DVR-2000B Excitation Regulator 
 
 
User Guide 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
NANJING TURBINE    ELECTRIC MACHINERY GROUP 
NANJING TURBINE POWER CONTROL CO.,LTD 
 
  2 
Contents 
1 I ntroduction .................................................................................................................. 1 
 
2 Features and Applications........................................................................... 2 
2.1 Product Festures ................................................................................................................ 2 
2.2 Application areas ............................................................................................................... 3 
2.3 Operating condition .......................................................................................................... 3 
 
3 Functional Overview and Specification ....................................... 4 
3.1 Functional Overview ......................................................................................................... 4 
3.1.1 Regulation and Control ......................................................................................... 4 
3.1.2 Limit and protect .................................................................................................... 4 
3.1.3 Other auxiliary function ........................................................................................ 5 
3.2 Summary of qualification ................................................................................................. 5 
3.2.1 A/D input parameter .............................................................................................. 5 
3.2.2 Switching value input and output capability ....................................................... 5 
3.2.3 Output parameters ................................................................................................. 6 
3.2.4 Network interface ................................................................................................... 6 
3.2.5 Power supply parameter ........................................................................................ 6 
3.2.6 Index parameter ..................................................................................................... 6 
 
4 System allocation .................................................................................................... 8 
4.1 Electrical allocation ........................................................................................................... 9 
4.1.1 Excitation system diagram .................................................................................... 9 
4.1.2 Input/output interface sketch map ....................................................................... 9 
4.1.3 Hardware component .......................................................................................... 10 
4.2 Structure allocation ......................................................................................................... 10 
4.2.1 Cabinet constitution ............................................................................................. 10 
4.2.2 Layered introduction ........................................................................................... 10 
 
5 Fundamental Principle.................................................................................. 14 
5.1 Fundamental Principle ................................................................................................... 14 
5.2 Single board principle ..................................................................................................... 15 
5.3 software instruction ........................................................................................................ 18 
5.3.1 Main dispatcher .................................................................................................... 18 
5.3.2 Interrupt routine .................................................................................................. 18 
6 Keyboard, Display and Operation ..................................................... 23 
  3 
6.1 Key board Operation Instructions................................................................................. 23 
6.2 Main Menu Display ......................................................................................................... 23 
6.3 Main Menu Display ......................................................................................................... 25 
6.3.1 Measurement display ........................................................................................... 25 
6.3.2 Parameter Setting ................................................................................................. 26 
6.3.3 Protection Withdrawal ......................................................................................... 30 
6.3.4  Switching input status ......................................................................................... 30 
6.3.5 Drive Test .............................................................................................................. 31 
6.3.6 System Test ............................................................................................................ 31 
6.3.7 Fault Recall ........................................................................................................... 32 
6.3.8 Fault Waveform .................................................................................................... 33 
6.3.9 Event Recording ................................................................................................... 33 
6.3.10 Accuracy Setting ................................................................................................. 34 
6.3.11 Unit Parameters .................................................................................................. 34 
6.3.12 System Configuration ........................................................................................ 35 
6.3.13 Test Option .......................................................................................................... 36 
6.3.14 Other Test ............................................................................................................ 36 
 
  1 
1    I ntroduction 
DVR-2000B  excitation  regulator  is  a  new  generation  of  microprocessor-based  excitation 
regulator,  which  depends  on  China  Electric  Power  Research  Institute,  and  developed  by 
Nanjing  Turbine  &  Electric  Machinery  Group  Co.  Ltd.  It  has  consummate  function  of 
adjustment,  control  and  limit  protect,  and  prodigious  improvement  in  computation  speed, 
anti-EMI, reliability as well as facility in use. 
  DVR-2000B  generator  excitation  regulator  takes  the  newest  high  speed  32-bit  DSP  of  TI 
Corporation  as  the  core,  with  the  auxiliary  device  of  large  scale  programmable  logic 
controller,  to  make  the  control  system  on  a  chip  and  greatly  improve  the  system  stability. 
Simultaneously,  external  plate  machine  and  large  screen  LCD  greatly  upgrades  the 
human-machine interface and provide enormous convenient to the users. 
 
  2 
2   Features and Applications 
2.1 Product Futures 
DVR-2000B  Excitation  Regulator,  as  a  new  generation  of  microcomputer  excitation 
product, unifies the latest results of the excitation system research and many years operating 
experience  with  the  first  generation  of  excitation  regulation  device.  The  latest  computer 
control  technology,  digital  signal  processor  (DSP)  technology  and  advanced  network  and 
communication  technology  have  been  successfully  applied  on  this  new  product.   
DVR-2000B has following features: 
1.  Clear and accurate model 
DVR-2000B  excitation  control  system  uses  the  series  adjustment  with  excitation 
voltage hard negative feedback; all the models used are demonstrated to be with small 
error  and  high  precision  in  the  discretization  by  computer  simulation  and  dynamic 
signal analyzer measurement. 
2.  High measurement accuracy 
DVR-2000B  excitation  regulator  using  sampling  24  points  per  cycle,  FFT,  Completely 
eliminates  influence  of  null  shift  to  measuring  accuracy,  and  14-bit  A/D  conversion 
ensures accuracy and rapidity of measurement channel.   
3.  Strong network communication function   
DVR-2000B  excitation  regulator  is  provided  with  strong  communication  function, 
double-channel, regulator and power cabinet are connected with reliable CAN-BUS, So 
as to achieve data share and coordinate control.   
4.  Convenient and friendly human-machine interface 
DVR-2000B excitation  regulator  use  large  screen LCD  (240*128),  tree  menu  structure. 
The  convenient  and  visual  menu  can  achieve  setting  parameter,  measurement  display, 
test  control,  and  other  functions  with  keyboard.  Test  waveform  fault  type  and  event 
SOE are also can be displayed on the screen, using ESM-V1.0 software package makes 
realize the functions above more convenient 
5.  Domestic fastest excitation regulator   
DVR-2000B  uses  the  TI  Corporation  32-bit  DSP,  whose  speed  is  up  to  150MHz. 
formidable  data-handling  capacity  and  fast  floating-point  computation  ability  of  DSP 
provide  the  guarantee  for  the  accurate  digitization  of  excitation  regulator  model  and 
realizations of other auxiliary functions.   
6.  Highly integrate hardware design 
DVR-2000B  uses  large  scale  programmable  logic  controller  CPLD,  which  realize 
conventional dozens of chips combination completed function by flexible programming, 
one  chip  accomplish  all  the  peripherals  circuit.  Less  hardware  decrease  device  fault 
point, so the entire system reliability increases.   
7.  Handsome and practical cabinet design, advanced and normative technique of product 
DVR-2000B  uses  standard  4U  cabinet;  back-insert  structure  makes  signal-flow 
direction  all  the  same,  which  decrease  the  affect  of  signal  cross,  and  increase  the 
anti-interference  ability  of  the  system.  Cabinet  uses  totally  increased  structure, 
Integrated all boards which the regulator needs inside, whose self being a system. Main 
boards are all use multilayer, surface mounting technique. 
  3 
8.  Unique anti-interference design 
By well-design, properly arrange earth connection, filtering, masking and other details, 
DVR-2000B anti-interference ability achieve stern level 3 in Chinese standard. 
 
2.2 Applications   
DVR-2000B  excitation  regulator  is  applicable  for  three  machine  (brushless)  excitation 
system with permanent magnetism machine excitation system. 
 
2.3 Operating condition 
1.  No more than 1,000 meters above sea level 
2.  Surrounding temperature -1040 
3.  Relative humidity less than 90% 
4.  No fire and explosion   
5.  No conductive dust and chemical corrosion gas 
6.  No strong electromagnetic interference 
  4 
3 Functional Overview and Qualification 
 
