0% found this document useful (0 votes)
62 views21 pages

SR750 & SR760 FEEDER Management Relays

The document describes Schweitzer Engineering Laboratories' SR750 and SR760 feeder management relays, which provide total protection, control, metering, and monitoring for utility distribution feeders. The relays meet customer requirements through features like overcurrent protection, autoreclosing, synchrocheck, metering, communications, inputs and outputs, and a user interface. They offer benefits like a full protection and metering package, easy setup, flexibility, and reliability.

Uploaded by

sayedmh
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
62 views21 pages

SR750 & SR760 FEEDER Management Relays

The document describes Schweitzer Engineering Laboratories' SR750 and SR760 feeder management relays, which provide total protection, control, metering, and monitoring for utility distribution feeders. The relays meet customer requirements through features like overcurrent protection, autoreclosing, synchrocheck, metering, communications, inputs and outputs, and a user interface. They offer benefits like a full protection and metering package, easy setup, flexibility, and reliability.

Uploaded by

sayedmh
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 21

SR750 & SR760 FEEDER MANAGEMENT RELAYS

Total Protection, Control, Metering & Monitoring of Utility Distribution Feeders

Presentation Overview
k

Requirements k Meeting the Needs k Cost Analysis

Our Strengths k Key Benefits k Ordering

Customer Requirements
k

Protection k Control k Monitoring k Metering

Communication k Inputs & Outputs k User Interface k Reliability

Meeting the Needs of Protection


k

Phase Timed Overcurrent (51P)


k
k

Voltage Restraint
(12 selectable curves plus 2 Flexcurves)

k k k k

Ground Timed Overcurrent (51N) Phase & Ground Loset Overcurrent (50PL, 50NL) Phase & Ground Hiset Overcurrent (50PH, 50NH) Phase & Ground Directional Control
k k

Zero Sequence (67P) Negative Sequence (67N)

k k k k k

Negative Sequence Instantaneous (46/50) and Time (46/51) Overcurrent Voltage Phase Reversal (47) Negative Sequence Overvoltage (59Q) Undervoltage & Overvoltage (27-1, 27-2, 59-1, 59-2) Underfrequency & Overfrequency (81U-1, 81U-2, 81O-1, 81O-2)
5

Meeting the Needs of Control


k k k

Full Remote/Local Control Manual Close Control 4 ShotAutoreclose (760)


k k

TOC Curves Selection Between Reclosures Current Supervison

k k k k k k

Synchrocheck (Voltage, Phase Angle and Frequency) Cold Load Pickup Power Factor Control Load Shedding & Restoration Control 4 Settings Groups Transfer scheme
6

Cold Load Pickup

Capacitor Switching

Meeting the Needs of Monitoring


k

Event Recorder (Last 128 Events) k Trace Memory (10 x 16 Cycle Captures) k Fault Locator k Breaker Trip & Close Coil Detection k Breaker Failure k VT Failure k Total Breaker Arcing
9

Waveform Analysis

10

Breaker Arcing

11

Meeting the Needs of Metering


k

Individual Voltages & Currents k Real, Reactive & Apparent Power Demand k Real & Reactive Power Costs & Usage k Running & Maximum Demand Levels k Frequency & Power Factor k Synchronizing Voltage & Frequency

12

Meeting the Needs of Communications


k

RS485/RS422 Serial Port (PLC, SCADA, PC, DNP 3.0 etc.) k Front Panel RS232 Program Port k Fully programmable front keyboard with a 40 character display & status indicators

13

Meeting the Needs of Inputs


k

1 analog input channel k Universal Power Supply (ac/dc) k 3 phase CTs & VTs k Zero Sequence ground CT k 14 selectable logic inputs (21 functions)

14

Meeting the Needs of Outputs


k

6 E/M aux relays, 10A Continuous & 30A make/carry k E/M trip, and close relays 20A Continuous & 40A make/carry (0.2s) k 1 solid state, 15A @ 250Vdc for 500ms k 8 analog outputs

15

Meeting the Needs of User Interface


k

Setup Software k Flash Memory for Future or Utility Upgrades or modifications k Fully Programmable keyboard with 40 character display and status indicators k Fast and easy to use k Draw out construction
16

Meeting the Needs of Reliability


k

Extensive IEC & ANSI Testing k Complete Burn-in and testing on Relays k Self Testing k Draw out Case (no external hardware) k Front Door with Gasket and Lock Provision k Heavy Duty Terminals k ISO 9002 Certified, UL, CSA, ACA (Australian Standard) & UK Approvals k Halt testing and CE
17

Cost Analysis
k

Full Protection Package k Full Metering Package complete with Transducers k Time Saving Fast and Easy User Setup k Programmable inputs and outputs k Fault Recording and Simulation Testing

18

Our Strengths
k

Customer Input for Design & Application k High Quality & Dependable Products k Built in Flexibility including Flash Memory k Continuous Upgrading & Windows Software k Full Technical & Applications Service

19

Key Benefits
k

Combines all elements into one, easy to use, reliable, cost effective package: Protection Control Monitoring Metering Communications User Interface

20

Ordering
k k k k k

k k

Specify SR 750 or SR 760 Specify phase current of 5 amp or 1 amp Specify ground current of 5 amp or 1 amp Specify sensitive ground current of 5A or 1A. LO Power Supply range is - DC: 20 to 60V AC: 20 to 48 V @ 48 to 62 Hz HI Power Supply range is - DC: 88 to 300 V AC: 70 to 265 V @ 48 to 62Hz Specify Analog outputs: 0-1mA, 0-5mA, 0-10mA and 420mA Specify Breaker Closed LED: Red or Green
21

You might also like