Low Voltage
Canalis
Catalogue 2010
prefabricated busbar trunking from 20 to 400 A
Canalis, a comprehensive and consistent for lighting and power distribution
A new path for achieving your electrical installations
Canalis is part of a comprehensive offer of products that are perfectly coordinated to meet all medium and low voltage electrical distribution requirements. All of these products have been designed to work together: electrical, mechanical and communication compatibility. The electrical installation is thus both optimised and high-performance.
Optimum system performance is ensured by coordination between the protection circuit breakers and the busbar trunking used for decentralised distribution. Decentralised electrical distribution with total coordination perfectly satisfies all your requirements in terms of safety, continuity of service, upgradeability and simplicity. Decentralised electrical distribution with total coordination is the ideal solution for a wide range of applications including factories, warehouses, commercial premises and laboratories.
busbar trunking system in all types of buildings
Easier
Coordination Schneider Electric proposes coordinated busbar trunking and circuit breaker combinations for all your applications. For typical applications with power ratings up to 630 kVA, a solution including the low-voltage electrical switchboard, circuit breakers and Canalis busbar trunking ensures an installation sized to handle all short-circuit levels encountered. Design With Canalis busbar trunking, electrical power is available throughout your installation. The electrical installation can be designed without knowing the exact location of the equipment to be supplied. Operation Canalis opens the door to total upgradeability throughout the installation. Tap-off units with standard performance circuit breakers can be installed at any point along the busbar trunking run, whatever the prospective short-circuit current.
Safer
Decentralised distribution system When all aspects are coordinated, safety and continuity of service are maximised. The combination of cascading and discrimination techniques guarantees optimum safety and continuity of service. Design Total discrimination for enhanced protection as standard and at a lower cost. Operation Any changes to your installation are carried out in complete safety. Tap-off units can be plugged in and out with the trunking live. They are equipped with interlocking systems to prevent incorrect mounting. Coordination guarantees their installation at any point on the busbar trunking system.
Canalis for the decentralised distribution
Canalis busbar trunking
b For lighting and power socket distribution. b For medium and high power distribution.
Canalis components are available from your official distributor... in less than one hour.
Canalis, closer to you
Canalis perfectly integrates into your environment
b The Canalis KN and KS ranges are now white (RAL 9001).
More than 50,000 km of Canalis busbar trunking have been sold around the world.
Canalis range is fully compatible with the existing range
Contents
11 points that make the difference Presentation
Canalis KDP and KBA For lighting and power socket distribution Canalis KN and KS For low and medium power distribution
6 7
Where to use Canalis
Canalis, an installation that matches your inspiration! 8
Catalogue numbers
Canalis KDP trunking, 20 A For lighting and power socket distribution Canalis KBA trunking, 25 A For lighting and power socket distribution Canalis KN trunking, 40 to 160 A For low-power distribution Canalis KS trunking, 100 to 400 A For medium-power distribution 16 14 12 10
Dimensions
Canalis KDP trunking For lighting and power socket distribution Canalis KBA trunking For lighting and power socket distribution Canalis KN trunking For low-power distribution from 40 to 160 A 21 Canalis KS trunking For medium-power distribution from 100 to 400 A 23 19 18
Simplified design guide
Summary of performance characteristics 29
CanBrass design and quotation software
Tools and assistance by your side 30
11 points
For you, the electrical contractor
Canalis offers a number of advantages thanks to prefabricated design and qualities of Canalis
1 2 3 4
Maximise safety
Interlocking systems prevent mounting errors and reduce inspection times. Work is carried out safely without exposure to live connections. Live parts in Canalis tap-off units are not accessible. Tap-off units can be added and removed with the trunking energised. Interlocking devices eliminate connection errors. The PE conductor is connected before the phase and neutral conductors to enhance protection.
