Panelboard Eaton
Panelboard Eaton
September 2009
1-1 1-1
Panelboards
Contents
Description Section 1 - General Information Product Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EZ Box and EZ Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Application Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Standards and Certications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Data and Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Integrated Equipment Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section 2 - Lighting & Distribution Panelboards Type PRL1a Lighting Panelboard, 240 Vac Maximum . . . . . . . . . . . . . . . . . . . Type PRL2a Lighting Panelboard, 600Y/347 Vac Maximum. . . . . . . . . . . . . . Type PRL3a Lighting or Small Power Panelboard, 600 Vac Maximum . . . . . Type PRL4 Power Distribution Panelboard, 600 Vac Maximum . . . . . . . . . . . Type PRL1a-LX Column Type Panelboard, 240 Vac Maximum . . . . . . . . . . . . Type PRL2a-LX Column Type Panelboard, 600Y/347 Vac Maximum . . . . . . . Box and Trim Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Accesories and Modications (1a, 2a, 3a, 4, Column Type) . . . . . . . . . . . . . . Page 1-2 1-5 1-4 1-7 1-9 1-10 1-13
Section 3 - Specialty Application Panelboards Type PRL5P Power Distribution Panelboard, 600 Vac Maximum, Plug-on . . . . 3-1 Retrot Panelboard PRL1R / PRL2R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7 Pow-R-CommandLighting Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
1 1
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-2
September 2009
1-5
Product Types
Type PRL1a
Bolt-on Circuit Breakers 240V AC Maximum
Type PRL3a
Bolt-on Circuit Breakers 240V, 480V or 600V AC; 250V DC Maximum
Type PRL5P
Plug-on Circuit Breakers 240V, 480V or 600V AC; 250V DC Maximum
Main Lugs Only 600 amperes maximum. Main Circuit Breaker 400 amperes maximum. Branch Circuit Breakers 100 amperes maximum. (1 pole and 3 pole) 125 amperes maximum. (2 pole)
Main Lugs Only 600 amperes maximum. Main Circuit Breaker 600 amperes maximum. Branch Circuit Breakers 225 amperes maximum, 1-, 2- and 3-pole.
Main Lugs Only 1200 amperes maximum. Main Circuit Breaker 1200 amperes maximum. Branch Circuit Breakers 1200 amperes maximum, 1-, 2- and 3-pole.
Type PRL3a
Type PRL5P
1
Type PRL2a
Type PRL1a
Type PRL4
Circuit Breakers or Fusible Switches 240V, 480V or 600V AC; 250V DC Maximum
Pow-R-Command
Bolt-on Circuit Breakers 240V or 480Y/277V AC
Main Lugs Only 600 amperes maximum. Main Circuit Breaker 400 amperes maximum. Branch Circuit Breakers 100 amperes maximum, 1-, 2- and 3-pole.
Main Lugs Only 1200 amperes maximum. Main Circuit Breaker 1200 amperes maximum. Main Fusible Switch 1200 amperes maximum. Branch Circuit Breakers 1200 amperes maximum, 1-, 2- and 3-pole. Branch Fusible Switches 1200 amperes maximum, 2- and 3-pole.
Main Lugs Only 400 amperes maximum. Main Circuit Breaker 400 amperes maximum. Branch Circuit Breakers 225 amperes maximum, 1-, 2- and 3-pole. Integral Power Switching Controls.
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-6
1-3
Retrot Panel
Retrot Panel
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
1-4 1-7
September 2009
Product Description
Lighting and Distribution Panelboards
Cutler-Hammer assembled panelboards by Eaton Corporation are designed for sequence phase connection of branch circuit devices. This allows complete exibility of circuit arrangement (1-, 2- or 3poles) to allow balance of the electrical load on each phase. Sturdy, rigid chassis assembly assures accurate alignment of interior with panel front; prevents exing and minimizes possibility of loosening or damage to current carrying parts during and after installation. Four-point in-and-out adjustment of panel interior is provided to meet critical depth dimensions on ush installations. This compensates for possible misalignment of box at installation. Main lugs are mechanical solderless type and approved for copper or aluminum conductors.
The fronts for lighting and appliance branch circuit panelboards and small power distribution panelboards include a door with rounded corners and concealed hinges. A ush-type latch and lock assembly is included. All locks are keyed alike. These trims are available in both surface and ush mounted designs.
11
Enclosures
Boxes are code-gauge galvanized steel. Standard panelboard cabinets are designed for indoor use. Alternate types are available for indoor and special purpose applications. All enclosures are furnished in accordance with Canadian Standards Association and include wiring gutters with proper wire bending space. Special cabinets can be provided at an additional charge. The box dimensions shown are inside dimensions. For outside dimensions, add 1/4-inch (6.4 mm).
EZ Trim features standard door-in-door with no exposed hardware or sharp edges (no tools are required for installation)
Fronts
Fronts (trims) for all panelboards are made of code-gauge steel and have a high durability ASA-61 light gray nish applied by a baked-on polyester powder coating paint system.
The three-piece trim for larger power distribution panelboards provides for easy handling and installation
Fronts for power distribution panelboards utilize a unique breaker front cover design in which each device has a dedicated bolt-on steel cover. The individual covers form a single deadfront for the panelboard that is used in conjunction with two wiring gutter covers to complete the trim. A door is not nished as part of the standard offering on these panelboards but can be provided, for an additional charge, using a deeper than standard box.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
1-2
1-5
September 2009
Features
Virtually eliminates sharp edges. Trim installs in seconds rather than minutes. Door-in-door is standard. Ability to adjust ush box to wall irregularities. Trim installs without the need for tools. No exposed hardware (because there is none). Multipoint door latch over breakers.
the nished wall after the wall material is installed to help correct wall irregularities. The new box ange also provides the means for attaching the EZ trim.
The EZ box anges are bent and painted, which virtually eliminates the sharp edges associated with traditional boxes. Additionally, all steel panelboard chassis parts are painted. This signicantly reduces potential injury for material handlers and installers. Each ange is adjustable outward up to 3/4 inch. This feature allows the installer to adjust ush box applications to be level and at with
1
Flange Detail
Eatons new EZ box and EZ trim represents the rst signicant change in panelboard box and trim designs in more than a half-century. The EZ box and EZ trim have been designed for faster, more secure and safer installations. The new EZ box and EZ trim are provided standard for Cutler-Hammer Pow-R-Line 1a and Pow-R-Line 2a lighting panelboards, as well as our Pow-R-Line 3a mid-range panelboard.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
1-6
September 2009
1-3
Fast Installation
The EZ trim incorporates a patent pending, ground breaking design that installs in seconds, rather than minutes. The standard trim features include door-in-door construction; no exposed hardware and no tools are required for installation. Each EZ trim includes hangers attached on the right side. The bottom trim hanger has a notch in its base. To install, the bottom hanger is inserted into the bottom right side box ange opening, resting the notch on the ange.
The balance of the hangers are aligned with the other ange openings and pushed in. When all hangers are in the box ange, the trim is lifted up slightly to clear the notch on the bottom hanger, and the trim in self-supported on the EZ box. The installation is completed by swinging the trim to the closed position, then lifting and pushing slightly to the right. The trim will drop into place totally secured. The multi-point catches on the left side of the trim will lock into the left side box ange openings. To prevent the trim from being removed by non-authorized persons, a unique sliding means automatically latches in place when the trim door is closed. For added safety, a screw is provided to secure the latch for those who require extra security. The new EZ trim utilizes an exclusive catch system that fastens the door to multiple points. Along with a new lock, the EZ trim offers a high degree of door security.
1
Trim Hanging on Surface Mounted Box
Standards
When used with Eatons Cutler-Hammer panelboard chassis, EZ boxes and EZ trims meet the following applicable industry standards: CSA C22.2#29 approved. NEMA Standard PB1. Canadian Electrical Code
New Lock Trim Installed with Door Open and Trim Sliding Latch
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-8
1-7
September 2009
Application Description
Panelboard Selection Factors
In selecting a panelboard, the following factors must be considered: Service (voltage and frequency). Interrupting capacity (fully or series rated). Ampere rating of main. Ampere ratings of branches. Environment.
Multi-Section Panelboards
Separate fronts for each box are standard. Where the required number of branch circuit devices ex-ceeds the available space in any single panelboard, multiple-section assemblies may be provided. These assemblies consist of two or more close-coupled enclosures with provisions for inter-connecting power cables or bus.
Sub-Feed Lugs
Sub-feed lugs (see Figure 1-1) are one means of interconnecting multi-section panels. The sub-feed (second set of) lugs are mounted directly beside the main lugs. These are required in each section except the last panel in the lineup. The feeder cables are brought into the wiring gutter of the rst section and connected to the main lugs. Another set of the same size cables are connected to the sub-feed lugs (Section 1) and are carried over to the main lugs of the adjacent panel. Cross connection cables are not furnished by Eaton. Sub-feed lugs are only available on main lug only panels.
Box Box
Neutral
Figure 1-1. Sub-Feed Lugs In situations requiring large numbers of overcurrent protective devices, or when site conditions demand panelboards may be supplied in multiple sections.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
1-8 1-9
September 2009
Through-Feed Lugs
Through-feed lugs (see Figure 1-2) are another method to interconnect multisection panelboards. The incoming feeder cables are connected to the main lugs or main breaker at the bottom of panel (Section 1). Another set of lugs (through-feed) are located at the opposite end of the main bus. The interconnecting cables are connected to the through-feed lugs in Section 1 and are carried over to the main lugs in Section 2. The connection arrangement could be reversed, i.e., main lugs at top; through-feed lugs at bottom end of panel. Cross cables are not furnished by Eaton.
Box Box Cross Cables Main Lugs Neutral Panel
3/4 (19.1)
Wall
3/4 (19.1)
3/4 (19.1)
Trim
Trim
Wall
Contractor to Mount Boxes 1-1/2-inch (38.1 mm) Apart to Allow for 3/4-inch (19.1 mm) Extension on Both Flush Trims Trim Outside Edge of Box
ThruFeed Lugs
Panel
3/4 (19.1)
3/4 (19.1)
3/4 (19.1)
11
Main Lugs Conduit
Neutral
Flush Trim Extends 3/4-inch (19.1 mm) Beyond Outside of Box on All Four Sides
Figure 1-3. Multiple Section Panelboard Flush Mounted Dimensions in Inches (mm)
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
1-9
CAT.38.03.S.K
1-10
September 2009
1-11
PRL4B
Where copper-aluminum terminals are supplied on designated panelboard types, best results are obtained if a suitable joint compound is applied when aluminum conductors are used. Check Eatons Cutler-Hammer standard terminal sizes versus customer requirements. In particular, 400 and
800 ampere breakers often require nonstandard lugs. Optional 750 kcmil mechanical screw-type terminals are available upon request. Panelboard dimensions may be affected, refer to Eaton.
PRL1a-LX #12 #1/0 PRL2a-LX #12 #1/0 PRC750/ 1000/ 2000 PRC25 PRL5P #12 #1/0
#12 #1/0
#6 300 kcmil
(2) #4 500 kcmil (1) #1/0 500 kcmil or (2) #1/0 250 kcmil
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
September 2009
1-12 1-11
1 1
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-12
Panelboards
1-13
Table 1-5. Moulded Case Circuit Breaker Ratings Table 1-5. Moulded Breaker Ratings Note: Circuit breakersCase equalCircuit or exceed Federal Specification W-C-375b requirements for the particular class associated with each circuit breaker type.
Continuous Ampere Rating
15 70 15 125 15 100 15 30 15 30 15 40 15 50 15 20 15 70 15 100 15 100 15 30 15 30 15 20 15 100 15 100 15 - 70 15 - 100 15 60 15 30 15 30 15 100 15 100 15 100 15 150 15 150 15 225 15 225 15 150 15 225 15 225 15 - 30 15 225 15 100 100 225 100 225 100 225 70 250 70 250 70 250 250 400 100 400 100 400 100 400 125 400 300 600 300 600 300 600 300 600 300 600 300 600 400 800 400 800 600 1200 600 1200 600 1200 15 100 70 400 300 800
Number of Poles
1 2 2, 3 1 2 1 2 1 1 2 2, 3 1 2 1 1 2, 3 1 2, 3 1 1 2 1 2, 3 1 2, 3 1 2, 3 3 1 2, 3
Volts ac
120 120/240 240 120 120/240 120 120/240 120 120 120/240 240 120 120/240 277 277 480Y/277 347 600Y/347 277 277 480Y/277 277 480 347 600 347 600 600 347 600
240
10 22 65 65 65 18 18 18 65 65 100
480
14 14 14 14 14 35 35 65
600
10 14 18 14 14 25 25
125
10 14 18 18 25
250
14 14 10 10 10 10 10 10
250
14 14 10 10 10 22 22 10 22 22 10 10 22 22 22 10 42 50 25 25 22 25
FD FDE HFD HFDE FDC FDC FCL ED EDH EDC JD HJD JDC DK KD, CKD HKD, CHKD KDC LCL LD , CLD LGE LGH LGU HLD , CHLD LDC , CLDC MDL , CMDL HMDL , CHMDL ND , CND HND , CHND NDC , CNDC FB-P LA-P NB-P
3
1 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 3 3 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3 2, 3
600
347 600 480 240 240 240 600 600 600 240 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600
100
200 200 65 100 200 65 100 200 65 65 100 200 200 65 65 100 200 100 200 65 100 65 100 200 200 200 200
65
100 150 35 65 100 35 65 100 200 35 35 65 150 65 100 50 65 50 65 100 200 200 200
25
30 35
25
35 18 25 35 25 35 65 100 25 18 35 65 35 50 25 35 25 35 65 200 200 200
DC ratings apply to substantially non-inductive circuits. 15 and 20 amperes 1-pole switching duty rated for uorescent applications. 1-, 2- and 3-pole HACR rated. DC rated 1-pole, 15 70 amperes only 2- and 3-pole HACR rated. 100% rated circuit breaker. Available with integral ground fault protection. DC rating not available with electronic trip. 100k based on NEMA test procedure. 50 ampere devices available as 2-pole only.
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-14
1-13
September 2009
Integrated Equipment Ratings - Series Combinations Integrated Equipment Ratings - Series Combinations
The electrical standards of Canada provide 2 different methods of applying assemblies such as panelboards, switchboards, etc into an electrical system: Fully Rated: The short circuit protective devices at all levels have a rating that matches or exceeds the system available fault level. Series Rated or Integrated Equipment Rated: The electrical standards permit the use of downstream equipment (such as moulded case circuit breaker panelboards) with protective devices having lower interrupting ratings than the available system fault level when protected by an upstream fully rated device. This series application of upstream and downstream devices must comply with CSA standards which require that any installation supplied in this fashion makes use of devices which have been tested as a series combination. For more information on the use of series rated combinations in electrical assemblies, please refer to Eatons Integrated Equipment Ratings Application handbook, Publication number 20-1773, latest revision.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
1-14
Panelboards
September 2009
Panelboards
1-15
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
September 2009
1-16 2-1
Product Description
Product Selection
Table 2-1. 1-6. Base Congurations PRL1a
Ampere Rating Interrupting Rating (kA Sym.) 240V AC 10 18 22 65 65 100 100 65 100 65 65 100 200 Breaker Type
240V AC maximum. 3-phase 4-wire, 3-phase 3-wire, 1-phase 3-wire, 1-phase 2-wire. 600 ampere maximum main lugs. 400 ampere maximum main breaker. 100 ampere maximum branch breakers (2 Pole 125A). Bolt-on branch breakers. Tin plated aluminum bus or silver plated copper bus. Factory assembled.
Main Breaker
Type PRL1a
Application Description
Fully rated or series rated. Interrupting ratings up to 200 kA symmetrical. Suitable for use as Service Entrance Equipment, when specied on the order.
Ampere Rating
Breaker Type
12
DNBA (twin) BAB BAB BAB BAB (2 Pole) QBGF QBGFEP QBCAF BAB-D BAB-C BABRSP QBHW QBHW QBHW QBHW (2 Pole) QBHGF QBHGFEP
1-pole breakers are rated 120V AC maximum. 240 volt breakers must be used on 3-phase, 3-wire, 240 volt delta systems or on the high leg of a midpoint delta grounded system. 50 ampere devices are available as 2-pole only. GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. Combination Arc fault circuit breaker. HID (High Intensity Discharge) rated breaker. Switching Neutral Breaker. 1-pole device requires 2-pole space, 2-pole device requires 3-pole space. Solenoid operated breaker.
