NOTES ON MDBFP AUTO START
1. "TDBFP Tripped " contact is generated from trip oil pressure very low (2 out of 2 logic). Turbine running contact(Derived from Turbine speed > 500 RPM) is used for runback in CMC. 2. " Scoop tube at minimum" permissive will be bypassed if MDBFP Auto/Manual switch is in Auto mode. 2(a) If MDBFP Auto/Manual switch is kept in MAN mode and if pump is not running , scoop tube will drive to minimum position without human intervention and permissive will also present. 3. Recirculation valve will be in auto and in full open condition and it will be regulated with MDBFP Pump suction flow. 4. 2TF3 is a time delay to drop out relay and set for 7 sec .This relay contacts were used for Energizing /De-energising the hydraulic coupling rapid start solenoid valves. 5. 2TF2 is also a time delay to drop out relay whose contacts are going to close the MDBFP breaker .Auto start command is parallel to the Manual start command. 6. "Pump not running and drive scoop to minimum" interlock will be bypassed and scoop is to be kept in auto, so that it will track FW pump Master command. 7. When unit is not running / MDBFP not available , MDBFP Auto /Manual Switch is to be kept in "Manual" position.
1LR1 BFP-A TRIPPED
2LR1 BFP-B TRIPPED
2K87 BFP-C ON AUTO
7 8
4A
MANUAL BFP-C START COMMAND
M A
BFP A/B TRIPPED
5 6
5 6 2K88
10
4B
MDBFP NOT RUNNING L1
2LR8
2K87
2TF3
L2
BFP-C ON AUTO
BFP-A/B TRIPPED
BFP-C AUTO COMMAND
X2395 / 9
ARP 3S/K41
ARP3S/59
SBF31J
4A MDBFP START SWITCH HS-0699A 4B X2395 / 10
ARP 3S/K42 L
START(S)
ARP3S/59
HC RAPID START START SOL.VALVES
240 V AC (UPS)
1 5
2 6 2TF3
SV91
SV92
3P37 220 V DC FROM BKR CKT
PR1 PR2 PR3
7 8
SCOOP AT MINIMUM PR5
MDBFP ON AUTO 2K87
PR9
3P38
NOTE: PR1 TO PR9 ARE THE PERMISSIVE FOR STARTING MDBFP
" SCOOP AT MINIMUM" PERMISSIVE IS IN PARALLEL WITH "MDBFP ON AUTO " CONTACT
220V DC BFP-C BKR CKT
3R01 2K88 3 4 3 2K87 4 BFP-C ON AUTO NAS S BFP-A/B TRIPPED T NAT
2TF2
BFP-C START RELAY
Modification for Manual Starting of MDBFP even when Auto/Manual switch is kept in Auto position Requirement: 2 cables (cores) from ARP-3 to UCB (Near) switch-HS0699A) Existing available cable:
X2452 X2453
BF31J 14C
ARP-3
ARP-3R 13 TO 22
ARP-3 S59
X2395 / 9
S41
START
SBF 31J K,L CORES
10
S42
S60
MD BFP START/STOP SWITCH (HS-0699A)