K S RF M 805 T: Otron Mart Odel Ransmitter

KOTRON (r) SMART RF MODEL 805 TRANSMITTER These units have been tested to EN 50081-2 and EN 50082-2 and are in compliance with the EMC Directive 89 / 336 / EEC and Directive 94 / 9 / EC for Equipment or protective system for use in potentially explosive atmospheres.

Uploaded by

German Toledo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
69 views16 pages

K S RF M 805 T: Otron Mart Odel Ransmitter

KOTRON (r) SMART RF MODEL 805 TRANSMITTER These units have been tested to EN 50081-2 and EN 50082-2 and are in compliance with the EMC Directive 89 / 336 / EEC and Directive 94 / 9 / EC for Equipment or protective system for use in potentially explosive atmospheres.

Uploaded by

German Toledo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

R.F.

Capacitance
Level
Measurement

Installation and Operating Manual


KOTRON

SMART RF
MODEL 805 TRANSMITTER
These units have been tested to EN
50081-2 and EN 50082-2 and are
in compliance with the EMC
Directive 89/336/EEC and Directive
94/9/EC for Equipment or protective
system for use in potentially explosive atmospheres.
2
UNPACKING
Unpack the instrument carefully. Make sure all components
have been removed from the foam protection. Inspect all
components for damage. Report any concealed damage to
the carrier within 24 hours. Check the contents of the car-
ton/crates against the packing slip and report any discrep-
ancies to Magnetrol. Check the nameplate model number
(Model number/approvals as per inserted separate sheet) to
be sure it agrees with the packing slip and purchase order.
Check and record the serial number for future reference
when ordering parts.
MOUNTING
Nameplate:
- partnumber
- amplier
- serial n
- tag n
2 cable entries (one plugged): M20 x 1.5, 3/4" NPT or PG 13.5
Handtighten or use Size: 33 mm (1 1/8") or adjustable wrench
WARNING: Never mount or dismantle a threaded probe by the
upper mounting nut for the amplier (a), ALWAYS use the lower
probe mounting nut (b).
KOTRON R.F probes
d2
min. 1" - 150 lbs
DN 25 PN 16
3/4"
1"
G1(1"BSP)
d1
d1 = d2
For replacing electronics only:
The electronic insert can easily be removed by loosening the 3 mounting screws
and unplugging the module. The probe wire is xed to the PCB by means of a
spade plug.
Disconnect white probe wire always at the probe - never at the electronics (see
above).
(For installation details see bulletin BE50 - 125)
Bent probe
Guarded probe
Flexible probe
Probe with inactive sheath Stillwell probe
inactive sheath
Wrong
(b)
(a)
3
WIRING
CAUTION: power must be switched OFF before wiring the unit.
IS +
IS
T
B
1