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-17 2-2
September 2009
Product Selection
Table 2-3. 1-8. Standard Catalogue Numbering
Ampere Rating Main Lug Only 100 225 400 600 Main Breaker 15 100 BAB 21 27 18 100 EHD 24 30 24 30 225 ED 42 60 72 24 30 400 DK 42 60 72 P1aB4A1-15BAB P1aB4A1-21BAB P1aB4A1-27BAB P1aB4A1-18EHD P1aB4A1-24EHD P1aB4A1-30EHD P1aB4A2-24ED P1aB4A2-30ED P1aB4A2-42ED P1aB4A2-60ED P1aB4A2-72ED P1aB4A4-24DK P1aB4A4-30DK P1aB4A4-42DK P1aB4A4-60DK P1aB4A4-72DK P1aB1A1-15BAB P1aB1A1-21BAB P1aB1A1-27BAB P1aB1A1-18EHD P1aB1A1-24EHD P1aB1A1-30EHD P1aB1A2-24ED P1aB1A2-30ED P1aB1A2-42ED P1aB1A2-60ED P1aB1A2-72ED P1aB1A4-24DK P1aB1A4-30DK P1aB1A4-42DK P1aB1A4-60DK P1aB1A4-72DK P1aB4C1-15BAB P1aB4C1-21BAB P1aB4C1-27BAB P1aB4C1-18EHD P1aB4C1-24EHD P1aB4C1-30EHD P1aB4C2-24ED P1aB4C2-30ED P1aB4C2-42ED P1aB4C2-60ED P1aB4C2-72ED P1aB4C4-24DK P1aB4C4-30DK P1aB4C4-42DK P1aB4C4-60DK P1aB4C4-72DK P1aB1C1-15BAB P1aB1C1-21BAB P1aB1C1-27BAB P1aB1C1-18EHD P1aB1C1-24EHD P1aB1C1-30EHD P1aB1C2-24ED P1aB1C2-30ED P1aB1C2-42ED P1aB1C2-60ED P1aB1C2-72ED P1aB1C4-24DK P1aB1C4-30DK P1aB1C4-42DK P1aB1C4-60DK P1aB1C4-72DK 18 24 30 42 18 24 30 42 60 72 84 24 30 42 60 72 84 24 30 42 60 72 84 P1aL4A1-18 P1aL4A1-24 P1aL4A1-30 P1aL4A1-42 P1aL4A2-18 P1aL4A2-24 P1aL4A2-30 P1aL4A2-42 P1aL4A2-60 P1aL4A2-72 P1aL4A2-84 P1aL4A4-24 P1aL4A4-30 P1aL4A4-42 P1aL4A4-60 P1aL4A4-72 P1aL4A4-84 P1aL1A1-18 P1aL1A1-24 P1aL1A1-30 P1aL1A1-42 P1aL1A2-18 P1aL1A2-24 P1aL1A2-30 P1aL1A2-42 P1aL1A2-60 P1aL1A2-72 P1aL1A2-84 P1aL1A4-24 P1aL1A4-30 P1aL1A4-42 P1aL1A4-60 P1aL1A4-72 P1aL1A4-84 P1aL4C1-18 P1aL4C1-24 P1aL4C1-30 P1aL4C1-42 P1aL4C2-18 P1aL4C2-24 P1aL4C2-30 P1aL4C2-42 P1aL4C2-60 P1aL4C2-72 P1aL4C2-84 P1aL4C4-24 P1aL4C4-30 P1aL4C4-42 P1aL4C4-60 P1aL4C4-72 P1aL4C4-84 P1aL4C6-24 P1aL4C6-30 P1aL4C6-42 P1aL4C6-60 P1aL4C6-72 P1aL4C6-84 P1aL1C1-24 P1aL1C1-30 P1aL1C1-42 P1aL1C1-18 P1aL1C2-18 P1aL1C2-24 P1aL1C2-30 P1aL1C2-42 P1aL1C2-60 P1aL1C2-72 P1aL1C2-84 P1aL1C4-24 P1aL1C4-30 P1aL1C4-42 P1aL1C4-60 P1aL1C4-72 P1aL1C4-84 P1aL1C6-24 P1aL1C6-30 P1aL1C6-42 P1aL1C6-60 P1aL1C6-72 P1aL1C6-84 Main Device Type Number of Branch Circuits 3Ph, 4W Aluminum Catalogue Number 1Ph, 3W Aluminum 3Ph, 4W Copper 1Ph, 3W Copper
1 2
All possible combinations not shown for alternate main breakers, substitue breaker type sufx from Table 2-1. Add breaker trip rating to end of catalogue number.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
1-18
2-3
Instructions
1. Using description of the required panelboard, select the rating and type of main required. 2. Count the total number of branch circuit poles, including provisions, required in the panelboard. Do not count main breaker poles. Convert 2- or 3-pole branch breaker to single-poles, i.e., 3-pole breaker, count as 3 poles. Determine sub-feed breaker or through-feed lug requirements. 3. Select the main ampere rating section from Table 2-4. 4. Select panelboard type from rst column. 5. From Step #2, determine the number of branch circuits in Column 2.
100
18 24 30 42 18 24 30 42 60 72 84 24 30 42 60 72 84 18 24 30 42 18 24 30 42 60 72 24 30 42 60 72 18 24 30 42 18 24 30 42 60 72 84 24 30 42 60 72
30 30 30 36 30 36 36 42 54 60 72 42 48 54 60 72 72 30 30 30 36 30 36 36 42 60 60 48 54 60 72 72 30 30 30 36 30 36 36 42 54 60 72 48 54 54 60 72
20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75 5.75
225
400 /600
100
6. Read box size, box and trim catalogue numbers across columns to the right. Specify surface or ush mounting on the order.
225
Cabinets
Fronts are code-gauge steel, ASA-61 light gray painted nish. Boxes are code-gauge galvanized steel without knockouts. Standard depth is 5-3/4 inches (146.1 mm). Standard width is 20 inches (508.0 mm). An optional 28inch (711.2 mm) wide box is available.
400/600
100
225
400/600
per phase #500kcmil. Through-Feed lugs are recommended for 400A applications.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
2-4
1-19
PRL1a
Instructions
1. Using description of the required panelboard, select the rating and type of main required. 2. Count the total number of branch circuit poles, including provisions, required in the panelboard. Do not count main breaker poles. Convert 2- or 3-pole branch breaker to single-poles, i.e., 3-pole breaker, count as 3 poles. Determine sub-feed breaker or through-feed lug requirements. 3. Select the main ampere rating section from Table 2-5. 4. Select panelboard type from rst column, main breaker frame from second column. 5. From Step #2, determine the number of branch circuits in Column 3. 6. Read box size, box and trim catalogue numbers across columns to the right. Specify surface or ush mounting on the order.
EHD, ED, EDH, 18, 24 FD 30 (Vertical) 42 60 72, 84 DK, KD, HKD, KDC (Vertical) 24 30 42 60, 72 15, 21, 27
400
MAIN BREAKER WITH THROUGH-FEED LUGS 100 100/225 BAB, QBHW (Horizontal)
EHD, HFD, FD 18 (Vertical) 24, 30 42 60 72 DK, KD, HKD, KDC (Vertical) BAB, QBHW (Horizontal) 24 30 42 15, 21, 27
400
EHD, ED, EDH, 18 FD 24 (Vertical) 30 42 60 72 DK, KD, HKD, KDC (Vertical) 24 30, 42 60 72
Cabinets
Fronts are code-gauge steel, ASA-61 light gray painted nish. Boxes are code-gauge galvanized steel without knockouts. Standard depth is 53/4 inches (146.1 mm). Standard width is 20 inches (508.0 mm). An optional 28inch (711.2 mm) wide box is available.
400
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-20
Panelboards
2-5
Product Description
Product Selection
Table 2-7. 1-13. Base Conguration PRL2a
Ampere Rating Interrupting Rating (kA Symmetrical) 240V AC 480Y/277V AC 14 14 14 35 14 65 100 14 35 65 100 35 65 100 35 65 100 600Y/347V AC 10 18 14 25 35 14 18 25 35 18 25 35 25 35 65 125/250V DC 14 14 10 10 10 22 22 10 10 22 22 10 22 22 10 22 22 GHB GBH EHD FD FDB HFD FDC ED FDB FD HFD FDC JD HJD JDC KD HKD KDC Breaker Type
600Y/347 V AC. 480Y/277V AC . 125V AC 3-phase 4-wire 1-phase 3-wire, 1-phase 2-wire. 3-phase 3-wire. 600 ampere maximum main lugs. 400 ampere maximum main breaker. 100 ampere maximum branch breakers. Bolt-on branch breakers. Tin plated aluminum bus or silver plated copper bus. Factory assembled.
Main Breaker
100 100 100 100 100 100 100 225 225 225 225 225 250 250 250 400 400 400
1
Type PRL2a
Breaker Type 600Y/347V AC 125/250V DC 10 10 14 14 14 14 GHB GBH GHB GBH GHQRSP GHBGFEP GHBHID
Application Description
Fully rated or series rated. Interrupting ratings up to 200 kA symmetrical. Suitable for use as Service Entrance Equipment, when specied on the order.
480Y/277V AC 14 14 14 14 14 14 14
65 65 65 65 65
Interrupting ratings in this column are applicable to 120V AC for 1-pole breakers. At 480V, must be used on 480Y/277V grounded wye systems only. Solenoid operated breaker. GFP for 30 mA equipment protection. Requires 2-pole spaces. 277V AC only. HID (High Intensity Discharge) rated breaker. 240V AC maximum rating for these systems. At 600V, must be used on 600Y/347V grounded wye systems only.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
2-6
1-21
PRL2a
Product Selection
Table 2-9. 1-15. Standard Catalogue Numbering
Ampere Rating Main Lug Only 18 100 24 30 42 24 30 42 225 60 72 24 30 400 42 60 72 24 30 600 42 60 72 Main Breaker 15 100 GBH 21 27 18 100 FDB 24 30 24 30 225 FDB 42 60 72 24 30 400 KD 42 60 72 P2aB4A1-15GBH P2aB4A1-21GBH P2aB4A1-27GBH P2aB4A1-18FDB P2aB4A1-24FDB P2aB4A1-30FDB P2aB4A2-24FDB P2aB4A2-30FDB P2aB4A2-42FDB P2aB4A2-60FDB P2aB4A2-72FDB P2aB4A4-24KD P2aB4A4-30KD P2aB4A4-42KD P2aB4A4-60KD P2aB4A4-72KD P2aB4C1-15GBH P2aB4C1-21GBH P2aB4C1-27GBH P2aB4C1-18FDB P2aB4C1-24FDB P2aB4C1-30FDB P2aB4C2-24FDB P2aB4C2-30FDB P2aB4C2-42FDB P2aB4C2-60FDB P2aB4C2-72FDB P2aB4C4-24KD P2aB4C4-30KD P2aB4C4-42KD P2aB4C4-60KD P2aB4C4-72KD P2aL4A1-18 P2aL4A1-24 P2aL4A1-30 P2aL4A1-42 P2aL4A2-24 P2aL4A2-30 P2aL4A2-42 P2aL4A2-60 P1aL4A2-72 P2aL4A4-24 P2aL4A4-30 P2aL4A4-42 P2aL4A4-60 P2aL4A4-72 P2aL4C1-18 P2aL4C1-24 P2aL4C1-30 P2aL4C1-42 P2aL4C2-24 P2aL4C2-30 P2aL4C2-42 P2aL4C2-60 P2aL4C2-72 P2aL4C4-24 P2aL4C4-30 P2aL4C4-42 P2aL4C4-60 P2aL4C4-72 P2aL4C6-24 P2aL4C6-30 P2aL4C6-42 P2aL4C6-60 P2aL4C6-72 Main Device Type Number of Branch Circuits 3Ph, 4W Aluminum Catalogue Number 1Ph, 3W Aluminum 3Ph, 4W Copper 1Ph, 3W Copper
A A - Aluminum C - Copper
42 Number of Circuits
All possible combinations not shown. For alternate main breakers, substitue breaker type sufx from Table 2-7 . Add breaker trip rating to end of catalogue number.
CAT.38.02.S.K CAT.38.03.S.K
For more visit us at: www.eatoncanada.ca For moreinformation information visit: www.eatoncanada.ca
1-22
2-7
September 2009
Trim Catalogue Number EZT2030 S or F EZT2036 S or F EZT2030 S or F EZT2036 S or F EZT2042 S or F EZT2054 S or F EZT2060 S or F EZT2072 S or F EZT2042 S or F EZT2048 S or F EZT2054 S or F EZT2060 S or F EZT2072 S or F EZT2030 S or F EZT2036 S or F EZT2036 S or F EZT2042 S or F EZT2048 S or F EZT2060 S or F EZT2072 S or F EZT2048 S or F EZT2054 S or F EZT2060 S or F EZT2072 S or F
Instructions
1. Select the rating and types of mains required from Tables. 2. Count the total number of branch circuit poles (including spaces) required in the panelboard. Do not count main breaker poles. Convert 2 or 3 pole branch breakers to single poles, i.e., 3-pole breaker, count as 3 poles. (140 amps per connector maximum). 3. Using the correct table, type of mains and ampere rating per step 1 above, nd total on the table, use the next higher number. 4. Read box size, box and trim catalogue numbers across column to the right. On trim catalogue numbers, specify surface or ush mounting on the order.
Main Lugs with Through-Feed Lugs 100 Amp Main Lugs 225 Amp Main Lugs
Cabinets
Fronts are code-gauge steel, ASA-61 light gray painted nish. Boxes are code-gauge galvanized steel without knockouts. Standard depth is 5-3/4 inches (146.1 mm). Standard width is 20 inches (508.0 mm).
2
Box Dimensions Inches H 30 36 42 48 60 72 48 54 60 72 30 36 42 48 60 72 60 72 72 W 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 D 5-3/4 5-3/4 5-3/4 5-3/4 5-3/4 5-3/4 5-3/4 5-3/4 5-3/4 5-3/4 5-3/4 5-3/4 5-3/4 5-3/4 5-3/4 5-3/4 5-3/4 5-3/4 5-3/4 Box Catalogue Number Trim Catalogue Number
Number of Branch Circuit Poles 15, 21, 27 18, 24 30 42 60 72, 84 24 30 42 60, 72 15, 21, 27 18, 24 30 42 60 72 24 30 42
100 100/225
GBH, GHB (horizontal) FDB, FD, HFD, FDC EHD (vertical) KD HKD KDC (vertical) GBH, GHB (horizontal) FDB, FD, HFD, FDC EHD (vertical) KD HKD, KDC (vertical)
EZB2030RC EZT2030 S or F EZB2036RC EZB2042RC EZB2048RC EZB2060RC EZB2072RC EZB2048RC EZB2054RC EZB2060RC EZB2072RC EZT2036 S or F EZT2042 S or F EZT2048 S or F EZT2060 S or F EZT2072 S or F EZT2048 S or F EZT2054 S or F EZT2060 S or F EZT2072 S or F
400
Main Breaker with Through-Feed Lugs EZB2030RC EZT2030 S or F EZB2036RC EZB2042RC EZB2048RC EZB2060RC EZB2072RC EZT2036 S or F EZT2042 S or F EZT2048 S or F EZT2060 S or F EZT2072 S or F
400
In Sub-Feed conguration, maximum incoming and outgoing cables are 1 per phase #500kcmil. Through-Feed lugs are recommended for 400A applications.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
2-8
September 2009
1-23
Product Description
Product Selection
Table 2-13. 1-19. Base Congurations PRL3a
Ampere Rating 100 250 400 600 100 100 100 100 100 100 100 225 225 225 225 225 225 250 250 250 400 400 400 400 600 600 Interrupting Rating (kA Symmetrical) 240V AC 18 18 65 100 65 100 200 65 100 200 65 100 200 65 100 200 65 65 100 200 65 100 480V AC 14 14 35 65 100 35 65 100 35 65 100 35 65 100 35 65 600V AC 14 18 25 35 18 25 35 18 25 35 25 35 65 18 35 250V DC 10 10 10 22 22 10 22 22 10 22 22 10 10 22 22 22 42 Breaker Type EHD FDB ED EDH FD HFD FDC ED EDH EDC FD HFD FDC JD HJD JDC DK KD HKD KDC LGE LGH
600V AC maximum (250V DC). 3-phase 4-wire, 3-phase 3-wire, 1-phase 3-wire, 1-phase 2-wire. 600 ampere maximum main lugs. 600 ampere maximum main breaker. 225 ampere maximum branch breakers. Bolt-on branch breakers. Factory assembled.
Main Breaker
Type PRL3a
Application Description
Lighting and appliance branch panelboard or power distribution panelboard. Fully rated or series rated. Interrupting ratings up to 200 kA symmetrical. Suitable for use as Service Entrance Equipment, when specied on the order.