3.1 Functional Overview 
DVR-2000B  excitation  regulator  is  mainly  designed  for  keeping  terminal  voltage  stabile, 
distributing reactive power between parallel units by proper droop setting, increasing power 
system  transient  stabilization  and  static  stabilization  by  fast  excitation  response.  Besides, 
DVR-2000B  also  has  some  auxiliary  functions  such  as  fault  wave  recordingevent  looking 
back, system self checking, intelligent debugging etc. 
3.1.1 Regulation and Control 
1.  Generator constant terminal voltage PIDproportionintegraldifferential coefficient
is achieved by Auto mode.   
2.  Generator constant excitation current PID is achieved by Manual mode. 
3.  Auto and manual mode is followed each other, realizing no disturb by the mode switch. 
4.  Channels is followed each other, realizing no disturb by the channel switch. 
5.  Generator running on Constant Trigger angel. 
6.  Reactive  power droop  setting  adjusting, whose  direction  can  be  set  sign; Droop setting 
coefficient can be adjust 0-15% with step 0.1% 
7.  Static excitation system startup control 
8.  Possible  to  achieve generator  unit  stably  running  and  smoothly  adjusting  on both  load 
and no load condition 
9.  Online parameter modify, insuring that data would not lost when power fail 
10.  DVR-2000B excitation system can be connected to the power plant DCS system by SCI 
or  Internet.  So  that  to  achieve  real  time  data  transferring  to  host  computer  and 
receiving host computer instruction 
11.  Generator operating on Constant Power factor   
12.  Generator operating on Constant reactive power   
3.1.2 Limit and protect 
1.  PT(Potential  Transformer)  wire-broken  protect,  estimate  wire-broken  by  comparing 
two  groups  of  PTs  or  different  phases  of  one  PT.  manual  switching    when  excitation 
wire-broken or sending signal when instrument wire-broken 
2.  V/Hz protectimplement step limit and protect V/Hz, for protecting over-magnetic flux 
of generator and main transformer   
3.  Over-excitation  limit  and  protect,  implement  step  over-excitation  limit  and  protect  for 
generator rotor 
4.  Under-excitation limit and protect 
5.  Over-voltage protect when no load   
6.  Trigger pulse lost detection 
7.  Communication failure detection 
8.  Thyristor fault detection 
9.  Power  supply  detection,  monitoring  if  CPU  power  and  24V  operation  power  are 
normally working. 
10.  Diode  or  fuse  failure  in  the  rotating  assembly  is  detected.  If  rotating  diode  or  rotating 
fuse is failure, the light emitting diode provides local indicaton ,at the sametime giving 
  5 
remote alarm by DVR-2000B.   
11.  Limit  and  protect  values,  protect  launching  or  cutting  are  all  able  to  be  set  when 
field-work   
3.1.3 Other auxiliary function 
1.  Fault wave recording, DVR-2000B excitation regulator record data at the time between 
10  sec.  before  and after  fault.  Record  data  include generator  voltage UG1UG2,  auto 
setting  value  U
GREF
manual  setting  value  IF
REF, 
  trigger  angle  ARF,  active  power  P, 
reactive  power  Q,  rotor  voltage  U
fd
,  field  current  I
fd
,  generator  frequency  F0,  local 
cabinet  output  current  ILA,  other  cabinet  output  current  ILB.  Almost  all  the  analog 
variables are included. Fault waveform can display on the LCD of the Controller, which 
also can transfer to notebook by SCI, displayed, managed and printed using EMS v1.0 
2.  Test  wave  recording,  DVR-2000B  excitation  regulator  is  able  to  record  test  waveforms 
by  manual  startup,  such  as  10%  step  response,  de-excitation,  cutting  load,  etc. 
Recording  time  is  between  1  second  before  test  start  and  19  seconds  after  test  start, 
Record  data  are  the  same  as  fault  wave  recording.  Display  mode  is  the  same  as  fault 
wave recording 
3.  Fault  recording,  which  is  able  to  record  20  fault  acting  value,  breakdown  time 
(millisecond  precision)  and  fault  type  by  the  rule  of  FIFO,  all  the  massage  can  be 
display on LCD or host computer. 
4.  Event recording, by the rule of FIFO , which is able to record 20 fault acting value, fault 
time(millisecond  precision)  ,  such  as  turning  on  or  off  magnetic  blow-out  switch  , 
launching or cutting channels,    changing operation mode.   
5.  Strong  communication  function,  DVR-2000B  uses  standard  MODBUS  protocol,  which 
is  able  to  communicate  between  channels  and  achieve  interface  between  excitation 
regulator  and  DCS  system  or  other  Power  plant  monitor  system  by  flexible 
communication mode, RS232RS485 or CAN. 
6.  Software  potentiometer  function,  for  which  all  analog  variables  management  loops 
cancel  potentiometer,  Menu  set  software  potentiometer  makes  debugging  work  easier 
and more flexible   
7.  Strong  test  functionwhich  expediently  running  all  tests  by  keyboard  operating  on 
controller.  Such  as  switch  variable  driving  test,  over-excitation  limit,  under-  excitation 
limit,  step  response  test,  AC  excitation  machine  time  constant  test  etc,  and  also 
proceeding auto waveform record. 
 
3.2 Summary of qualification 
3.2.1 A/D input parameter 
A/D sample channel: 16-channel 
Analog variable input general view: 
Terminal voltage PT1:      rated 105v 
Terminal voltage PT2:      rated 105v 
Stator current:          rated 5A    (or:    1A) 
Exciting current of exciter:    75mv (from LEM) 
 
3.2.2 Switching value input and output capability 
  6 
16-channel electric isolated input; 
10-channel switching value output, where 2 channels optoelectronic output, 8 channels relay 
output, which can be extended to 18 cannels. 
 
3.2.3 Output parameters 
Trigger pulse: 6 phase double pulse for 3 phase full controlled bridge, whose width is 100us, 
which can trigger less than 4 groups of 3 phase full controlled bridge, and give single phase 
full controlled(or semi-controlled) bridge trigger pulse. 
 
3.2.4 Network interface 
SCI1:            RS-232(isolated) 
SCI2:            RS-485(isolated) 
CAN bus:          CANH,CANLisolated 
Communication protocol:    standard modbus protocol 
 
3.2.5 Power supply parameter 
Working AC power supply:    from PMG 
Working DC power supply:    DC220V20%or DC110V20% 2A 
Auxiliary AC power supply:  station-service    AC220V15% 2A 
Supply power:          less than 400W 
 
3.2.6 Index parameter 
DVR-2000B  excitation  regulator  satisfies  well  of  GB/T  7409.3-1997  criteria  of  excitation 
system for synchronous electrical machines technical requirement of excitation system    for 
large and medium synchronous generators. Detailed Index parameter as following: 
1.  CPU type:              32-bit high-speed DSP 
2.  CPU speed:              up to 150MHz 
3.  Thyristor pilot angle  resolution:    0.0048 degree per yard 
4.  ADC resolution:            2
-14
16-channel 
5.  Control calculate speed:        3.3 ms 
6.  Voltage adjust range:          10%130% 
7.  Voltage adjust precision:      <0.5% 
8.  Shift range:    0170degree, upper and lower limit can be set in program   
9.  Droop setting: software reactive power droop setting, sign and magnitude adjust step is 
1%. 
10.  Frequency character:   generator  terminal  voltage  change  less  than  0.25%  of    rated 
voltage while 1% change of Frequency 
11.  Setting  value  adjusting  speed:  programmable,  no  faster  than  1%  per  second  and  no 
slower than 0.3% per second. 
12.  When  no-load  with  rated  voltage,  when  generator  setting  step  is  10%,  generator 
voltage overshoot is less than 30%, surge is less than twice and settle time is less than 5 
second 
13.  When generator voltage startup from zero, terminal voltage overshoot is less than 10%, 
oscillations is less than twice and adjust time is less than 5 second 
  7 
14.  Operation mode: host/standby mode 
  8 
     
 
CT 
PT 
 
   SCR 
 
    F 
 
   LB 
FIG3 
 
 
 
 
START  
POWER 
 
DVR-2000B 
FIG2 
 
 
   SCR 
PT 
    F 
CT 
 
 
   SCR 
DVR-2000B 
EXC 
 
    F 
PMG 
 
EXC 
 
 
   SCR 
 
   SCR 
 
PT 
CT 
 
DVR-2000B 
 
PT 
 
   
DVR-2000B 
    F 
FIG4 
 
   SCR 
EXC 
 
 
   SCR 
 
PT 
 
CT 
 
 
   LB 
DVR-2000B 
FIG1.  
  9 
 
4    System configuration 
 
4.1 Electrical allocation 
DVR-2000B  takes  simple  and  reliable  as  principle,  configuring  corresponding  excitation 
system  for  different  excitation  mode.  This  chapter  makes  an  introduction  and  takes  a  3 
machine excitation system as example 
4.1.1 Excitation system diagram 
Fig 1 is the system block diagram of 3 machine excitation system. Under this mode, regulator 
operate  under  host/standby  mode,  host/standby  channel  communicate  each  other,  backup 
channel work as a backup trailing channel, and also can switch without disturbance. 
4.1.2 Input/output interface sketch map 
Analog  variable  range  is  5V;  operating  loops  all  use  24v  power.  Respected  signal 
diagrammatic is as following figure: 
 
 
 
 
 
 
 
 
 
 
 
 
 
Fig 4-1 Input/output interface 
Jump switch 
Limitation& Protection 
Const power factor 
Const reactive power 
PSS switch 
Manual Run 
Auto Run 
Run/Trail 
PSS switch in/out 
Decrease magnetic 
Increase magnetic 
Power cabinet 
  fault 
Position 
Magnetic 
blow-out swith 
Pulse output 
CAN 
Rs-485 
Rs-232 
4-20mA 
4-20mA 
D/A 2 
D/A 1 
System voltage 
(optional) 
Rotor voltage 
(output) 
Rotor current 
  (output) 
 
                                                       
                                     
 
 
   
Analog 
Input 
 
 
 
 
 
 
 
 
 
 
 
      Signal   
      output 
Switching   
Variable   
Input 
 
 
 
 
 
 
 
 
 
 
    Switching   
    Variable   
    Output 
 
 
 
Meter PT 
Measurement PT 
 
Stator current 
Test signal 
Channel switch in/out 
 
 
 
  10 
4.1.3 Hardware component 
DVR-2000B  excitation  regulator  is  a  highly  integrated  controller,  including  almost  all 
function blocks from switching power to pulse amplification. Each control channel includes: 
1.  Switching power module1  +5V12V--PWR1 
2.  Switching power module2  24V124V2--PWR2 
3.  Main board--CPU 
4.  Switch variable input and output boardDI/DO 
5.  Pulse amplification board--PGC 
6.  Analog signal conditioning board--SPB 
7.  PT/CT and sync transformer boardPT/CT 
8.  Power unit boardRE.U 
9.  Bus back soleplate 
10.  Keyboard and LCD panel 
See Fig 4-1a and Fig 4-1b. 
4.2 Structure allocation 
4.2.1 Cabinet constitution 
DVR-2000B  generator  microprocessor-based  excitation  regulators  use  assembling  cabinet 
structure.  The  cabinet  is  quite  smooth  and  artistic,  with  doors  fore  and  after.  The  cabinet 
intensity  greatly  surpasses  the  welding  cabinet.  The  cabinet  surface  uses  the  technology  of 
polyester powder coated,  with  the  color  code  provided  by  the  purchaser.  The  wirings  of 
strong  electricity  and  weak  electricity  in  the  cabinets  are  separated  to  avoid  mutual 
interference. The wire used in the current circuit of control cable is 2.5 mm, while others are 
1.5  mm.  The  wire  color  is  distinguished  according  to  the  Chinese  Standard,  where  AC  is 
distinguished  by  yellow,  green  and  red.  All  cables  are  not  permitted  to  be  branched  and 
spliced.  All  wire  sizes  and  number  plates  are  printed  with  special  printer  to  be  neat  and 
consistent. The  size  of  horizontal  earth  copper  bus  is no  smaller  than  6*25  mm
2
.  The  earth 
connection of every screen is achieved by connecting the bolt ground bus to the naked metal. 
Tow  terminals  of  the  bus  are  connected  to  the  120mm
2
/2*60mm
2
  (4/OAWG)  copper  core 
ground  connected  cable,  which  comes  from  the  ground  mat  of  the  power  plant.  Ground 
terminals  are  provided  on  the  excitation  cabinet  for  equipment  shield.  The  moisture-proof 
heater  can  be  installed  in  the  cabinet,  and  also  the  lighting  equipment  is  installed  which 
controlled by the door. The front of the regulator cabinet is a glass door, which is convenient 
for  monitoring.  20%  of  the  terminals  are  reserved.  The  external  dimension  of  standard 
cabinet is 800*600*2260 mm (also can be decided by the user). Ventilating windows are also 
installed in the cabinet up and down. 
 
