 231,100 281,000 226,100 3 75.0 22.8 348,800 285,800 332,800 279,200 4 80.0 15.7

BLOWER SECTION Airow - CFM Standard Motor - horsepower External Static Pressure (E.S.P.) - inches of W.G. Number of motors/fans Maximum E.S.P. 2,700 3 0.5 1/1 0.8 3,600 3 0.5 1/1 1.5 4,500 5 0.5 1/1 1.5 4,800 5 0.5 1/1 1.5 6,400 5 0.5 1/2 1.2 8,000 7.5 0.5 1/2 1.5 9,000 10 0.5 1/2 1.5 12,000 5 0.5 3/3 1.5

ELECTRICAL SECTION

Standard Motor

Electrical data based on STANDARD unit, electric reheat - YES, steam generator humidier - YES, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/77/80 29/35/40 23/28/30 72/83/90 36/42/45 26/30/35 84/96/110 39/44/50 31/35/40 93/106/110 107/130/150 116/140/150 161/181/225 183/218/253 45/51/60 52/63/70 56/68/70 73/82/100 84/101/110 35/40/45 40/49/50 44/53/60 60/68/80 70/83/90

Electric data based on: electric reheat - NO, steam generator humidier - YES, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/73/80 29/34/35 22/26/30 72/83/90 36/42/45 26/30/35 84/96/110 39/44/50 31/35/40 93/106/110 103/118/125 115/130/150 161/181/225 184/205/253 45/51/60 53/60/70 59/66/80 73/82/100 86/96/110 35/40/45 40/46/50 45/50/60 60/68/80 74/82/100

Electric data based on: electric reheat - YES, steam generator humidier - NO, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/77/80 29/35/40 23/28/30 68/83/90 33/40/45 25/30/35 77/92/100 35/42/45 28/34/35 81/98/110 107/130/150 116/140/150 144/172/200 183/218/253 38/46/50 52/63/70 56/68/70 65/78/90 84/101/110 30/36/40 40/49/50 44/53/60 53/63/70 70/83/90

Electric data based on: electric reheat - NO, steam generator humidier - NO, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 35/38/50 16/18/20 12/13/15 44/48/60 23/26/35 16/17/20 56/61/80 26/28/35 21/22/30 65/71/90 32/35/45 25/27/35 75/82/110 40/44/60 30/33/45 87/95/125 133/145/175 155/169/225 46/50/60 60/66/80 74/80/100 34/37/50 50/55/70 63/69/90

FLA - Full load amps

MCA - Minimum circuit amps (wire sizing amps)

MOP - Maximum rating of the overcurrent protective device

R-410A

32

ENERGY SAVER-GLYCOL COOLED: Performance data at OPTIONAL airow

CAPACITY in Btu/hr - Gross MODEL NUMBER 75 DB/62.5 WB 50% RH 72 DB/60 WB 50% RH Rows of coils GPM Pressure drop - psi Total Sensible Total Sensible

(based on 45 F entering uid temperature with 40% glycol solution) DAGU/D-06 DAGU/D-08 DAGU/D-10 DAGU/D-13 DAGU/D-16 DAGU/D-20 DAGU/D-26 DAGU/D-30 71,600 61,500 68,200 59,900 4 21.0 3.8 100,300 89,700 95,700 87,400 4 29.0 6.8 118,100 112,900 112,600 110,300 4 35.0 10.3 152,100 130,600 145,200 127,400 3 45.5 21.2 200,900 171,300 191,800 167,200 4 56.0 14.7 243,800 207,000 231,400 201,500 4 70.0 22.4 300,300 244,900 286,800 239,400 3 75.0 22.8 357,500 311,400 341,300 303,800 4 80.0 15.7

BLOWER SECTION Airow - CFM 3,300 4,400 Standard motor - horsepower 3 3 External Static Pressure (E.S.P.) - inches of W.G. 0.5 0.5 Number of fans/motors 1/1 1/1 * Limited External Static Pressure (see below for maximum E.S.P.) Maximum E.S.P. 1.4 1.5 5,500 5 * 1/1 5,600 7.5 0.5 1/1 8,000 5 0.5 2/1 9,000 7.5 0.5 2/1 10,000 10 0.5 2/1 14,000 5 0.5 3/3

0.5

0.6

1.5

1.5

1.0

1.5

ELECTRICAL SECTION

Standard Motor

Electrical data based on STANDARD unit, electric reheat - YES, steam generator humidier - YES, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/77/80 29/35/40 23/28/30 72/83/90 36/42/45 26/30/35 84/96/110 101/115/125 107/130/150 116/140/150 161/181/225 183/218//253 39/44/50 49/56/60 52/63/70 56/68/70 73/82/100 84/101/110 31/35/40 38/43/50 40/49/50 44/53/60 60/68/80 70/83/90

Electrical data based on; electric reheat - NO, steam generator humidier - YES, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/77/80 29/34/35 22/26/30 72/83/90 36/42/45 26/30/35 84/96/110 101/115/125 103/118/125 115/130/150 161/181/225 184/205/253 39/44/50 49/56/60 53/60/70 59/66/80 73/82/100 86/96/110 31/35/40 38/43/50 40/46/50 45/50/60 60/68/80 74/82/100

Electrical data based on; electric reheat - YES, steam generator humidier - NO, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/77/80 29/35/40 23/28/30 68/83/90 33/40/45 25/30/35 77/92/100 35/42/45 28/34/35 90/106/110 107/130/150 1116/140/150 144/172/200 183/218/253 43/51/60 52/63/70 56/68/70 65/78/90 84/101/110 33/39/45 40/49/50 44/53/60 53/63/70 70/83/90