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-24
Panelboards
2-9
September 2009
480V AC
14 14 14 14 14 14 14 14 14 14 14 14 14 35 35 25 65 65 65 100 100 100 35 35 35 35 35 35 65 65 65 65 65 65
600V AC
10 10 14 14 14 14 18 18 18 18 25 25 25 35 35 35 18 18 18 18 18 18 25 25 25 25 25 25
250V DC
14 14 14 14 14 10 10 10 10 10 10 10 10 22 22 22 22 22 22
Breaker Type
DNBA (Twin) BAB BAB-H BAB BAB-H BAB BAB-H QBGF QBGFEP GFCBB QBCAF BAB-D BAB-C BABRSP QBHW QBHW-H QBHW QBHW-H QBHW QBHW-H QBHGF QBHGFEP GHQ GHB GBH GHB GBH GHQRSP GHBGFEP GHBHID EHD EHD FDB FDB FDB FDB FD FD FD FD HFD HFD HFD FDC FDC FDC ED EDH EDC FDE322533 FDE322532 FDE316033 FDE316032 FDE308033 FDE308032 HFDE322533 HFDE322532 HFDE316033 HFDE316032 HFDE308033 HFDE308032 LS LSI LS LSI LS LSI LS LSI LS LSI LS LSI
15 60 70 100 15 60 15 150 70 100 110 150 15 60 15 150 70 100 110 225 15 60 70 100 110 225 15 60 70 100 110 225 100 225 100 225 100 225 100 225 100 225 60 150 60 150 15 80 15 80 100 225 100 225 60 150 60 150 15 80 15 80
1-pole breaker rated 120V AC. 2-pole breaker rated 120/240V AC. 50 ampere devices are available as 2-pole only. Combination Arc fault circuit breaker. HID (High Intensity Discharge) rated breaker. Switching Neutral Breaker. 1-pole device requires 2-pole space, 2-pole device requires 3-pole space. Solenoid operated breaker. 1-pole breaker rated 277V AC. For use on 480Y/277V systems only. AIC rating for 2- and 3-pole breakers only. Maximum of six breakers per panel, 175 225 amperes. 1-Pole breaker rated 347V AC. For use on 600Y/347V systems only 3-Pole only
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
2-10
1-25
PRL3a
48 60 72 48 60 72
1219.2 EZB2048RC EZT2048S or F 1524.0 EZB2060RC EZT2060S or F 1828.8 EZB2072RC EZT2072S or F 1219.2 EZB2048RC EZTV2048S or F 1524.0 EZB2060RC EZTV2060S or F 1828.8 EZB2072RC EZTV2072S or F
600 Amperes
ED, EDH, EDC, EHD, FDB, FD, HFD, FDC 150A Max. Per Branch Breaker (300A Max. Per Connector)
600 ampere panels are optionally available with 28-inch (610 mm) wide box. Consult factory for availability.
Cabinets
2X 2-Pole 3X 3-Pole 5X 8X 5X 8X Horizontal Mounting Vertical Mounting 2X 2-Pole 3X 3-Pole 7X ED, EDH, EDC FD, HFD, FDC
Layout Example
1. Description of Panel Type PRL3a 3phase, 4-wire, 120/208V AC ush mounting. Panel to have short circuit rating of 22,000 symmetrical amperes. Main breaker 400 amperes, 3-pole, bottom mounting. Branch circuits bolt-on as follows:
Fronts are code-gauge steel, ASA-61 light gray painted nish. Boxes are code-gauge galvanized steel without knockouts. Standard depth is 5-3/4 inches (146.1 mm). Standard widths are: 20-inch (508.0 mm) 100 600 amperes.
2- or 3-Pole
(175 - 225A) 250A-400A 600A 250A 400-600A EHD, FDB, FD, HFD, FDC ED, EDH, EDC
Standard Depth
5-3/4 inches (146.1 mm).
12 20 ampere 1-pole QBHW 1 200 ampere 3-pole ED 1 225 ampere 3-pole ED 2 125 ampere 3-pole ED 2. Layout Information from Figure 1-4: a. b. c. d. 400 ampere Neutral . . . . . = 5X 12-poles of QBHW . . . . . . = 5X Two 3-pole ED break ers . . . = 6X Two 3-Pole ED break ers . . . = 3X Main break ers 40 0 amperes e. 3-pole DK . . . . . . . . . . . . . .= 15X Total Height. . . . . . . . . . . . = 34X 3. From Table 2-15: a. 34X Height (use 40X box) b. Box Height . . . . . . . . . . 72 inches (1828.8 mm) c. Box Catalogue Number . . . . . . . . . EZB2072RC
Side Gutters
4 inches (101.6 mm) minimum.
FCL, FB-P
6X 8X
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-26
2-11
Type PRL4
Product Description
Application Description
Power distribution panelboard. Fully rated or series rated. Interrupting ratings up to 200 kA symmetrical. Suitable for use as Service Entrance Equipment, when specied on the order.
600V AC maximum (250V DC). 3-phase 4-wire, 3-phase 3-wire, 1-phase 3-wire, 1-phase 2-wire. PRL4B circuit breaker panelboard. PRL4F fusible switch panelboard. 1200 ampere maximum mains. 1200 ampere maximum branch devices. Bolt-on branch devices. Factory assembled.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
2-12
September 2009
1-27
Product Selection
Table 1-22. 2-16.
Ampere Rating
Main Breaker
250 250 250 250 400 400 400 400 400 400 400 400 600 600 600 600 600 600 600 600 600 800 800 800 800 800 800 800 800 800 800 800 1200 1200 1200 1200 1200 1200
100% rated breaker. Requires copper bus. Breaker only available in 3-pole frame. Requires 44-inch (1117 .6 mm) wide box.
Interrupting Rating (kA Symmetrical) 240V AC See Table 2-20 480V AC / 600V AC Device Type FDPB FDPW FDPW FDPW FDPW FDPB FDPW FDPW FDPW FDPW
Fuses not included. Specify required fuse clips on all switches. Class J Fuse provisions are applicable only to 600 volt units. When required, use price and dimensions of 600 volt units for all voltages 600 and below. No DC rating on 600, 800 and 1200 ampere switches .
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-28
Panelboards
2-13
September 2009
Interrupting Rating (kA Symmetrical) 240V AC 10 10 10 10 10 10 22 22 22 22 22 65 65 65 65 18 18 18 18 18 65 65 65 100 100 100 200 200 200 200 65 100 200 65 65 65 65 65 65 65 65 65 65 65 65 100 100 100 100 100 100 100 100 100 100 100 100 DigiView 480V AC 14 14 14 14 14 14 14 14 14 35 35 35 65 65 65 100 100 100 150 35 35 35 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 65 65 65 65 65 65 600V AC 10 10 14 14 14 18 18 18 25 25 25 35 35 35 18 18 18 18 18 18 18 18 18 18 18 18 25 25 25 25 25 25 25 25 25 25 25 25 250V DC 14 14 14 14 10 10 10 10 10 10 10 10 22 22 22 22 22 22
Breaker Type DNBA (Twin) BAB BAB-H BAB BAB-H QBGF QBHW QBHW-H QBHW QBHW-H QBHGF GHB GHB GBH GBH EHD EHD FDB FDB FDB FD FD FD HFD HFD HFD FDC FDC FDC FCL ED EDH EDC FDE322533 LS FDE322532 LSI FDE322535 LSG FDE322536 LSIG FDE316033 LS FDE316032 LSI FDE316035 LSG FDE316036 LSIG FDE308033 LS FDE308032 LSI FDE308035 LSG FDE308036 LSIG HFDE322533 LS HFDE322532 LSI HFDE322535 LSG HFDE322536 LSIG HFDE316033 HFDE316032 HFDE316035 HFDE316036 HFDE308033 HFDE308032 HFDE308035 HFDE308036
For use on 3ph, 3w or 3ph, 4w only. 50 ampere devices are available as 2-pole only. 1-pole breakers rated 120V AC. 2-pole breakers rated 120/240V AC. 1-pole breakers rated 277V AC. At 480V, must be used on 480Y/277V grounded wye systems only. AIC rating for 2- and 3-pole breakers only. 100% rated breaker. Requires copper bus. Not available in Type 12, 4 and 4X enclosures. Breaker only available in 3-pole frame. Available in single branch mounting only. 1-pole breakers rated at 347V AC. At 600V, must be used on 600Y/347V grounded wye systems only.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
2-14
PRL4 PRL4
September 2009
Panelboards
Panelboards
1-29
Device Type JD JD HJD HJD JDC JDC LCL DK KD CKD HKD CHKD KDC LCL LGE LGH LGU LD CLD HLD CHLD LDC CLDC MDL HMDL CMDL CHMDL ND HND NDC CND CHND CNDC ND HND NDC CND CHND CNDC FB-P LA-P LA-P NB-P NB-P
400 800 400 800 400 800 400 800 400 800 400 800 600 1200 600 1200 600 1200 600 1200 600 1200 600 1200 15 100 125 225 250 400 400 600 700 800
For use on 3ph, 3w or 3ph, 4w only. 50 ampere devices are available as 2-pole only. 1-pole breakers rated 120V AC. 2-pole breakers rated 120/240V AC. 1-pole breakers rated 277V AC. At 480V, must be used on 480Y/277V grounded wye systems only. AIC rating for 2- and 3-pole breakers only. 100% rated breaker. Requires copper bus. Not available in Type 12, 4 and 4X enclosures. Breaker only available in 3-pole frame. Available in single branch mounting only. 1-pole breakers rated at 347V AC. At 600V, must be used on 600Y/347V grounded wye systems only.
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-30
Panelboards
Pow-R-Line C Panelboards
2-15
September 2009
Table 1-26. Table 1-26. 1-26. FDPW and FDPB Switch Ratings, Table 2-20. 240 or 600V AC
Ampere Rating 30 100 200 Single 200 Twin 400, 600 800, 1200
Short Circuit Ratings (Sym. Amperes) 200,000 200,000 200,000 200,000 200,000
100% rated breaker. Requires 44-inch (1117 .6 mm) wide box. 100,000 AIC based on NEMA test procedure. Fuses not included. Specify required fuse clips on all switches. For T fuse clips, specify as an option (T fuse clips not available for When branches of a twin unit are of different ampere ratings, as a 30 60 twin unit and layout as a 60 60 twin unit; when a 60 100 twin unit layout as a 100 100 twin unit. No DC rating on 600, 800 and 1200 ampere switches. Twin 200 ampere switches are not available with Class R fuse clips at 600 volts. No DC rating on 600, 800 and 1200 ampere switches. Class J fuse provisions are applicable to 600 volt units. When required, use price and dimensions of 600 volt units for all voltages 600 volts and below. Twin 200 ampere switches are not available with Class R fuse clips at 600 volts. When shunt trip is required, 400 600 ampere switches used with Class R fuses are rated 100,000 AIC.
CAT.38.03.S.K
For more information visit: www.eatoncanada.ca For more information visit us at: www.eatoncanada.ca
CAT.38.02.S.K
2-16
September 2009
1-31
Standard Main Lug, Through-Feed and Sub-Feed Lugs (500 kcmil Maximum) MLO, SFL MLO, TFL 10X 250A, 400A, 600A, 800A N 10X N
16X
Main Breaker
*
7X
*
ThroughFeed Lugs
* *
3Ph 4W 3Ph 3W
MLO, TFL N
800A Vertically Mtd. MDL Main Breaker only in 24-inch (609.6 mm) wide box. Available with 38X and 50X Panel Height only.
2X
Blank
*
2X
Blank
*
7X
ThroughFeed Lugs
Blank
*
2X
Blank
3Ph 4W, 3Ph 3W Optional Main Lugs, Through-Feed and Sub-Feed Lugs (750 kcmil Maximum) MLO, SFL 20X 250A, 400A, 600A, 800A N 20X MLO, TFL N 400A, 600A, 800A 13X
3Ph 4W
3Ph 3W
13X
*
3X
Blank
*
9X 3Ph 4W
ThroughFeed Lugs
*
3X
Blank
*
9X 3Ph 3W
ThroughFeed Lugs
MLO, TFL N 15X 1200A 38-inch (965.2 mm) Minimum Width 5X 15X
*
5X
Blank
*
11X 3Ph 4W
ThroughFeed Lugs
*
Blank
*
11X 3Ph 3W
ThroughFeed Lugs
Sub-Feed lugs are available 250 600 amperes. For 600 ampere use 1200 ampere space. 750kcmil lugs available on some Main Breaker arrangements. Consult Eaton.
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-32
2-17
September 2009
1 PRL4B panelboard, 600Y/347V, 3-phase 4-wire 25 kA, 800 amperes, main lug, consisting of: 12 20A/1P HFD 2 250A/3P HJD 1 400A/3P KD
20A/1P 20A/1P 1X 20A/1P 20A/1P 1X 20A/1P 20A/1P 1X 20A/1P 20A/1P 1X 20A/1P 20A/1P 1X 20A/1P 20A/1P 1X 250A/3P 250A/3P 400A/3P Main Lugs 800A 10X 3X 3X 4X
Box depth is 10.4 inches (264.2 mm), cover adds .9 inches (22.9 mm) to depth.
Note: 800 ampere maximum bus size in 24-inch (609.6 mm) wide box. Flush trims not available on PRL4B panels.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
2-18
September 2009
1-33
1X
Breaker To Fusible Transition, All Widths 18 Poles 42 Poles BAB 100 Amp QBHW GHB, GBH Max.
12X
1P 2P
1P 2P
24-Inch (609.6 mm) Wide Box
1X 2X
3P
3P
3X
EHD, 225 Amp FDB, FD, Max. HFD, FDC FDE, HFDE(3P)
2P
2P
2X
3P
3P
2 or 3P 2 or 3P Load
3X
250 Amp JD, HJD, JDC Max. 400 Amp Max. DK, KD, HKD, KDC, CKD, CHKD 600 Amp Max. LGE, LGH, LGU 600 Amp LD, HLD, CLD, CHLD, LDC Max.
3X
4X
2 or 3P
6X
2 or 3P 2 or 3P 2 or 3P 2 or 3P
2 or 3P 2 or 3P 2 or 3P
100 Amp FCL, FB-P Max. 250 Amp Max. JD, HJD, JDC
3X
4X
400 Amp DK, KD, HKD, KDC, Max. CKD, CHKD 400 Amp LCL, LA-P Max. 800 Amp MDL, HMDL, Max. CMDL, CHMDL 1200 Amp ND, HND, NDC Max. 400 Amp Max. 800 Amp Max. DK, KD, HKD, KDC NB-P
6X
2 or 3P
44-Inch (1117.6 mm) Wide Box
6X
2 or 3P
2 or 3P
4X
2 or 3P
6X
1-7. Layout for Branch and Horizontally Mounted Main Devices PRL4B Figure 2-4.
BAB and QBHW breakers with shunt trips require one additional pole space, i.e., 1-pole is 2-pole size, 2-pole is 3-pole size, and 3-pole is 4-pole size. If panel contains only BAB or QBHW branch breakers, use a PRL1a panelboard. GHB and GBH breakers cannot be mixed on same subchassis as BAB, QBHW. If panel contains only GHB and GBH branch breakers, use a PRL2a panelboard. When only one single-pole breaker of the group is required on either side of chassis, the single-pole breaker space required changes from 1X to 2X. Minimum 38-inch (965.2 mm) wide box is required if optional #6 300 kcmil lug is required.
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-34
2-19
September 2009
Standard Main Lug, Through-Feed and Sub-Feed Lugs (500 kcmil Maximum) MLO, SFL MLO, TFL 10X 250A, 400A, 600A, 800A N 10X N
21X
Main Switch
*
7X
*
ThroughFeed Lugs
* *
3Ph 4W 3Ph 3W 7X
*
N
400A and 600A Vertically Mounted Main Switch MLO 12X 1200A N 12X MLO, TFL N 1200A 26X 800A, 1200A 25X - 800A (750 kcmil max.) 21X - 800A (250 kcmil max.)
*
2X
Blank
*
7X
Through-Feed Lugs
*
7X N
800A & 1200A Vertically Mounted Main Switch 38-inch (965.2 mm) or 44-inch (1117.6 mm) Wide Box
3Ph 4W, 3Ph 3W Optional Main Lugs, Through-Feed and Sub-Feed Lugs (750 kcmil Maximum) MLO, SFL 20X 250A, 400A, 600A, 800A N 20X MLO, TFL N 400A, 600A, 800A 13X
3Ph 4W
13X
*
3X
Blank
*
9X 3Ph 4W
ThroughFeed Lugs
*
3X
Blank
*
9X 3Ph 3W
ThroughFeed Lugs
*
5X
Blank
*
11X 3Ph 4W
ThroughFeed Lugs
*
5X
Blank
*
11X 3Ph 3W
ThroughFeed Lugs
Sub-Feed lugs are available 250 600 amperes, for 600 ampere use 1200 ampere A space. 800 ampere and 1200 ampere mains available only in vertical mounting.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
2-20
September 2009
1-35
43X
mm Depth 11-5/16 11-5/16 11-5/16 11-5/16 Height 1866.9 2286.0 1866.9 2286.0 Width 965.2 965.2 1117 .6 1117 .6 Depth 287 .0 287 .0 287 .0 287 .0
Box depth is 10.4-inch (264.2 mm) cover adds .9-inch (22.8 mm) to depth.
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-36
2-21
September 2009
1X
4X
60A
4X
6X
100A
100A
5X
9X
11X
200A
200A
6X
2
44-inch (1117.6 mm) Wide Box
9X
400A Main or Branch 600A Main or Branch 800A Branch 1200A Branch
11X
11X
15X
Figure 1-10. 2-7. Branch and Horizontally Mounted Main Device Layout PRL4F
Note: See Page 2-19 for MLO or Neutral and Vertically Mounted Main space requirements.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
2-22
September 2009
1-37
Product Description
Product Selection
Table 2-23 1-28. PRL1a-LX Table
Ampere Rating Interrupting Rating (kA Sym.) 240V AC 10 18 22 65 65 100 100 65 100 Breaker Type
240V AC maximum. 3-phase 4-wire, 3-phase 3-wire, 1-phase 3-wire, 1-phase 2-wire. 225 ampere maximum mains. 100 ampere maximum branch breakers. Bolt-on branch breakers. Factory assembled.