Control deadlines
Prefabricated design ensures smooth work flow. Installation times can be precisely planned in advance and, if plans must be changed, a fast and effective solution is always available with the adaptable and upgradeable Canalis system. The result is improved productivity.
Make modifications easy
With Canalis, electrical equipment can be moved or a machine added easily and quickly. That is the type of service that customers appreciate. With cables, the same modification could take over a day. That can become a real problem if another job has already been scheduled. What is more, customers today expect this type of service at no extra cost.
Create a new image for electrical contracting
The worksite remains clean, with no cable ends or waste scattered about. Stand out from the crowd and gain customer recognition by installing modern upgradeable systems.
that make the difference
For your customer
5 6 7 8 9 10 11
Provide greater continuity of service
In the industrial sector, customers want continuity of service. Canalis avoids costly production shutdowns. Tap-off units can be connected or disconnected with the trunking live. This makes it possible to add or remove loads without cutting power to the rest of the installation.
Offer quick modifications
at no cost to you! Accept last-minute changes with a smile. Your customers will be even more satisfied and that means more business for you. The need to change the electrical distribution network will no longer be an obstacle to development projects.
Offer total freedom for upgrades
Your customers will have access to electrical power throughout their installations. Easy upgrading of the electrical installation become a routine part of future investment projects.
Offer flexibility in machine layout
without taking any risks on your quote. In the early stages of a project, firm information on machine layout is not always available. The customer nevertheless needs a good idea on the costs and deadlines that you can meet. With Canalis, you have the solution in hand because: b the product can handle any and all modifications, b worksite uncertainties are reduced to a minimum and deadlines remain under control, b the customer is reassured, they now have the time to analyse and finalise the layout. Canalis offers a degree of flexibility unmatched by any conventional solution.
Offer a reusable system
Canalis is 100% reusable, producing major savings when changing layouts or increasing power ratings.
Simplify maintenance
Due to successive modifications, many customers lose a clear understanding of their electrical installation over the course of time. With Canalis, the entire distribution network remains clear, consistent and easy to understand, whatever the changes.
Offer an attractive solution
Provide your customer with a discreet product that blends in with the on-site architecture. This represents a clear advantage over cable trays running under ceilings and along walls. This added touch will show your customer that your know-how goes beyond technical aspects.
Presentation
Canalis KDP and KBA
For lighting and power-socket distribution
KDP For lighting and power-socket distribution
b Flexible 20 A trunking b Used when the luminaires are attached to the building structure (false ceilings, beams, etc.) b Available in 192-metre reels, single-phase or three-phase b Fixing systems for all types of building structures b 10 and 16 A tap-off units, with fixed polarity or phase selection.
A special tap-off unit for lighting control
The installation is finished in a snap Three levels of illuminance
KBA For supply and fixing of luminaires
b Rigid 25 A trunking b Available in 3-metre lengths, single-phase or three-phase b 10 and 16 A tap-off units, with fixed polarity or phase selection.
Very rigid carrier rail
The installation is finished in a snap 3 illuminance levels in three-phase systems
Canalis KN and KS
For low and medium-power distribution
KN Trunking for low-power distribution from 40 to 160 A
b For loads rated 16 to 63 A b For supply of Canalis KBA or KDP lighting systems b Available in 3-metre lengths b Tap-off units with circuit breaker or fuse protection or SPD (Surge Protection Device) b Tap-off units with power sockets.
Unmatched upgrading possibilities
500 m
The installation is finished in a snap
KS Trunking for medium-power distribution from 100 to 400 A
b For loads rated 25 to 160 A b Available in 3-metre lengths b Tap-off units with circuit breaker or fuse protection or SPD (Surge Protection Device) b Tap-off units with power sockets.
Light and easy to handle
The installation is finished in a snap Excellent contact
Where to use Canalis
Canalis, an installation that matches your inspiration!
Canalis in workshops and factories
Example: in a plastics factory
Electricity where you need it!
