PROTECTION AND INTERLOCKING SCHEME OF MV SWITCHGEAR
MURTAZA HUSSAIN DY, MGR, SWITCHGEAR ENGINEERING DIV.
SWITCHGEAR IEC/IS
BHEL Manufacture Switchgear as per IEC:62271-1002001, IS:3427:1997/IEC:298:1990, IS:13118:1991/ IEC:56:1987
IEC:62271-100-2001 High voltage alternating current circuit breaker.
IS:3427:1997/IEC:298:1990 AC Metal enclosed switchgear and Controlgear for rated voltage above 1 kV & upto & including 52 kV. IS:13118:1991/IEC:56:1987 Specification for High Voltage Alternating current circuit breaker.
SWITCHGEAR
A GENERAL TERM COVERING SWITCHING DEVICES AND THEIR COMBONATION WITH ASSOCIATED CONTROL, MEASUREING, PROTECTIVE AND REGULATING EQUIPMENT, ALSO ASSEMBLIES OF SUCH DEVICES AND EQUIPMENT WITH ASSOCIATED INTERCONNECTIONS, ACCESSORIES, ENCLOSURE AND SUPPORTING STRUCTURES.
CIRCUIT BREAKER
A MECHANICAL SWITCHING DEVICE CAPABLE OF MAKING, CARRYING, AND BREAKING CURRENTS UNDER NORMAL CIRCUIT CONDITIONS AND ALSO MAKING, CARRYING FOR A SPECIFIED TIME AND BREAKING CURRENTS UNDER SPECIFIED ABNORMAL CIRCUIT CONDITIONS SUCH AS THOSE OF SHORT CIRCUIT.
CHAMBERS IN SWITCHGEAR
Breaker Chamber Busbar Chamber
HT CHAMBER
CT/PT Chamber
Instrument Chamber (Relay/meters/switches etc.)
LT CHAMBER
LOCATION OF VARIOUS MAJOR COMPONENTS IN SWITCHGEAR
Circuit Breaker Current Transformer Instruments Potential Transformer Surge Suppressor Busbar
INSERT PICTURE
SWITCHGEAR IN POWER SYSTEM CAN ACT AS :
Incomer Feeder TIE Feeder Transformer Feeder Motor Feeder Bus Coupler Plant Feeder / Outgoing feeder Bus PT Line PT
Incomer Feeder: Switchgear Panel intended for supply power to the Switchboard. TIE Feeder: Switchgear panel which connects the two same voltage level switchboard. Power can flow in either direction TIE feeder. Motor Feeder: Switchgear panel employed for feeding the motor.
Transformer Feeder: Switchgear panel employed for feeding the transformer.
Plant / Outgoing Feeder: Switchgear panel employed for supply power to other switchboard. Bus PT: Switchgear panel having voltage transformer and used for the detection of bus voltage. Feeder/Line PT: Switchgear panel having voltage transformer and used for the detection of feeder/line side voltage.
TIE TIE
INCOMER INCOMER LINE PT LINE PT OUTGOING/ OUTGOING/ PLANT FDR PLANT FDR MOTOR FDR MOTOR FDR
BUS PT BUS PT
Typical Power Plant Single Line Diagram (SLD) (PART)
TRAFO FDR TRAFO FDR
SWITCHGEAR INTERLOCK SCHEME
The major functions of switchgears are protection, control and facilitating the maintenance of the electrical network including the switchgear itself. Control and inter-locking schemes constitute a very important aspect of medium voltage switchgears. The switching operation involves a variety of control and inter-locking schemes. Following are the variety of schemes which are being used:
Safety Interlocks & schemes using position limit switches; Closing Scheme; Tripping schemes; Trip circuit supervision schemes; Voltage selection schemes; Alarm schemes, Synchronizing schemes and Automatic supply transfer schemes.
SWITCHGEAR INTERLOCK SCHEME
Safety Interlocks & schemes using position limit switches; Closing Scheme; Tripping schemes; Trip circuit supervision schemes; Voltage selection schemes; Alarm schemes, Synchronizing schemes and Automatic supply transfer schemes.