Main Breaker
100 100 100 100 100 100 100 225 225
Breaker Interrupting Rating (kA Sym.) Type 240V AC 10 10 10 10 10 10 10 10 10 22 22 22 22 22 BAB BAB BAB QBGF QBGFEP QBAF QBAG BABR BABRS QBHW QBHW QBHW QBHGF QBHGFEP
Application Description
Lighting and appliance branch panelboard. Column mounting width. Fully rated or series rated. Interrupting ratings up to 200 kA symmetrical.
1-pole breakers are rated 120V AC maximum. 240 volt breakers must be used on 3-phase, 3wire, 240 volt delta systems or on the high leg of a midpoint delta grounded system. 50 ampere devices are available as 2-pole only.
GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. Arc fault circuit breaker. Arc fault circuit breaker with GFCI. Solenoid operated breaker.
Table 2-25. 1-30. Pull Box With Extension Trough Includes pull box with trough extension. For additional trough extensions.
Description Pullbox with 36" Trough Pullbox with 48" Trough Pullbox with 60" Trough Pullbox with 72" Trough Pullbox with 84" Trough Catalogue Number XCTXB036 XCTXB048 XCTXB060 XCTXB072 XCTXB084
1-31. Additional Trough Extensions Table 2-26. Width and depth are the same as the panelboard.
Length Inches 36 48 60 72 84 mm 914.4 1219.2 1524.0 1828.8 2133.6 Catalogue Number CTXB036 CTXB048 CTXB060 CTXB072 CTXB084
Neutral Bars
When Column Type panels are furnished with trough e xtensions and pull bo x, the neutral bar will be placed in the pull bo x unless other wise speci ed. When troughs and pull bo x are not furnished, the neutral bar will be located on the panel at the same end as the main.
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-38
2-23
September 2009
16 (406.4) 12 (304.8)
Instructions
1. Using description of the required panelboard, select the rating and type of main required. a. 100 ampere panelboards Table 2-28. b. 225 ampere panelboards Table 2-29. 2. Count the total number of branch circuit poles, including provisions, required in the panelboard. Do not count main breaker poles. Convert 2or 3-pole branch breaker to single poles, i.e., 3-pole breaker, count as 3 poles. Determine sub-feed breaker or through-feed lug requirements. 3. Select the panelboard main ampere rating from Tables 2-28 or 2-29.
Pull Box Pull box is furnished without knockouts. Standard dimensions Table 2-27. Pull Box Dimensions
Height Inches mm 12 Width Inches mm Depth Inches mm 152.4 6 (152.4)
304.8 16
406.4 6
4. Panelboard Type from rst column, main breaker Frame and Designation, if applicable from second column, and sub-feed breaker Frame and Designation, if applicable, from the third column. 5. From Step #2, determine the number of branch circuits in Column 4. 6. Read box size, box and trim catalogue numbers across columns to the right. All panels are surface mounted.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
2-24
September 2009
1-39
8-5/8 (219.2) 8-5/8 (219.2) 8-5/8 (219.2) 8-5/8 (219.2) 8-5/8 (219.2) 8-5/8 (219.2)
Main Lugs or Main Breaker with 100A Through-Feed Lugs or Sub-Feed Breaker
Add sufx B to trim catalogue number for bottom fed panelboards (i.e., LTC969SB).
Table 2-29. 1-33. 225 Ampere Maximum PRL1a-LX Column Type Panelboard Sizing Table
Panelboard Types Main Breaker Types Vertical Mounting Sub-Feed Breaker Types Maximum Number of Branch Circuits Including Provisions 30 42 30 42 Box Dimensions Inches Height Width Depth Box Trim Catalogue Catalogue Number Number
Main Lugs or Main Breaker Main Lugs or Main Breaker with 225A Through-Feed Lugs or Sub-Feed Breaker
Add sufx B to trim catalogue number for bottom fed panelboards (i.e., LTC969SB).
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-40
2-25
September 2009
Product Description
Product Selection
Table 2-30. 1-34. Base Prices PRL2a-LX
Ampere Rating 100 225 Interrupting Rating (kA Symmetrical) 240V AC 65 18 65 100 200 65 18 65 100 200 Breaker 600Y/347V AC 125/250V DC Type 14 10 10 22 22 10 10 22 22 GBH FDB FD HFD FDC ED FDB FD HFD FDC
600Y/347V AC maximum (125V DC). 3-phase 4-wire, 3-phase 3-wire, 1-phase 3-wire, 1-phase 2-wire. 225 ampere maximum mains. 100 ampere maximum branch breakers. Bolt-on branch breakers. Factory assembled.
Main Breaker
100 100 100 100 100 225 225 225 225 225
Breaker 480Y/277V AC 600Y/347V AC 125/250V DC Type 14 14 14 14 14 14 14 10 10 14 14 14 GHQ GHB GHB GHBS GBH GBH GHBGFEP
Application Description
Lighting and appliance branch panelboard. Column mounting width. Fully rated or series rated. Interrupting ratings up to 200 kA symmetrical.
Table 2-32. 1-36. Pull Box With Extension Trough Includes pull bo x with trough e xtension. For additional trough extensions, refer to Table 2-33 .
Description Pullbox with 36" Trough Pullbox with 48" Trough Pullbox with 60" Trough Pullbox with 72" Trough Pullbox with 84" Trough Catalogue Number XCTXB036 XCTXB048 XCTXB060 XCTXB072 XCTXB084
Interrupting ratings in this column are applicable to 120V AC for 1-pole breakers. At 480V, must be used on 480Y/277V grounded wye systems only. Solenoid operated breaker. GFP for 30 mA equipment protection. Requires two pole spaces. At 600V, must be used on 600Y/347V grounded wye systems only.
Table 2-33. 1-37. Additional Trough Extensions Table Width and depth are the same as the panelboard.
Length Inches 36 48 60 72 84 mm 914.4 1219.2 1524.0 1828.8 2133.6 Catalogue Number CTXB036 CTXB048 CTXB060 CTXB072 CTXB084
Neutral Bars
When Column Type panels are furnished with trough e xtensions and pull bo x, the neutral bar will be placed in the pull bo x unless other wise speci ed. When troughs and pull bo x are not furnished, the neutral bar will be located on the panel at the same end as the main.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
2-26
1-41
Type PRL2a-LX
6 (152.4)
16 (406.4) 12 (304.8)
Instructions
1. Using description of the required panelboard, select the rating and type of main required. a. 100 ampere panelboards Table 2-35. b. 225 ampere panelboards Table 2-36. 2. Count the total number of branch circuit poles, including provisions, required in the panelboard. Do not count main breaker poles. Convert 2or 3-pole branch breaker to single poles, i.e., 3-pole breaker, count as 3 poles. Determine sub-feed breaker or through-feed lug requirements. 3. Select the panelboard main ampere rating from Tables 2-35 or 2-36. 4. Panelboard Type from rst column, main breaker Frame and Designation, if applicable from second column, and sub-feed breaker Frame and Designation, if applicable, from the third column. 5. From Step #2, determine the number of branch circuits in Column 4. 6. Read box size, box and trim catalogue numbers across columns to the right. All panels are surface mounted.
Pull Box
Pull box is furnished without knoc kouts. Standard dimensions: Table 2-34. 1-38. Pull Box Dimensions Table
Height Inches mm 12 Width Inches mm Depth Inches mm 152.4 6 (152.4)
304.8 16
406.4 6
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-42
2-27
8-5/8 (219.2) 8-5/8 (219.2) 8-5/8 (219.2) 8-5/8 (219.2) 8-5/8 (219.2) 8-5/8 (219.2)
Main Lugs or Main Breaker with 100A Through-Feed Lugs or Sub-Feed Breaker
Add sufx B to trim catalogue number for bottom fed panelboards (i.e., LTC969SB).
Table 2-36. 1-40. 225 Ampere Maximum PRL2a-LX Column Type Panelboard Sizing Table
Panelboard Types Main Breaker Types Vertical Mounting Sub-Feed Breaker Types Maximum Number of Branch Circuits Including Provisions 30 42 30 42 Box Dimensions Inches Height Width Depth Box Trim Catalogue Catalogue Number Number
Main Lugs or Main Breaker Main Lugs or Main Breaker with 225A Through-Feed Lugs or Sub-Feed Breaker
Add sufx B to trim catalogue number for bottom fed panelboards (i.e., LTC969SB).
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
2-28
1-43
48 60 72 Height Inches
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-44
Panelboards
2-29
September 2009
PRL2a
PRL3a
PRL4B
PRL4F
2a.
No No No
2b 2c. Yes Yes Yes Yes Yes Yes Yes No Yes No No No Yes Yes Yes No Yes No No No Yes
No No No
Yes No No Yes Yes Yes Yes No Yes No No No Yes Yes Yes No Yes No No No Yes
Yes No No
Yes No No Yes Yes Yes Yes Yes Yes Yes No No Yes Yes No Yes Yes Yes No No Yes
Yes No No
Yes No No Yes Yes No No Yes Yes Yes Yes No Yes No No Yes Yes Yes Yes Yes Yes
Yes No No
Yes No No Yes Yes No No Yes Yes Yes Yes No Yes No No Yes Yes Yes Yes Yes Yes
3a. 3b.
4a.
4b.
5a.
6a.
7a. 7b. 7c. 8a. 8b. 9a. 9b. 10a. 10b. 11a.
Yes Yes Yes Yes Yes Std. Std. Std. Yes Yes
Yes Yes Yes Yes Yes Std. Std. Std. Yes Yes
Yes Yes Yes Yes Yes Std. Std. Std. Yes Yes
No No No Yes Yes No No No No No
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
2-30
September 2009
Panelboards
1-45
PRL2a
PRL3a
PRL4B
PRL4F
Column Type Yes No No No No No No No No No No No No No No No No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
12a.
Yes Yes No Yes No No No Yes No Yes No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Yes Yes No Yes No No No Yes No Yes No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Yes No Yes Yes Yes Yes Yes No Yes Yes Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Yes No Yes Yes Yes Yes Yes No Yes Yes Yes Yes Yes Yes No No No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Yes No Yes Yes Yes Yes Yes No Yes Yes Yes Yes Yes Yes No No No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
13a.
13b.
14a. 15a. 15b. 15c. 16a. 16b. 17a. 18a. 19a. 19b. 20a. 20b. 20a. 20b. 20c. 20d.
Tin Plating of Copper Bus Nameplates and Circuit Directories Engraved Lamicoid Nameplates - supplied loose or factory installed. Circuit Directory Holder (Steel frame & acetate cover) Circuit Breaker Handle Lock-off Devices Non-Padlockable (supplied loose) Padlockable (supplied loose) Main or Branch Circuit Breaker Accessories Auxiliary Switch (1A / 1B) Shunt Trip Undervoltage Release Alarm Switch (1A / 1B)
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-46
Panelboards
2-31
September 2009
FB TRIPAC BREAKER 3 POLE 100A max. JD SINGLE - 250A max. - (3X) JD TWIN - 250A max. - (3X) KDL / KD SINGLE - 400A max. - (4X) KDL / KD TWIN - 400A max. - (4X)
CKD SINGLE - 400A max. - (4X) 100% RATED LCL BREAKER 3 POLE 400A max. LA TRIPAC BREAKER 3 POLE 400A max. LA/HLA/LC/HLC/LD/HLD/LDC/CLD BREAKER 3 POLE 600A max. MA/HMA/MC/HMC BREAKER 3 POLE 800A max. MDL/HMDL BREAKER 3 POLE 800A max. NB TRIPAC BREAKER 3 POLE 800A max. NB/HNB/ND/HND/NDC BREAKER 3 POLE 1200A max. CND BREAKER 3 POLE 1200A max.
Note - Connectors for all branch devices are included with PRl-1a, 2a and Column Type panelboards
CAT.38.02.S.K
CAT.38.03.S.K
2-32
Panelboards Modications
September 2009
processor-based equipment downtime and damage are voltage transients and electrical noise. Electrical loads and microprocessorbased equipment are highly susceptible to both high and low energy transients. High energy transients include lightning Typessurges PRL1a,and 2a, 3a, 4, Column induced power company switching. These high energy transients can destroy components instantly. More frequently the electrical system 1-47. Integrated Clipper Power System, Table 2-44. experiences low energy transients and and Visor Series high frequency noise.
Description
PRL2a - 277Y/480V AC Maximum PRL2a - 347Y/600V AC Maximum PRL3a - 600V AC Maximum PRL4B - 600V AC Maximum PRL4F - 600V AC Maximum
Column - 240V AC or 347Y/600V AC Max.
Panelboards Modications
Monitor Package Options AdVisor Status indicating lights Form C contacts Audible Alarm - enable/disable
OPT
OPT
OPT
The effects of continual low energy tranAdVisor 160kAfeatures 200kA plus: 250kA 300kA 400kA 500kA sients and high frequency noise can100kA 120kATransient Counter, Push-to-Test Button STD cause erratic equipment performance or Availability Power Quality Meter (no date stamp) sudden failure of electronic circuit board Pa - 240V AC Maximum Yes Yes Yes Yes No No No No components.
PRL2a - 277Y/480V AC Maximum
STD
STD
Eaton can provide protective and diagPRL2a - 347Y/600V Maximum No nostic systems AC integral to panelboards. The SPD (Surge Protective Device) is PRL3a - 600V AC Maximum Yes integrated into the panelboards using a PRL4B - 600V AC Maximum Yes zero lead length direct bus bar connecPRL4F Yes tion. - 600V AC Maximum Suppression (TVSS) and Monitor Package Options
Yes
No No
No OPT No
AC Maximum Yes PRL2a Yes - 277Y/480V Yes Yes Yes Yes PRL2a 347Y/600V AC Maximum Yes Yes Yes Yes Yes Yes Yes PRL3a Yes - 600V YesAC Maximum Yes Yes Yes PRL4B No - 600V No AC Maximum No No PRL4F - 600V AC Maximum No
Column - 240V AC or 347Y/600V AC Max. No No The SPD provides Transient Voltage Surge
active hybrid ltering. It also protects sensitive elecColumn - 240V AC or 347Y/600V AC Max. N/A AdVisor tronic equipment from the damaging Status indicating lights Integral Disconnect is cable connected. effects of high and low energy transients, Form C contacts OPT OPT OPT OPT OPT OPT OPT OPT as well as high frequency noise. Audible Alarm - enable/disable
SuperVisor STD STD STD STD STD STD STD STD
The effects of continual low energy tranAdVisor features plus: sients and high frequency noise can Transient Counter, Push-to-Test Button cause erratic equipment performance or Power Quality Meter (no date stamp) sudden failure electronic circuit board Table 2-44 SPD of Series Surge Protective Device components. SPD Series replaces CPS Visor Series - effective Aug.
2009 can provide protective and diagEaton nostic systems integral to panelboards. Description The SPD (Surge Protective Device) is integrated into the panelboards using a zero lead y length direct bus bar connecAvailabilit tion. PRL1a - 240V AC Maximum PRL2a - 277/480V AC Maximum The SPD provides Transient Voltage Surge PRL2a - 347/600V AC Maximum Suppression (TVSS) and active hybrid lPRL3a -It 600V Maximum tering. alsoAC protects sensitive elecPRL4Bequipment - 600V AC Maximum tronic from the damaging effects high and low energy transients, PRL4F -of 600V AC Maximum as well as high frequency noise. Column Panels
Integral Disconnect PRL1a - 240V AC Maximum
OPT
50kA 80kA PRL2a - 347Y/600V AC Maximum 100kA Yes Yes No AC Maximum No No PRL4F - 600V YesAC or 347Y/600V Yes Yes Column - 240V AC Max. Yes Yes Yes Integral Disconnect is cable connected. Yes Yes Yes No No No
PRL4B - 600V Yes AC Maximum Yes PRL3a - 600V AC Maximum
200kAN/A 300kA N/A N/A No STD No No STD No STD STD Yes N/A Yes N/A N/A Yes Yes Yes Yes No No
STD Yes STD
Yes
Yes
Yes
Yes
Yes
No
SPD Feature Package Basic - Dual Colored LED Per Phase to Indicate Protection Status OPT - Dual Colored LED to Indicate Protection Status of the NG Mode on Units with a Neutral Wire - Single Colored LED to Indicate the Lack of a Neutral Wire Connection on Systems Requiring a Neutral Wire Standard - All features included in the Basic package plus the following: - Audible Alarm with Silence Button STD - Form 'C' Relay Contact - EMI / RFI Filtering Providing 50dB of Noise Attenuation @ 100kHz CAT.38.02.S.K Standard + Surge Counter - All Features Included in the Standard Package Plus The Addition of a Surge Counter with Reset Button OPT Integral Disconnec t PRL1a - 240V AC Maximum OPT PRL2a - 277/480V AC Maximum OPT PRL2a - 347/600V AC Maximum OPT PRL3a - 600V AC Maximum STD PRL4B - 600V AC Maximum STD PRL4F - 600V AC Maximum STD
OPT
OPT
OPT
OPT
OPT
OPT
OPT
STD
STD
STD
STD
STD
STD
STD
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-48
Panelboards
Panelboards
September 2009
2-33
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
3-1
September 2009
Panelboards Pow-R-Line
Type PRL5P
Panelboards Pow-R-Line
Type PRL5P
1-49
Product Description
The PRL5P panelboard incorporates Eatons proven Cutler-Hammer plug-on power panelboard experience with modern manufacturing technology to provide the most exible plug-on design in the industry. Designed to eliminate the multitude of parts associated with other similar products, the PRL5P panelboard is the choice for applications where additions and changes must be fast and convenient.