Electrical data based on; electric reheat - NO, steam generator humidier - NO, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 35/38/50 16/18/20 12/13/15 44/48/60 23/26/35 16/17/20 56/61/80 26/28/35 21/22/30 73/79/100 37/40/50 28/30/35 75/82/110 40/44/60 30/33/45 87/95/125 133/145/175 155/169/225 46/50/60 60/66/80 74/80/100 34/37/50 50/55/70 63/69/90

FLA - Full load amps

MCA - Minimum circuit amps (wire sizing amps)

MOP - Maximum rating of the overcurrent protective device

33

R-410A

AUXILIARY CHILLED WATER COIL: Performance data at STANDARD airow

CAPACITY in Btu/hr - Gross MODEL NUMBER 75 DB/62.5 WB 50% RH 72 DB/60 WB 50% RH Rows of coils GPM Pressure drop - psi Total Sensible Total Sensible

(based on 45 F Entering Fluid Temperature) DA*U/D-06 DA*U/D-08 DA*U/D-10 DA*U/D-13 DA*U/D-16 DA*U/D-20 DA*U/D-26 DA*U/D-30 69,400 55,400 66,300 54,200 4 18.0 2.7 97,300 80,300 92,800 78,400 4 24.0 4.6 115,400 100,800 110,000 98,300 4 30.0 7.2 148,400 119,800 141,700 117,100 3 39.0 11.8 193,400 152,000 184,300 148,600 4 48.0 9.9 239,100 193,900 227,800 189,300 4 60.0 15.1 294,500 231,100 281,000 226,100 3 75.0 18.3 348,800 285,800 332,800 279,200 4 80.0 13.8

* Insert A for air cooled, W for water cooled, or G for glycol cooled

BLOWER SECTION Airow - CFM Standard motor - horsepower External Static Pressure (E.S.P.) - inches of W.G. Number of motors/fans Maximum E.S.P. 2,700 3 0.5 1/1 0.7 3,600 13 0.5 1/1 1.5 4,500 5 0.5 1/1 1.5 4,800 5 0.5 1/1 1.5 6,400 5 0.5 1/2 1.2 8,000 7.5 0.5 1/2 1.5 9,000 10 0.5 1/2 1.5 12,000 5 0.5 3/3 1.5

ELECTRICAL SECTION

Standard Motor

Electrical data based on STANDARD unit; electric reheat - YES, steam generator humidier - YES, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/77/80 29/35/40 23/28/30 72/83/90 36/42/45 26/30/35 84/96/110 39/44/50 31/35/40 93/106/110 107/130/150 116/140/150 161/181/225 183/218/253 45/51/60 52/63/70 56/68/70 73/82/100 84/101/110 35/40/45 40/49/50 44/53/60 60/68/80 70/83/90

Electrical data based on, electric reheat - NO, steam generator humidier - YES, and STANDARD MOTOR. 208-230/3/60 FLA/MCA/MOP 63/73/80 72/83/90 84/96/110 93/106/110 103/118/125 115/130/150 161/181/225 184/205/253 460/3/60 FLA/MCA/MOP 29/34/35 36/42/45 39/44/50 45/51/60 53/60/70 59/66/80 73/82/100 86/96/110 575/3/60 FLA/MCA/MOP 22/26/30 26/30/35 31/35/40 35/40/45 40/46/50 45/50/60 60/68/80 74/82/100 Electrical data based on, electric reheat - YES, steam generator humidier - NO, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/77/80 29/35/40 23/28/30 68/83/90 33/40/45 25/30/35 77/92/100 35/42/45 28/34/35 81/98/110 107/130/150 116/140/150 144/172/200 183/218/253 38/46/50 52/63/70 56/68/70 65/78/90 84/101/110 30/36/40 40/49/50 44/53/60 53/63/70 70/83/90

Electrical data based on, electric reheat - NO, steam generator humidier - NO, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 35/38/50 16/18/20 12/13/15 44/48/60 23/26/35 16/17/20 56/61/80 26/28/35 21/22/30 65/71/90 32/35/45 25/27/35 75/82/110 40/44/60 30/33/45 87/95/125 133/145/175 155/169/225 46/50/60 60/66/80 74/80/100 34/37/50 50/55/70 63/69/90

FLA - Full load amps

MCA - Minimum circuit amps (wire sizing amps)

MOP - Maximum rating of the overcurrent protective device

R-410A

34

AUXILIARY CHILLED WATER COIL: Performance data at OPTIONAL airow

CAPACITY in Btu/hr - Gross MODEL NUMBER 75 DB/62.5 WB 50% RH 72 DB/60 WB 50% RH Total Sensible Total Sensible

(based on 45 F Entering Fluid Temperature) DA*U/D-06 DA*U/D-08 DA*U/D-10 DA*U/D-13 DA*U/D-16 DA*U/D-20 DA*U/D-26 DA*U/D-30 71,600 61,500 68,200 59,900 100,300 89,700 95,700 87,400 118,100 112,900 112,600 110,300 4 30.0 7.2 152.100 130,600 145,200 127,400 3 39.0 11.6 200,900 171,300 191,800 167,200 4 48.0 9.9 243,800 207,000 231,400 201,500 4 60.0 15.1 300,300 244,900 286,800 239,400 3 75.0 18.3 357,500 311,400 341,300 303,800 4 80.0 13.8

Rows of coils 4 4 GPM 18.0 24.0 Pressure drop - psi 2.7 4.6 * Insert A for air cooled, W for water cooled, or G for glycol cooled

BLOWER SECTION Airow - CFM Standard motor - horsepower External Static Pressure (E.S.P.) - inches of W.G. Number of motors/fans 3,300 3 0.5 1/1 4,400 3 0.5 1/1 1.5 5,500 5 * 1/1 0.5 5,600 7.5 0.5 1/1 0.6 8,000 5 0.5 1/2 1.5 9,000 7.5 0.5 1/2 1.5 10,000 10 0.5 1/2 1.0 14,000 5 0.5 3/3 1.5

Maximum E.S.P. 1.4 * Limited External Static Pressure (see maximum E.S.P.)