4.2.2 Layered introduction 
The front and back view of self excitation and shunt excitation cabinet is shown 
in Fig DVR-2000B excitation cabinet assemble. 
1.  Instrument layer 
  11 
It  is  located  in  the  first  layer  of  the  cabinet.  The  related  instruments  are  arranged  in  the 
front.  The  generator  terminal  voltage  meter  ,PMG  terminal  voltage  meter  and  excitation 
current meter are installed generally.    So it is easy to operation or monitor test on site. 
2.  Operation layer 
5 console switches are installed on this layer to operate the regulator on line.   
1QK:The  channel  selection  switch  is  used  to  select  CHA  or  CHB  for  current  operating 
channel or current following channel. In the operation, undisturbed switchover can be done 
with the handle.   
6QK:The channel ON/OFF switch is selection the regulator for the put in/cut off . 
3QK:Mode  selection  switch  is  used  to  select  the  operation  mode  of  the  regulator,  including 
manual operation/ automatic operation.   
5QK:Increase/decrease  switch,  which  is  a  self-restoring  switch,  is  used  to  adjust  the 
magnitude  of  the  generator  voltage  or  reactive  power.  In  order  to  prevent  the  increase 
/decrease switch node from conglutinating, the increase/decrease switch will be locked by the 
procedure  if  the  increase/decrease  switch  operates  continuously  over  3  seconds,  revert  the 
switch to unblock the lock command.   
4QK:  Running  mode  switch  is  used  to  select  constant  Power  factor  control,  constant 
generator terminal voltage control and constant reactive power control. 
2QK:Remote  control/local  control  switch  is  used  to  decide  the  regulator  accepts  the  local 
control  command  or  remote  control  command.  The  above  switches  are  invalid  while  this 
switch  is  in  remote  control  state,  and  regulator  is  controlled  by  the  switches  on  the  remote 
control station. When this switch is in local control state, the regulator accepts the operation 
commands on the screen, and the operations on the remote control station are invalid. Make 
sure  to  set  the  local  control  and  remote  control  in  a  corresponding  consistent  condition 
before switch the remote control and local control in the operation. 
3.    Control layer 
Control layer is the core layer (master control unit) of DVR-2000B generator microcomputer 
excitation  regulator.  It  assembles  almost  all  the  excitation  regulator  functional  modules. 
Controller  uses  4U  standard  cabinet  with  surface  oxidized,  which  looks  really  handsome. 
Board  adopts  back-insert  structure.  Fig  4-1  is  the  front  and  back  view  of  DVR-2000B 
controller.  A  240*128  large-screen  liquid  crystal  display  device,  a  keyboard  controller  and 
some operation indicator lamps are mounted on the regulator board; in the right lower side 
of the board there is a RS232 connector. 
 
  12 
 
Fig 4-1a DVR-2000B excitation regulator front panel 
 
Fig 4-1b DVR-2000B excitation regulator back panel 
In the left upper side of the host control unit board is the mark of the regulator; in the left 
lower side is the company name; in the middle are large-screen liquid crystal display device 
and operation keyboard, about which more information can be seen in <chapter 6 keyboard, 
display and operation>; in the right side of the board is operation indication area, from 
upper to lower which contains: auto, manual, PSS (for generator units lower than 100MW, 
PSS is not needed, which is stand-by here), constant reactive power, constant power 
factor(for units upper than 100MW, this operation mode doesnt exist, which is stand-by 
here), channel fault. All the six indicator lamps listed above display green to present normal 
status except the channel fault indicator lamp, which display red when status is normal. 
The channel fault indicator lamp acts when any protects or limits act. Detailed action types 
will be displayed in the top line of the LCD. If several protects act at the same time, only the 
fault type of the last one is displayed here. More detailed action type, action time and action 
value can be inquired in menufault recall. 
See figure 4-4b, the boards of controller is inserted from the back of cabinet. There are 10 
independent boards including two extendable stand-by boards. The boards in cabinet must 
be inserted into corresponding slots by sequence. If sequence wrong, the board would be 
damaged.     
RE  . U    CPU  PWR    2  PWR    1 
Reset 
Test 
Diode Fault 
Alarm 
EXT ST 
OUT EXT 
-CK 
-AG 
-AK 
-BG 
-BK 
-CG 
24VCOM 
0V2COM 
+AG 
+AK 
+BG 
+BK 
+CG 
+CK 
J10 
J9 
IFD_T 
ILD- 
ILD+ 
IFD- 
IFD+ 
485- 
485+ 
CANL 
CANH 
OUT3 
OUT2 
OUT1 
OUT0 
IN1' 
IN1 
GND1 
GND1 
DA 1 
DA2 
Uran 
GND 
IN0' 
IN0 
PF EN 
VAR EN 
DEC 
AUTO EN 
INC 
RUN EN 
CH EN 
PSS 
 
EN 
CH ERR 
FCR ON 
AVR ON 
PSS ON 
SPARE 
SPARE 
SPARE 
START 
FCB 
TRIP 
PF ON 
VAR ON 
COM 
24V1 
0V1 
+ KM 
-KM 
DYB-B 
DYB-A 
DYB-C 
DCOUT+ 
DCOUT- 
0V2 
24V2 
-12V 
5V 
+12V 
GND 
FG 
SPARE      DI/DO      SPB          PT/CT 
 