Panelboard Installation
Plug-on Mains and Branches provide the exibility to move devices on factory assembled panels after the boards are received at the job site. The electrician may move branch devices and place them into a conguration that ts the particular wiring needs of that installation. Breakers are mounted to an adapter which includes the bus connection hardware. The breaker to bus bar connection is positive and secure. This proven connection has been utilized in plug-on power panelboards since 1984.
48-Inch (1219.2 mm) Wide. Provides for mains up to 1200 amperes. The 1200 ampere lug adapter unit accepts up to 750 kcmil conductors. Two 600 ampere breakers can be mounted across from one another. Another exclusive allows breakers of different sizes to be mounted across from one another, providing the ability to maximize space within the panel. There are no restrictions or predetermined spaces where branch devices must be placed.
1
400 Ampere K-Frame Breaker
An Oversized Area is Provided for Neutral Connections with Ample Lugs for Ease of Installation
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-50
Panelboards Pow-R-Line
Type PRL5P
Panelboards Pow-R-Line
Type PRL5P
3-2
September 2009
Product Description
Product Selection
Panelboard Selection and Layout
Select either single-row or double-row bus chassis. Single-row bus chassis maximum 800 ampere main breaker or main lug only. Select main device and X space from Table 3-1. Select branch devices and corresponding X space from Tables 3-2 through 3-5.
600V AC maximum (250V DC). 3-phase 4-wire, 3-phase 3-wire, 1-phase 3-wire. 1200 ampere maximum mains. 1200 ampere maximum branch devices. Plug-on branch devices. Factory assembled.
Type PRL5P
Refer to layout data on Tables 3-6 and 3-7 . Make a layout sketch of the main and branch devices utilizing either a singlerow or double-row bus chassis indicating the X space for each device. The maximum total X space cannot exceed 40X for any panelboard. Should more than 40X be required, add the appropriate through-feed lug adapter or breaker to feed an additional panelboard.
1
Application Description
Power distribution panelboard. Fully rated or series rated. Interrupting ratings up to 200 kA symmetrical.
Main Interrupting Rating (kA Symmetrical) Main Ampere 240V AC 480V AC 600V AC 250V DC Device Rating Type
Main X Space 8X 8X 8X 7X 7X 4X 4X 4X 4X 6X 6X 6X 6X 6X 6X 6X 6X 6X 6X
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
3-3
September 2009
Panelboards Pow-R-Line
Type PRL5P
Panelboards Pow-R-Line
Type PRL5P
1-51
Table 1-49. 3-2. Branch Devices Single-Pole Breakers in Single Adapter Units PRL5P Table
Ampere Rating 15 60 15 60 15 60 Interrupting Rating (kA Symmetrical) 120V AC 14 35 65 277V AC 14 35 65 347V AC 18 25 125V DC 10 10 10 Breaker Type EHD FD HFD 2 Each 1-Pole X Space 2X 2X 2X 3 Each 1-Pole X Space 3X 3X 3X
Note: Includes, as indicated, two or three single-pole 15 through 60 ampere breakers assembled on one adapter.
3-3. Branch Devices Two and Three-Pole Breakers in Single Adapter Units PRL5P Table 1-50.
Ampere Rating 100 225 100 225 100 225 15 60 70 100 15 60 70 100 110 225 15 60 70 100 110 225 15 60 70 100 110 225 70 225 250 70 225 250 70 225 250 100 400 250 400 250 400 250 400 300 600 300 600 300 600 400 800 400 800 400 800 400 800 400 800 600 1200 600 1200 600 1200
Interrupting Rating (kA Symmetrical) 240V AC 65 100 200 18 18 65 65 65 100 100 100 200 200 200 65 65 100 100 200 200 65 65 100 200 65 100 200 65 100 65 100 200 65 100 200 480V AC 14 14 35 35 35 65 65 65 100 100 100 35 35 65 65 100 100 35 65 100 35 65 100 50 65 50 65 100 50 65 100 600V AC 18 18 18 25 25 25 35 35 35 18 18 25 25 35 35 25 35 50 25 35 50 25 35 25 35 50 25 35 50 250V DC 10 10 10 10 10 22 22 22 22 22 22 10 10 22 22 22 22 10 22 22 22 25 25 22 25
Breaker Type ED EDH EDC EHD EHD FD FD FD HFD HFD HFD FDC FDC FDC JD JD HJD HJD JDC JDC DK KD HKD KDC LD HLD LDC MDL HMDL ND HND NDC ND HND NDC
X Space 8X 8X 8X 7X
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-52
Panelboards Pow-R-Line
Type PRL5P
Panelboards Pow-R-Line
Type PRL5P
3-4
September 2009
Note: Any two breakers listed above may be mounted on the same 2X or 3X dual breaker adapter. Dual breaker adapters may be mounted in single-or double-row chassis. Dual breaker adapters can NOT be mounted across from another in a double-row chassis.
Table 3-6. 1-53. Layout Information PRL5P Box Sizes and Maximum Component Unit Ampere Rating Depth = 14 inches (355 mm)
Bus Chassis Type Total X Space 24X 32X 40X 24X 32X 40X Box Width Inches 30 30 30 48 48 48 mm 762.0 762.0 762.0 1219.2 1219.2 1219.2 Box Height Inches 64 75 86 64 75 86 mm 1625.6 1905.0 2184.4 1625.6 1905.0 2184.4 Maximum Ampere Rating of Plug-on Components Main Lugs 800 800 800 1200 1200 1200 Branch Lugs 600 600 600 1200 1200 1200 Main Breaker 800 800 800 1200 1200 1200 Branch Breaker 600 600 600 1200 1200 1200
Single-Row Bus
Double-Row Bus
Deduct X space for main breaker or lugs from the total available X spaces listed above.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
1-53 3-5
September 2009
Chassis Layout
Double-Bus Interior Mounted in 48-inch (1219.2 mm) Wide Enclosure Depth = 14 inches (355 mm)
48 (1219.2) 10 (254.0)
Single-Bus Interior in 30-inch (762.0 mm) Wide Enclosure Depth = 14 inches (355 mm)
30 (762.0) 10 (254.0)
Neutral No "X" Space Required Top or Bottom 2X 3X 2X 2X 3X 2-Pole 2-Pole EHD, FD, HFD, FDC, ED, EDH, EDC EHD, FD, HFD, FDC, ED, EDH, EDC 3-Pole 3-Pole EHD, FD, HFD, FDC, EHD, FD, HFD, FDC, ED, EDH, EDC ED, EDH, EDC
2-Pole 2-Pole EHD, FD, HFD, FDC, EHD, FD, HFD, FDC, ED, EDH, EDC ED, EDH, EDC
Neutral No "X" Space Required Top or Bottom 2X 3X 2X 2X 3X 2-Pole EHD, FD, HFD, FDC, ED, EDH, EDC
2-Pole 2-Pole EHD, FD, HFD, FDC, ED, EHD, FD, HFD, FDC, ED, EDH, EDC EDH, EDC 3-Pole 3-Pole EHD, FD, HFD, FDC, ED, EHD, FD, HFD, FDC, ED, EDH, EDC EDH, EDC
2X 2X 3X
Blank Wireway
2-Pole 2-Pole EHD, FD, HFD, FDC, EHD, FD, HFD, FDC, ED, EDH, EDC ED, EDH, EDC
Blank Wireway
3-Pole 3-Pole EHD, FD, HFD, FDC, EHD, FD, HFD, FDC, ED, EDH, EDC ED, EDH, EDC
3-Pole EHD, FD, HFD, FDC, ED, EDH, EDC 2- or 3-Pole JD, HJD, JDC Bus Cover 2- or 3-Pole DK, KD, HKD, KDC Main or Branch
3X
Blank Wireway
3X 1X-6X
4X
Filler Plate
4X
3X
4X
3X
31
6X 800A MDL, HMDL Main or Branch 6X
6X
800A MDL, HMDL Main Only 6X 800A ND, HND, NDC Main or Branch 6X
6X
Main Lug or Sub-feed Lug Kit 800A Max. 6X 1200A ND, HND, NDC Main or Branch 6X 7 (177.8) 7X Main Lug or Sub-feed Lug Kit 1200A Maximum 7X 10 (254.0)
8X
10 (254.0)
10 (254.0)
10 (254.0)
10 (254.0)
3-1. PRL5P Chassis Layout X Unit Layout of Circuit Breaker and Lug Units Figure 1-12. X = 1-3/8 inches (34.9 mm) Dimensions in Inches (mm)
Blank wireway llers are required opposite any dual breaker unit. If used as a main device, must be mounted at the neutral end of panel. Fixed bus covers are required for unused spaces if NEC six circuit disconnect rule is to be met.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
1-54
Panelboards Pow-R-Line
Type PRL5P Modications 1. Complete Assembly
Complete assembly of panelboard box, interior and trim prior to shipment when required. 2. Copper Main Bus Silver-plated copper main bus - 800A single-bus interior - 1200A double-bus interior 2a. Tin-Plated Copper Main Bus Tin-plated copper main bus - 800 A single-bus interior - 1200 A double-bus interior
Panelboards Pow-R-Line
Type PRL5P Modications
5. Trim and Door Modications
Hinged door over distribution devices - Type 1 enclosure
3-6
September 2009
7. Circuit Breaker Handle Lockoff Devices 8. Nameplates, Engraved 9. Copper Wire Only Terminals for Moulded Case Circuit Breakers
To replace standard Al/Cu terminals) Table 1-54. 3-8.
Breaker Frame Maximum Breaker Ampere Rating 200 250 225 350 400 600 600 800 700 1000 1200 Terminal Material Stainless Steel Stainless Steel Copper Copper Copper Copper Copper Copper Copper Copper Copper Wire Range #4 4/0 #4 350 (1) #3 350 (1) 250 500 (2) 3/0 250 (2) 250 500 (2) #2/0 500 (3) #3/0 300 (2) #2/0 500 (3) #3/0 500 (4) #3/0 400
F J K
L M N
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
3-7
Panelboards Overview
1-55. Catalogue Numbering System - Pow-R-Line 1R Table 3-9.
1-62
Product Description
PIR-240V maximum, P2R-347/600/V maximum Single-phase 3-wire or single-phase 2-wire. 3-phase 3-wire or 3-phase 4-wire. 400 amperes maximum. 100 ampere maximum branch breakers. Fits existing box depths from 4.50 to 6.00 inches (114.3 to 152.4 mm) deep. Integrally mounted neutral assembly. Ground bar and bonding conductor included. Neutral and ground convertible from left-right. Bolt-on branch breakers. Factory assembled.
Application Description
Lighting and appliance branch panelboards. Fully rated or series rated. Interrupting capacities to 100 kA symmetrical.
Panel Type P2R Main Device L = MLO B = Main Breaker System Type
Bus Type A = Aluminum C = Copper Bus Ampere Rating 1 = 100 A 2 = 225 A 4 = 400 A
Circuits 18 = 18 24 = 24 30 = 30 42 = 42
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-63
Panelboards Overview
Product Selection
3-8
Table Table 3-11. 1-57. Base Catalogue Numbers PRL-1R (240 max) & PRL-2R (600/347V max) - Main Lug Only
Ampere Rating Number of Circuits Interrupting Rating Main (kA Sym.) 240 Vac Type Pow-R-Line 1R 208/120V 3ph, 4w Catalogue Number Pow-R-Line 2R 600/347V 3ph, 4w Catalogue Number
225
MLO
400
MLO
1-57a. Base Catalogue Numbers PRL-1R (240 max) Main Breaker Table 3-12.
Ampere Rating Number of Circuits Interrupting Rating Main (kA Sym.) 240 Vac Breaker Type Pow-R-Line 1R 240/120V 1ph, 3w Catalogue Number Pow-R-Line 1R 208/120V 3ph, 4w Catalogue Number
Main Breaker
18 30 42 18 30 42 100 18 30 42 18 30 42 18 30 42 18 30 42 18 30 42
BAB, Add
10
BAB
P1RB1A1-18BAB-** P1RB1A1-30BAB-** P1RB1A1-42BAB-** P1RB1A1-18EHD-** P1RB1A1-30EHD-** P1RB1A1-42EHD-** P1RB1A1-18QBHW-** P1RB1A1-30QBHW-** P1RB1A1-42QBHW-** P1RB1A1-18ED-** P1RB1A1-30ED-** P1RB1A1-42ED-** P1RB1A1-18EDH-** P1RB1A1-30EDH-** P1RB1A1-42EDH-** P1RB1A2-18ED-** P1RB1A2-30ED-** P1RB1A2-42ED-** P1RB1A2-18EDH-** P1RB1A2-30EDH-** P1RB1A2-42EDH-**
P1RB3A1-18BAB-** P1RB3A1-30BAB-** P1RB3A1-42BAB-** P1RB3A1-18EHD-** P1RB3A1-30EHD-** P1RB3A1-42EHD-** P1RB3A1-18QBHW-** P1RB3A1-30QBHW-** P1RB3A1-42QBHW-** P1RB3A1-18ED-** P1RB3A1-30ED-** P1RB3A1-42ED-** P1RB3A1-18EDH-** P1RB3A1-30EDH-** P1RB3A1-42EDH-** P1RL3A2-18ED-** P1RL3A2-30ED-** P1RL3A2-42ED-** P1RL3A2-24EDH-** P1RL3A2-30EDH-** P1RL3A2-42EDH-**
18
EHD
22
QBHW
65
ED
100
EDH
225
65
ED
100
EDH
Standard
QBHW and GBH main devices consume available circuit space positions. (2 circuits for Single-Phase; 3 circuits for 3-Phase.) main breaker ampere rating suffix. May NOT exceed main bus rating. trim included. Select standard trim from either Table 3-27 or Table 3-28 on Page 3-13. Custom trims are available for an additional charge. Refer to Table 3-14 on Page 3-14 for custom trim details. A neutral assembly is included with the base chassis. For Single-Phase 2-
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
1-64 3-9
3-13. Base Catalogue Numbers PRL-2R (600/347V max) Main Breaker Table 1-57b.
Ampere Rating Number of Circuits Interrupting Rating Main (kA Sym.) 600/347 Type Vac Pow-R-Line 2R 600/347V 3ph, 4w Catalogue Number P2RB3A1-18GBH-** P2RB3A1-30GBH-** P2RB3A1-42GBH-** P2RB3A1-18FDB-** P2RB3A1-30FDB-** P2RB3A1-42FDB-** P2RB3A1-18FD-** P2RB3A1-30FD-** P2RB3A1-42FD-** P2RB3A1-18HFD-** P2RB3A1-30HFD-** P2RB3A1-42HFD-** P2RB3A1-18FDC-** P2RB3A1-30FDC-** P2RB3A1-42FDC-** P2RB3A2-18FDB-** P2RB3A2-30FDB-** P2RB3A2-42FDB-** P2RB3A2-18FD-** P2RB3A2-30FD-** P2RB3A2-42FD-** P2RB3A2-18HFD-** P2RB3A2-30HFD-** P2RB3A2-42HFD-** P2RB3A2-18FDC-** P2RB3A2-30FDC-** P2RB3A2-42FDC-**
Main Breaker
18 30 42 18 30 42 100 18 30 42 18 30 42 18 30 42 18 30 42 18 30 42 18 30 42 18 30 42 10 GBH
14
FDB
18
FD
25
HFD
35
FDC
14
FDB
18
FD
225
25
HFD
31
35
FDC
Notes:
BAB, QBHW and GBH main devices consume available circuit space positions. (2 circuits for Single-Phase; 3 circuits for 3-Phase.) Add main breaker ampere rating sufx. May NOT exceed main bus rating. Standard trim included. Select standard trim from either Table 3-27 or Table 3-28 on Page 3-13. Custom trims are available for an additional charge. Refer to Table 3-14 on Page 3-14 for custom trim details. A neutral assembly is included with the base chassis. For Single-Phase 2-
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
1-65
3-10
Number of Poles 1,2,3 2,3 2 1,2 1 1,2 1,2 1 1 1,2,3 2,3 2 1,2 1,2 Pole Pole Pole Pole Pole Pole Pole Pole Pole Pole Pole Pole Pole Pole
BAB BAB BAB BABRSP DNBA QBGF QBGFEP QBCAF BAB-D QBHW QBHW QBHW QBHGF QBHGFEP
Single-pole breakers are rated 120 Vac maximum. 240 volt breakers must be used on 3-phase, 3-wire 240 volt delta systems or on the high leg of a mid-point delta grounded system. 50 ampere devices available as 2-pole only. Remote controllable circuit breaker. GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. Arc fault circuit breaker. Combination Arc fault circuit breaker HID (High Intensity Discharge) rated breaker. Twin Breaker.