Characteristics b Area: 1500 m2 (50 x 30 m) b Loads: v 30 plastic injection presses, v fluorescent lighting.
Prisma Plus System G electrical distribution switchboard
Canalis products installed For power distribution 1- 2 KS 400 A runs, 48 m long, equipped with cable trays, 15 x 50 A tap-off units and 4 x 100 A tap-off units, 2- 1 KN 100 A run, 24 m long, equipped with 5 x 16 A tap-off units and 1 x 25 A tap-off unit. For lighting 3- 3 x 48 m long and 1 x 21 m long KBA lighting runs to supply the luminaires, 4- 48 KBL industrial luminaires (2 x 58 W). For office lighting, see next page.
Canalis in warehouses
Example:
Electricity where you need it!
Characteristics b Area: 4800 m2 (60 x 80 m) b Loads: v automatic doors, v battery chargers for forklifts, v T5 fluorescent lighting (2 x 80 W).
Prisma Plus System G electrical distribution switchboard
Canalis products installed For power distribution 1- 1 KNA 160 A run, 15 m long, to supply the battery chargers, 2- 1 KNA 63 A run, 75 m long, to supply the automatic doors. For lighting 3- 1 KNA run, 57 m long, to supply the lighting circuits, 4- 6 x 57 m long, 1 x 42 m long and 2 x 29 m long KBA 25 A runs to supply the luminaires 5- 90 KBL T5 2 x 80 W luminaires. For office lighting, see next page.
Canalis in a supermarket
Example:
Light up your business!
Characteristics b Area: 600 m2 (30 x 20 m) b Loads: v refrigerated display cases and cash registers, v fluorescent lighting.
Prisma Plus System G electrical distribution switchboard
Canalis products installed For power distribution 1- 2- 2 KBA 25 A runs, 12 m long, to supply the cash registers and refrigerated display cases For lighting 3- 4 KBA 25 A runs, 25 m long, for the store 4- 1 KBA run, 12 m long, for the cash registers. 5- 32 KBL industrial luminaires (2 X 58W). For office lighting, see below.
Canalis in offices
Example: in a partitioned office
Change office layouts easily!
Characteristics b Area: 1000 m2 (40 x 25 m) b Loads: v power: supply to power sockets and VDI network, v fluorescent lighting (3 x 36 W).
Prisma Plus System G electrical distribution switchboard
Canalis products installed For power distribution 1- 2 KN 63 A runs, 21 m long, installed as feeders to supply the lighting circuits. For lighting 2- 4 KDP runs, 21 m long, to supply the 180 3 x 36 W luminaires - 7 KBC single-switch units for the offices, - 1 KBC two-way switch unit for the meeting room, - 3 timer switch units for the entrance, washrooms and hall.
Catalogue numbers
Canalis KDP trunking, 20 A
For lighting and power socket distribution
KDP 20EDppppppp KDP ZFpp
KDP 20ABG4
Run components
Fixing system
b Rating: 20 A b 2 or 4 live conductors Polarity Single-phase L + N + PE Distance between Reel tap-offs (mm) 1200 1350 1500 3000 1200 1350 1500 3000 192 m 183 m 192 m 192 m 192 m 183 m 192 m 192 m Cat. no. KDP 20ED2192120 KDP 20ED2183135 KDP 20ED2192150 KDP 20ED2192300 KDP 20ED4192120 KDP 20ED4183135 KDP 20ED4192150 KDP 20ED4192300
b The fixing system is used to attach Canalis KDP to the sides of cable trays, metal structures or concrete slabs Fixing on Pre-slotted sheet-metal cable trays Mesh trays Metal structure 4... 6 1...8 8...13 13...17 17...22 Thickness (mm) Order in multiples of 100 Cat. no. KDP ZF10