ELECTRICAL SECTION

Standard Motor

Electrical data based on STANDARD unit; electric reheat - YES, steam generator humidier - YES, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/77/80 29/35/40 22/28/30 72/83/90 36/42/45 26/30/35 84/96/110 101/115/125 107/130/150 116/140/150 161/181/225 183/218/253 39/44/50 49/56/60 52/63/70 56/68/70 73/82/100 84/101/110 31/35/40 38/43/50 40/49/50 44/53/60 60/68/80 70/83/90

Electrical data based on, electric reheat - NO, steam generator humidier - YES, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 63/73/80 29/34/35 22/26/30 72/83/90 36/42/45 26/30/35 84/96/110 101/115/125 103/118/125 115/130/150 161/181/225 184/205/253 39/44/50 49/56/60 53/60/70 59/66/80 73/82/100 86/96/110 31/35/40 38/43/50 40/46/50 45/50/60 60/68/80 74/82/100

Electrical data based on, electric reheat - YES, steam generator humidier - NO, and STANDARD MOTOR. 208-230/3/60 FLA/MCA/MOP 63/77/80 68/83/90 77/92/100 90/106/110 107/130/150 116/140/150 144/172/200 183/218/253 460/3/60 FLA/MCA/MOP 29/35/40 33/40/45 35/42/45 43/51/60 52/63/70 56/68/70 65/78/90 84/101/110 575/3/60 FLA/MCA/MOP 23/28/30 25/30/35 28/34/35 33/39/45 40/49/50 44/53/60 53/63/70 70/83/90 Electrical data based on, electric reheat - NO, steam generator humidier - NO, and STANDARD MOTOR. 208-230/3/60 460/3/60 575/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP 35/38/50 16/18/20 12/13/15 44/48/60 23/26/35 16/17/20 56/61/80 26/28/35 21/22/30 73/79/100 37/40/50 28/30/35 75/82/110 40/44/60 30/33/45 87/95/125 133/145/175 155/169/225 46/50/60 60/66/80 74/80/100 34/37/50 50/55/70 63/69/90

FLA - Full load amps

MCA - Minimum circuit amps (wire sizing amps)

MOP - Maximum rating of the overcurrent protective device

35

R-410A

DATA AIRE SERIES 6, 8, & 10 ton - Downow

36

DATA AIRE SERIES 6, 8, & 10 ton - Upow

37

DATA AIRE SERIES 6, 8, and 10 ton - Downow with Energy Saver Coil

38

DATA AIRE SERIES 6, 8, and 10 ton - Upow with Energy Saver Coil

39

DATA AIRE SERIES 13 ton - Downow

40

DATA AIRE SERIES 13 ton - Upow

41

DATA AIRE SERIES 13 ton - Downow with Energy Saver Coil

42

DATA AIRE SERIES 13 ton - Upow with Energy Saver Coil

43

DATA AIRE SERIES 16, 20, and 26 ton - Downow

44

DATA AIRE SERIES 16, 20, and 26 ton - Upow

45

DATA AIRE SERIES 16, 20 and 26 ton - Downow with Energy Saver Coil

46

DATA AIRE SERIES 16, 20 and 26 ton - Upow with Energy Saver Coil

47

DATA AIRE SERIES 30 ton - Downow

48

DATA AIRE SERIES 30 ton - Upow

49

DATA AIRE SERIES 30 ton - Downow with Energy Saver Coil

50

DATA AIRE SERIES 30 ton - Upow with Energy Saver Coil

51

DATA AIRE SERIES - Plenum and Floorstand

Plenum

Floorstand

52

DATA AIRE Air Cooled Condensers, DARC 06-50, Dual Circuit

53

DATA AIRE Air Cooled Condensers, DARC 06-50, Dual Circuit

54

DATA AIRE Fluid Coolers, DAFC MODEL 06-50

55

DATA AIRE Fluid Coolers, DAFC MODEL 06-50

56

DATA AIRE DOUBLE WIDE Air Cooled Condenser, DARC 57-100, Dual Circuit

57

DATA AIRE Double Wide Fluid Coolers, DAFC Model 57 thru 100

58

Standard Condenser Electrical Data

Standard Condenser Electrical Data


208/1/60 Model DARC 03 DARC 05 DARC 06 DARC 07 DARC 09 DARC 11 DARC 15 DARC 17 DARC 21 DARC 24 DARC 28 DARC 30 DARC 37 DARC 40 DARC 44 DARC 50 DARC 57 DARC 61 DARC 75 DARC 80 DARC 88 DARC100 FLA/MCA/MFS 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 9.2/10/15 9.2/10/15 9.2/10/15 14/15/20 14/15/20 14/15/20 18/20/25 18/20/25 18/20/25 23/24/25 23/24/25 28/29/30 37/38/40 37/38/40 37/38/40 46/47/45 46/47/45 208/3/60 FLA/MCA/MFS 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 9.2/10/15 9.2/10/15 9.2/10/15 14/15/20 14/15/20 14/15/20 18/20/25 18/20/25 18/20/25 23/24/25 23/24/25 28/29/30 37/38/40 37/38/40 37/38/40 46/47/40 46/47/40 460/3/60 FLA.MCA.MFS 2.3/2.9/15 2.3/2.9/15 2.3/2.9/15 2.3/2.9/15 2.3/2.9/15 4.6/5.2/15 4.6/5.2/15 4.6/5.2/15 6.9/7.5/15 6.9/7.5/15 6.9/7.5/15 9.2/9.8/15 9.2/9.8/15 9.2/9.8/15 12/12/15 12/12/15 14/14/15 18/19/20 18/19/20 18/19/20 23/24/25 23/24/25