Catalogue Number
To convert base chassis catalog number from aluminum main bus to copper main bus, change the 6th digit of the aluminum base chassis catalog number to C. (i.e., P1RL1A1-42 becomes P1RL1C1-42).
Table 3-17. 1-61. Copper Terminal Ground Bar for Copper Cable Only
Copper Ground Bar Catalog Number P1RGBC
Each base chassis includes a neutral bar that contains one connection point for every circuit space available. Use this kit when additional connection points are required or the neutral must be separately mounted to meet existing cable locations.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
3-11
1-66
Catalogue Number
Catalogue Number
This option includes any mounting plate extensions (from Table 1-66) required to match existing mounting studs. Detailed stud location drawings must accompany the order or a Field Survey (Table 1-64) must be purchased.
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
September 2009
1-67 3-12
Application Guidelines
Instructions
In order to meet minimum wire bending space requirements and to ensure ease of installation, minimum enclosure space dimensions have been dened for each chassis. In order to ensure a proper t, every panelboard to be renovated must be carefully surveyed prior to installation. Determine the electrical requirements of the panelboard to be renovated (i.e., main breaker or main lugs, amperes, interrupting rating, circuit space, branch breakers, accessories). Using the electrical requirement data, select a base chassis and any required breakers, options and accessories. Table 3-26 provides the minimum dimensions of the enclosure, in which each base chassis may be installed, These dimensions assume that the chassis is mounted in the center of the existing box, both vertically and horizontally. Where site conditions require the chassis to be offset from this centrally mounted position, it is the installer's responsibility to ensure wire bending space and electrical clearance requirements are met. Table 3-26 provides a Trim Door Size Code. Using this code, select a standard trim from Table 3-27 and 3-28 that will t the outside dimensions of the existing box. Refer to Table 3-29 to dene non-standard trim requirements.
31
225
MLO
400
MLO
Main Breaker
100 BAB
EHD
QBHW
ED
EDH
ED
EDH
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
September 2009
In order to meet minimum wire bending space requirements and to ensure ease of installation, minimum enclosure space dimensions have been dened for each chassis. In order to ensure a proper t, every panelboard to be renovated must be carefully surveyed prior to installation. Determine the electrical requirements of the panelboard to be renovated (i.e., main breaker or main lugs, amperes, interrupting rating, circuit space, branch breakers, accessories). Using the electrical requirement data, select a base chassis and any required breakers, options and accessories. Table 3-26 provides the minimum dimensions of the enclosure, in which each base chassis may be installed, These dimensions assume that the chassis is mounted in the center of the existing box, both vertically and horizontally. Where site conditions require the chassis to be offset from this centrally mounted position, it is the installer's responsibility to ensure wire bending space and electrical clearance requirements are met. Table 3-26 provides a Trim Door Size Code. Using this code, select a standard trim from Tables 3-27 and 3-28 that will t the outside dimensions of the existing box. Refer to Table 3-29 to dene non-standard trim requirements.
Table 1-71. Table 3-27. Standard Trim Selection 20-Inch (508.0 mm) Wide Enclosure
Trim Door Enclosure Size Code Height Inches A A A B B B B C C C D D D D E E E E E 24.00 30.00 36.00 30.00 36.00 42.00 48.00 36.00 42.00 48.00 30.00 36.00 42.00 48.00 36.00 42.00 48.00 54.00 60.00 mm 609.6 762.0 914.4 762.0 914.4 1066.8 1219.20 914.4 1066.8 1219.2 762.0 914.4 1066.8 1219.2 914.4 1066.8 1219.2 1371.6 1524.0 RTA2024 RTA2030 RTA2036 RTB2030 RTB2036 RTB2042 RTB2048 RTC2036 RTC2042 RTC2048 RTD2030 RTD2036 RTD2042 RTD2048 RTE2036 RTE2042 RTE2048 RTE2054 RTE2060 Surface Type Catalog Number Trim Dimensions Height Inches 24.00 30.00 36.00 30.00 36.00 42.00 48.00 36.00 42.00 48.00 30.00 36.00 42.00 48.00 36.00 42.00 48.00 54.00 60.00 mm 609.6 762.0 914.4 762.0 914.4 1066.8 1219.2 914.4 1066.8 1219.2 762.0 914.4 1066.8 1219.2 914.4 1066.8 1219.2 1371.6 1524.0 Width Inches 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 20.00 mm 508.0 508.0 508.0 508.0 508.0 508.0 508.0 508.0 508.0 508.0 508.0 508.0 508.0 508.0 508.0 508.0 508.0 508.0 508.0 RTA2226 RTA2232 RTA2238 RTB2232 RTB2238 RTB2244 RTB2250 RTC2238 RTC2244 RTC2250 RTD2232 RTD2238 RTD2244 RTD2250 RTE2238 RTE2244 RTE2250 RTE2256 RTE2262 Flush Type Catalog Number Trim Dimensions Height Inches 26.00 32.00 38.00 32.00 38.00 44.00 50.00 38.00 44.00 50.00 32.00 38.00 44.00 50.00 38.00 44.00 50.00 56.00 62.00 mm 660.4 812.8 965.2 812.8 965.2 1117.6 1270.0 965.2 1117.6 1270.0 812.8 965.2 1117.6 1270.0 965.2 1117.6 1270.0 1422.4 1574.8 Width Inches 22.00 22.00 22.00 22.00 22.00 22.00 22.00 22.00 22.00 22.00 22.00 22.00 22.00 22.00 22.00 22.00 22.00 22.00 22.00 mm 558.8 558.8 558.8 558.8 558.8 558.8 558.8 558.8 558.8 558.8 558.8 558.8 558.8 558.8 558.8 558.8 558.8 558.8 558.8
13
Surface Type Trim Dimensions Catalog Number Height mm 609.6 762.0 914.4 762.0 914.4 1066.8 914.4 1066.8 1219.2 762.0 914.4 1066.8 914.4 1066.8 1219.2 RTA1424 RTA1430 RTA1436 RTB1430 RTB1436 RTB1442 RTC1436 RTC1442 RTC1448 RTD1430 RTD1436 RTD1442 RTE1436 RTE1442 RTE1448 Inches 24.00 30.00 36.00 30.00 36.00 42.00 36.00 42.00 48.00 30.00 36.00 42.00 36.00 42.00 48.00 mm 609.6 762.0 914.4 762.0 914.4 1066.8 914.4 1066.8 1219.2 762.0 914.4 1066.8 914.4 1066.8 1219.2 Width Inches 14.00 14.00 14.00 14.00 14.00 14.00 14.00 14.00 14.00 14.00 14.00 14.00 14.00 14.00 14.00 mm 355.6 355.6 355.6 355.6 355.6 355.6 355.6 355.6 355.6 355.6 355.6 355.6 355.6 355.6 355.6
Flush Type Catalog Number Trim Dimensions Height Inches RTA1626 RTA1632 RTA1638 RTB1632 RTB1638 RTB1644 RTC1638 RTC1644 RTC1650 RTD1632 RTD1638 RTD1644 RTE1638 RTE1644 RTE1650 26.00 32.00 38.00 32.00 38.00 44.00 38.00 44.00 50.00 32.00 38.00 44.00 38.00 44.00 50.00 mm 660.4 812.8 965.2 812.8 965.2 1117.6 965.2 1117.6 1270.0 812.8 965.2 1117.6 965.2 1117.6 1270.0 Width Inches 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 mm 406.4 406.4 406.4 406.4 406.4 406.4 406.4 406.4 406.4 406.4 406.4 406.4 406.4 406.4 406.4
24.00 30.00 36.00 30.00 36.00 42.00 36.00 42.00 48.00 30.00 36.00 42.00 36.00 42.00 48.00
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
1-69
3-14
September 2009
Instructions
In order to accommodate instances where the standard trims (Tables 3-27 and 3-28 ) do not suit an installation, custom-sized trims may be ordered. Since the trim mounts to the retrot chassis, and not the existing enclosure, custom trims can solve many problems encountered with differing enclosure sizes and congurations. Use the dimension and sizing parameters listed below to dene a custom trim catalog number. Contact your local satellite plant to ensure manufacturability and determine lead time required.
Outer Dimensions
The outer dimensions are the overall OUTSIDE dimensions of the trim. In surface-mounted applications, this is usually the same as the outside dimensions of the enclosure to be renovated. For ush-mounted applications, an additional amount of trim material extends beyond the outer edge of the box, in order to cover any gap between the wall material and the box. Extending the outer dimensions can cover larger than normal wall gaps or imperfections that may be encountered. W = Trim Width Total outside width of the TRIM, including that required to overlap the box in a ush application. H = Trim Height Total outside length of the TRIM, including that required to overlap the box in a ush application.
Note: This example is for a custom trim that has overall dimensions of 20 inches (508.0 mm) in width and 48 inches (1219.2 mm) in height. The trim door is offset 1.00 inch (25.4 mm) to the RIGHT, in order to accommodate a flush-mounted, double-tub arrangement in which the boxes are bolted together without any spacers.
3
OT
Offset
Offset allows a retrot chassis to be relocated from the central mounting position required for standard trims. This can accommodate many challenging site conditions such as short cables, physical obstructions, closecoupled boxesetc. OR = Offset Right This is the distance from the centerline of the CHASSIS to the right-hand edge of the TRIM. OL = Offset Left This is the distance from the centerline of the CHASSIS to the left-hand edge of the TRIM. OT = Offset Top This is the distance from the centerline of the CHASSIS to the top edge of the TRIM. OB = Offset Bottom This is the distance from the centerline of the CHASSIS to the bottom edge of the TRIM.
OB
OL
OR
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
1-70 3-15
Application Guide
Surface-Mount Panelboards Data Sheet
Electrical Data
Panel Designation or Location _________________________________________________________ _________________________________________________________ Service:________Vac ________Phase ________Wire Circuits:________ Bus Amps:________(A) Main Lugs Only Main Breaker Top Entry Bottom Entry Amps:________(A)
13
End View F
Side View FF
W F
Finished Wall
H W FF
Finished Wall
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
1-71 3-16
31
Side View
FF
HH WW Finished Wall FF DD W H
HH H
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
3-17
Retrot Panel
September 2009
Panelboards
1-72
Chassis Mounting
In some applications it is required to drill mounting holes that match the location of hardware points (studs or bolts) in the existing panel. All dimensions to these hardware points are measured from the CENTRELINE of the enclosure. Follow the guidelines below to ensure that these holes are located properly, ensuring a quick and easy installation. 1. Measure and mark the vertical centerline point. This measurement should be taken from the INSIDE surface of the enclosures END. 2. Measure and mark the horizontal centerline point. This measurement should be taken from the INSIDE surface of the enclosures SIDE. 3. Measure the distance from the centerline marks to the center of the hardware point to be matched and record below. 4. Measure and record the diameter of the stud or bolt to be matched. In some cases the mounting hardware may NOT be placed symmetrically about the center of the enclosure. Ensure that all desired hardware locations are measured to the CENTRELINE. H:________ W:________ ST:________ SB:________ SL:________ SR:________ D:________ (Bolt or Stud Diameter) Figure 1-17. Figure 3-5. Chassis Mounting Dimensions
Front View W SL SR
ST
Mounting Studs
Centerline
SB
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-73
Panelboards
3-18
Pow-R-Command Family
Eatons Cutler-Hammer brand Pow-RCommand family of lighting control panelboards is designed to meet the lighting control needs for buildings of all sizes and complexity. The system incorporates microprocessor-based distributed intelligence within a traditional panelboard, simplifying wiring in the eld.The system can be networked over customers or directly interfaced to the Internet, allowing for password protected web access. The panelboard design allows the Pow-R-Command lighting control system to meet short circuit ratings, as required by the National Electrical Code (NEC).
Flexibility : Lighting control panelboards allow simple and inexpensive changes during start-up. Contactor and relay panels often require rewiring to make changes in the eld. Choices : The Cutler-Hammer brand of lighting control panelboards offers varying levels of exibility, from six zones per panel with the Pow-R-Command 25 up to 250 zones per panel with the Pow-R-Command 2000. We have added wireless capabilities using our Pow-R-Command Small building Controller with wireless I/O modules. Space : Lighting control panelboards eliminate contactor panels and/or relay panels, freeing up valuable wall space. Pow-R-Command panels are the same width as standard panelboards. Retrot Applications : Retrotting traditional lighting control methods into an existing electrical distribution system often requires extensive rewiring and unwanted downtime. In most cases, a Pow-R-Command panel interior can be installed into an existing panelboard back box, and the cables can be re-terminated on the new circuit breakers, with minimal downtime. The wireless I/O modules also allow for discrete ON/OFF load control through and on-board relay capable of switching 120V or 277V ballasts.
Labor : Because contactors and relays are eliminated, the labor associated with installing them and the additional cables and conduit associated with them is eliminated. Start-up: Start-up for the Pow-RCommand panelboards is straightforward. The PRC25 requires no startup. It is prewired at the factory. The PRC100 is provided with factory startup assistance for trouble-free installation. The PRC750 is provided with an LCD display and keypad for on-site programming. The PRC1000 and PRC2000 are programmed over the network. They have an optional display available for local interface.
Operational Considerations
Failure Modes : If a lighting contactor or relayfailstooperateduetoamec hanical or control system failure, it is very difcult to control the lights manually. Often, it is necessary to hard-wire around the device on a temporary basis. With a lighting control panelboard system, the circuit breaker can be manually switc hed on or of f as necessary until the system is back in operation. Flexibility : In many cases, the lighting control scheme may change over the life of the facility. With traditional lighting control methods, changes require major rewiring and facility downtime. Break er control sc hemes can be c hanged within the lighting control panelboard, often with a simple modication through software.
Installation Considerations
SimplicityLighting : control panelboards are as easy to install as standard panelboards. There are no additional components to install.
Design Considerations
Short Circuit Protection : In the past, contactors or relay panels were mounted close to the lighting load and short circuit ratings were not a major concern. Today, most of the lighting control devices are located in electrical rooms, often adjacent to the panelboards that feed them. These devices are subjected to short circuit conditions almost as high as those of the electrical distribution equipment. The current version of the National Electrical Code now requires that these lighting control devices carry a short circuit rating (Article 110-10). Although some traditional lighting control components are available with short circuit ratings, these ratings are limited and may require upstream fusing. A lighting control panelboar d mak es meeting the requirements of NEC 1 10-10 as simple as specifying the shor t circuit rating of the panelboar d.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
1-74 3-19
Inputs
Switch Universal (Switch or Analog) Optional Switch Input Expander Total Inputs
Outputs
Outputs Digital (Maximum Controllable Zones) Analog Universal I/O Module Telephone Override Data Logging Remote Access Power Supply for External Devices Maximum Number of Loads (Breaker/Relay) Number of Satellite Panels Manual Override Dimming Maximum Number of Dimming Ballasts Daylight Harvesting (Using Dimming Ballasts) Daylight Switching (On/Off Circuit Switching) Time Clock Time Schedules
13
Scheduling Zones On/Off Periods per Schedule Holidays Blink Notice Maximum Override Time (hrs) RS-232 Port RS-485 Port Ethernet Port Ethernet via External Gateway Input/Output Matrix Across Controllers Input/Output Matrix Within Controller Local LCD/LED Display Local LED Status Indicators Non-Volatile Program Memory Battery Back-up for Program Memory Clock Memory Back-up Flash Firmware Memory
Protocols
Modbus ASCII/RTU Modbus TCP Johnson Controls N2 BACnet LonWorks SOAP/XML OPC
Start-up and Integration by Eaton is not mandatory when utilizing the PRC2000B with BACNET protocol. Each rail drives 21 breakers. Rails can be distributed individually over a total of eight panels (max. SLAN wire-length of 150 ft.). 250 additional schedules with optional Network Interface Box NIB. 16 additional holidays with optional Network Interface Box NIB.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
1-75 3-20
Browser Access
TCP/IP External Device
Standards
UL 916 Energy Management Equipment California Title 24 NEC 110-10 UL 67 Panelboards CSA C22.2 #29 Panelboards Baud Rate Maximum Controllers/Network Password Protected
Mounting
3-Pole Breaker Housing External Bracket Mount Available
3 1
Pow-R-Command 25 (PRC25)
Eatons Cutler-Hammer PRC25 Panelboard replaces contactors and relay panels in lighting control and other load switching systems. It is the most basic and cost-effective way to remotely control loads. The PRC25 is ideal for any building that requires a xed lighting control scheme with a low installed cost. Examples may include small commercial buildings, tenant spaces, and other light commercial facilities.
Pow-R-Command 750
Designed for stand-alone applications, the Cutler-Hammer PRC750 is a premier microprocessor-based lighting control system that can be used to control all of the lighting in your industrial facilities, high-rise ofce buildings and airports. A single PRC750 panel can be connected to a maximum of three expansion panels for the ability to control up to a total of 168 Smart Breakers . The PRC750 also boasts load override, holiday scheduling, memory loss protection, astronomical time clocks and scheduling, 16 switch inputs, and alarm and message log features.