3-phase 3L + N + PE
100 100 100 50 50
KDP ZF14 KDP ZF10 KDP ZF11 KDP ZF12 KDP ZF13 KDP ZF20 KDP ZF21
Feed units (supplied with end cover)
Wood or concrete
fixing with cable tie 100 concrete fixing plug 100 for 8 mm hole
b The feed units and end covers receive the cables supplying one end of Canalis KDP trunking Mounting Cable connection Terminals (mm2) 4 Cat. no. Cable gland maxi (mm) PG 16, 15
Left or right
KDP 20ABG4
10
KBZ ppppppp
KBC pppppppp KBZ ppppppp
Tap-off units
Connection leads
Type of busbar trunking Tap-off unit, direct connection 10 A with fixed polarity
Polarity
Colour of lock
Order in Cat. no. multiples of
Used to Connect the luminaires Connect to tap-off units Connect between luminaires Used to Splitter block
Length (m) 1 1 3 5 2 3 5 Function T-shape, 1 male input 2 female outputs T-shape, 1 male input 5 female outputs
Order in multiples of 10 10 10 10 10 10 10 Order in multiples of 20
Cat. no. KBZ 31EMC010 KBZ 31EFC010 KBZ 31EFC030 KBZ 31EFC050 KBZ 31EFM020 KBZ 31EFM030 KBZ 31EFM050 Cat. no. KBZ 32DBA12
L1 + N green L2 + N yellow L3 + N brown 10 A tap-off unit with phase selection Without prewiring all polarities Pre-wired, S05Z1Z1-F all polarities 3 x 1.5 mm2, 1 m long
10 10 10 10 10
KBC 10DCS101 KBC 10DCS201 KBC 10DCS301 KBC 10DCB20 KBC 10DCC211
10 A single-phase tap-off units for lighting control, with phase selection 10 A with fixed polarity Single-circuit Double-circuit switching Two-way switching Timer or impulse switch all polarities all polarities all polarities all polarities 10 10 10 10 KBC 10DSA20 KBC 10DDA20 KBC 10DVV20 KBC 10DMT20
10 50 10 10
KBZ 32DBA15 KBZ 32APFR2 KBZ 32APMR2 KBZ 30ZVP01
Connector to be wired Lock
female male resists pulling
11
Catalogue numbers
Canalis KBA trunking, 25 A
For lighting and power socket distribution
KBA 40ZFU
KBA 25EDpppp
KBA 40ZFSU KBA pppppp KBC pppppppp
Run components
Fixing system
b Rating: 25 A Type of component Length (m) Number of tap-offs 2 2 2 Order in multiples of 6 6 6 Cat. no.
b The fixing system ensures that Canalis KBA is well secured Designation Mounting Max. load (kg) 60 50 Order in Cat. no. multiples of 10 10 KBA 40ZFU KBA 40ZFPU
Busbar trunking fixings Standard straight length L + N + PE Standard straight length 3L + N + PE 3 3 2 KBA 25ED2302 KBA 25ED4302 KBA 25ED4202 Universal fixing bracket (1) Spring fixing bracket (1) Cable suspension system Pigtail hook Luminaire fixings Designation Rating Mounting Cable connection Cat. no. (A) Terminals Cable gland 2 (mm ) maxi (mm) left right 4 10 PG 16, 15 KBA 25ABG4 PG 21, 19 KBA 40ABD4 Universal fixing bracket (1) for direct suspension under trunking 60 10 KBA 40ZFU suspended on threaded rod or lateral (except wall) Adjustable suspension for threaded rod, M6 universal fixing bracket and steel cable, 3 m long suspended by small chain
Feed units (supplied with end cover)
60
10
KBA 40ZFSU
60
10
KBB 40ZFC
End feed unit 25 Feed unit 25
(1) Optional white-lacquered metal enclosure: add W to cat. no. Example: KBA 40ZFUW.