SAFETY INTERLOCKS: i) The VCB truck cannot be racked in or out unless circuit breaker is in 'Open' condition. The VCB truck can not be racked in unless secondary Plug & socket are engaged. The circuit breaker electrical closing operation is not possible unless secondary plug & socket are engaged. The secondary plug and socket can not be disengaged When the VCB truck is in 'Service or any Intermediate position between test and service positions. The circuit breaker closing operation is not possible unless the truck is in 'Service' or 'Test' position. The interlock mechanism cannot be operated unless the circuit breaker is in 'Open' condition.
ii)
iii)
iv)
v)
vi)
VII)
Inter changeability of trucks of different current ratings are not possible.
VIII)
Provision for Earthing
Earthing feature & Interlock (operation of Earthing module) a) FEB Feeder Earthing Breaker b) BEB Bus Bar Earthing Breaker
IX)
Earthing Truck (Test to Service) Limit Switch
Enable tripping of upstream/ downstream breaker Block closing of upstream/ downstream breaker
X)
Fool proof Mechanical interlock arrangement for Busbar earthing
SWITCHGEAR INTERLOCK SCHEME
Safety Interlocks & schemes using position limit switches; Closing Scheme; Tripping schemes; Trip circuit supervision schemes; Voltage selection schemes; Alarm schemes, Synchronizing schemes and Automatic supply transfer schemes.
SWITCHGEAR INTERLOCK SCHEME
Safety Interlocks & schemes using position limit switches; Closing Scheme; Tripping schemes; Trip circuit supervision schemes; Voltage selection schemes; Alarm schemes, Synchronizing schemes and Automatic supply transfer schemes.
CLOSING CIRCUIT : The closing circuit consists of fuses, control switch, anti pumping device, spring charged limit switch & closing coil. Closing command is executed by control switch through breaker NC contact when spring is charged. All auxiliary switch contacts position changes i.e. NO contact closes and NC contact opens. The CB can be closed manually by green coloured manual close knob provided in the mechanism box.
ANTI PUMPING : Anti pumping device prevent the CB from getting repeated closing and tripping impulses when a continuous closing command is given before the tripping impulse is withdrawn.
SWITCHGEAR INTERLOCK SCHEME
Safety Interlocks & schemes using position limit switches; Closing Scheme; Tripping schemes; Trip circuit supervision schemes; Voltage selection schemes; Alarm schemes, Synchronizing schemes and Automatic supply transfer schemes.
SWITCHGEAR INTERLOCK SCHEME
Safety Interlocks & schemes using position limit switches; Closing Scheme; Tripping schemes; Trip circuit supervision schemes; Voltage selection schemes; Alarm schemes, Synchronizing schemes and Automatic supply transfer schemes.
Tripping Schemes
Shunt Tripping Schemes
Series Tripping Schemes
SHUNT TRIPPING CIRCUIT :
The tripping circuit consists of fuses, control switch, protective relay & tripping coil. Breaker can be opened intentionally by control switch & on fault, breaker gets tripping command from relay. All aux. switches will restore their original positions i.e. NO will open and NC will close.
Note : The tripping spring gets charged while the closing spring is discharged.
Series Tripping Schemes
Using Relays Using Summation CT Using Motor Protection Circuit Breaker (MPCB) Using Time Limit Fuses
PANEL ILLUMINATION : 40W filament lamp is provided inside the instrument panel. The door operated panel illumination lamp gets automatically lighted on opening the door.
3 PIN SOCKET& SWITCH: 5/15 Amps, 240 V, 5 Pin socket with piano switch is also provided on the panel for hand lamp.
ANTI CONDENSATION :
Two tubular heaters with thermostat and piano switch are provided for anti condensation in breaker chamber and CT chamber.
SWITCHGEAR INTERLOCK SCHEME
Safety Interlocks & schemes using position limit switches; Closing Scheme; Tripping schemes; Trip circuit supervision schemes; Voltage selection schemes; Alarm schemes, Synchronizing schemes and Automatic supply transfer schemes.
SWITCHGEAR INTERLOCK SCHEME
Safety Interlocks & schemes using position limit switches; Closing Scheme; Tripping schemes; Trip circuit supervision schemes; Voltage selection schemes; Alarm schemes, Synchronizing schemes and Automatic supply transfer schemes.
Trip Circuit Supervision Schemes
The Trip circuit extends beyond the protection relay and other components such as fuses, relay contacts, switches etc requires considerable amount of circuit breaker wiring with intermediate terminal boards. These interconnections coupled with the importance of the circuit, results in the requirement to monitor the integrity of the circuit .