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
3-21
1-75
Sustainability Green Buildings Solutions for a Greener Planet Environmental stewardship, innovation and leadership are becoming increasingly important as we take steps to create a sustainable environment for future generations by going green. This is particularly important when it comes to construction of new buildings or major renovations of older ones. To this end, Eaton Corporation offers a broad range of energy efficient and environmentally-friendly electrical solutions that can help a building go green and qualify for Leadership in Energy and Environmental Design (LEED) credits through the Canadian Green Buildings Council (CaGBC). For customers like you, Eaton offers an exceptional array of equipment, tools and services to reduce energy consumption and leave a smaller footprint on the worlds environment. As you work to achieve your own goals for environmental sustainability, when you partner with Eaton, you can be sure your power equipment is doing its part too. The world is more energy conscious these days. But unlike you, most of the world doesnt pay a utility bill that rivals the cost of a four bedroom home. You understand the need to know where energy is being expended in your facility and how you can make it more of an asset and less of a chronic liability. It starts with the right products in the right places. Whether you are looking for a special piece of gear to help identify energy loss, or a full blown solution for full blown asset optimization, you are bound to find what you need from Eaton.
Through automated building management systems you reduce your energy consumption by 10 to 30 percent. Simple protocols can control your facilities lighting, heating and air conditioning, and electrical loads. End the manual exercise of checking where energy is being wasted. Eatons industry-leading Pow-R-Command lighting control systems turn off the lights when a space is empty. A lighting control system can contribute significantly to achieving LEED credit points. The following represent potential points available when applying Eatons Pow-R-Command as part of a lighting control system. o SS Credit 8: Lighting Pollution Reduction (1 point) o EA Prerequisite 1: Fundamental Commissioning of the Building Energy Systems (Required) o EA Prerequisite 2: Minimum Energy Performance (Required) o EA Credit 1: Optimize Energy Performance (110 points) o EA Credit 3: Enhanced Commissioning (1 point) o EA Credit 5: Measurement & Verification (1 point) o EQ Credit 8.1: Daylight & Views: Daylight 75% of Spaces (1 point) o ID Credit 11.4: Innovation in Design (14 points) For more information see Eatons LEED Credits Guide SA08300002E Latest Revision.
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-77 3-22
Pow-R-Command 2000/2000B
General Description
Eatons Cutler-Hammer Pow-RCommand 2000 is a microprocessorbased programmable lighting control system with an embedded webserver for robust control. The PRC2000 can be used as a stand-alone panelboard or networked as a system. An upgrade can be purc hased to integrate the unit within BA Cnet nati ve control networks.
Features
PRC 2000/1000/750/100 common features list see Page 3-1 9.
LCD display and keypad. Memory loss protection. Power failure/brownout recovery. Astronomical real-time clock. Time scheduling. Holiday scheduling. Input to output switch matrix. Message/alarms. Daylight optimization. Switch Override Controller (SOC). Telephone Override Controller (TOC).
Components
Embedded webserver. Intelligent power switching equipment. LCD programming display and keypad. Application Specic Controllers (ASCs). Software and support. Integration components.
31
BACnet Protocol
The PRC2000 unit can be upgraded to the B series for integration within BACnet native control networks. BACnet is a communications protocol widely used in building automation and controls and adds even more exibility to the control system.
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
Pow-R-Command 1000
General Description
Eatons Cutler-Hammer Pow-RCommand 1000 is a microprocessorbased programmable lighting control system. The PRC1000 can be used as a stand-alone panelboard or networked as a system.
Features
PRC 2000/1000/750/100 common features list see Page 3-1 9.
LCD display and keypad. Memory loss protection. Power failure/brownout recovery. Astronomical real-time clock. Time scheduling. Holiday scheduling. Input to output switch matrix. Message/alarms. Daylight optimization. Switch Override Controller (SOC). Telephone Override Controller (TOC).
Components
13
Pow-R-Command 1000 Panel
Intelligent power switching equipment. LCD programming display and keypad. Application Specic Controllers (ASCs). Software and support. Integration components.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
1-79 3-24
Pow-R-Command 750
General Description
Eatons Cutler-Hammer Pow-R-Command 750 is a microprocessor-based programmable lighting control system. The Pow-R-Command 750 can be used as a stand-alone panel, or the user has the option to connect up to three expansion panels to the 750 creating its own stand-alone subnetwork.
Features
PRC 2000/1000/750/100 common features list see Page 3-1 9.
LCD display and keypad. Memory loss protection. Power failure/brownout recovery. Astronomical real-time clock. Time scheduling. Holiday scheduling. Input to output switch matrix. Message/alarms. Daylight optimization. Switch Override Controller (SOC). Telephone Override Controller (TOC).
Components
Pow-R-Command 750 Panel
Intelligent power switching equipment. LCD programming display and keypad. Integration components.
31
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
Pow-R-Command 100
General Description
Eatons Cutler-Hammer Pow-RCommand 100 is a microprocessor-based programmable lighting control system. ThePRC100canbeusedasastand-alone panelboard or networked as a system.
Features
PRC 2000/1000/750/100 common features list see Page 3-1 9.
LCD display and keypad. Memory loss protection. Power failure/brownout recovery. Astronomical real-time clock. Time scheduling. Holiday scheduling. Input to output switch matrix. Message/alarms. Daylight optimization. Switch Override Controller (SOC). Telephone Override Controller (TOC).
Components
Intelligent power switching equipment. Application Specic Controllers (ASCs). Software and support. Integration components.
13
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
1-81
Panelboards
3-26
Pow-R-Command 25
System Congurations
The Pow-R-Command 25 Panelboard provides the ability to group up to 42 remotely operated controllable breakers into six individual zones. Each zone is designed to be switched by a dry or control signal contact from an external device. Each Pow-R-Command 25 panelboard has an integral zoning board where the zone designations are pre-wired at the factory and linked to specic contact inputs. Limited changes may be made to zone designations in the eld through wiring changes. The Pow-R-Command 25 Panelboard is CSA approved to C22.2 NO 29.
Pow-R-Command 25 Panel
General Description
Eatons Cutler-Hammer Pow-RCommand 25 is designed to replace lighting control systems involving multi-pole lighting contactors and relay panels. The Pow-R-Command 25 utilizes controllable circuit breakers in a panelboard which are grouped into zones and switched by a dry or control signal contact from an external source. The controllable br eak ers ar e pre-wired at the f actory in up t o six customer-designated zones with up to 16 break ers per z one.
Note: Refer to factory for zoning restrictions.
Components
Intelligent power switching equipment. Maintained-to-momentary board (MTM).
BAS
Integration
The Pow-R-Command Lighting Control system can be integrated with Building Automation Systems via the following optional components:
13
Native Modbus Controller. The Native Modbus Controller takes the place of the PRC100 System Controller. The Native Modbus Controller is designed as a slave Modbus node. JCI100 Controller. The JCI100 Controller is designed to take the place of the PRC100 System Controller. The JCI Controller is designed specically for use in a Johnson Controls Metasys network. The JCI100 communicates using JCIs N2 protocol and is treated as an addressed slave node on an N2 bus. OPC Server. The PRC OPC Server is a software addition onto a PRC100 or 1000 system. It is designed as an interface between the PRC system and an OPC server/client. SOAP Server. The PRC SOAP Server is a PRC100 system network add-on. The PRC SOAP Server is designed as an interface between a PRC100 or 1000 system and a SOAP client. BACnet Server. The PRC BACnet Server is a PRC system network add-on. The BACnet Server is designed to interface between the PRC100 or 1000 system and a BAS provider using the BACnet protocol. PRC2000 web-enabled BACnet Controller. The PRC2000 BACnet Controller provides direct interface via the web to a BACnet BAS system.
Computer
Software
Provides programming for the following equipment: Power switching equipment Application specic controllers The Lighting Management Software provides fully interactive easy-to-use software screens for the following functions: System Setup System Management Controller Access and Modication Data Logging and Back-up Remote Monitoring
The programming screens provide access to all the capabilities that exist in the power switching and application specic controllers. Additional software components can be purchased that will allow for the creation and use of custom graphic screens and/or Web access to a PRC100 system. Network components provide exibility in establishing a PRC100 network. The network can consist of either a pure twisted shielded network or a combination of a twisted shielded network and Ethernet. Ethernet networks are accomplished using the PRC100 Ethernet Server. To connect to a PRC100 network via a PC, modem, or remote LAN/WAN connection, a Network Access Device is required. There are two types of Network Access Devices offered. The rst is a Network Interface Box, which allows connection via an RS-232 port. The second is an Ethernet Server, which is used for connection via Ethernet.
Further Information. . . . . . . . . . . . . . . CAT.73.01.T.E For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca CAT.38.02.S.K
CAT.38.03.S.K
1-83 3-28
Control Software
Control Cabinet (Accommodates Three ASCs)
General Description
The Control Cabinet contains a PRC100 System Controller. The Control Cabinet is ideal for retrot applications where existing panelboards are utilized. Remote controllable breakers may be utilized in an existing panelboard. When remote controllable breakers are connected to the Control Cabinet full system functionality is provided. The wiring between each panelboard mounted controllable break er and the system controller is a 28 Vac 3-wire or 4-wire circuit up to 200 feet (61 m) in length.
It is possible to program the panelboard directly through its local RS-485 maintenance port with a hand-held programmer or with the lighting management software over a shielded twisted pair cable by way of a central operators station.
Time Scheduling
Pow-R-Command 100 supports 50 schedules as local control functions. Any of the 50 local time schedules in a controller can be designated as a back-up schedule to execute only if the master sc hedules fail or cease execution.
Provides the ability to connect and monitor up to 48 additional 2-wire dry contact closures from wall switches, occupancy sensors, photocells, building automation system relay contacts or any remotely mounted device with a dry contact. Input connections to the controller are self-powered. It is possible to program any input to the switch override controller to control any breaker or group of breakers in the system. Inputs are capable of being individually time-schedule enabled for different days of the week.
31
Holiday Scheduling
Pow-R-Command 100 supports 16 system holidays through the Network Access Device and, additionally, each controller can execute 30 local holiday denitions.
Messages/Alarms
The system will maintain an alarm log. The log will record where the alarm occurred, alarm reason, date and time of the alarm. The log is maintained in non-volatile memory. The alarm log can store up to 300 alarms.
Daylighting Optimization
Daylighting optimization is available using a combination of inputs on the PRC100 controller or a Switch Override Controller and dimming cable.
CAT.38.02.S.K CAT.38.03.S.K For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
3-29
1-84
System Congurations
PRC2000 Network Architecture
Containing an embedded webserver, each Pow-R-Command 2000 system is programmed with a unique IP address for communication via any standard Internet browser. Web access is standard with the PRC2000. Eight 21-circuit control buses congured as needed throughout PRL1 and 2 panels. The PRC2000B directly interfaces to a BACnet Client Workstation.
5th Floor RS-485 PRC EP 1 4th Floor RS-485 PRC EP 2 3rd Floor RS-485 PRC EP 2 2nd Floor RS-485 PRC 2000 Customer LAN PC with Internet Browser PRC EP 1
Ground
1
Remote Access Thru VPN
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-85
Panelboards
3-30
PRC1000 Application
Customizable extension panels allow for combinations of both regular and remote controllable breakers for individualized solutions as shown in this riser diagram. Eatons Cutler-Hammer Pow-R-Command 1000 Controller can support up to eight Breaker Control Bussescontainedwithinfourstandard panelboards or split between a maximum of eight. When connected to the buildings Internet, all master and expansion panels can be controlled.
PRC EP PRC 1 5th Floor
5th Floor EP 1
RS-485 RS-485
RS-485
2nd Floor
PRC 1000
RS-485
RS-485
RS-485 IIIB PC with PC Software
PRC 1000
Ground
RS-485
IIIB
with Software
Remote Access Thru Remote Modem
Ground
3
Access Thru Modem
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
3-31
Panelboards
1-86
1
Table Figure3-10. 1-22. PRC750 Stand-alone System Architecture
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-87 3-32
PRC100-EC
PRC100
USC SOC
USC
USC
PRC100-EC
PRC100
PRC100-EC
USC SOC
USC
USC SOC
Typical branches: Up to 42 controllable circuits. Chassis mounted controllable breakers can be mixed with standard non-controllable branch breakers.
Control Cabinet Main Network Cable (Twisted Pair) PRC100 PRC100 PRC100
Photocell Switch or LV Switch Analog Phone Line Standard Analog Modem USC USC USC 120 Vac RS-232/Serial Cable Serial Switching Box
31
NIB Optional Networked PCs Access to Graphics Program via DDE Optional Computer/ Software PC RS-232 Cable Keyboard Central PC/DDE Server Monitor
As shown, the central personal computer (PC) is optional since each panelboard is a stand-alone operating lighting control system with basic lighting control functions. The PC may be used for programming changes; downloading software; scheduling, viewing system status and conguration, etc.
Legend
PRC100 = Standard Pow-RCommand 100 Panel PRC100-EC = Pow-R-Command 100 with Expansion Chassis USC = Universal System Controller Board PC = Personal Computer NIB = Network Interface Box SOC = Switch Override Controller
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
3-33
1-88
Product Features
Bolt-on line-side terminal. Cable connected load-side terminal. 3- or 4-wire (BABRP) control terminal. Status switch. Bi-metal assembly for thermal overload protection. Fast acting short circuit protection. Arc-runner and arc-chute assembly for fast acting arc extinction.
Three-position handle: OFF, TRIP (Center), ON. Handle permits manual switching when control power is lost. Mechanical trip indicator. 15 and 20 ampere breakers SWD (switching duty) rated. HID ratings for HID (high intensity discharge) lighting.
Table 1-79. 3-34. BABRP and BABRSP UL 489 and CSA 22.2 Interrupting Ratings and Catalogue Numbers
Circuit Breaker Type BABRSP1015 BABRSP1020 BABRSP1025 BABRSP1030 BABRSP2015 BABRSP2020 BABRSP2025 BABRSP2030
Number of Poles
Interrupting Capacity (Symmetrical Amperes) Ampere Rating 15 20 25 30 15 20 25 30 Volts ac (50/60 Hz) 120 10,000 10,000 10,000 10,000 120/240 10,000 10,000 10,000 10,000
1 1 1 1 2 2 2 2
Description This 60-inch (1219.2 mm) wire pigtail provides a connection from a single BABRSP control plug to a customers pushbutton, relay or PLC. Each box contains 12 pigtails. Wires are 22 AWG, 600 V. Order in multiples of 12. Same as SLBKRPTL1 except 72 inches (1828.8 mm) long and connects up to four BABRSP breakers on the same pigtail. Each box contains 4 pigtails. Order in multiples of 4.
SLBKRPTL4
BABRSP Breaker
General Description
BABRSP circuit breaker is a bolt-on branch circuit breaker designed for use in panelboards and are ideally suited for lighting control or energy management applications. In addition to providing conventional branch circuit protection, they include a unique solenoid-operated mechanism that provides for efcient break er pulse-on andpulse-of foperation whenusedwith a suitable controller like the Eatons Cutler-Hammer Pow-R-Command lighting control system. BABRSP break er can also be operated by a pushbutton, relay or PLC. A breaker status feature is included.
Note: BABRSPhasmonitoringonlyofthe status of the break er contacts.
Same as SLBKRPTL4 except it connects up to six BABRSP breakers on the same pigtail. Each box contains 4 pigtails. Order in multiples of 4.
SLBKRPTL6
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-89
Panelboards
3-34
Black
Yellow
Red
ON Coil
Remote Status
Line
RM b
RM a
BKR a
Black
Yellow
Ambient temperature: 0C 40C. Nominal pulse magnitude: 28 Vac rms, 24 Vac (BABRP). Tolerance: +10% to -15% of nominal voltage. Pulse duration: 1/2 cycle (8 10 ms). Minimum recommended pulse current at nominal voltage: BABRP , BABRSP, GHQRSP 1-Pole: 1.0 amperes peak 2-Pole: 2.0 amperes peak Breaker operating time: 20 40 ms. Maximum breaker cycling: six operations per minute. Humidity: 0 95% non-condensing. The BABRSP and GHQRSP are rated for 250,000 operations.
Red
ON Coil
OFF Coil
Breaker Status
Blue
Blue
Figure 1-24. 3-12.Circuit Breaker Schematic Diagram for the BABRP and BABRSP Breakers
Note: 2-pole break er s have two solenoids.
CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
CAT.38.02.S.K
3-35
1-90
Technical Data
Panelboard Ratings
Voltage: 240 Vac 480Y/277 Vac Main lugs: 100 through 400 amperes Main breakers: 100 through 400 amperes Branches: 15 through 100 amperes Controllable from 15 through 30 amperes
Main lugs only ampere ratings: 100 and 225 and 400.
Service
3-phase, 4-wire 208Y/120 V, 480Y/277 Vac and 240/120 V Delta. Single-phase, 3-wire, 120/240 V.
Mains
For available mains, refer to Table 1 -81 .
Branch Circuits
For available branch circuit devices, refer to Table 3-37 .