        PGC  SPARE 
EXT_OTH 
OTH_EXT 
95 SPED 
  13 
4  Power switch layer 
DVR-2000B generator microcomputer excitation regulator is two-channel supplied. Two 
working power AC and DC supply the switch power in control unit through gas switches 
respectively.   
5.  Rest parts of an apparatus 
It  contains  supply  transformer,  LEM,  FL1,  FL2,  RX,  diode  and  relay  1k,2k,3k,4k  etc.   
Supply  transformer  transforms  AC  voltage  to  165V/85V  5%  in  the  secondary.  After 
rectified, it is DC220/110 and supplies a regulator in parallel with station service DC power 
through  inverse  diodes.  For  excitation  systems  whose  power  supply  voltage  is  higher  than 
220V/110V,  synchronization  signal  must  be  step  down  through  a  synchronization 
transformer. LEM, FL1, FL2: is used to measured the excitation current 
  14 
5    Fundamental Principle 
5.1 Fundamental Principle 
Main function of the generator microprocessor-based excitation regulator is to maintain the 
voltage  stabilization  of  the  generator.  Simultaneously  by  the  use  of  microprocessor-based 
excitation regulator, the reactive power could be distributed logically among the parallel unit. 
Excitation  regulator  takes  a  very  important  role  in  enhancing  the  stability,  not  only  the 
transient  stability  but  also  the  dynamic  stability.  The  input  electric  signals  include  the 
generator  PT.  voltage,  the  meter  PT.  voltage  and  the  three-phase  stator  current  signal  CT. 
which comes from the generator current transformer. The direct current signals include the 
generator  armature  current,  the  regulator  output  current  and  the  signal  reflecting  the 
voltage  of  the  power  supply.  By  signal  processing  and  transforming  circuit,  each  signal  is 
filtered, isolated and amplified, and then transformed to be suitable to A/D sampling. These 
signals  are  sent  into  A/D  converter,  transformed  to  digital  variables  by  the  program 
controlling process and then deposited in the memory for regulator use. 
By the data gathered above, the generator behavior, all the information like the excitation 
system parameters and the regulator output parameters can be obtained by the software 
computation. For example, the AC variables, such as, effective value of the three-phase 
voltage, effective value of the three-phase current, active power P and reactive power Q. 
Main control or local selection of the regulator operation mode, the operation for increasing 
or  decreasing  the  excitation,  switch  variable  input  signal  like  Field  Suppression  switch  and 
switch  variable  output  signal  like  malfunction  alarm  are  linked  with  CPU  by  photoelectric 
isolation.  Simultaneously,  run  indicating  signal  which  reflects  the  regulators  state  and  the 
fault  indicating  signal  enter  the  acousto-optics  alarm  system  of  the  power  plant,  by  the 
optical  coupler  and  the  relay  isolation  by  means  of  switch  variable  output.  Meanwhile,  the 
regulator  provides  the  communication  interface,  which  could  communicate  with  the  DCS 
(ECS) system of the power plant. There are 16 groups of switch variable input and 10 groups 
of  switch  variable  output  channels  in  the  DVR-2000B  generator  excitation  regulator.  The 
number  of  switch  variable  input  and  output  channels  could  be  expanded  according  to  the 
user. 
The  power  output  device  of  the  regulator  cabinet  is  three-phase  fully  controlled  thyristor 
rectifier  or  single-phase  (half)  fully  controlled  bridge.  In  order  to  guarantee  the  output DC 
voltage  continuously  adjustable  and  in  the  inversion  operation,  the  control  angle  must  be 
only  adjusted  between  10  to  170  degree.  During  the  limited  scope,  user  could  set  the  max 
value  and  the  min  value  of  the  trigger  angle  on  the  menu.  In  the  regulator,  the  pulse 
synchronizing circuit guarantees various thyristors conduct in turn. Digital value is directly 
transformed  to  the  trigger  pulse  signal  of  control  angle  with  the  large-scale  logical  device, 
and the phase-shifting way is cosine. 
The 300Hz interrupt control routine, calculates the difference between the generator voltage 
and  the  reference  voltage  and  does  the  PID  calculations  to  obtain  a  control  variable  to 
change the conducting angle of the thyristor after considering the extra droop setting signal. 
That  is  the  main  regulation  circle  of  the  excitation  regulator.  The  correct  selection  of  PID 
  15 
parameters,  will  directly  affect  the  static  state  and  the  dynamic  characteristic  of  the 
regulator. 
The protect function modules of the regulator, such as, the missing pulse examination, the 
low excitation limit, the over excitation limit, the V/Hz limit, the PT fault-line protect and so 
on, are realized with software. 
The  environment  of  installation  site  of  the  excitation  regulator  is  quite  bad  and  the 
electromagnetic  interference  is  quite  serious.  The  anti-interference  ability  is  extremely 
important  to  the  microprocessor-based  excitation  regulator.  This  regulator  has  the  unique 
anti-interference measure, such as, double-shield in the core device of the regulators control 
board,  the  photoelectric  or  electromagnetic  isolation  circuit  on  each  input  or  output  circuit 
and  the  switch  power  supply  isolation,  moreover  the  hardware  and  software  auto-revert 
circuit is specially designed. When the program runs out of control or in endless loop by any 
chance, the circuit makes the program execute back to the start automatically. 
The front panel of the regulator cabinet is equipped with the operation and display interface 
for the man-machine interaction. The man-machine interface uses the liquid crystal display 
and  the  English  menu.  All  the  analog  variables  the  computer  gathers  are  displayed  on  the 
liquid-crystal  display  as  real  value  to  the  advantages  for  the  monitoring.  Moreover  the 
functions, such as, real-time state display of the switch variable input, the compulsory output 
of  the  switch  variable,  control  and  protect parameters  setting,  the  extracting of breakdown 
wave  recording,  the  wave  display  and  so  on,  could  be  realized  in  this  man-machine 
interaction window. 
The regulator working power supply is also independent, with the switch power supply. The 
output  voltage  includes  four  types:  +5v,  12v,  the  power  supply  for  the  main  engine  board 
and  the  operational  amplifier  uses;  24VI  for  the  pulse  circuit,  24VII  for  the  relay  and  the 
operation circuit. The power supply uses two groups: one comes from the accumulator; the 
other  comes  from  the  anode  voltage  rectification. Power  supply  of  the  two  groups works  in 
parallel operation with check diode. No matter which group power off, the regulator can still 
work normally. 
In summary, this regulator does not need external transducer, such as, the voltage, the active 
power,  the  reactive  power  transducer  and  any  machinery  or  the  electronic  voltage-given 
structure.  Software  is  fully  used  and  the  hardware  circuit  is  simple,  which  enhance  the 
reliability and make it convenient for the maintenance. 
5.2 Single board principle 
As  the  excitation  system  for  synchronous  generator,  the  reliability  is  very  important  to  the 
unit  and  the  network  security.  Therefore,  DVR-2000B  microprocessor-based  excitation 
regulator  takes  the  system  reliability  the  first  important  content  in  the  designing  time. 
Establishing a stable hardware observing and controlling platform makes the foundation to 
the enhancement of the system reliability. 
The  control  panels  above  are  inserted  in  a  special  4U  cabinet  (see  figure  4-1b).  In  order  to 
enhance  the  anti-interference  ability  of  the  system,  the  cabinet  uses  the  metallic  shield 
cabinet,  and  all  the  plug-in  units  are  inserted  backwards  ensuring  the  signal  flows  to 
uniqueness,  avoiding  the  serial  disturbance  between  the  signals,  as  well  as  overlapping 
  16 
between  strong  and  the  weak  electric  signals.  The  important  board  uses  the  advanced 
surface-pasting technology; the bus board is installed in the front part of the cabinet. There 
is  a  240128  lattice  liquid-crystal  display  on  the  panel  for  the  monitoring  of  the  running 
status. And there are some other important status indicating lamps on the front panel. 
  Power supply system (PWR1,PWR2) 
In order to enhance the reliability of the system, power supply makes up by two groups 
of  redundancies.  The  AC  power  supply  from  the  excitation  transformer  or  station 
supply  is  rectified  to DC  by  the  insulating  transformer,  and  then  on  parallel  operation 
with the DC from the plant battery with the diode. They supply the switch power in the 
cabinet  together.  In  order  to  enhance  the  anti-interference  ability  of  the  system,  the 
system power supply divides into 3 parts. 
1)  CPU  power  supply:  5V,  12V,  where  DSP  chip  essence  voltage  1.8V,  peripheral 
voltage  3.3V,  and  the  low  voltage  system  assure  the  low  power  loss  of  the  high  speed 
CPU and the reliability. 
2)  Operation  power  supply:  24V2,  used  in  the  input  and  the  output  of  the  switch 
variable.  To  the  double  channel  excitation  system,  the  two  channels  24V2  provide  the 
operation signal by parallel with the diode. The two channels 0V2 are directly parallel, 
which makes the 24V2 power supply redundancy. 
3) Pulse power supply: 24VI, used in the pulse amplifying circuit and the trigger circuit. 
The power supply systems above are mutually independent to avoid disturbs. 
 
  Main board of computer (CPU) 
This  board  is  the  systems  central  control  panel.  It  composes  the  most  popular  32-bit 
DSP  chip  which  contains  much  operation  experience  after  many  years  work  and 
large-scale programmable logical array CPLD. For the programmable logical array, the 
system  enables  the  certain  open  users  to  make  the  logical  configuration  according  to 
their  own  scene  reality,  which  greatly  simplifies  the  circuit,  thus  makes  all  the  bus  on 
board and enhances the system reliability. This board is composed by the below parts. 
  DSP  (digital  signal  processor):  The  chip  used  as  main  chip  in  this  system  is  the 
C2  series  chip  which  is  specially  promoted  for  the  control  domain  by  the 
famous DSP firm Texas Instruments. This CPU got the following characteristic:   
1) The highest operating frequency reaches 150MHz; the execution period of each 
instruction is only 6.67ns   
2)  The  32-bit  data  wires  and  the  24  address  wires  make  the  addressing  space  to 
4M. 
3)  Harvard  structure  and  the  high  speed  pipeline  instruction  operation  further 
enhance the running speed. 
4) Powerful peripheral function:   
An enhanced type CAN bus driver 
A serial peripheral interface (SPI) 
  17 
Two serial communications interface (SCI) 
Three 32-bit timers/counters 
On-piece 128K16-bit FLASH   
5) A/D transformation: 16 groups of high speed (400KSPS) high accuracy (14) A/D, 
synchronized sampling, which can avoid the phase-shift due to the sampling speed 
and increase the precision. The sampling frequency is 0.833ms.   
6)  Two  groups  of programmable  D/A  output,  provides  the  hardware  interface  for 
the PSS parameter setting and the regulator model identification. 
7)  Large-scale  logical  array  CPLD:  Completing  the  form  of  pulse,  the  input  and 
output of switch variable, as well as some other logical operations and the decoding 
function.   
8)  External  memory:  A  piece  of  128K/16-bit  data-memory  used  to  memorize  the 
breakdown  recording  data,  16K-bit  serial  EEPROM  memory  parameter  and  the 
important breakdown data.   
9) Watch dog circuit: Using the special watch dog monitoring chip.   
10) Communication part: This board provides a group of RS232, a group of RS485 
and  a  group  of  CAN-BUS;  the  modular  product  is  used  on  the  isolation  and  the 
level  translation.  RS232  outputs  from  the  front  board,  RS485  outputs  from  the 
phoenix terminal, and CAN outputs from the phoenix terminal. 
11) Clock circuit: The clock uses DS1305, the clock chip.   
12) Four groups of switch variable inputs of optical coupled isolation; the requiring 
voltage rank of operation supply voltage is 24V.   
13) Four groups of switch variable outputs of optical coupled isolation; the output 
is the active signal of this channel 24V2. 
 
  Analog variable processing board (SPB) 
The  main  function  of  the  board  is  to  transfer  and  isolate  the  voltage.  Due  to  the  AC 
sampling,  the  current  circuits  and  the  voltage  circuits  are  filtered  and 
voltage-transferred  to  the  A/D  measurement  range  by  the  isolation  with  high  precise 
minitype  CT  and PT;  and then  enter  the  main  board.  The DC  value  is  sampled  by  the 
filtered  and  voltage-transferred  rotor  current.  Meanwhile  the  synchronized  signal  is 
reshaped to the square-wave, producing the pulse for CPU on main board. 
  18 
 
  Switch variable input relay output board (DI/DO) 
On  the  board  the  16  groups  of  switch  variable  input  signals  enter  monitoring  CPU 
board  by  photoelectric  isolation  for  state  judgment.  Moreover  all  the  power 
examination  circuits  are  also  on  this  board.  The  16  groups  of  switches  variable  output 
signals driver the relay by photoelectric isolation to output the signals. 
 