12
KBA 40ZFPU
KBL pppppppp
Tap-off units
KBL luminaires
b The 10 and 16 A tap-off units pre-wired or not, offer phase selection or fixed polarities, and can be used with the whole range
b The IP20 luminaires are designed for lighting in premises of low to medium height (industrial) or high premises (intensive) b The IP55 luminaires are designed for premises of low to medium height with severe environments Type (1) of tube Type of ballast Power (W) Cat. no.(2)
Type of trunking
Polarity
Colour of lock
Order in multiples of
Cat. no.
10 A tap-off unit, direct connection with phase selection, 2L + PE All types possible all polarities 10 KBC 10DCB20
IP20 industrial luminaires (delivered with 10 A tap-off unit with phase selection, pre-wired with S05Z1Z1-F 3 x 1.5 mm2) T8 electronic 2 x 58 KBL 258HF T5 electronic 2 x 49 KBL 249T5 IP20 intensive luminaires (delivered with10 A tap-off unit with phase 2 selection, pre-wired with S05Z1Z1-F 3 x 1.5 mm ) T5 electronic 2 x 80 KBL 280T5 IP55 polycarbonate dust and damp-proof luminaires (delivered with10 A tap-off unit with phase selection, pre-wired with S05Z1Z1-F 3 x 1.5 mm2) T8 T5 electronic electronic 2 x 58 2 x 49 KBL 258HFE KBL 249T5E
10 A tap-off unit, direct connection with phase selection, 2L + PE, pre-wired S05Z1Z1-F 3 x 1.5 mm2, 1 m long All types possible all polarities 10 KBC 10DCC211
Tap-off unit, direct connection pre-wired S05Z1Z1-F 3 x 1.5 mm2, 0.8 m long 10 A with fixed polarity, 2L + PE Single-circuit switching and balancing on 3 phases or 3-circuit switching L1 + N L2 + N L3 + N green yellow brown 10 10 10 KBC 10DCS101 KBC 10DCS201 KBC 10DCS301
(1) Tubuler are not supplied (2) Sale by inseparable quantity of 30, beyond 30, sale by unit is possible
13
Catalogue numbers
Canalis KN trunking
For low-power distribution from 40 to 160 A
KNB 160ZFPU
KNA ppppppppp
KNA pppppp KNB ppppppp
Run components
Feed units (supplied with end cover)
b 4 live conductors Polarity Rating (A) Length (mm) Number of tap-off outlets Cat. no.
b The feed units, delivered with end covers, receive the cables supplying at one end of Canalis KN trunking Designation Rating Mounting (A) End feed unit Feed unit 40 and 63 100 160 left or right left or right left or right Connection Max. size (mm2) Flexible Rigid terminals 16 25 KNA 40ED4303 KNA 63ED4303 KNA 100ED4303 KNA 160ED4303 KNA 63ED4204 KNA 100ED4204 KNA 160ED4204 Cat. no. KNA 63DL4 KNA 100DL4 KNA 160DL4 KNA 63AB4 Cat. no.
Standard lengths 3L + N + PE or 3L + PEN Additional lengths 3L + N + PE or 3L + PEN Designation Flexible elbow,
40 63 100 160 63 100 160 Rating
3000 3000 3000 3000
3 3 3 3
lugs 35 (M8 screws) lugs 95 (M8 screws)
50 95
KNA100AB4 KNA 160AB4
2000 4 2000 4 2000 4 Direction (edgewise) left or right left or right left or right
40 to 63 100 160 * Minimum curve radius: 70 mm
for internal or external angle, 80 to 180*
14
KNA ppppppppp
KNB 160ZF1
Tap-off units and tap-off units with isolators
Fixing system
b They are used to supply loads from 16 to 63 A Designation Rating 16 A Single-phase tap-off unit 32 A Four-pole tap-off unit 32 A Tap-off unit with power sockets (2) 63 A Tap-off unit with isolator 16 A Single-phase tap-off unit 25 A Four-pole tap-off unit 50 A Tap-off unit with isolator Connector with a surge arrester Tap-off unit with a surge arrestor Distribution Protection Cat. no.