59

DATA AIRE SERIES Dimensional and Weight Data

Standard Units
Air Cooled Operating Shipping Weigh Weight Water/Glycol Cooled Operating Shipping Weight Weight

Model

Length

WidtH

Height

DA*D/U-06xx DA*D/U-08xx DA*D/U-10xx DA*D/U-13xx DA*D/U-16xx DA*D/U-20xx DA*D/U-26xx DA*D/U-30xx

62.00 62.00 62.00 74.50 93.25 93.25 93.25 125.00

34.50 34.50 34.50 34.50 34.50 34.50 34.50 34.50

78.00 78.00 78.00 78.00 78.00 78.00 78.00 78.00

1,060 lbs 1,075 lbs 1,090 lbs 1,345 lbs 1,520 lbs 1,560 lbs 1,605 lbs 2,050 lbs

1,210 lbs 1,225 lbs 1,240 lbs 1,520 lbs 1,720 lbs 1,760 lbs 1,805 lbs 2,300 lbs

1,110 lbs 1,120 lbs 1,190 lbs 1,405 lbs 1,550 lbs 1,710 lbs 1,755 lbs 2,280 lbs

1,260 lbs 1,275 lbs 1,340 lbs 1,580 lbs 1,850 lbx 1,910 lbs 1,955 lbs 2,530 lbs

Units with Auxiliary Chilled Water Coil or Energy Saver Coil


Air Cooled Operating Shipping Weight Weight Water/Glycol Cooled Operating Shipping Weight Weight

Model

Length

Width

Height

DA*D/U-08xx-C/E DA*D/U-10xx-C/E DA*D/U-13xx-C/E DA*D/U-16xx-C/E DA*D/U-20xx-C/E DA*D/U-26xx-C/E DA*D/U-30xx-C/E

62.00 62.00 74.50 93.25 93.25 93.25 125.00

40.50 40.50 40.50 40.50 40.50 40.50 40.50

78.00 78.00 78.00 78.00 78.00 78.00 78.00

1,200 lbs 1,240 lbs 1,525 lbs 1,720 lbs 1,785 lbs 1,880 lbs 2,350 lbs

1,350 lbs 1,390 lbs 1,700 lbs 1,920 lbs 1,985 lbs 2,080 lbs 2,600 lbs

1,245 lbs 1,340 lbs 1,585 lbs 1,750 lbs 1,935 lbs 2,030 lbs 2,580 lbs

1,395 lbs 1,490 lbs 1,760 lbs 2,060 lbs 2,135 lbs 2,230 lbs 2,830 lbs

* - Insert: A - air cooled, W - water cooled, G-Glycol cooled.

60

DATA AIRE SERIES 6 to 30 ton DX units - Guide Specications

GENERAL The environmental control units shall be provided with a high sensible cooling system, factory assembled, piped, wired, and run tested prior to shipment and designed for the following air pattern: ___ Down Discharge ___ Top Discharge with Duct Connection ___ Top Discharge with Plenum The system shall be designed for draw through air arrangement to insure even air distribution to the entire face of the coil. Units shall be ETL or UL listed. CABINET and FRAME The frame shall be constructed of 14 gauge welded tubular steel and coated with a heavy corrosion inhibiting nish for long life. All internal fans shall be of high grade steel and shall be coated and sealed for utmost protection against corrosion. The unit shall have complete front and side access by means of high quality furniture grade steel doors with heavy duty hinges. The doors shall be lined with one inch thick, 11/2 pound density berglass insulation coated with neoprene. Each door shall be provided with sure close latches which shall be quickly removable for easy access and a polyurethane gasket to prevent air leakage. The doors shall be painted to match or contrast with other equipment in the space. Bypass air shall be provided around the cooling coil to preclude saturated air from being distributed to other equipment in the controlled space. The cooling coil shall sit in a stainless steel drain pan. The unit shall be painted _________________. REFRIGERATION CIRCUIT Air Cooled with Remote Outdoor Condenser - The refrigeration system shall be split type with an indoor evaporator section and remote outdoor condenser. The indoor evaporator section shall include the cooling coil, compressors, humidier, reheat, lters, and controls. The cooling coil shall be in a cross circuited or interlaced A frame arrangement to allow maximum coil surface in a small cabinet. The large faced coil area shall be constructed with 1/2 O.D. copper tube with 12 ns per inch of corrugated aluminum for maximum heat transfer. Maximum face velocity shall be less than 500 feet per minute. The expansion valves shall be of the adjustable thermostatic type with external equalization. The compressors shall be of the hermetic scroll or semi-hermetic type, with complete overload protection on all three power lines, internal thermostat for winding protection, anti-slug device, crankcase heater, sight-glass, and low pressure override timer for positive starting at low temperatures. The lter drier shall be of the are tting type for non-torch servicing. The circuit shall contain high and low pressure safety switches. The high and low pressure safety switches shall be installed with shraeder type ttings with valve core. Each system shall include a low prole, slow speed, direct drive propeller fan type air cooled condenser. The air discharge shall be vertical to minimize the effects of wind blowing through the coil at low ambient temperatures. The condenser shall be constructed of galvanized steel with a powder coated nish. The condenser shall contain a 1/2 O.D. copper tube coil with corrugated aluminum ns for maximum heat transfer. The condenser shall have fan speed control with transducers to modulate the speed of the rst condenser fan motor and provide positive start-up and operation at ambient temperatures to -20 F. Additional condenser fan motors are to be controlled by ambient thermostats. All controls including the fan speed controller shall be factory mounted in the air cooled condenser in an integral factory wired and tested control panel. The air cooled condenser shall be manufactured by the manufacturer of the indoor unit.