www.magnetrol.com
P1
+

P2
LOOP
CURRENT
0 % 100 %
Positive supply to (+) terminal/HART

connection
Negative supply to (-) terminal/HART

connection
min. 11 V DC required
Ground wire to green grounding screw or to external
grounding screw
Standard shielded twisted
pair cable
Current
loop test
points
Galvanic Barrier:
max: 28,6 V DC @ 140 mA
ANALOG I/O
or
DIGITAL I/O
(only for units with HART)
Customer supplied
local current meter
Ex
Non Ex
Ex
Non Ex
Ex
Non Ex
CAUTION: ALWAYS check for proper grounding, Improper grounding will cause malfunction of the unit.
CALIBRATION
NOTE: When connected to an approved barrier, the intrinsically safe electronics of the Kotron 805 allow to remove both
covers with power switched on even if the area is known to be hazardous
IMPORTANT: When the amplier is not connected to a probe, the screen will show "NO LEVEL SIGNAL". Ignore
this message for bench conguration.
Pushbuttons
Enter
Down
Up
2 line 8 characters LCD
Default display cycles every 5 s
through LEVEL/% OUTPUT/LOOP
Returns to default display if after
5 minutes no keystrokes are sensed
4
CALIBRATION - TRANSMITTER WITH LCD SCREENMENU: STEP BY STEP PROCEDURE
Units!
cm
Units
cm
Units!
cm
Ent Pass
0
New Pass
4096
New Pass
0000
Ent Pass!
1
Press : The last character on the rst line of the display changes to "!". This sign conrms
that the values/choices of the second line can be modied via the and push
buttons.
Press :
*
Scroll through the choices or increase/decrease the values on the second line
of the display by and pushbuttons.
*
Accept values/choices as selected by pushbutton.
Press : Scroll through the menu.
20 mA Level
(100%-point)
min. 2 % of
probe length
cm or Inch
4 mA Level
(0%-point)
TERMINOLOGY
Units cm or inches
Select the units of measurement in which the unit will be
calibrated and will show values.
20 mA Level = cm or inches
or 100 % level point, is measured from the end of the
probe. Keep this reference point also for the introduction of
all future values.
Hi Cal = cm or inches
High Calibration point is the highest level from which the
calibration is performed. Hi Cal is measured from the end
of the probe.
Lo Cal = cm or inches
Low Calibration point is the lowest level from which the cal-
ibration is performed. Lo Cal is measured from the end of
the probe.
4 mA Level = cm or inches
or 0 % level point, is measured from the bottom of the
probe. The 4 mA level is by preferrence located on the
probe. The unit will not measure below the end of the
probe.
"0" means that no password is introduced Factory default setting
Press and last character changes into "!" Changing password
Enter a value between 1 up to 255
as your personal password with and
Display shows an encrypted value, enter your password Data is protected by a valid
or call Magnetrol for assistance to recoop your password Password
if necessary
Protect data by new password Data is not protected
Hi Cal
Lo Cal
NOTE: The above example shows the end of the probe as reference point. Also the bottom or top of the tank can be used as refer-
ence point. Whichever point is used, it must always be used for all further values.
Display Action Comment
Display Comment
5
Screen Action Comment
Transmitter Display Transmitter default display. Level, % Output, and Loop
values cycle every 5 seconds.
Transmitter Display Transmitter displays Level measurement in cm or in.
Transmitter Display Transmitter displays % Output measurement derived from the
4-20 mA span.
Transmitter Display Transmitter displays Loop measurement (mA).
Select units for level cm or inches.
measurement readout.
Enter level value of the low Set level at low calibration point
calibration point and adapt with Up and Down the displayed value
Transmitter Display Transmitter displays capacitance at low calibration point in pF
Enter level value of the high Set level at high calibration point
calibration point and adapt with Up and Down the displayed value
Transmitter Display Transmitter displays capacitance at high calibration point in pF
Enter the level value for the 4 mA level cannot be set at a lower level than the end of the probe
4 mA point.
Enter the level value for the 20 mA level cannot be set at a higher level than the top of the
20 mA point. probe
Enter the damping factor. A Damping factor (1-45 seconds) may be added to smooth a
noisy display and/or output due to turbulence.
Enter the default value. Select 3.6 mA, 22 mA or HOLD (last value). 3.6 mA is not
valid if unit includes HART.
Enter HART ID number. Select a HART poll address (0-15). Enter 0 for a single
transmitter installation.
Fine tune the 4 mA point. Attach a mA meter to the output. If the output does not equal
4.0 mA, adjust the value on the display to equal 4.00 mA.
Fine tune the 20 mA point. Attach a mA meter to the output. If the output does not equal
20.0 mA, adjust the value on the display to equal 20.00 mA.
Enter a mA Output value. Set mA Output to any given value to perform loop test.
None, do not adjust. Transmitter displays capacitance at present level
None, do not adjust. Transmitter displays internal timing count with xed capacitance
(factory diagnostic)
None, do not adjust. Transmitter displays internal timing count with probe disconnected
(factory diagnostic)
None, do not adjust. Transmitter displays internal timing count at present level
(factory diagnostic)
Reinitialize all values. Reinitialize - choose YES to reset all conguration values
back to factory defaults.
None, do not adjust. Transmitter displays version number of rmware
Enter new password. Use arrows to select desired value. Values between 1 and
255
CALIBRATION - TRANSMITTER WITH LCD SCREENMENU: STEP BY STEP PROCEDURE
R
u
n