SWITCHGEAR INTERLOCK SCHEME
Safety Interlocks & schemes using position limit switches; Closing Scheme; Tripping schemes; Trip circuit supervision schemes; Voltage selection schemes; Alarm schemes, Synchronizing schemes and Automatic supply transfer schemes.
SWITCHGEAR INTERLOCK SCHEME
Safety Interlocks & schemes using position limit switches; Closing Scheme; Tripping schemes; Trip circuit supervision schemes; Voltage selection schemes; Alarm schemes, Synchronizing schemes and Automatic supply transfer schemes.
Voltage Selection Schemes
Need for Voltage Selection scheme ?
Voltage signals to instruments and meters mounted on switchgear panels are derived from the potential transformer (PTs). These PTs are either Bus connected or Feeder connected. Incase of fault any source feeder, arrangement should be made in such a way that PT signal should be available to meters and instruments
SWITCHGEAR INTERLOCK SCHEME
Safety Interlocks & schemes using position limit switches; Closing Scheme; Tripping schemes; Trip circuit supervision schemes; Voltage selection schemes; Alarm schemes, Synchronizing schemes and Automatic supply transfer schemes.
SWITCHGEAR INTERLOCK SCHEME
Safety Interlocks & schemes using position limit switches; Closing Scheme; Tripping schemes; Trip circuit supervision schemes; Voltage selection schemes; Alarm schemes, Synchronizing schemes and Automatic supply transfer schemes.
Alarm Schemes
Alarm Cancellation Scheme Alarm Annunciation Scheme
SWITCHGEAR INTERLOCK SCHEME
Safety Interlocks & schemes using position limit switches; Closing Scheme; Tripping schemes; Trip circuit supervision schemes; Voltage selection schemes; Alarm schemes, Synchronizing schemes and Automatic supply transfer schemes.
SWITCHGEAR INTERLOCK SCHEME
Safety Interlocks & schemes using position limit switches; Closing Scheme; Tripping schemes; Trip circuit supervision schemes; Voltage selection schemes; Alarm schemes, Synchronizing schemes and Automatic supply transfer schemes.
Synchronizing Schemes
To bring new bus (source) into the switchboard when old one is running and shifting to new one. To meet synchronizism that means two AC supplies are correctly paralleled following condition should be satisfied. a) The voltages of the two supplies must be within acceptable limits. b) The frequencies of the two supplies must be within acceptable limits. c) The phase difference of the two supplies must be within acceptable limits. Methods adopted for synchronization are : Manual Synchronization By Check Synchronizing Relays A check synchronizing relay is used to prevent inter-connection of two badly synchronized supplied. Its dual purpose is to Safeguard manual synchronizing.
SWITCHGEAR INTERLOCK SCHEME
Safety Interlocks & schemes using position limit switches; Closing Scheme; Tripping schemes; Trip circuit supervision schemes; Voltage selection schemes; Alarm schemes, Synchronizing schemes and Automatic supply transfer schemes.
SWITCHGEAR INTERLOCK SCHEME
Safety Interlocks & schemes using position limit switches; Closing Scheme; Tripping schemes; Trip circuit supervision schemes; Voltage selection schemes; Alarm schemes, Synchronizing schemes and Automatic supply transfer schemes.
Automatic Supply Transfer Schemes
Requirement of Automatic Bus Transfer Scheme ? Unit Switchgear Station Switchgear
Modes of Bus Transfer
A. Manual Bus Transfer i) Without Voltage Interruption ii) With Voltage Interruption a) Slow changeover b) Fast changeover B. Automatic Bus Transfer (under fault condition) with Voltage Interruption a) Slow changeover b) Fast changeover
Electrical Interlock Electrical Interlock in Closing Circuit in Closing Circuit
Electrical Interlock Electrical Interlock in Tripping Circuit in Tripping Circuit
Electrical Interlocking scheme is guided by the logic diagram.
Protection Schemes for Medium Voltage Switchgear
Importance of Protection System in Electrical System ? 5-S Security Principles : Protective system should be reliable so that security of supply is ensured.
Sensitivity : Protective system should be able to sense minimum value of fault current, thereby reducing the consequent damage. Speed : Protective system should be able to isolate fault in the shortest possible time. Selectivity : Protective system should be able to select and trip only the nearest circuit breaker. Stability : Protective system should not operate for external faults.