HID (High Intensity Discharge) rated breaker. Switching neutral breaker. 1-pole device requires 2-pole space; 2-pole device requires 3-pole space. Controllable breaker. GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. 50 ampere devices are available as 2-pole only.
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-91 3-36
Service
3-phase, 4-wire 208Y/120 V 240/120 V Delta and 480Y/277 V. Single-phase, 3-wire 120/240 V.
Branch Breakers
The types GHQRSP and BABRSP are the controllable circuit breakers. Controllable breakers are available in 1- and 2-pole styles, from 15 through 30 amperes. Non-controlled breakers can be located within the panelboard chassis. Table 3-39. 1-84. Branch Circuit Breakers Table
Breaker Type Ampere Rating Number Interrupting of Poles Rating (kA Symmetrical) 240 V BAB BAB BABRSP GHQRSP GHB GHB EHD EHD FDB FD FD HFD HFD FDC ED EDH EDC
Mains
For available mains, refer to Table 3.38 .
Branch Circuits
For available branch devices, refer to Table 3-39 .
Low Voltage Control Bus Controllable Breakers
480 V 14 14 14 14 14 14 25 25 65 65
15 70 1 15 100 2, 3 15 30 1, 2 15 20 1, 2 15 100 1 15 100 2, 3 15 60 1 80 100 2, 3 15 150 2, 3 15 100 1 15 100 2, 3 15 100 1 15 100 2, 3 15 150 2, 3 100 225 2, 3 100 225 2, 3 100 225 2, 3
10 10 10 65 65 65 18 18 18 18 65 100 100
31
Panelboard Ratings
Voltage: 240 Vac maximum 480 Vac maximum Main lugs: 100 through 400 amperes Main breakers: 100 through 400 amperes Branches: 15 through 225 amperes Controllable from 15 through 30 amperes
1-pole breaker rated 120 Vac. Controllable breaker. 1-pole breaker rated 277 Vac. Controllable breaker ratings limited to 65 kA.
EHD FDB FD HFD FDC FCL FB-P FDB FD HFD FDC ED EDH EDC JD HJD JDC JD HJD JDC DK KD HKD KDC
18 18 65 100 200 200 200 18 65 100 200 65 100 200 65 100 200 65 100 200 65 65 100 200
240 Vac: 65 kA maximum fully rated. 480 Vac: 65 kA maximum series rated.
Top-feed only.
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
3-37
1-92
EHD FDB FD HFD FDC ED EDH EDC JD HJD JDC DK KD HKD KDC
240 Vac: 65 kA maximum fully rated. 480Y/277 Vac: 65 kA maximum series rated.
Service
3-phase, 4-wire 208Y/120 V, 480Y/277 Vac and 240/120 V Delta. Single-phase, 3-wire, 120/240 V.
Number of Poles 1 2 2, 3 1, 2 1, 2 1, 2 1, 2 1, 2
Mains
For available mains refer to Table 3-40.
Branch Circuits
For available branch circuit devices refer to Table 3-41 .
HID (High Intensity Discharge) rated breaker. Switching neutral breaker. 1-pole device requires 2-pole space; 2-pole device requires 3-pole space. Controllable breaker. GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. 50 ampere devices are available as 2-pole only.
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-93 3-38
13
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
3-39
1-94
Layout Example
1. Panel Description: a. PRC2000, 3-phase 4-wire, 208Y/ 120 Vac, interrupting rating of 10,000 AIC symmetrical: 225 ampere main lugs only at bottom, surface mounted and the following branch breakers b. 36 20 ampere, 1-pole BABRSP c. 6 20 ampere, 1-pole BABRSP spaces 2. Layout information from Figure 3-13 . a. PRC2000 with 42-circuit Interior 26 in. b. 225 ampere Main Lugs Section 4 in. c. Total Panelboard Height 30 in. 3. From Table 3-42 : Panel Height: 30 in. 20 in. wide x 5.75 in. deep Box Height: 48 in. Box Catalogue Number: EZB2048RC Trim Catalogue Number: EZT2048S
14 in. - 18 Ckt. Chassis Includes PRC2000 Controller 20 in. - 30 Ckt. Chassis Includes PRC2000 Controller 26 in. - 42 Ckt. Chassis Includes PRC2000 Controller 40 in. - 60 Ckt. Chassis Includes PRC2000 Controller 47 in. - 72 Ckt. Chassis Includes PRC2000 Controller 53 in. - 84 Ckt. Chassis Includes PRC2000 Controller Note: PRC2000 Chassis is located at the top of the panelboard immediately above the breakers.
Cabinets
Trims are code gauge steel, ASA 61 light gray painted nish. Boxes are code gauge galvanized steel without knockout. Standard size is 20 in. wide x 5.75 in. deep.
2 in. 100 Amp MLO 4 in. 225 Amp MLO 8 in. 100 Ampere Frame EHD, EDB, EDS, ED, EDH, FDB, HFD 9 in. 225 Ampere Frame EHD, EDB, ED, EDH, FDB, HFD, FDC
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-95 3-40
Cabinets
Bussing
Tin-plated aluminum is standard, copper is available as an option.
2. Required mains (lugs, breaker or fuse pullout). 3. Select appropriate neutral. 4. Select branch breakers and additional chassis space, as needed. 5. Layout panel as shown in Table 3-44 , using appropriate X units. Total X units determine box height shown in Table 3-43 . When total X units exceed the number shown, use next size box size, e.g., if total X equals 25, use 31X box or EZB2060RC. Layout Example: Panel description Pow-R-Command 100; 3-Phase, 4-Wire; 480Y/277 Vac; interrupting rating, 14,000 AIC symmetrical; 250 ampere main lugs only; bottom; surface mounted and the following branch breakers:
Boxes
Boxes are made from code gauge galvanized steel. Blank ends are supplied as standard.
Trims/deadfronts are code gauge steel, ANSI 61 nish. Boxes are code gauge galvanized steel without knockouts. Standard size is 20 inches wide x 5-3/4 inches (508.0 mm x 146.1 mm) deep. Top and Bottom Gutters: 6-3/8 inch (161.9 mm) minimum. Side Gutters: 4-inch (101.6 mm) (minimum) on 20-inch (508.0 mm) wide box.
Box Height, Inches (mm) Box Catalogue Number Trim Catalogue Number
Trims
Trims are made from code gauge steel and painted ASA 61 gray. Doors 48 inches (1219.2 mm) or less have a single point lock, doors over 48 inches (1219.2 mm) have a three point catch and lock.
20 inches wide x 5-3/4-inch (508.0 mm x 146.1 mm) deep boxes 23X 31X 40X 53X 48 (1219.2) 60 (1524.0) 72 (1828.8) 90 (2286.0) EZB2048RC EZB2060RC EZB2072RC EZB2090RC EZB2048S or F EZB2060S or F EZB2072S or F EZB2090S or F
36 20 ampere, 1-pole. 6 20 ampere, 1-pole spaces. Smart chassis 24 circuit add-on chassis 250 ampere neutral 250 ampere main lugs only Total panelboard height 13X 10X 5X 5X 33X
31
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
3-41
1-96
ckt 1 3 5 7 9 11 13 15 17 Pow-R-Command 100 System Controller and 18 Pole Spaces for Controllable Breakers Neutral Section
ckt 2 4 6 8 10 12 14 16 18
Smart chassis is always located at the bottom of the chassis immediately below all breakers. 5X 100, 250 Ampere 8X 400, 600, 800 Ampere 2X 100 Ampere 5X 250 Ampere 8X 400 Ampere See branch mounted EHD, FD, FDB, HFD, FDC, ED, EDH, EDC Above 7X EHD, FDB, FD, HFD, FDC, ED, EDH, EDC 7X 100 Ampere Class T Fused Main 9X 200 Ampere Class T Fused Main 9X FBP 14X JD, HJD, JDC 15X DK, KD, HKD, KDC 21X LCL
All F frame branch mounted breakers must be mounted above (top) of all controllable breakers on the chassis. ED, EDH and EDC branch mounted breakers may be mounted with load lugs on either left or right. Specify on order. All add-on GHB/GHQRSP and BABRSP/BAB branch spaces must be adjacent to smart chassis poles. GHQRSP and GHB breakers may be mixed on the same connector. GHB breakers are NOT controllable breakers. Panelboards may have GHB/GHQRSP type breakers or BABRSP/BAB type breakers, but the two types may not be mixed in one panel. BABRSP and BAB breakers may be mixed on the same connector. BAB breakers are not controllable breakers. 120/240 V or 120/208 V only. Top mounted main only. LCL main breaker requires 6-1/2-inch (165.1 mm) deep box.
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
1-97 3-42
Boxes
Boxes are made from code gauge galvanized steel. Blank ends are supplied as standard.
2. Required mains (lugs, breaker or fuse pullout). 3. Select appropriate neutral. 4. Select branch breakers and additional chassis space, as needed. 5. Layout panel as shown in Table 1 -91 , using appropriate X units. Total X units determine box height shown in Table 1 -90 . When total X units exceed the number shown, use next size box size, e.g., if total X equals 25, use 31X box or EZB2060RC. Layout Example: Panel description Pow-R-Command 100; 3-Phase, 4-Wire; 480Y/277 Vac; interrupting rating, 14,000 AIC symmetrical; 250 ampere main lugs only; bot tom; surface mounted and the following branch breakers: 36 20 ampere, 1-pole. 6 20 ampere, 1-pole spaces.
Cabinets
Trims
Trims are made from code gauge steel and painted ANSI 61 gray. Doors 48 inches or less have a single point lock, doors over 48 inches (1219.2 mm) have three point catch and lock.
Trims/deadfronts are code gauge steel, ANSI 61 nish. Boxes are code gauge galvanized steel without knockouts. Standard size is 20 inches wide x 5-3/4 inches (508.0 mm x 146.1 mm) deep. Top and Bottom Gutters: 6-3/8 inch (161.9 mm) minimum. Side Gutters: 4-inch (101.6 mm) (minimum) on 20-inch (508.0 mm) wide box size.
Box Height, Inches (mm) Box Catalogue Number Trim Catalogue Number
20 inches wide x 5-3/4 inch (508.0 mm x 146.1 mm) deep boxes 31X 40X 53X 60 (1524.0) EZB2060RC EZT2060S or F 72 (1828.8) EZB2072RC EZT2072S or F 90 (2286.0) EZB2090RC EZT2090S or F
31
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
3-43
1-98
ckt 1 3 5 7 9 11 13 15 17 Pow-R-Command 100 System Controller and 18 Pole Spaces for Controllable Breakers Expansion Chassis Accepts Up to 1 Application Specic Controllers Neutral Section Main Lug Section
ckt 2 4 6 8 10 12 14 16 18
20X Pow-R-Command 100 EC Smart Expansion Chassis includes spaces for: 18 Poles:
Note: Smar t c hassis is always located atthebot tomofthec hassisimmediately belowallcontrollablebreak er s.Allother break er s, excluding mains, are located abo ve all controllable break er s.
5X 100, 250 Ampere 8X 400 Ampere 2X 100 Ampere 5X 250 Ampere 8X 400 Ampere See branch mounted EHD, FD, FDB, HFD, FDC, ED, EDH, EDC Above 7X EHD, FDB, FD, HFD, FDC, ED, EDH, EDC 7X 100 Ampere Class T Fused Main 9X 200 Ampere Class T Fused Main 9X FBP 14X JD, HJD, JDC 15X DK, KD, HKD, KDC
All F frame branch mounted breakers must be mounted above (top) of all controllable breakers on the chassis. ED, EDH and EDC branch mounted breakers may be mounted with load lugs on either left or right. Specify on order. All add-on GHB/GHQRSP and BAB/BABRSP branch spaces must be adjacent to smart chassis poles. GHQRSP and GHB breakers may be mixed on the same connector. GHB breakers are NOT controllable breakers. Panelboards may have GHB/GHQRSP type breakers or BABRSP/BAB type breakers, but the two types may not be mixed in one panel. BABRSP and BAB breakers may be mixed on the same connector. BAB breakers are not controllable breakers. 120/240 V or 120/208 V only. Top mounted main only.
CAT.38.02.S.K CAT.38.03.S.K
For more information visit us at: www.eatoncanada.ca For more information visit: www.eatoncanada.ca
3-44
General overview
The Power-R-Commande4000 (PRC4000) is designed to act as the coordinator of the wireless lighting network. It has a multitude of advanced features that perform the seamless control of every zone in your entire facility, as well as complex energy-management tasks. All configuration and control can be done through a standard Web browser, a familiar environment, to help get you up and running quickly without the headache of learning a new software platform. In addition, the PRC4000 is networkable with the Pow-RCommand lighting control RS-485 network with the ability to expand its capabilities. The PRC4000 also comes equipped with analog and digital inputs/outputs to accommodate an extended array of input devices, switching, and dimming needs. Mainly, the PRC4000 wirelessly communicates to the PRC wireless I/O modules using the IEEET 802.15.4 standard. The PRC wireless I/O modules allow local connectivity of low voltage switches, photo sensors, occupancy sensors, any 010 Vdc dimming ballasts, and other auxiliary devices. The I/O module also adds discrete on/off load control through an onboard relay for loads up to 120/277V, 20A. Running control wires from each device in the facility back to the electrical room is no longer required. The configuration and programming is stored in the internal memory of the PRC wireless I/O module. This allows for distributed intelligence that adds reliability to an already robust lighting control network.
CAT.38.03.S.K
3-45
Figure 1. 3-13 PRC40000 controller I/O Figure Figure 3-13. PRC4000 controller I/O Figure 4. PRC4000 controller I/O
BLK BLUE RED N/C
TB1
Digital output: For direct load control 120/277V 20A AC. Analog output: Outputs 0 to 10 Vdc. Typically used for control of dimmable ballasts. DC power output: 15V 100 mA DC output to power auxiliary devices.
SV1
SV2
Not Used 15 Vdc 100 mA Output Analog Output Ground Universal Input 1 Ground Universal Input 2 Ground Digital Input 1 Ground Digital Input 2 Ground
Wireless Radio
Wireless I/O module I/O board layout Figure 3-14 2. Wireless I/O module I/O board layout
Figure 3-14 Wireless I/O module connected Figure 3. Wireless I/O module connected toto aa standard 4x4 junction box standard 4x4 junction box
CAT.38.03.S.K
3-46
Programming
All programming and configuration is done through a standard Web browser. Once the PRC4000 is set up and given a static IP address, just navigate to that IP address through your Web browser, and you will be prompted for a username and password. The PRC4000 was completely designed from the ground up with the customer in mind. We wanted to make an interface that was very efficient and simple to use. After using it for a short amount of time, you will see just how easy it is to completely customize your lighting control network. Please reference the PRC4000 and wireless I/O module installation guide for more information.
Network philosophy
The PRC4000 and wireless I/O module is a completely wireless network. Each facility will typically have one PRC4000 and up to 99 wireless I/O modules communicating back to it. Each wireless I/O module is digitally addressed from 1 to 99 through onboard rotary address switches. After addressing each wireless I/O module, the PRC4000 will automatically discover the device.
In addition to wireless I/O modules, the PRC4000 can communicate directly to the Pow-R-Command wireless switch. The wireless Easy installation switch adds more local functionality to the wireless system through its onboard I/O. See document TD01412054E for more details. The PRC4000 and wireless I/O module were designed to lower Aside from the wireless communication, the PRC4000 can connect the cost of material and labor involved with installation of a lighting control system. The wireless I/O module can be powered by 120 Vac to a Pow-R-Command RS-485 network with complete access to all of your Pow-R-Command panelboards. or 277 Vac, giving it the ability to be powered by any 120/277 Vac circuit nearby. With that in mind, the wireless I/O module was See Figure 3-17 for a network example. For more information, please designed to easily mount in a drop ceiling. No communication wires reference the PRC4000 and wireless I/O module installation guide. are needed. The I/O module wirelessly communicates back to the PRC4000 through the IEEE 802.15.4 standard. The PRC4000 controller unit can be placed on a desktop or shelf in the facility. 3 For the basic PRC4000 and I/O module system, the only requirements are a 120 Vac outlet and a connection to your facilitys Ethernet network.
CAT.38.03.S.K
3-47
CAT.38.03.S.K
3-48
The Pow-R-Command Wireless Switch is a state-of-the-art microprocessor-based, low voltage wireless communication device, based on the 802.15.4 wireless standard.
Each switch has the ability to communicate to a Pow-RCommand 1000 line of lighting controllers through a Pow-RCommand Wireless Switch interface unit or communicate directly to the PRC4000 Wireless Small Building controller. For each switch interface, you can have up to 99 wireless switches connected to the system. This gives distributed lighting control throughout the entire facility at a much lower cost of installation and maintenance. Each Pow-RCommand Wireless Switch is completely customizable and can be programmed to precisely meet the needs of the customers lighting control strategy. The PowR-Command Wireless Switch configuration is stored directly in the integrated memory of the switch that adds to the robustness of the device. In addition to the wireless network communication capabilities, the Pow-R-Command Wireless Switch has built-in input and output capable of connecting photo sensor, occupancy sensor, and dimmable ballasts to achieve fully integrated zone lighting control capability from one device.
Wireless Switch and Wireless Switch Interface Unit
Features