  The pulse amplifying board (PGC) 
The  board  power-amplifies  and  outputs  the  double-narrow  pulse  made  by  the  CPU 
board;  power  of  each  group  of  pulse  could  driver  more  than  5  groups  of  parallel 
thyristor  bridges  above.  Simultaneously  there  are  indicating  lamps  on  this  board  to 
demonstrate  whether  the  pulse  is  normal.  On  the  board,  with  the  jumper  the  pulse 
transformer could be set as inside type or outside type. 
  PT/CT board (PT/CT) 
Generator  measuring  PT,  meter  PT,  system  PT  and  the  timing  voltage  signals  are 
isolated  with  minitype  potential  transformer,  thus  they  are  adapted  to  weak  electric 
signals in the A/D range. Signals from the stator current transformer are isolated with 
internal minitype current transformer, thus they are adapted to weak electric signals in 
A/D range. 
 
5.3    Software instruction 
5.3.1 Main dispatcher 
Main dispatcher mainly completes the following functions:   
1) Initialization processing   
When  reset  power  on  or  press  the  reset  key,  firstly  the  hardware  and  the  software  are 
initialized. The hardware initialization includes CPU and other intelligent chips initialization 
and the software initialization refers to set some variables at initial value.   
2) Keyboard analysis and liquid crystal display   
During each cycle period of the program, the small keyboard is sampled. That different keys 
are  pressed  down  corresponds  to  the  different  processing  subroutine.  Simultaneously  the 
different menu instructions demonstrate on the liquid-crystal display. Through coordination 
of  the  keyboard  and  the  liquid  crystal  display,  the  man-machine  interaction  could  be 
achieved,  including:  real  time  display  of  operation  parameters,  on-line  monitoring  of  the 
status  of  switch  variable,  compulsory  output  of  switch  variables  for  debugging,  parameter 
modification, accident recall, extracting and displaying of failure data. 
 
5.3.2 Interrupt routine 
As interrupt service routine: The main control program has the highest severance priority, 
the severance cycle is 0.833 ms. The interrupt routine achieves the following functions:   
1)  AC sampling 
The  analog  input  variables  include  the  generator  measuring  PT  output  voltage,  the 
instrument PT output voltage as well as the stator current (three-phase), moreover the rotor 
current  and  the  regulator  output  current  and  so  on.  Analog  variables  are  sampled  in  the 
main control program, 24 point per circle.   
  19 
2)  FFT fast Fourier transforms and other data processing   
32-bit DSP chips separately calculate the generators three-phase voltage, three-phase 
current, active power and reactive power through the FFT transformation. 
3)  Droop setting calculation 
Take  calculation  according  to  the  set  droop  setting  coefficient  and  droop  setting  sign.  Add 
(minus) the extra droop setting to given value. 
tiaocha ref ref ref
  U U U
_
 =   (Positive droop setting) 
K
Q
Q
U U
N
GN tiaocha ref
    =
_
 
tiaocha ref ref ref
  U U U
_
+ = (Negative droop setting) 
Where, K is droop setting coefficientUref is voltage reference value, Uref_tiaocha is extra 
given droop setting value. 
4)  Realization of control rule   
Calculate the control variable according to the given control rule and the operation 
parameter. DVR-2000B uses the series adjustment model, the transfer function of the system 
is shown in figure 5-1.   
 
 
 
 
 
 
 
 
 
Figure 5-1 Transfer function of auto segment 
  Under-excitation limitation and protect 
Under-excitation  limitation  set  by  double  stage.  See  figure  5-3.  The  first  line  is  the 
limitation  line,  and  the  second  line  is  the  guard  line.  Something  to  explain,  there  is  a 
constant reactive PI close loop named reactive loop for short. When the reactive power 
hasnt  entered  the  under-excitation  limitation  line,  auto  control  loop  enables.  At  that 
time, the reactive power loop tracks and the control variable does not output. When the 
reactive power enters the low-excitation limitation zone, the control variable will output 
to  the  thyristor.  The  regulator  runs  under  const  reactive  power  mode,  which  controls 
the  reactive  power  nearby  the  limit  value  not  to  continue  to  reduce,  simultaneously 
sends the alarm signal. If system operation status changes and the control variables are 
       
                                                            Rotor negative voltage feedback 
                        Lead-lag  segment                                            Thyristor  segment     
Generator 
 
                                 
                                                    _       
                           
 
                                                                Measurement segment 
 
 
     
S T
 S T
S T
 S T
K
P
4
3
2
1
1
1
1
1
+
+
+
+
                           
S T
K
e
e
+ 1
 
 
s T
c
+ 1
1
 
S T
K
R
R
+ 1
 
S T
d 0
1
1
+
 
  20 
larger  than  the output  value  of  const  reactive  power,  the  regulator  is  switched  to  const 
voltage  mode  and  exits  from  the  low-excitation  loop.  If  the  regulator  enters  the 
limitation under some operating mode and has not been controlled, the reactive power 
continues  to  decrease.  When  the  reactive  power  is  lower  than  the  guard  line,  the 
regulator sends the alarm signal and enters the manual mode.   
Low-excitation  limitation  line  and  low-excitation  loop  parameter  could  be  set  on  the 
menu. Guard line value is as large as 1.25 times of reactive power on the limitation line. 
I
II
 
Q
P
Qa
Qb
1.25Qa
 
Fig 5-3 Under-excitation limitation diagrammatic sketch 
Where, Qa is the reactive power value, when the active power is zero and the generator 
condensive  operation  is  allowed.  Qb  is  the  max  reactive  power  value,  when  the 
generator condensive operation is allowed. 
  Over-excitation limitation 
Over-excitation  limitation  is  to  prevent  the  generator  rotor  excitation  winding  from 
long-term  over-excitation.  Considering  heat  from  the  rotor  excitation  winding,  when 
reinforce  excitation,  the  tolerance  time  t  has  an  inverse  relation  along  with  the 
generator exciting current Ifd2. See figure 5-4. 
If(A)
t(s)
1.1Ifdn
Ifd_max
 5-4 
1.5S
Fig 5-4 Max exciting current inverse time-lag protection 
Over-excitation limitation and protect follow the rules: 
  21 
a)  When rotor current I
fd
I
fd_max
, delay 1.5 seconds until the locked pulse exits 
operation. 
I
d_max
 is the instant over-excitation value for menu setting 
b)  When I
fd
1.1I
fdn
  I
fd
1.0I
fdn
, calculate the inverse time lag equivalent time 
Heat=(I
fd
2
- I
fdn
2
)t    ;     
Heat_n= (I
fd
2
set- I
fdn
2
)t
_set
 ; 
Where, I
fd
_set is the setting reinforce excitation multiple. 
t
_set
 is reinforce excitation time. 
% 100
_
0    =
n Heat
Heat
H
    H0 is demonstrated on the LCD for monitoring. 
c)  When H0>50%send signal, limit the addition of the excitation. 
H0>80%change to manual operation mode and the given value set to 90%Ifdn 
H0<10%reverting over-excitation signal is allowed 
  V/Hz limit and protect 
V/Hz is to prevent magnetic saturation of the generator and the outlet transformer. The 
principle of the limit and protect is: 
a)  When V/Hz>setting value, lock and add excitation, send over V/Hz signal, limit the 
addition of excitation. 
b)  When V/Hz>(setting value+0.05),    V/Hz fault instruction lamp on, over V/Hz 
relay actsexcitation regulator changes to the manual mode. 1s later, if the V/Hz 
remains acting, this channel exits. 
c)  When frequency >45Hz and <47.5Hz, constant proportional decrease the given 
value of the auto operation voltage. 
d)  When frequency<45Hz, operation exits instantly. 
  System self-checking protect 
System  self-checking  function  contains  the  memory  verification,  the  power  supply 
examination, the thyristor fault checking, and the communication fault checking and so 
on.  When  fault  occurs,  channel  fault  signal  send.  Meanwhile  this  channel  withdraws 
from operation. As to the main backup system, the spare channel launches by itself.   
  Fault wave recording   
Record  all  the  analog  data  collected  between  10s  before  the  fault  and  10s  after  it. 
DVR-2000B records 5 groups of wave recording data according to the FIFO principle. 
The wave profile demonstrates on the liquid crystal screen, and also could be uploaded 
to mater computer for analyzing and printing.   
  Test wave recording 
Record  all  the  analog  data  collected  between  1s  before  the  fault  and  19s  after  it.  The 
number of recording channels is 12. The wave profile demonstrates on the liquid crystal 
screen, and also could be uploaded to mater computer for analyzing and printing. The 
value and time of step response test could be set on the menu. 
  SOE Event recall 
Record  the  time  of  20  groups  of  events  according  to  the  precedence  (precise  to 
millisecond),  including:  the  operation  signal  like  channel  switch  in  or  out;  switch 
variable input signal like magnetic blow-out switch in or out. 
  22 
  Fault recall 
Record  the  time  of  20  groups  of  faults  according  to  the  precedence  (precise  to 
millisecond), fault acting value. 
  Test function 
The function could set the position of the signal adding point, compensation test ability 
or  not,  the  regulators  output  according  to  constant  trigger  angle,  output  the  value  of 
triggers angle and set it adjustable between the min and max value. The operation can 
measure the time-constant of the AC exciter. 
 