FAULT : It is defined as any abnormal condition, which causes reduction in the basic insulation level strength of system. FAULT DETECTION : POSITIVE, NEGATIVE & ZERO Phase sequence component of system.
PROTECTION SCHEMES IN MV SWITCHGEAR
Non Directional Over Current for Phase Faults (50/51) Non Directional Over Current for Earth Fault (50N/51N) Directional Over Current for Phase Faults (67) Directional Over Current for Earth Fault (67N)
UNIT PROTECTION SCHEME
In Unit Protection sections of power system are protected individually as a complete unit without reference to other section. Some of the Unit scheme which MV Switchgear employed Pilot Wire Protection Scheme For the protection of CABLE connecting two Feeder Bus Differential Protection Scheme For the protection of BUSBAR Motor/ Transformer Differential Protection Scheme For the protection of MOTOR/ TRANSFORMER WINDINGS Restricted Earth Protection Scheme For the protection of TRANSFORMER WINDINGS
TRANSFORMER PROTECTION
Non- Directional Over Current and Earth Fault Protection (50/51/50N/51N) Sensitive Earth Fault Protection (50N/2) Differential Protection (87T) Restricted Earth Fault Protection (64R) Incipient Faults (49/63TX)
MOTOR PROTECTION
Wide range of A.C Motors Motor characteristics due to various duties All Motor needs protection and choice should be independent of a type of motor & load connected.
NEED FOR PROTECTION
Allowing operation under normal conditions. Quick isolation from supply under abnormal conditions. Averting damage to the motor & driven mechanism. Enhancement of life of motor.
A. MOTOR INDUCED
MOTOR PROTECTION
1. INSULATION FAILURE 2. BEARING FAILURE 3. MECHANICAL FAILURE 4. LOSS OF FIELD (SYNCHRONOUS MOTOR)
B. LOAD INDUCED
1. OVERLOAD/ UNDERLOAD 2. JAMMING 3. HIGH INERTIA 1. HIGH AMBIENT TEMPERATURE 2. HIGH CONTAMINATED LEVEL-BLOCKED VENTILATION 3. COLD, DAMP AMBIENT TEMPERATURE
C. ENVIRONMENT INDUCED
D. SOURCE OR SYSTEM INDUCED
1. PHASE FAILURE 2. OVER VOLTAGE/UNDER VOLTAGE 3. PHASE REVERSAL 4. OUT-OF-STEP
E. OPERATION AND APPLICATION INDUCED
1. SYNCHRONIZING, CLOSING OR RECLOSING OUT OF PHASE 2. HIGH DUTY CYCLE 3. JOGGING
MOTOR PROTECTION
Thermal Over Load protection (49) Single phasing/ Negative Phase Sequence Protection (46) Short-circuits between phases or between phase and earth in the motor winding or its connections. (50/51) Partial or complete collapse of voltage (27) Locked rotor (51S) Start or Stall Protection(48/51LR) Earth Fault Protection (50N) Loss-Of-Load Protection (37) Out of Step Protection (46) RTD/BTD Protection (26) Limitation of the number of start, Time between start (66)
PROTECTION AGAINST SWITCHING SURGES: What is an Electrical Surge ? External surge & Internal surge
Atmospheric Lightning cause External surge Switching action of devices cause internal surge
CAUSES OF SURGE GENERATION: Normal Switching On of a stationary motor. Normal switching Off of a stationary motor. Switching a Stalled motor or one running upto speed.
PROTECTION AGAINST SWITCHING SURGES:
SURGE
PROTECTION DEVICES:
These devices limits the over voltages in electrical system to the specified protection level, principally lower than the withstand voltage of equipment.
a/ C-R type surge suppressors. b/ ZnO type surge arrestors.