61

DATA AIRE SERIES 6 to 30 ton DX units - Guide Specications, continued

Air Cooled with Remote Outdoor Condenser - The refrigeration system shall be split type with an indoor evaporator section and remote outdoor condenser. The indoor evaporator section shall include the cooling coil, humidier, reheat, lters, compressors and controls. Compressors shall be hermetic scroll (standard) or semi-hermetic type with complete overload protection on all three power lines, internal thermostats for winding protection, anti-slug device, crankcase heater, sight-glass, and low pressure override timer for positive starting at low temperatures. The lter drier shall be of the are tting type for non-torch servicing. Circuits shall contain high and low pressure safety switches and suction accumulator. The high and low pressure safety switches shall be installed with shrader type tting with valve core. The cooling coil shall be in a cross circuited or interlaced A frame arrangement to allow maximum coil surface in a small cabinet. The large faced area coil shall be constructed with O.D. copper tube with 12 ns per inch of corrugated aluminum for maximum heat transfer. Maximum face velocity shall be less than 500 feet per minute. The expansion valves shall be of the adjustable thermostatic type with external equalization. The outdoor condenser unit shall be constructed of aluminum and include a low prole, slow speed, direct drive propeller fan air cooled condenser section. The air discharge shall be vertical to minimize the effects of wind blowing through the coil at low ambient temperatures. The condenser coil shall be constructed with copper tube and aluminum n. The condenser shall have fan speed control with transducers to modulate the speed of the rst condenser fan motor and provide positive start-up and operation at ambient temperatures to -20 degrees F. Ambient thermostats shall control additional condenser fan motors. All controls including the fan speed control shall be factory mounted in an integral factory wired and tested control panel. The condenser shall be manufactured by the manufacturer of the indoor unit.

Air Cooled with Floor Mounted Indoor Condenser - The refrigeration system shall be split type with an indoor evaporator section and oor mounted indoor condenser section. The indoor evaporator section shall include the cooling coil, compressors, humidier, reheat, lters, and controls. The cooling coil shall be a cross circuited or interlaced A frame arrangement to allow maximum coil surface in a small cabinet. The large faced coil area shall be constructed with 1/ O.D. copper tube with 12 ns per inch of corrugated aluminum for maximum heat transfer. Maximum face velocity shall be less than 500 feet per minute. The expansion valves shall be of the adjustable type with external equalization. The compressors shall be of the hermetic scroll or semi-hermetic type, with complete overload protection on all three power lines, internal thermostat for winding protection, anti-slug device, crankcase heater, sight-glass, and low pressure override timer for positive starting at low temperatures. The lter drier shall be of the are tting type for non-torch servicing. The circuits shall contain high and low pressure safety switches. The high and low pressure switches shall be installed with shraeder type ttings with valve core.
2

Each system shall include a oor mounted, indoor air cooled condenser section. The condenser frame shall be constructed of 14 gauge welded tubular steel and be coated with a heavy corrosion inhibiting nish for long life. The unit shall have complete front and side access by means of high quality furniture grade steel doors with heavy duty hinges. The doors shall be lined with one inch thick, 11/2 pound density berglass coated with neoprene. Each door shall be provided with sure close latches which shall be quickly removable for easy access and a polyurethane gasket to prevent air leakage. The doors shall be painted to match or contrast with other room equipment. The blower section shall be belt driven centrifugal type, double width, double inlet and shall be statically and dynamically balanced at the factory as a complete assembly to a maximum vibration level of two mills in any plane. The blower wheel shall be a minimum of 15 inches in diameter. The blower wheel shall be supported on a heavy steel shaft having self-aligning ball bearings with a minimum life span of 100,000 hours. The blower wheel shall be driven by a motor mounted on an adjustable slide base. The drive motor shall be 1750 rpm. The drive package shall be belt driven with two belts and a variable pitch sheave, sized for 200% of the fan motor horsepower. The condenser coil shall be constructed of copper tubes and corrugated aluminum ns. The condenser coil shall be equally circuited for each refrigeration compressor. A receiver shall be factory mounted with head pressure control and solenoid valve for each circuit.