b Used to secure Canalis KN whatever the type of building structure Designation Spring fixing bracket (1) Fixing bracket (2) Rating (A) 40 to 160 40 to 160 Mounting suspended on threaded rod suspended on threaded rod Order in multiples of 10 Cat. no. KNB 160ZFPU KNB 160ZF1
single-phase C 60N circuit KNB 16CM2 L + N + PE breaker (supplied) with phase selection 3-phase 3L + N + PE (1) or 3L + Np + PE 3-phase 3L + N + PE 3-phase 3L + N + PE (1) circuit breaker (5 x 18 mm modules) circuit breaker (8 x 18 mm modules) circuit breaker (8 x 18 mm modules) KNB 32CM55 KNB 32CP15F KNB 63SM48 KNB 16CF2 KNB 25CF5 KNB 50SF4
10
(1) Maximun load: 100 kg (2) Maximun load: 80 kg Maximum recommended distance between fixings : 3 meters
single-phase NF fuses L + N + PE 8.5 x 31.5 with phase selection (not supplied) 3-phase 3L + N + PE (1) 3-phase 3L + N + PE (1) 3-phase 3L + N + PE(1) 3-phase 3L + N + PE(1) NF fuses 10 x 38 (not supplied) NF fuses 14 x 51 (not supplied)
Quick PF10 surge KNB QPF arrester (supplied) Quick PRD40r KNB QPRD surge arrestor (supplied)
(1) Also suitable for tap-off unit 3L + PE (N not distributed) (2) Power socket polarity according to the case
15
Catalogue numbers
Canalis KS trunking
For medium-power distribution from 100 to 400 A
KSA pppEDpppp KSB 400ZF1 KSA pppAB4
Run components with tap-off outlets
Feed units (supplied with end cover)
b 4 live conductors Polarity Rating (A) Length (mm) Number of tap-off outlets Cat. no.
b The feed units, delivered with end covers, receive the cables supplying at one end of Canalis KS trunking Designation Rating Mounting (A) End feed unit End feed unit 100 left or right left or right left or right Connection Max. size (mm2) Flexible or rigid terminals 5 x 16 KSA 100AB4 KSA 100ED4306 KSA 160ED4306 KSA 250ED4306 KSA 400ED4306 KSA 250ED4208 100 to 250 400 lugs (M10 screws) lugs (M10 screws) 240 KSA 250AB4 Cat. no.
Standard lengths 3L + N + PE or 3L + PEN Additional lengths 3L + N + PE or 3L + PEN Designation Edgewise elbow 250 2000 8 100 160 250 400 3000 3000 3000 3000 6 6 6 6
2 x 240
KSA 400AB4
Rating 100 to 250
Direction (edgewise) left or right
Cat. no. KSA 250DLC40
16
KSA 250DLC40
KSB pppppppp
Tap-off units and tap-off units with isolators
Fixing system
b They are used to supply loads from 25 to 160 A Designation Rating 32 A Tap-off units 32 A Tap-off unit with power sockets (3) 63 A Tap-off unit with isolator 100 A Tap-off unit with isolator 160 A Tap-off unit with isolator 32 A Tap-off units 50 A Tap-off unit with isolator 100 A Tap-off unit with isolator 160 A Tap-off unit with isolator Distribution 3-phase 3L + N + PE(2) 3-phase 3L + N + PE 3-phase 3L + N + PE(2) 3-phase 3L + N + PE(2) 3-phase 3L + N + PE(2) 3-phase 3L + N + PE(2) 3-phase 3L + N + PE(2) 3-phase 3L + N + PE(2) 3-phase 3L + N + PE(2) Protection circuit breaker (5 x 18 mm modules) circuit breaker (8 x 18 mm modules) circuit breaker (8 x 18 mm modules) circuit breaker (12 x 18 mm modules) Cat. no. KSB 32CM55 KSB 32CP15F KSB 63SM48 KSB 100SM412
b Used to secure Canalis KN whatever the type of building structure Designation Fixing bracket (1) Rating Mounting (A) 100 to wall or 400 suspended on threaded rod Order in multiples of 10 Cat. no. KSB 400ZF1
(1) Maximun load: 70 kg Maximum recommended distance between fixings : 3 meters
