Disconnectors and Switchers - 2-arm Pantograph : COELME EGIC
Pgina 1 de 2
Who we are...
Our products
Our services
Our references
Download Area
FAQ
Our products
Disconnectors Centre Break Double Break Vertical Break Knee-Type 1-arm Pantograph 2-arm Pantograph Earthing Switches Operating Mechanisms Power Switches Line Switcher CapSwitcher Circuit Switchers
Home > Our products > Disconnectors > 2-arm Pantograph
Vertical Reach disconnectors are the best solution for busbar selection, since they can ensure isolation/connection directly across the vertical gap between lower and upper busbar. More than 30 years of experience in this design ensures the necessary performances and sturdiness to fulfil all possible requirements, worldwide. This design allows easy bay maintenance since the all the switchgear and components of the line (including the disconnector itself) can be reached while the upper busbar is energized. Furthermore, the bay is more compact than with every horizontal disconnecting solution. Under a new internationally oriented name (VR2D stands for Vertical Reach 2-arm Disconnector), the former ranges of 2-arm pantographs previously named SP or SPC disconnectors have been unified, for more consistency to our customers (see our information sheet here ). The live parts are made of aluminium, hard drawn silver plated copper, with stainless steel hardware. Rotary contacts are self cleaning and can bear thousands of cycles maintenance-free. The base frame and all steelworks are hot dip galvanised. This product is available from 72.5 kV to 550 kV (BIL 1800), and up to 4000 A . Options 1 integrated earthing switch Making and breaking of bus transfer currents up to 1600 A as per IEC 62271-102 10 or 20 mm of ice operation ability (according to IEC 62271-102) Custom HV terminals
RATED VALUES
Ur (kV) Rated power TE Ud (kV) frequency withstand Ud AID voltage (kV) Rated voltage 72.5 140 160 123 230 265 145 275 315 170 325 375 395 460 950 (IEC) 900 (ANSI) 1050 245 460 530 300 380 435 362 450 520 420 520 610
325 (IEC) Rated lightning 350 Up TE impulse (kV) (ANSI) withstand voltage Up AID 375 (kV) Us Rated switching TE (kV) impulse withstand Us voltage AID (kV) TE : To Earth AID : Across the Isolating Distance Rated Ir permanent (A) current
550
650
750
1050
1050 1050
1175 1175
1425 1425
630 -
750 -
860 -
1200 -
(+170) (+205) (+240 850 700 950 800 1025 900
(+245) (+295) (+345
Up to 4000 A IEC / ANSI
http://www.coelme-egic.com/-2-arm-Pantograph-
23/05/2006
Disconnectors and Switchers - 2-arm Pantograph : COELME EGIC
Pgina 2 de 2
Rated short-time withstand current Rated peak withstand current
Ik (kA) Ip (kA)
Up to 63 kA / 3s Up to 160 kA 1126 2008+T 2238+T 2638+T 3378+T 3378+T 3378+T 3661+T 4555
DIMENSIONS A (mm)
B C D E F ? 2500 A > 2500 A IEC +/200
1090 1220+T 1500+T 1700+T 2100+T 2300+T 2300+T 2900+T 3400 300 770 425 640 0 800 1220 940 800 204 0 800 1500 1045 800 204 0 800 1700 1250 800 204 0 800 2100 1600 800 204 0 800 2300 1600 800 204 0 800 2300 1600 800 204 0 800 2900 1825 800 204 0 800 3350 1900 800 0 0
H J K L M
502 628 628 628 628 628 628 628 760 4 4 4 4 4 4 4 4 818 (20x38) (18x40) (18x40) (18x40) (18x40) (18x40) (18x40) (18x40) 300 275 137,5 137,5 137,5 137,5 137,5 137,5 137,5 90 85 85 85 85 85 85 85 -
Disclaimer - Site map - Con
http://www.coelme-egic.com/-2-arm-Pantograph-
23/05/2006