Power System Analysis
Power System Analysis
two-winding
transformer current transformer
two-winding
transformer voltage transformer
generator capacitor
G2 Load B
Load A
One-line diagram
IEEE 30bus system
Impedance and Reactance Diagrams
1 T1 T2 3
2 Load B
Load A
E1 E2 E3
E1 E2 E3
actual value
per unit value =
base value
The per unit system values can also be expressed as per cent values.
Base value
Specify the base values of current and voltage,
base impedance, kilovoltamperes can be
determined
Quantities and base value selected
voltage, base value in kilovolts, kV
current, base value in ampere, A
Base values
Generally the following two base values are chosen :
The base power = nominal power of the equipment
The base voltage = nominal voltage of the
equipment
The base current and The base impedance are determined by
the natural laws of electrical circuits
Base values
Usually, the nominal apparent power (S) and
nominal voltage (V) are taken as the base values
for power (Sbase) and voltage (Vbase).
Z
For actual quantity that has complex number,
Z pu =
Per unit can be expressed as:
ZB
Per unit can be expressed in rectangular Z pu = Rpu + jX pu
form:
S pu = Rpu + jQpu
Power: S
S pu = = V pu I *pu
Sb
P
Ppu = = V pu I pu cos
Sb
Q
Q pu = = V pu I pu sin
The picture can't
be displayed.
Sb
exercise
A generator has an impedance of 2.65 ohms. What
is its impedance in per-unit, using bases 500MVA
and 22kV
Per Unit system for 3- Circuits
Have the same per unit values for line to line and line
to neutral quantities.
Make everything look like a single phase circuit.
Balanced three phase circuits can be solved in per
unit on a per phase basis after converting delta load
impedance to equivalent Y impedance.
Base value can be selected on a per phase basis or
on a three phase basis.
Per Unit system for 3- Circuits (Voltage)
VLL VLN
So: VLLpu = VLNpu =
VB,LL VB,LN
VB,LL = 3VB,LN
Per Unit system for 3- Circuits (Power)
S3 = 3S1
We know:
S3 S1
S =S
pu
3
pu
1 =
SB,3 SB,1
So:
SB,3 = 3SB,1
Per Unit system for 3- Circuits (Current)
We know:
S pu = V pu I pu
So:
S VLL ILL
S =V I
pu pu pu
=
SB,3 VB,LL IB
SB,3
IB =
3VB,LL
Per Unit system for 3- Circuits (Impedance)
IB SB,3 SB,3
3VB,LL
Example 1
Given base kVA for 3 phase systems is 30 000kVA and
voltage base line to line 120kV. Find:
SB,1
Vpu
VB,LN
VLN
For actual line-to-line voltage 108 kV, the line-to-neutral voltage, VLN is 108/ √3 = 62.3
Per unit value - example
ZB,old
Z npeuw = Z opl ud
Z B,new
V 2
But we always have : Z B = B
SB
2
S B,new V
Z npeuw = Z o lpdu B,old
S B,old V
B,new
Change of Base
If VB,new = VB,old
So
SB,new
Z npeuw = Z opl ud
S B,old
Example 2
The reactance of a generator designated X” is given as 0.25
per unit based on the generator’s nameplate rating of 18 kV,
500 MVA. The base for calculations is 20kV, 100 MVA. Find
X” on the new base
2
S new
V old
new
Z pu = Z pu
old
Bold Bnew
S V
B B
pu = 0.25
Zold VBold = 18 kV B = 500 MVA
Sold
VBnew = 20 kV Snew
B = 100 MVA
Example 2
pu = 0.25
Zold VBold = 18 kV B = 500 MVA
Sold
VBnew = 20 kV Snew
B = 100 MVA
2
100 18
Znew
pu = X"= 0.25 = 0.0405 per unit
500 20
Exercise 2
Generator rated at 10MVA, 20kV
XS = 0.9pu on the basis of the generator rating
Given SB,new =100MVA and VB,new=20kV
Find: X new
S
Solution:
Exercise 3
Transformer rated at 10MVA, 33/11kV
Z = 10% and R = 1%
Given SB,new=200MVA and VB,new=22kV (HV side transformer)
Find: i. Zbase(HV and LV sides)
ii. actual Z and R referred to primary and secondary
iii. Transformer losses in kW, if 0.033 p.u (selected base) of current
flow through R
Solution:
Procedure for Per Unit Analysis
1. Pick SBase for the system.
2. PickVBase according to line-to-line voltage.
3. Calculate Z for different zones.
Base
Vb1 Vb2
V1/V2
V2
Vb 2 = •V b1
V1
How to Choose Base Values ?
Divide circuit into zones by transformers.
Specify two base values out of IB ,VB , ZB , SB ; for
example, SBase and VBase
Specify voltage base in the ratio of zone line to line
voltage.
V1 :V2 V2 :V3 V3 :V4
Source
Vg = 13.2kV
Ig Zline = 10 + j100
~ Zload = 300
5 MVA 10 MVA
13.2 Δ – 132 Y kV 138 Y - 69 Δ kV
X1 = 0.1p.u. X 2 = 0.08p.u.
5 MVA 10 MVA
13.2 Δ – 132 Y kV 138 Y - 69 Δ kV
X1 = 0.1p.u. X 2 = 0.08p.u.