Compact NS circuit KSB 160DC4 breaker (Without Vigi module) NF fuses 10 x 38 (not supplied) NF fuses 14 x 51 (not supplied) NF fuses 22 x 58 (not supplied) blade-type fuses (not supplied) KSB 32CF5 KSB 50SF4 KSB 100SF4 KSB 160SF4
(2) Also suitable for tap-off unit 3L + PE (N not distributed) (3) Power socket polarity according to the case
17
Dimensions
Canalis KDP trunking, 20 A
For lighting and power socket distribution
Run components
KDP 20EDppppppp KDP20EDp19pppp
780
648
Feed units (supplied with end cover)
KDP 20ABG4 End cover
Fixing system
KDP ZF10 KDP ZF11 KDP ZF12 KDP ZF13 KDP ZF14
Tap-off units
KBC 10DCSp01 KBC 10Dpp20 KBC 10DCB20 / KBC 10DCC21p
23
84
30
60
Connection leads
KBZ 31EMC010 KBZ 32ZVP01
KBZ 31EFC0p0
KBZ 32DBA12
KBZ 32DBA15
58
KBZ 31EFM0p0 KBZ 32APpR2
3x4
50 68 L
75
18
34
16
42 58
53
42 62
Canalis KBA trunking, 20 A
For lighting and power socket distribution
Run components
KBA 25EDp302
KBA 25ED4202
Feed units (supplied with end cover)
KBA 25ABG4 with end cover
KBA 40ABD4 with end cover
Fixing system
KBA 40ZFU KBA 40ZFSU KBB 40ZFC KBA 40ZFPU
19
Dimensions
Canalis KBA trunking, 25 A
For lighting and power socket distribution (cont.)
KBL luminaires
KBL 258C, KBL 258HF, KBL 249T5 KBL 258C KBL 258HF KBL 249T5 Dim. in mm 1526 1526 1475
1375 1375 1325
KBL 280T5
KBL 258CE, KBL 258HFE, KBL 249T5E
Nota : All KBL luminaires come equipped with a 10 A tap-off unit, with phase selection. This tap-off unit is prewired with a S05Z1Z1-F, 3 x 1 mm2 cable. KBL are supplied with fixing brackets.
20
Canalis KN trunking
For low-power distribution from 40 to 160 A
Run components
KNA pppED4303 92
27,5 KNA pppED4204 92
150
1000
3000
1000
850
27,5
150
500
500 2000
500
350
Component for changing direction (one dimension)
KNA pppDL4
Feed units (supplied with end cover)
KNA pppAB4 Dim. A B C D E 40 to 63 A 265 165 100 71 92 100 A 340 238 102 112 127 160 A 256 258 98 130 185
Fixing system
KNB 160ZF1 KNB 160ZFPU
21
Dimensions
Tap-off unit and tap-off unit with isolator
KNB 16CF2 KNB 16CM2 Centre line of tap-off outlets Cable exit
KNB 25CF5
KNB 32CM55, KNB QPF
KNB 32CP15F
(1)
KNB 50SF4, KNB QPRD
(1)
KNB 63SM48, KNB QPRD
(1)
(1) protruding
22
Canalis KS trunking
For medium-power distribution from 100 to 400 A
Run components with tap-off outlets
KSA pppED4306 KSA pppED4208
Components for changing direction
KSA 250DLC40
Feed units (supplied with end cover)
KSA 100AB4 KSA 250AB4 KSA 400AB4
Fixing system
KSB 400ZF1
23
Dimensions
Tap-off unit and tap-off unit with isolator
KSB 32CF5 KSB 32CM55, KSB QPF Centre line of tap-off outlets Cable exit
KSB 32CP15F
(1)
KSB 50SF4, KSB 100SF4 Dim. A B C D E F KSB 50SF4 356 153 167 309 103 202 KSB 100SF4 444 178 202 397 128 220
(1)
KSB 63SM48, KSB 100SM412, KSB QPRD Dim. A B C D E F KSB 63SM48 KSB QPRD 357 158 167 309 108 202 KSB 100SM412 444 183 202 397 133 220
KSB 160DC4
KSB 160SF4
(1)
(1)
(1) protruding
24
25
Simplified design guide
Due to its flexible design, KDP busbar trunking simplifies routing and thus reduces design and installation times. It is the optimum solution for installations with false ceilings or floors. KBA and KBB busbar trunking is ideal where the building structure cannot support the luminaires. It offers an IP55 degree of protection which means they can be installed in all types of buildings.