  Transfer switch 
In  manual  operation  mode,  automatic  channel  real-time  track  generator  voltage.  In 
auto  operation  mode,  manual  channel  delay  30  seconds  to  follow  rotor  current  (or 
output current). The two modes can undisturbed interchange. 
The operation data can exchange between the double automatic channels with the high 
speed  CAN,  thus  complete  the  backup  channels  follow  to  operation  channel. 
Simultaneously,  the  regulator  figures  out  the  corresponding  trigger  angle  and  it  takes 
real-time comparison to the follow results of these two  kinds of  follow ways to prevent 
the  error  and  fault  track.  That  enhances  the  system  reliability.  Before  the  artificial 
channel  switch  test,  one  should  firstly  inspect  the  status  of  backup  channel  on  the 
tacking  mode.  The  displayed  trigger  angle  of  track  channel  should  be  approximately 
equal  to  the  one  of  operation  channel.  Given  value  of  auto  voltage  UGR  should  be 
approximately equal, so is IFR. 
 
  Operation mode selection 
There are four operation modes of the regulator for choosing 
  constant terminal voltage regulation( AVR) 
  constant excitation regulation( AER) 
  constant power factor regulation   
  constant reactive power regulation   
The four modes above can undisturbed interchange. Where, the latter two modes is the 
auxiliary function superimposed on the fist mode. 
  23 
6    Keyboard, Display and Operation 
DVR-2000B  Microprocessor-based  excitation  regulator  uses  a  large  240*128  LCD,  with  15*8  = 
120 Chinese characters or 30*16 = 480 characters to be shown. It uses T6963C as the control chip, 
with  two  display  modes:  Graphics  mode  and  text  mode.  The  LCD  has  negative  power  supply 
inside, and must be used with external backlight and chip power supply control circuit. 
The  LCD  primarily  implements  the  function  of  Human-Computer  Interaction.  Main  operations 
include measurement display, parameter setting, fault display and invent recall display. All of the 
operations above are completed with the key board. 
 
6.1 Key board Operation Instructions 
OK
Q
RST
 
UP,  DOWN,  LEFT,  RIGHT  arrow  key  is  used  to  select  a  current  item  of  the  menu.  After  the 
selection, it is divided into following two situations: 
(1) The menu displayed in white reverse will be displayed in white reverse form 
(2)  The  menu  displayed  with  cursor  will  put  the  cursor  to  the  selected  position  and  make  it 
glittery. 
In the operation of parameter modification, both UP, DOWN keys can be used. UP key are used to 
increase the number, while DOWN key are used to decrease. 
OK is used to confirm the current selected menu to enter the lower menu items. In the operation 
of  parameter  modification,  it  is  used  to  confirm  the  amendment.  Press  ENTER  in  the  initial 
interface to display the lower main menu interface. 
Q  is  used  to  quit  the  sub-menu  and  return  to  the  higher  menu.  In  the  operation  of  parameter 
modification, it is used to ignore the amendment. 
RST is used to reset the signals which appear in the operation. 
6.2 Main Menu Display 
The main menu is used to display the system operation state and primary measurement data. The 
screen is divided into 4 regions from the top down. 
  24 
Region 1: Fault display area 
Located in the top line, Display Microprocessor-based excitation regulator when the regulator is in 
normal  operation,  and  the  corresponding  fault  when  some  fault  occurs,  such  as  +B  phase  pulse 
fault. Press INVERT to show Microprocessor-based excitation regulator again. 
Region 2: Data display area 
The  corresponding  display  variables  define  as  follows.  All  of  the  variables  is  displayed  in  real 
value. 
UG1:  Mean value of three phase terminal line voltages 
IG1:  Mean value of three phase stator currents 
UFD:  Exciting voltage. Zeros is shown for brushless excitation systems. 
IFD :    Exciting current. Regulator output current is shown for brushless excitation systems. 
UGR:  Preset reference voltage for automatic PID (constant terminal voltage regulation)   
IFR:  Preset  reference  current  for  manual  PID  (constant  rotor  current  or  constant  output 
current regulation) 
P:    Active power 
Q:    Reactive power 
ARF:  Thyristor trigger angle 
COS:  Power factor 
F0:    Terminal voltage frequency 
ILD:    Current output current in double cabinets flow equalization mode 
 
 
Region 3: State display area 
In the region, the main switching values are displayed, including: 
De-excitation  switch:  Unless  particularly  explained,  the  de-excitation  switch  is  connected  to 
normal closed auxiliary junction. State displays break or closing. 
Main oil switch: used to display whether the unit is combined to the grid or no-load running. The 
main oil switch state is judged according to the stator current. 
Channel state: To indicate the operation state of the regulator channel. It includes three conditions: 
operation, trail and exit. 
Operation  mode:  To  denote  current  operation  mode,  including  automatic  operation  mode  and 
Digital Excitation System   
----------------------------------------------------------- 
UG1:    13.80KV        IG1:      6.25    KV 
UFD:    265.1 V                      IFD:    1650    A 
UGR:    13.81KV              IFR:      1651    A 
P      :    125.2MW                  Q    :    -10.13    M 
ARF:    150.1                    COS :    0.866 
F
0 
  :      50.01 Hz             ILD:    50.12      A 
----------------------------------------------------------- 
ECB:    ON/OFF      CH STATE: ON/STBY/EXT 
Main BRK:    ON/OFF          MODE:        AUTO/MAN 
----------------------------------------------------------- 
2003-8-18      161220 
 
  25 
manual  operation  mode.  Automatic  operation  mode  is  constant  generator  terminal  voltage 
regulation,  and  manual  operation  mode  is  constant  rotor  current  closed  loop  regulation.  In 
brushless  excitation  systems,  as  the  rotor  current  cant  be  measured,  manual  operation  mode  is 
constant regulator output current regulation. 
6.3 Main Menu Display 
Press ENTER to get into the main menu display. Press UP, DOWN, LEFT and RIGHT to select 
item. Press Q back to display menu step by step. 
 
6.3.1 Measurement display 
This menu shows all of the measured data and computed values on the screen. 
Corresponding display variables: 
UAB1, UBC1, UCA1: Measured PT three phase line voltages 
UG1:  Mean value of measured PT three phase line voltages 
UAB2, UBC2, UCA2: Measured PT three phase line voltage on the instrument 
UG2:  Mean value of PT three phase line voltages on the instrument 
IA,IB,IC: Three phase stator current 
IG:    Mean value of three phase stator current 
ILA,  ILB:  Utility  in  three  generator  brushed  excitation  systems,  with  the  operation  mode  of 
double-cabinet  current  equalization.  ILA  is  the  excitation  current  of  local  cabinet  and  ILB  is  the 
excitation current of the other one. 
F0:    Terminal voltage frequency of generator 
F1:    Frequency of excitation power supply 
URAN:  External superimposed test signal 
UPSS:  PSS  output.  When  put  in  PSS,  check  this  signal  first.  There  is  no  impulse  when  this 
signal is zero. 
UFD:  Rotor voltage 
IFD:    Rotor current 
P:    Active power 
Q:    Reactive power 
COS:  Power factor, which is rounded to three decimal places. 
ARF:  Trigger angle 
U5V:  5V power supply 
U12V:  12V power supply 
H0:    The percentage of heat productivity 
      -----    MAIN          MENU    ------ 
 
          + Measurements    + Para Setup 
+ Protector on/off    + DI Status 
+ DO Test      + System Test 
+ Fault Record    + Fault Waveform   
+ Event record     + Accuracy Setup 
+ Unit Para      + System Setup 
+ Test Option      + Other Tests 
  26 
US  Voltage in the power system side 
 
6.3.2 Parameter Setting 
This  menu  is  used  to  set  the  parameters  which  are  needed  for  unit  operations,  such  as  PID 
parameters,  PSS  parameters  and  protection  and  limitation  parameters.  The  items  with   
indicate that there is a lower menu. The items without  can be modified directly in current 
menu.  The  menu  needs  password  for  entry.  The  method  to  modify  parameters  is  explained  as 
follows: 
Select  relevant  item  and  press  ENTER  first,  and  then  a  glittery  cursor  appears.  Press  LEFT  and 
RIGHT  to  move  the  cursor  to  the  position  for  modification.  Press  UP  and  +  key  to  increase 
number, and DOWN and - key to decrease number. After modification, press ENTER to make 
amendment  valid  and  cursor  disappears.  Press  Q  to  make  amendment  invalid  and  cursor 
disappears. 
 
----------      Measurements      --------- 
 
UG1            K V    ILA      A 
UAB1          KV    ILB      A 
UBC1    KV    P:                MW 
UCA1    KV    Q:                  MVar 
IG    KA    COS 
IA    KA    F0                  Hz 
IB                KA        F1                  Hz 
IC    KA    ARF 
UG2    KV    URAN   V 
UAB2    KV    UPSS    V 
UBC2    KV    U5V    V 
UCA2    KV    U12V    V 
      UFD        V    H0    % 
IFD    A    US:      KV 
 
 
            -------    Para Setup  ------ 
 
          + AUTO PID      + MAN PID     
+ PSS Para      + UEL Para       
+ MAXIF1 VAL  2.0    + DLY IF MAX  10 S   
+ Max I
f
2
 VAL   2.2    + V/Hz VAL          1.15 
+ Q_droop         +/-    + Q_droop VAL      5% 
+ Max Angle         150          + Min Angle          20 
+ Xq        0.7    + Inc/dec      0.2% 
               
  27 
6.3.2.1 Automatic PID 
This menu is used to set the PID parameters which are needed for system operations graphically. 
The method of modification is same to that described above. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
6.3.2.2 Manual PID 
This menu is used to set the PID parameters which are needed for manual operations. 
       