13.2kV 138kV
VB = x138kV = 13.8kV VB2 = x69kV = 138kV
1
132kV 69kV
5 MVA 10 MVA
13.2 Δ – 132 Y kV 138 Y - 69 Δ kV
X1 = 0.1p.u. X 2 = 0.08p.u.
Z B1 =
VB1
=
(13.8k ) 2
= 19.04 Z B2 =
VB2
=
(138k ) 2
= 1904 Z B3 =
VB3
=
(69k )2
= 476
SB 10M SB 10M SB 10M
SB31 10M S B32 10M SB33 10M
I B1 = = = 418.4 I B2 = = = 41.84 I B3 = = = 83.67
3 VB 1 3 13.8k 3 VB 2 3 138k 3 VB 3 3 69k
Step 4: All in Per Unit Quantities
Vg = 13.2kV T1 T2
Ig Zline = 10 + j100
~ Zload = 300
5 MVA 10 MVA
13.2 Δ – 132 Y kV 138 Y - 69 Δ kV
X1 = 0.1p.u. X 2 = 0.08p.u.
+
-
Calculate Vg in per unit
Calculate the new reactance for X1 and X2 in per unit
Calculate the impedance in per unit
Draw the impedance diagram
Step 4: All in Per Unit Quantities
X 2, pu = 0.08p.u.
2
+ S B,new V B,old
- Z npeuw = Z o lpdu Zload 300
S B,old V B , n e w Z load,p.u. = = = 0.63
Z B3 476
2
10MVA 13.2k
X 1,p.u. = 0.1 = 0.183
5MVA 13.8k
Vg 13.2kV
Vg,p.u. = = = 0.960
V B1 13.8kV Zline 10 + j100
Z line,p.u. = = = 5.2510−3 (1+ j10)
Z B2 1904
Step 5: One Phase Diagram & Solve
Zline,p.u. = 5.2510 −3 (1+ j10)
X1,p.u. = j0.183 X 2, pu = j0.08
+ Vg,p.u. = 0.960
- Zload,p.u. = 0.63
Vg,p.u. 0.960
I load,p.u. = = = 1.35 − 26.4
Z total,p.u. 0.70926.4
Vload,p.u. = Iload,p.u.Zload,p.u. = 0.8505 − 26.4
S load,p.u. = Vload,p.u. I load,p.u.
*
= 1.148
Ig,p.u. = I t-line,p.u. = Iload,p.u. = 1.35 − 26.4
Step 6: Convert back to actual quantities
Vg = 13.2kV
Ig Zline = 10 + j100
~ Zload = 300
HFAW'09
Advantages of P.U. system
Transformer equivalent circuit can be simplified by
properly specifying base quantities.
🞑 Give a clear idea of relative magnitudes of
various quantities such as voltage, current, power
and impedance.
🞑 Avoid possibility of making serious calculation error
when referring quantities from one side of transformer
to the other.
Advantages of P.U. system
Per-unit impedances of electrical equipment of
similar type usually lie within a narrow numerical
range when the equipment ratings are used as base
values.
🞑 Manufacturers usually specify the impedances of
machines and transformers in per-unit or percent in
nameplate rating.
Advantages of P.U. system
The circuit laws are valid in per unit systems, and
the power and voltage equation are simplified since
the factor √3 and 3 are eliminates in the per-unit
systems.
Ideal for the computerized analysis and simulation
of complex power system problems.
Advantages
Why Use the Per Unit System Instead of the
Standard SI Units?
Here are the main reasons for using the per unit
system:
When values are expressed in pu, the comparison of
electrical quantities with their "normal" values is
straightforward.
For example, a transient voltage reaching a
maximum of 1.42 pu indicates immediately that this
voltage exceeds the nominal value by 42%.
Advantages
The values of impedances expressed in pu stay fairly
constant whatever the power and voltage ratings.
For example, for all transformers in the 3 kVA to 300
kVA power range, the leakage reactance varies
approximately between 0.01 pu and 0.03 pu, whereas
the winding resistances vary between 0.01 pu and
0.005 pu, whatever the nominal voltage. For
transformers in the 300 kVA to 300 MVA range, the
leakage reactance varies approximately between 0.03
pu and 0.12 pu, whereas the winding resistances vary
between 0.005 pu and 0.002 pu.
Advantages
Similarly, for salient pole synchronous machines, the
synchronous reactance Xd is generally between
0.60 and 1.50 pu, whereas the subtransient
reactance X'd is generally between 0.20 and 0.50
pu.
It means that if you do not know the parameters for
a 10 kVA transformer, you are not making a major
error by assuming an average value of 0.02 pu for
leakage reactances and 0.0075 pu for winding
resistances.
Advantages
The calculations using the per unit system are
simplified. When all impedances in a multivoltage
power system are expressed on a common power
base and on the nominal voltages of the different
subnetworks, the total impedance in pu seen at one
bus is obtained by simply adding all impedances in
pu, without taking into consideration the transformer
ratios.
In a balanced 3-Φ system, the magnitude of voltages and
currents in every phase, is the same and is displaced by
120o.
i. rated voltage,
ii. rated power,
iii. phase impedance,
iv. type of connection (either Wye or Delta connection).
VL-base = 10 kV.
VA3Φ-base = 100 MVA.
The impedance diagram :
Example :
Find the load current, actual current in every component
and voltage drop in every component if the load voltage
is 1pu.
Vbase = 10 kV
VAbase = 50 MVA
Vbase-new = 20 kV
VAbase-new = 10 MVA,
Then
For Line
For load
Fault calculation