Which trunking for lighting distribution?
The busbar trunking: cannot support the luminaires must support the luminaires The fixing distance between centres is 3 m The required degree of protection is: >IP20
KDP
KBA, KBL
Calculate the operational current IB
b For lighting circuits
2 x 49 w
49 w
Industrial reflector type fluorescent luminaires (electronic ballasts) Discharge lamps
26
b For power distribution
Diversity coefficient K1
b Because not all loads operate at the same time, the diversity coefficient K1 is applied. b For heating and lighting applications, the coefficient K1 is always equal to 1.
IB = I total x K1
Number of loads
2
Protection by circuit breakers
Determine the busbar trunking rating according to the operational current and the selected protection
Operational current
Protection by fuses
>> Use of trunking at full rated load is the most economical solution
>> Limitation of the operational current (IB)e
27
Simplified design guide
Check the voltage drop (DU)
The maximum permissible voltage drop in the final circuit is: b 3% for lighting circuits (KBA) b 5% for power distribution circuits (KNA and KSA).
b Lighting circuits
The graph below indicates, for an operational current (IB) of 20 A, the trunking and cable lengths ensuring a maximum voltage drop of 3%.
Example The 3% voltage drop is reached if, for trunking 20 metres long, a 1 x 4 mm2 supply cable is 26 metres long or a 1 x 2.5 mm2 supply cable is 14 metres long.
b Power distribution
For lengths less than 100 meters (50 m + 50 m), KNA and KSA ensure voltage drops of less than 5%.
>> Use of trunking at full rated load
28
Summary of performance characteristics
Canalis, a high-quality system
In Safety IP55 Reliability IK08 IPxxD Cost
Canalis is halogen free and does not release smoke or toxic gases.
A high degree of protection (IP55) means Canalis can be installed in all types of buildings.
Interlocking devices prevent mounting errors, ensuring total safety for maintenance personnel.
IK08 for high impact strength.
IPxxD for total safety of maintenance personnel.
Lower cost than a conventional installation by cutting mounting time in half.
For lighting and power-socket distribution
Canalis KDP Canalis KBA
20 A 25 A
b b
b b
b b
IK07 IK06
b b
b b
Low and medium power distribution
Canalis KN Canalis KS
40 - 63 100 -160 A 100 - 160 250 - 400 A
b b
b b
b b
b b
b b
b b
29
Design and quotation software
Tools and assistance by your side
Design, cost and compare instantly using CanBrass software!
30
Contact Schneider Electric
31
32
Schneider Electric Industries SAS
35, rue Joseph Monier CS 30323 F - 92506 Rueil Malmaison Cedex RCS Nanterre 954 503 439 With capital of 896 313 776 www.schneider-electric.com
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper Design: Schneider Electric Photo: Schneider Electric Printing: 02-2010
DEBU023EN
ART.960136 2010 Schneider Electric Industries SAS - All rights reserved