62

DATA AIRE SERIES 6 to 30 ton DX units - Guide Specications, continued

Air Cooled with Remote Outdoor Condensing Unit - The refrigeration system shall be split type with an indoor evaporator section and remote outdoor condensing unit. The indoor evaporator section shall include the cooling coil, humidier, reheat, lters, and controls. The cooling coil shall be in a cross circuited or interlaced A frame arrangement to allow maximum coil surface in a small cabinet. The large faced coil area shall be constructed with 1/2 O.D. copper tube with 12 ns per inch of corrugated aluminum for maximum heat transfer. Maximum face velocity shall be less than 500 feet per minute. The expansion valves shall be of the adjustable thermostatic type with external equalization. The outdoor condensing unit shall be constructed of an aluminum housing and contain hermetic scroll or semi-hermetic type compressors with complete overload protection on all three power lines, internal thermostats for winding protection, anti-slug device, crankcase heater, sight-glass, and low pressure override timer for positive starting at low temperatures. The lter drier shall be of the are tting type for non-torch servicing. The circuits shall contain high and low pressure safety switches. The high and low pressure safety switches shall be installed with shraeder type ttings with valve core. The condensing unit shall include a low prole, slow speed, direct drive propeller fan air cooled condenser section. The air discharge shall be vertical to minimize the effects of wind blowing through the coil at low ambient temperatures. The condenser coil shall be constructed with copper tube and aluminum n. The condensing unit shall have fan speed control with transducers to modulate the speed of the rst condenser fan motor and provide positive start-up and operation at ambient temperatures to -20 F. Additional condenser fan motors shall be controlled by ambient thermostats. All controls including the fan speed control shall be factory mounted in an integral factory wired and tested control panel. The condensing unit shall be manufactured by the manufacturer of the indoor unit. Water/Glycol Cooled - The cooling coil shall be in a cross circuited or interlaced A frame arrangement to allow maximum coil surface in a small cabinet. The large face area coil shall be constructed of 1/2 O.D. copper tube with 12 ns per inch of corrugated aluminum for maximum heat transfer. Maximum face velocity shall be less than 500 feet per minute. The expansion valves shall be of the adjustable thermostatic type with external equalization. The compressors shall be of the hermetic scroll or semi-hermetic type with complete overload protection on all three power lines, internal thermostats for winding protection, anti-slug device, crankcase heater, sight-glass, condensers with sub-cooling and 2-way water regulating valve for head pressure control. The lter drier shall be of the are tting type for non-torch servicing. The circuits shall contain high and low pressure safety switches. The high and low pressure safety switches shall be installed with shraeder type ttings with valve core. Each system shall include a low prole, slow speed, direct drive propeller fan type air cooled uid cooler. Air discharge shall be vertical to prevent wind from blowing through the coil at low ambient temperatures. The uid cooler shall be constructed of aluminum and contain a 1/2 O.D. copper tube coil with corrugated aluminum ns for maximum heat transfer. The fan motors shall have cycling control provided on uid coolers with multiple fan motors. The uid cooler shall include surge tank and ll valve, pump contactor, and fan cycling controls with integral factory wired and tested control panel. The uid cooler shall be manufactured by the manufacturer of the indoor unit.

63

DATA AIRE SERIES 6 to 30 ton DX units Guide Specications, continued

BLOWER SECTION The blower shall be a belt driven centrifugal type, double width, double inlet and shall be statically and dynamically balanced at the factory as a complete assembly to a maximum vibration level of two mils in any plane. The blower wheel shall be a maximum of 15 inches in diameter.. The blower wheel shall be supported on a heavy steel shaft having self-aligning ball bearings with a minimum life span of 100,000 hours. The blower wheel shall be driven by a motor on an adjustable slide base. The drive motor shall be 1750 rpm. The drive package shall be belt driven with two (2) belts and variable pitch sheave sized for 200% of the fan motor horsepower. The blower shall be located to draw air over the coil to insure even air distribution and maximum coil performance.

FILTER CHAMBER The lter chamber shall be an integral part of the system, designed within the frame and cabinet. The lters shall be four inch (4) deep pleated design, rated not less than 30% efcient (based on ASHRAE Std. 52.1-1992).

ELECTRIC REHEAT The reheat shall be of the nned enclosed, sheath type, fabricated of stainless steel core sheath with plated ns to withstand moist conditions. The reheat shall be installed on the air discharge side of the cooling coil and shall have three (3) stages. Each stage shall be ___ kW. The total kW shall be ___ to operate on a supply of ____ volts.

HUMIDIFIER The unit shall be provided with steam generator type humidier. The steam generating humidier shall be of the self-contained disposable cylinder type with electronic controls. The capacity shall be adjustable from 10 to 30 pounds per hour. Power consumption at 22 pounds per hour shall be 7.7 kW or less. The humidier shall discharge pure steam with no material dust carryover and have a self-regulating automatic ush cycle. Cylinders shall be disposable not requiring cleaning or maintenance. The humidier ll level, water conductivity and ush rate shall automatically adapt, both in frequency and duration, to variations in the incoming water.

WATER SENSOR Units shall be provided with one (1) water sensor. The solid state water sensor shall be mounted under the unit to sense the presence of water. The sensor shall be connected to the microprocessor panel and activate an audible alarm. The water detector shall become an integral part of the microprocessor panel and shall display WATER DETECTED IN UNDER FLOOR AREA message when the sensor is activated.