m
o
d
e
D
i
a
g
n
o
s
t
i
c
s
C
o
n

g
u
r
a
t
i
o
n
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
22
*Level*
*%Output*
*Loop*
Level
xx.x cm
%Output
xx.x%
Loop
xx.xx mA
Units
xxx
Lo Cal
xxx.x lu
Lo Cap
Xxxx pF
Hi Cal
xxx.x lu
Hi Cap
Xxxx pF
Set 4mA
xxx.x
Set 20mA
xxx.x
Damping
xx sec
Fault
Choice
Poll Adr
xx
Trim 4
xxxx
Trim 20
xxxx
Loop Tst
xx.x mA
Prb Rdg
Xxxx pF
Osc Tst
Xxx tk
Opn Prb
xxxx tk
23
21
# Ticks
xxxx
Reint
xxx
Vern.nAa
= min. required calibration
24
New Pass
xxx
I/O Start up the device
1 Enter DEVICE SET UP
Press one of the following alphanumeric keys (if no key is sensed after 5 s, the
unit will automatically jump to RUN mode and alternatively show Level/% Output
and Loop signal
1 for entering CALIBRATION (see page 5 for additional information)
2 for entering BASIC SETUP general HART
3 for ADVANCED SET UP CONFIGURATION (see page 5 for additional infor-
mation)
4 for entering DIAGNOSTICS (see page 5 for additional information)
5 for entering REVIEW to review all settings.
CALIBRATION USING HART

IMPORTANT: Check whether your HART

communicator is equiped with the 805 Device Descriptors (DDs). Older pur-
chased devices may require an update consult your local HART Service Centre or Magnetrol for further assistance.
IMPORTANT: The digital HART

communication is superimposed on the


4-20 mA loop and requires a min. load resistance of 250 and a max load
resistance of 450 .
+
+
-
-
Junction
Control
Room
Display
Power
Supply
Current
Meter
250 < R
L
< 450
CONNECTIONS
Connection of your Hart communicator:
at power terminals (+) and (-) in wiring compartment
at rst junction box between unit and control room.
HART MENU
1 Device Setup
2 Level
3 % Output
4 Loop
1 Units
2 Empty Calibration
3 Full Calibration
4 4 mA Set Point
5 20 mA Set Point
6 Damping
7 Fault State
8 Date/Time/Initials
1 Model
2 Manufacturer
3 Dev Id, S/N
4 Tag
5 Descriptor
6 Date
7 Message
8 Units
9 Cap at empty Cal
10 Cap at full Cal
11 4 mA Set Point
12 20 mA Set Point
13 Damping
14 Fault State
15 Date/Time/Initials
16 Final Asmbly Num
17 Universal Rev
18 Fld Dev Rev
19 Software Rev
20 Poll Address
21 Num Req Preams
22 Firmware Version
1 Tag
2 Descriptor
3 Date
4 Message
5 Final Asmbly Num
6 Poll Address
7 New Password
1 Adjust Trim 4 mA
2 Adjust Trim 20 mA
3 4 mA Trim Value
4 20 mA Trim Value
5 Enter Password
6 Set Magnetrol S/N
7 Set Dev ID Number
1 Loop Test
2 Error Codes
3 Probe Reading
4 Cap at empty Cal
5 Cap at full Cal
1 3.6 mA
2 4 mA
3 20 mA
4 22 mA
5 Other
1 Calibration
2 Basic Setup
3 Advanced Setup/
Conguration
4 Diagnostics
5 Review
6
7
MAINTENANCE
TROUBLESHOOTING SYSTEM PROBLEMS LCD version
Symptom Problem Solution
LEVEL, % OUTPUT and LOOP values Basic conguration data is Check values and recalibrate if
are all inaccurate. questionable. necessary (either or both points).
LEVEL readings are repeatable but Conguration data does not Recalibrate if necessary.
consistently high or low from actual accurately match tank height.
by a xed amount.
LEVEL, % OUTPUT and LOOP Turbulence. Increase the Damping factor until the
values uctuate. readings stabilize.
LOOP value jittery, usually in tenths Factory settings corrupted. Check # of Ticks. If the number is
or hundredths digit. also jittery, consult the Factory.
HART device only: handheld will only Most current Device Descriptors Contact local HART service center for
read Universal Commands. (DDs) are not installed in handheld. the latest DDs.
HART device only; reads Product Early HART software does not Contact manufacturer of your HART
information (e.g., Mfgs. ID, Device #, account for Mfgs. ID #s greater master software for upgrade. This is a
Serial #, etc.) but will not read any than 63. Magnetrols ID is 86. shortcoming of early HART master
process variables. software.
OSC FAIL malfunctioning analog board and/or Check connection between electronics
(HART error code = 0x40) 32 pin connector (electronic module) and probe or replace electronic module.
between electronics and probe.
CORRUPT PARAMTRS Conguration parameters may Check all conguration parameters
(HART error code = 0x10) have been lost. and recalibrate if required.
805 FAULT Probe disconnected. Check white probe wire
(Open) (see page 2) and electronic module.
805 FAULT Probe shorted. Check white probe wire
(Shorted) (see page 2) and probe insulation.
LEVEL Unit is not calibrated. Enter both Low and High calibration
(Uncal) points.
ABV RNG Measured capacitance is higher Consult factory.
(Above range) than 12,000 pF.
SFWR ERROR Software error. Consult factory.
(Software error)
ERROR MESSAGES LCD version
Symptom Problem Solution
REPLACEMENT PARTS
1
2
3
4
3
5
Item Description Part number
1 Electronic module
English display and HART

