Cahaya Pandang

The document provides a detailed lighting design report for the Bukit Pandang area, including calculations for surface illuminance and specifications for luminaires. It outlines the total installed power of 5.74 kW and the use of a maintenance factor of 0.85. The average surface illuminance calculated is 140 lux, with minimum values noted in the report.

Uploaded by

this jannah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2 views3 pages

Cahaya Pandang

The document provides a detailed lighting design report for the Bukit Pandang area, including calculations for surface illuminance and specifications for luminaires. It outlines the total installed power of 5.74 kW and the use of a maintenance factor of 0.85. The average surface illuminance calculated is 140 lux, with minimum values noted in the report.

Uploaded by

this jannah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Bukit Pandang

PENERANGAN AREA KAWASAN BUKIT PANDANG


Date: 08-09-2025

Designer: INDRAJIT PRATAMA, ST

The nominal values shown in this report are the result of precision calculations, based upon precisely positioned luminaires in a fixed relationship to
each other and to the area under examination. In practice the values may vary due to tolerances on luminaires, luminaire positioning, reflection
properties and electrical supply.

CV. GLOBAL DESAIN KONSULTAN


JL. HASAN MUNADI SENDANGREJO RT.06 RW 07
NYATNYONO UNGARAN BARAT
SEMARANG

Telephone: 081225476154
Mobile Phone: 081225476154
E-Mail: cv.globaldesainkonsultan@gmail.com
CalcuLuX Area 7.7.0.1
Bukit Pandang CV. GLOBAL DESAIN KONSULTAN
PENERANGAN AREA KAWASAN BUKIT PANDANG Date: 08-09-2025

1. Summary

1.1 General Information

The overall maintenance factor used for this project is 0.85.

1.2 Project Luminaires

Code Qty Luminaire Type Lamp Type Power (W) Flux (lm)
B 12 5000K 60 1 * 5050 478.3 1 * 81320

Maintenance factor
Code
Luminaire Lamp
B 1.00 0.75

The total installed power: 5.74 (kWatt)

Number of Luminaires Per Arrangement:


Luminaire
Arrangement Code Power (kWatt)
B
Point 6 2.87
Point1 6 2.87

1.3 Calculation Results

(Il)luminance Calculations:
Calculation Type Unit Ave Min/Ave Min/Max
General Surface Illuminance lux 140 0.16 0.08

Philips Lighting B.V. - CalcuLuX Area 7.7.0.1 Page: 2/3


Bukit Pandang CV. GLOBAL DESAIN KONSULTAN
PENERANGAN AREA KAWASAN BUKIT PANDANG Date: 08-09-2025

2. Calculation Results

2.1 General: Graphical Table

Grid : General at Z = -0.00 m


Calculation : Surface Illuminance (lux)
80
70

23

32 40
60

38 55 73 85

34 57 90 130 157 148


50

44 79 136 202 250 234 187

95 176 257 284 281 229 143


40

173 255 288B 280 242 148 83

220 253 249 193 126 76


30

141 170 170 133 94 67 51

98 98 86 72 63 60 60
Y(m)
20

60 60 62 71 84 97 99

49 64 90 128 166 172 146


10

72 118 184 244 255 225 153

138 231 279 291 262 184


B
0

218 276 286 263 189 103

176 231 249 211 145 85 47


-10

145 158 134 95 60 37 22

86 75 57 40
-20

41 33
-30
-40
-50

-80 -70 -60 -50 -40 -30 -20 -10 0 10 20 30 40 50


X(m)

B 5000K 60

Average Min/Ave Min/Max Maintenance factors Scale


140 0.16 0.08 See summary 1:750

Philips Lighting B.V. - CalcuLuX Area 7.7.0.1 Page: 3/3