64

DATA AIRE SERIES 6 to 30 ton DX units Guide Specications, continued

Data Aire Data Alarm Processor III ( DAPTM III) The environmental system shall be furnished with a microprocessor based Data Alarm Processor-III panel. The panel shall include unit switching functions and display normal functions, malfunctions, and service diagnostics on a 2 row, 80 character, backlit liquid crystal display (LCD) in a clear vernacular format. The panel shall allow recall and display of the high and low temperature for the last 24 hours, high and low humidity for the last 24 hours, current percent of capacity and average percent of capacity for the last hour of operation for cool 1, cool 2, reheat, humidication, and dehumidication, component runtimes for fan motor, reheat, humidication, and dehumidication. Programming shall have multilevel password access to prevent unauthorized access. Programming shall be accomplished entirely from the front of the unit without the need to access, set, or program switches inside the unit (front door of unit does not need to be opened). Programmable functions shall be entered on ash memory to insure program retention should power fail. The historical data base shall be maintained by battery backup. Multiple messages shall be displayed by automatically scrolling from each message to the next. Alarm conditions, in addition to being displayed, shall enunciate an audible alarm. A summary alarm relay shall be available for remote alarms. Additional test or service terminal shall not be required for any functions. The control shall include temperature anticipation, moisture level humidity control and automatic ush cycles. An alarm condition shall continue to be displayed until the malfunction is corrected. Multiple alarms shall be displayed sequentially in order of occurrence and only those alarms which have not been acknowledged shall continue to sound an audible alarm. The Data Alarm Processor-III panel shall perform an automatic self-test on system start-up. A user accessible diagnostic program shall aid in system component trouble shooting by displaying on the unit LCD screen the name of the controlled item, output relay number, terminal plug and pin number for each controlled item. The following automatic control functions shall be included: Selectable water under oor alarm action Sequential load activation Dehumidication lockout Automatic reheat element rotation Energy saver (glycol operation)* Hot water coil ush cycle* Energy saver coil ush cycle* Start time delay Humidity anticipation Compressor short cycle Automatic or manual restart Auxiliary chilled water operation* Chilled water coil ush cycle* DX activation on Energy Saver system*

The following conditions, data and normal functions shall be monitored and displayed: Temperature setpoint Current temperature Cooling Reheat Humidication Humidity setpoint Current humidity Dehumidication Current percentage of capacity utilized Current discharge temperature* Chilled water temperature*

The following switching and control functions shall be included: System On/Off switch Menu selection buttons Menu exit button Select buttons Manual override for: Alarm silence button blower, cooling, reheat 1, humidication, water valve

65

DATA AIRE SERIES 6 to 30 ton DX units Guide Specications, continued

The following historical data shall be available: High temperature last 24 hours Average percentage of capacity Low humidity last 24 hours Low temperature last 24 hours Alarm history (last ten alarms) Equipment runtimes High humidity last 24 hours

The following alarm functions shall be monitored and displayed when they occur in addition to enunciating an audible alarm: High temperature warning Low humidity warning Under oor water detected Temperature sensor failure Maintenance required Manual override Person to contact on alarm* Local alarm* Discharge air sensor failure* Low temperature warning Dirty lter No air ow Low voltage warning Humidity sensor failure Firestat tripped Custom message* Smoke detected* Fan motor overload* High humidity warning Humidier failure Power failure restart Low pressure on compressor warning Compressor short cycle warning High pressure on compressor warning High condensate water level* No water ow*

The following functions shall be programmable: Temperature setpoint Humidity setpoint (65-85o F, 18.3-29.4o C) (30-70% RH) Temperature deadband Humidity deadband ( 1-5o F/C) (1-15% RH) Manual diagnostics Date and time Reset equipment runtimes Audio alarm mode Reheat stages Firestat temperature alarm limit Temperature scale Calibrate humidity sensor Calibrate temperature sensor Automatic self-test Delay for optional alarms Dehumidication mode Person to contact on alarm No airow alarm time delay Cooling stage-to-stage deadband Water underoor alarm action Humidication desaturation cycle Message for optional alarm* Energy Saver lockout time delay* Humidier auto ush timer* Power problem or restart mode Calibrate discharge air sensor* Low discharge temperature alarm limit* Calibrate chilled water sensor* Chilled water temperature setpoint for Energy Saver High temperature alarm limit Low temperature alarm limit High humidity alarm limit Low humidity alarm limit Mode and stage response time Dene password Scheduled maintenance Humidier Water valve mode System start delay Humidity anticipation Chilled water temperature deadband Fan speed* Short cycle warning* Remote alarm 1, 2, 3, 4 selection*

The DAP III control panel support the following network protocols for integration with a Building Management System (BMS) for Computer Room Air Conditioning system monitoring and control. The following are the supported protocols: Modbus RTU, ASCII or TCP/IP Johnson Control Metasys N2 BACnet IP SNMP version 1 LonWorks SNVT BACNet MS/TP

* Some of the programmable selections, displays, or alarms may require additional components or sensors. 66