CUSTOMER SPECIFIC SCHEME
BUS DIFFERENTIAL
PILOT WIRE PROTECTION
MOTOR RE-ACCELERATION
MOTOR DIFFERENTIAL
TWO OUT OF THREE BREAKER SCHEME
REVERSE BLOCKING SCHEME MECHANICAL INTERLOCKING SCHEME
NUMERICAL RELAYS AND COMMUNCATION SYSTEM
SYSTEM ON UCA2- IEC 61850
OPERATOR INTERFACE HMI & MAINTENANCE WEB access NR
NR
NR
FAST ETHERNET UCA2- IEC 61850
HV FEEDER BAYS
DC DC NR NR Main protection EHV FEEDER BAY I/Os I/Os NR COMMON BAY NR MV FEEDER BAYS NR NR NR
NR
NR
NR
FIG: 1
MV FEEDER BAYS
To ECS
HMI
Redundant Modbus RTU Link (RS 485)
GATEWAY
Laserjet Printer Ethernet Switch Ethernet Switch
Numerical Relays
Numerical Relays NR NR NR NR GPS
NR
NR
08 07 06 05 04 03
02
CPU
01
08 07 06 05 04 03
02
CPU
01
BIU 24x
Data Concentrator
Data Concentrator
NR
Ethernet Modbus (RS 485) Co-Axial Cable
NR
NR
NR
NR
BIU 24x
NR
NR
NR
Numerical Relays
Numerical Relays
FIG : 2
HMI
PROGRAMMER ROOM
LASER PRINTER
HMI
TO STATION LAN
FO
CER ROOM
FO DATA CONCENTRATOR DATA CONCENTRATOR
FO
TO DDCMIS (ON OPC)
TO DDCMIS (ON OPC)
MV SWGRS
SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH
ETHERNET SWITCHES (IEC61850) 16/8 CHANNEL NUMERICALRELAYS IN SWGR PANELS
LT SWGRS
SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH
FIG : 4
LOCATION CENTRAL CONTROL ROOM
TO MAIN SCADA
DATA CONCENTRATOR FO FO
(TYPICAL)
DATA CONCENTRATOR
TO MAIN SCADA
33KV SWGRS
SWITCH
SWITCH
(TYPICAL)
ETHERNET SWITCHES (IEC61850) 16/8 CHANNEL
11KV
SWITCH SWITCH
SWGRS
(TYPICAL)
NUMERICALRELAYS IN SWGR PANELS
LT
SWITCH
(TYPICAL)
SWITCH
SWITCH
SWGRS
FIG : 5
STAR ARCHITECTURE
SCADA/EMS
GATEWAY substation level
OI
ETHERNET SWITCH
DC NR
DC NR
DC NR
NR
NR
NR
NR
NR
NR
FIG : 6
REDUNDANT RING ARCHITECTURE
SCADA/EMS
GATEWAY substation level ETHERNET SWITCH
OI
DC DC DC NR NR
C264
NR
NR
FIG : 7
DOUBLE REDUNDANT RING ARCHITECTURE
SCADA/EMS OI GATEWAY
ETHERNET SWITCH
ETHERNET SWITCH
LAN n1
LAN n2
LAN: Local Area Network
DC DC
NR
FIG : 8
NR
NR
NR
Communication Standards Overview
Indications Commands Measured and MeteredValues Time Synchronisation Fault Records International StandardInteroperability Process Bus Communication Engineering support Data Transmission Transmission Speed [Mbit/s]
IEC 103
PROFIBUS DNP V3.00
Modbus without time stamp
UCA2
IEC 61850
No No Master/ Slave 0.19
No
No
Event Driven 100
without without time stamp time stamp
No No
No No No
No No Master/ Slave 12
No No Master/ Slave 0.12
No No Master/ Slave 0.12
No No Event driven 100
CABLE DIFFERENTIAL PROTECTION
CABLE DIFFERENTIAL PROTECTION
REVERSE BLOCKING LOGIC
Reverse blocking principle is adopted to cut down the grading time of upstream breaker of HT stream. The down stream protection when operated on a fault shall block upstream protection. For this one contact of short circuit and earth fault protection of each outgoing feeder on one switchboard shall be paralleled, and connected to digital input of numerical relay in incomer panel. The digital input if not energized allows the fast operation of upstream protection. however, delay protection shall always be available
INCOMER LOGIC
TIE FEEDER LOGIC
MECHANICAL INTERLOCKING SCHEME
WHY SUCH SCHEME IS REQUIRED ? It is required to prevent opening of CT cum CABLE termination & Busbar chamber under live-circuit condition. BASIC PRINCIPLE OF OPERATION :Under this scheme rear side bolted covers can be removed only when specific key is applied on CASTELL type mechanical interlocks located on covers and key is rotated 90 deg. Clockwise.
The mechanical interlocks and keys are arranged to achieve following requirements :
For opening of the Bolted covers of CT/Cable Chamber of Outgoing feeder For opening the bolted covers of CT/Cable chamber of Incomer feeders panels For opening the bolted covers of the bus chamber of any panel
THANK YOU