------ - AUTO    PID    PARA    ------ 
 
 
                                 
                                                    _       
                           
 
 
T1= 0.94 S          T3= 0.5S            KP=12 
T2=    9.4S          T4= 0.05S        b=0.02 
     
S T
 S T
S T
 S T
K
P
4
3
2
1
1
1
1
1
+
+
+
+
                           
S T
K
e
e
+ 1
 
b 
  28 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
6.3.2.3 PSS Parameters 
Display the PSS transformer function and relative parameters graphically. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
      -----    MAN    PID    PARA    ------- 
 
                                               
 
S T
 S T
S T
 S T
K
P
4
3
2
1
1
1
1
1
+
+
+
+
                           
                                               
 
T1=    0.8S        T3=2.0 S    KP=5 
T2=    8.0S        T4= 2.0 S         
     
                  ----    P S S    PARA ----- 
 
 
            9      10 
AW                      +         
 
 
    11      1213                        14-22 
AP                                                                                                 
 
   
                              24-27 
             
 
 
               
 
Tw1=0.15    Tw2=0.25    Ks2=1.00   
T5=0.15    T6=0.25    T7=1.00 
T8 =0.15      T9=0.25    M=4 
KS1=100    T1=0.13    T2=0.22 
T3=0.08    T4=0.05    Ks3=1.00 
S T
 S T
W
W
1
1
1+
 
S T
 S T
W
W
2
2
1+
 
S T
 S T
W
W
1
1
1+
 
S T
Ks
7
1
2
+
 
S T
  S T K
S
2
1
1
) 1 (
+
+
 
S T
 S T
4
3
1
1
+
+
 
 
Ks3 
M
S T
  S T
) 1 (
1
9
8
+
+
 
S T
 S T
6
5
1
1
+
+
 
  29 
6.3.2.4 Under-Excited Limit 
A:  Point A of under-excited limit 
B:  Point B of under-excited limit 
K:  The proportion factor of under-excited loop 
Ti:  The time constant of under-excited loop 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
6.3.2.4  Other Parameters Explanation   
Reinforced  exciting  multiple:  used  to  set  the  max  permitted  excitation  current.  When  the 
excitation current reaches the preset reinforced exciting multiple, the regulator strongly cuts down 
and restricts the excitation current under the preset multiple. 
Reinforced  exciting  time:  used  to  set  the  max  permitted  reinforced  excitation  time  when  the 
excitation current reaches the preset reinforced excitation multiple. 
Instant  over-excitation:  used  to  set  the  protection  action  value  for  instant  over  excitation.  1.5 
second time delay after excitation current reaches this value, cut off the regulator at once. 
V/Hz Multiple: used to set the V/Hz protection value. Setting range is from 1.00 to 1.50 
The  polarity  of  reactive  power  adjusting  characteristics:  it  can  be  set  to  positive  or  negative 
reactive power adjusting characteristics according to unit conditions. 
The coefficient of reactive power adjusting characteristics: it can be set in the range from 0% 
to 15% with 0.1% step. 
Max    angle:  used  to  set  the  maximal  limit  value  of  PID  output.  Generally,  150  for  fully 
controlled bridge and 170 for semi-controlled bridge. 
Min  angle: used to set the minimal limit value of PID output. Generally, 15 for fully controlled 
bridge and 50 for semi-controlled bridge. 
Quadrature axis reactance: a parameter for PSS computation. 
Increasing/decreasing rate: used to set the voltage change rate for the increasing and decreasing 
operations. Setting range is from 0.2% to 2% UGN/s. 
      -------      UEL    LIMITER ----------- 
           
                  Q                                                           
                      B     
                        P 
       
A 
 
 
A0200.2Mvar      B300.3MW0 
K1.0        Ti: 2.55S 
  30 
6.3.3 Protection Withdrawal 
Set  the  withdrawal  switch  of  protection  terms  in  this  menu.  Need  password  for  entry.  Notice: 
select the corresponding menu first, and then press ENTER to get into the modification state while 
a  glittery  cursor  appears. Press  UP  and DOWN  to  change  the  withdrawal  state.  Press  ENTER  to 
make  the  amendment  valid  and  the  cursor  disappears  at  the  same  time.  Press  Q  to  ignore  the 
amendment and the cursor disappears. 
 
6.3.4  Switching input status 
The switching input status display can totally show 20 real time state variables. The last five lines 
need to scroll the screen. Test method (switching input variable from the switching variable input 
board):  add  24V2  power  supply  on  the  back  terminal  in  term  to  observe  the  change  of 
corresponding  switching  input  variable.  It  will  display  closed  while  the  signal  is  valid  and  open 
while the signal is invalid. 
Notice:  among  all  of  the  switching  input  variables,  only  De-excitation  switch  and  (current 
equalization)  operation  are  required  to  be  normally  closed.  It  will  display  open  while  add 
24V2 power supply to these two switches, and closed with no signal added. 
         
------- PTOTECTOR ON/OFF ----------- 
 
          + PT BRK  ON/OFF        + V/HZ L       ON/OFF 
+ UEL    ON/OFF    + OEL:    ON/OFF 
+ PUS MON   ON/OFF    + SELFCHK   ON/OFF 
+ TRIP ECB   N/OFF    + OWN EXT ON/OFF 
   + OTH EXT   ON/OFF    + SPARE      ON/OFF 
+ SCR MON   ON/OFF    + SPARE    ON/OFF 
+ SPARE      ON/OFF    + SPARE    ON/OFF 
  31 
 
6.3.5 Drive Test 
The switching values are output constrainedly  in the drive test. Notice: the menu is only valid in 
the  halt  state  (when  the  de-excitation  switch  is  in  the  open  position).  The  menu  can  be  access 
without password. 
Test  method:  select  the  item  to  be  test  first.  Press  ENTER  and  a  glittery  cursor  appear. Press UP 
and DOWN to change the switching state and then press ENTER to confirm. Press Q to keep the 
corresponding switching state, and test whether the bit of the switching output in back terminal is 
changed. While each limit and protection acts, the channel fault indication on the regulator panel 
will be lighted. Only if all of the limit and protect test is canceled, the channel fault indication will 
be reverted. 
 
6.3.6 System Test 
Step response test can be implemented in this interface, and the waveform of the selected variable 
also can be shown in the form of norm value. Press LEFT and RIGHT to select the corresponding 
menu. Press ENTER to modify  the corresponding variable. Step variable can be modified with a 
deviation  of  20%.  Secondly,  set  the  hold  time  of  step  signal  with  a  range  from  0  second  to  15 
seconds and a minimal resolution of 0.1 second.   
Select START menu and then press ENTER to output step variable. Menu display is stopped until 
20 seconds record time is completed, and then the menu renews to display START. Press ENTER 
          --------      DO      TEST      -------- 
+ ON Auto        ON/OFF      + ON MAN        ON/OFF 
+ ON PSS            ON/OFF      + ON Q_CTRL      ON/OFF 
+ ON COS_CTRL ON/OFF      + PT_FAULT      ON/OFF 
+ V/HZ LIMIT  ON/OFF    + OEL FAULT       ON/OFF   
+ UEL          ON/OFF      + SELF_CHK        ON/OFF 
+ SCR fault      ON/OFF      + PUS lose      ON/OFF 
+ SPARE        ON/OFF      + TRIP        ON/OFF 
+ OTH_EXT          ON/OFF      + OWN_EXT      ON/OFF 
                   
        --------      DI      Status    --------- 
          + ECB :      ON/OFF        + Soft Start:    ON/OFF 
+ OTH EXT DI      ON/OFF      + 95%SPEED:  N/OFF 
+#1 fault:    ON/OFF        + #2 fault:    ON/OFF 
+ #3 Fault:    ON/OFF        + PSS :      ON/OFF 
+ CH Enable      ON/OFF    + CH Active:    ON/OFF 
+ AUTO mode :  ON/OFF    + INC         ON/OFF 
+ DEC :      ON/OFF    + Q_CTRL      ON/OFF 
+ COS_CTRL      ON/OF      + DI_SELFEXT    ON/OFF 
+ OTH_24V2      ON/OFF    + OWN_24V1    ON/OFF 
+ OWN_24V2      ON/OFF      + MBK        ON/OFF 
+ SPARE        ON/OFF    + SPARE        ON/OFF               
  32 
to  cancel  step  variable  once  some  abnormal  situations  occur  in  the  system  and  the  menu  display 
get back to START. 
After  the  test,  select  WAVE  menu,  and  then  press  ENTER  to  choose  the  record  variables  to  be 
shown.  Press  UP  and  DOWN  to  change  current  record  variable  to  display,  including  totally  12 
waveforms:  UG1,  UG2,  IG,  UFD,  IFD,  ILA,  ILB,  P,  Q,  o,  UGREF,  IFREF.  Press  ENTER  and 
then a vernier appears. The time and current amplitude of corresponding point is displayed on the 
right upper screen. Press LEFT and RIGHT to move slowly. Press DOWN to move right fast and 
UP to move left fast. Press Q to quit the menu step by step. The test interface need password for 
entry. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
6.3.7 Fault Recall 
Fault status and the data in the moment faults occur can be displayed in the menu, including action 
time  (in  millisecond  precise),  action  type  and  action  value.  Action  value  are  important  collected 
values of analog variable and computation values in the moment faults occurred, such as overheat 
cumulative value H0, the definition and computation method of which is described in Chapter 5 in 
detail.  For  power-fail  storage,  the  record  data  is  saved  to  serial  EEPROM  with  20  groups  of  this 
data totally. Press UP and DOWN to scroll. 
 
WAVE:UG1    ---------    System    Test    --------    
 
1.0pu          0.9pu,5.0 S     
                       
                       
                                     
                      20S 
 
 
 
STEP10%    TIME15S    START/STOP 
 
 
  33 
 
6.3.8 Fault Waveform 
As  the  system  test,  the  waveform  display  can  record  four  sets  of  waveform.  After  entering  the 
menu,  select  NUM  menu  automatically,  and  the  glittery  cursor  appear.  Press  UP  and  DOWN  to 
select  the  set  to  be  observed.  The  record  time  and  fault  type  of  this  waveform  appear  in  the 
undermost line. Its same to the system test to observe the waveform after selecting WAVE menu. 
 