OPTIONS

Energy Saver Coil - The environmental control units shall be provided with an Energy Saver Coil. The Energy Saver Coil shall be an integral part of the unit and will be capable of providing the total cooling capacity. Whenever the incoming water/glycol temperature is below the setpoint of the water changeover thermostat, Energy Saver cooling shall be available. The Energy Saver shall operate in the following range: Return air setpoint plus deadband plus 2 degrees. The Energy Saver shall operate providing there is a need for cooling. The valve shall open at setpoint plus deadband. The valve shall modulate as long as the space is between setpoint plus deadband plus 2 degrees. If the temperature falls below the deadband minus setpoint, the valve shall close and the space shall be considered satised. While still in Energy Saver with the valve modulating, if the temperature goes beyond setpoint plus deadband plus 2 degrees, the Energy Saver valve shall close and mechanical (DX) cooling shall begin. The Energy Saver Coil shall include 3-way pressure control valves on the condenser circuits and 3-way valve on the economy coil. Common piping for the energy coil and condensers shall be provided. Energy Saver/Compressor Supplement - Units with Energy Saver shall be provided with compressor supplement if the Energy Saver is not sufcient as a stand alone system. When the incoming water/glycol temperature is below the setpoint of the water changeover thermostat, the Energy Saver shall be enabled (even if there is no call for cooling). Upon a call for cooling (setpoint plus deadband), the valve shall open proportionally - 10% for each 0.1 above setpoint plus deadband. The compressor shall come on at setpoint plus deadband plus 1.3 (the valve shall be 100% open at this point). The compressor shall go off at setpoint plus 1.3 The valve shall close proportionally - 10% for each 0.1 below setpoint. An air discharge sensor shall be factory mounted. Auxiliary Chilled Water Coil - Units shall be provided with an Auxiliary Chilled Water Coil. The existing chilled water loop shall be utilized with the Auxiliary Chilled water coil. Units shall operate using the chilled water for cooling. Upon a loss of water ow or an increase in room temperature the system shall bring on compressor (DX) cooling. Separate piping shall be provided for the chilled water coil and refrigeration connections. Remote Temperature and Humidity Sensors - Units shall be provided with remote temperature and humidity sensors. Sensors shall be provided in a plastic case for remote mounting. 25 feet of shielded cable shall be provided for eld wiring. Disconnect - The environmental control unit shall include a nonautomatic disconnect switch mounted in the high voltage section of the electrical panel. The operating mechanism shall prevent access to the high voltage electrical components until switched to the OFF position. The operating mechanism shall protrude through the decorative door. Smoke Detector - The environmental control unit shall be provided with a smoke detector. The smoke detector shall be mounted with the sensing element in the return air stream. When the smoke detector is activated, it shall immediately shut down the unit. Condensate Pump - Units shall be provided with condensate pumps. Pumps shall be factory mounted/wired or shipped loose for eld installation and shall include sump, motor, and automatic control. The pumps shall be rated for 130 GPH @ 20 foot maximum head (40 GPH @ 20 feet with check valve). Tandem Scroll Compressors - Provide units with tandem hermetic scroll compressors with two step modulation for stage control. Each circuit shall contain two scroll compressors. Modulation shall allow one or both compressors (per circuit) to run depending upon the load of the system, resulting in part-load efciency equal to full load efciency.

67

OPTIONS, continued

Semi-Hermetic Compressors - Units shall be provided with semi-hermetic compressors. Compressor shall have suction gas cooled motor, thermal overloads, vibration isolators, oil sight-glass, reversible oil pump, suction and discharge ports, manual reset high pressure switch, with a maximum operating speed of 1750 rpm. The compressors shall be installed with hot gas mufers, liquid line solenoids, and crankcase heater. Four Step Control - Provide cylinder unloading on semi-hermetic compressors. The unit microprocessor shall control the solenoid valves which activate the unloaders in response to the return air temperature. Compressor staging shall be: Step 1 - Lead compressor starts with unloader valve activated Step 2 - Lead compressor running at full load condition Step 3 - Lag compressor starts with unloader valve activated Step 4 - Lag compressor running at full load condition A minimum of one compressor shall be fully in response to a call from the unit microprocessor for dehumidication to maintain proper humidity control. Hot Gas Bypass - Units shall be provided with hot gas bypass. The hot gas bypass valve shall be installed between the compressor discharge line and the leaving side of the expansion valve through a side outlet distributor. The system with the evaporator under full load shall maintain pressure on the leaving side of the hot gas bypass valve to keep the valve port closed. Should the load on the evaporator decrease to the point where the coil is below the desired setting, the pressure on the discharge of the hot gas bypass shall put pressure on the diaphragm overcoming the spring pressure of the seat allowing some hot gas to mix with the normal liquid discharge of the expansion valve raising the evaporator pressure. 3-Way Water Regulating Valves - Units shall be provided with a 3-way head pressure actuated regulating valve. The maximum water pressure shall be ___ psi. Recommended with dual pump package. High Efciency Filters - The environmental control unit shall include 60% efcient lters (based on ASHRAE Std. 52.1-1992). The lters shall be four inch (4) deep pleated design. Pre-Filters - The environmental control unit shall have one inch (1) pre-lters in addition to the unit lters. Upow Plenum - Units with top (upow) discharge shall be provided with plenum. The plenum shall have a front discharge air grille and be fully insulated with one inch (1) thick, 11/2 pound density berglass insulation coated with neoprene. The plenum height shall be 18 inches and shall be painted to match the unit color. Floorstand - Units shall be provided with oorstands and vibration isolation pads. The oorstand shall be a complete welded base engineered to support the operating unit. The oorstand height shall be ___ inches and adjustable 2 inches. Pump Package - A centrifugal pump shall be provided to circulate water or glycol solution. The pump shall be rated for ____ GPM at ___ feet of head and shall operate on ___ volts. On dual pump applications it is recommended that a 3-way water regulating valve be used in lieu of the standard 2-way valve. Pump Auto-Changeover - Dual pump packages shall be provided with a pump auto-changeover control and NEMA 4 ow switch. The pump auto-changeover control shall be factory wired and mounted in the dry cooler control box. The pump autochangeover control shall provide automatic pump changeover in the event of a pump failure. Upon pump changeover, an audible alarm shall sound at the indoor unit and a message (STANDBY PUMP ON) shall be displayed on the indoor unit microprocessor. The NEMA 4 ow switch shall be eld installed. Pump Enclosure - A pump enclosure shall be provided for the centrifugal pumps(s). The enclosure shall be vented and weather resistant. Pumps shall be factory mounted in enclosure ready for eld piping and wiring. Extended Compressor Warranty-Extended compressor warranties are available from Data Aire. Contact your local representative for one that best suites your needs. 68

www.dataaire.com e-mail: sales@dataaire.com


A Member of the CS Group of Companies 2010 Data Aire Inc.

230 W. BlueRidge Avenue Orange, CA 92865 800-347-2473

Data Aire, Inc. reserves the right to make design changes for the purposes of product improvement, or to withdraw any design without notice.

DADX-R410A-052010-D

You might also like