 
 
 
 
 
 
 
 
 
 
 
6.3.9 Event Recording 
Event Recording is used to record the change of important switching variable. The total number of 
recording  is  20  with  the  principle  of  FIFO.  Press  UP  and  DOWN  to  scroll.  Meanwhile,  indicate 
whether it is from 0 to 1 or from 1 to 0. 
      -------- FAULT Recall --------- 
           
2003-8-20            16:30:12:150    1/20 
Type      OEL 
FAULT value 
Ug1:    KV  Ug2:    KV 
Ufd:            V    Ifd          A 
P1:            MW  Q1:              MVar 
ARF:                       F0:              Mvar 
UGR:        KV         IFR:            A 
ILB:            A          ILA          A 
U12V    V    U5V    V 
H0:        100 %        COS     
WAVE  UG1--------    Fault Waveform  ---------- 
                          (0.92pu,1.23s) 
1.0pu                       
                                       
               
                           
20S   
 
NUM1/4 
 
Time2003-12-12 122034123      Fault 
 
 
  34 
 
6.3.10 Accuracy Setting 
The menu provides a function of software potentiometer to modify the difference between actual 
measured value and displayed value. It needs password for entry. 
Notice: it is set OK in the factory and generally no need to modify in field. 
   
6.3.11 Unit Parameters 
The way to modify unit parameters is just as that above. No mistake with the input unit parameters. 
Input the same value of rated exciting current to that of rated output current for brushless exciting 
system. 
      ---------      Event    Record    --------- 
           
1    2003-8-20            16:30:12:150     
ECB        01           
2    2003-8-20            16:30:12:150     
ECB        10           
3    2003-8-20            16:30:12:150     
ECB        10       
 
 
       
        ------    Accuracy    Aadjust    ------ 
             
UAB1:    1.000      UFD:  1.000 
UBC1:  1.000    IDF:   1.000 
UCA1:    1.000    URAN:  1.000 
IA:       1.000    AD16:  1.000 
IB:      1.000             ILB:   1.000 
IC:       1.000    ILA:  1.000 
UAB2:  1.000    U12V:  1.000 
UBC2:    1.000    U5V:  1.000 
UCA2:    1.000    P1  1.000 
USA:      1.000    Q1:    1.000 
USB:      1.000    U1:    1.000 
USC:   1.000    U2:    1.000 
 
   
  35 
 
6.3.12 System Configuration 
Baud  rate  1  is  the  baud  rate  of  RS232  communication  while  baud  rate  2  is  that  of  CAN 
communication.  DA1  and  DA2  output  are  optional  DA  output  of  two  channels.  Channel 
configuration  can  be  set  as  single  channel  operation or  dual  channels  operation. Operation  mode 
can  be  set  as  master  cabinet,  slave  cabinet  (double-cabinet  current  equalization)  or  primary 
stand-by  mode.  Fault  clearing  can  clear  the  recalled  fault.  Event  clearing  can  clear  the 
corresponding  event  recording.  This  menu  needs  password  for  entry.  Password  setting  can  set  a 
new  password.  Furthermore,  the  menu  also  provides  time  correction  function.  Channel 
configuration:  is  used  to  configure  the  channel  as  single  or  dual  channels  and  the  mutual  check 
function between the channels is latched while single channel is set. Operation mode: according to 
specific  excitation  mode,  the  channel  can  be  configured  as  master  cabinet,  slave  cabinet  and 
primary  standby.  For  an  excitation  regulator  of  double-cabinet  current  equalization  mode,  the 
setting  value  of  slave  cabinet  changes  with  the output  current  of  the  master  cabinet,  to  attain  the 
effect of double-cabinet current equalization. Two channels are equivalent in the primary standby 
mode, one operating while the other trail. 
 
 
-----------    Unit    Parameters    ------------ 
 
Rated UG  13.8    KV 
Rated IG        KA 
Rated UFD        A 
Rated IFD        V 
Rated No-load UFD0    V 
      Rated ILD        V 
      F_PWR Supply  350    Hz 
        -----    System    Settings    ------ 
 
Password  9999          COM ID  0001 
Baud rate1  9600          Baud rate2          40K 
DA1 NUM  0001          DA2 NUM        0001 
CH SET:    single/dual  Mode: master/slave /PRI-STBY 
-------------------------------------------------------------- 
Fault CLR  OK  Event CLR OK 
Time Set      2003-8-21 16:30:12                     
  36 
6.3.13 Test Option 
Test Enabling Signal: 
After  entering  the  menu,  the  test  enabling  signal  is  in  the  prohibition  state.  Press  ENTER  and 
glittery  cursor  appears.  Press  UP  and  DOWN  to  change  the  signal  to  the  permission  state.  Press 
ENTER again to add the test signal to test signal add point. Press CANCEL to make amendment 
invalid and cursor disappears. The test enabling signal is set to the prohibition state automatically 
before exiting. The test signal add point is corresponding to the position where the test signal adds 
in. 
0      Voltage setting value 
1-8      Reserved 
9-27   PSS transform function add point (see in PSS block diagram) 
Notice:  the  function  can  only  be  used  in  test.  Test  enabling  signal  must  be  forbidden  in  normal 
operation.   
Test  type  includes  test  with  compensation,  test  without  compensation  and  terminating  state. 
Set test type to test without compensation and PSS output to zero, and then test the characteristic 
of PID segment. Set test type to test with compensation and PSS output to zero, and then test the 
characteristic of PSS plus PID segment. Set test type to terminating state and PSS works normally. 
Notice:  quit  PSS  first  to  change  test  type.  After  that,  observing  the  displayed  measured  UPSS 
output, put PSS into operation until UPSS steady output near zero. 
PSS limit is the proportion of PID output, less than 10% in general. 
PSS  input  is  the  limit  of  corresponding  PSS  input.  That  is  to  put  PSS  into  operation  while  the 
generator active power reaches the rated active power proportion. 
PSS quit is the limit of corresponding PSS. That is to quit PSS while the generator active power 
reaches rated active power proportion. 
 
6.3.14 Other Test 
If constant pilot angle output enable is changed to a permission state, controller outputs constant 
pilot angle. It is not used commonly. 
Constant pilot angle output is used to set the angle of constant output, which can be set between 
the maximal and minimal pilot angle. 
        -----    Test    Option    ------ 
 
Test    Enable:     Enable/Disable 
Test signal NUM:    0-30 
Test type:   with compensation/without compensation/END 
PSS limitation value:  1%-10% 
PSS switch in    30% 
PSS switch out    20% 
 
 
  37 
 
 
 
6.4 Operation description 
6.4.1  Local operation 
  Switch 1QK to Shut off. 
  Turn on regulator power switch 1QS, 2QS. 
  Put remote/local on local 
  Close switch 1KKA, 1KKB 
  Switch  3QK  to  AUTO,  switch  1QK  to  channel  A  or  Channel  B,  generator  voltage 
raise to 90% rated voltage in several seconds. 
  Operate  INCREASE  5QK,  generator  voltage  increase  to  rated  voltage.  Parallel  with 
power system. 
6.4.2  Remote operation 
6.4.2.1  Be sure that the status QK1,QK3 on the remote console and 1QK,3QK on the cabinet are 
same  before  remote  operation.  Switch  2QK  to  remote.  The  others  are  same  as  local 
operation. 
Note: Be sure that the QK1, QK3 on the remote console and 1QK, 3QK on the cabinet are 
same state before switch 2QK from local to remote. And be sure that the 1QK, 3QK on 
the  cabinet  and  QK1,  QK3  on  the  remote  console  are  same  state  before  change  over  from 
remote to local. 
6.4.3  Normal Stop 
  Decrease generator reactive load to zero. 
  Deparallel generator. 
  Press decrease button, depress the voltage to lowest level. 
  Switch  1QK  and  QK1  to  quit  position,  shut  off  switch  1KKA,  1KKB,1QS,  2QS  ,  then 
DVR-2000B is quit. 
6.4.4  Others 
6.5    Maintenance   
The  hardware  of  DVR  are  simple  and  credible,  commonly  it  neednt  special  maintenance. 
When DVR is off, only be care for following: 
6.5.1  Check the junction and terminal of the DVR. 
6.5.2  Clean dust and foreign matter in the cabinet. 
6.5.3  Check switch and indicator light. 
6.5.4  Improve running environment, Increase natural life of the DVR. 
6.5.5  Study  theory  of  operation,  the  method  and  principle  of  function  of  components  setting. 
Thus can make properly regulation on time when working mode is changing. 
6.6    Checking item 
When DVR is serving, checking as following 
      ----    Other    Test    ------ 
 
Constant angle Enable:    Enable/Disable 
Constant Angle SET  150 
 
 
  38 
6.6.1  Check the junction of cabinet according to the wiring drawing. 
6.6.2  Check insulation: Test the insulation resistance between the terminal and the cabinet with 
the megaohm meter, and record it. 
6.6.3  Check  power  supply:  Put  on  DC  supply.  Test  all  DC  voltage  in  the  terminal  block,  and 
record. 
6.6.4  Check digital input: Connect the terminal block of digital input with DC24V2, select the 
position of operation switch in the cabinet, then read it on the LCD, check the validity and 
record. 
6.6.5  Check digital output: Open the digital output screen, change the digital output, Check the 
light and indicator on the IOX and relay boards. Record the result. 
6.6.6  Check simulant input:  Input the AC voltage and current in the terminal block, check the 
correspond value in the LCD. 
6.6.7  Check pulse circuit: Power on DVR, connect a load to DVR, select manual mode, Check 
pulse indicator light on PGC board and the output voltage waveform.