031-2809-001
French display and HART

031-2809-031
German display and HART

031-2809-041
Spanish display and HART

031-2809-021
HART

only 031-2809-002
English display only 031-2809-003
French display only 031-2809-033
German display only 031-2809-043
Spanish display only 031-2809-023
2 Terminal board
General Purpose (GP) 30-9106-003
Intrinsically Safe (IS) 30-9106-003
3 O-Ring (neoprene) 12-2201-237
4 Housing cover blind - Aluminium 04-9193-003
Housing cover blind - 316 SST Consult factory
5 Housing cover with glass 36-4410-001
Housing cover with glass - 316 SST Consult factory
8
APPROVALS
Agency Description
ATEX II 1G EEx ia IIC T4 (ambient -40 C to +40 C)
II 1G EEx ia IIC T6 (ambient -40 C to +80 C)
FM (*) Intrinsically safe
Class I, Div.1; Grps. A, B, C, D
Class II, Div.1; Grps. E, F, G
Class III,NEMA 4X
Non-Incendive
Class I, Div.2; Grps. A,B,C,D
Class II, Div.2; Grps. F,G
Class III,NEMA 4X
(*) Consult factory for proper part n and entity parameters.
Agency Description
CSA (*) Intrinsically safe
Class I, Div.1; Grps. A, B, C, D
Class II, Div.1; Grp. G
Class III,Type 4X
Non-Incendive
Class I, Div.2; Grps A, B, C, D
Class II, Div.2; Grps E, F, G
Class III, Type 4X
(*) Consult factory for proper part n
(*) and entity parameters.
9
MAINTENANCE
TROUBLESHOOTING FLOWCHART (LCD version)
Unit Equipped
with Display?
Check Voltage at
Terminal Board
No Voltage?
Check Power
Supply and Wiring
Negative
Voltage?
Reverse Wiring
Call Factory
Check Loop
Current at terminal
Board
Loop Current
Above 23 mA?
Remove Electronic
Module
Loop Current
Above 1 mA?
Replace Terminal
Board
Replace Electronic
Module
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Display has
Text?
No
Reseat Boards.
Check Power
Supply and Wiring
Loop
Resistance
Wrong?
Correct Loop
Resistance
Start
Good
Display
No
Active
HART
Yes
Failure to Operate
with Correct Loop
Inputs
No
Faint Display?
Yes
Yes
No
Some problems could be
temporarily solved by power
cycling the unit. Please call
factory if this problem persists.
Display
Working?
No
Yes
No
Retest Yes
HART
Communications
OK?
Voltage Above
36 Volts?
Voltage
< 11V IS or
14.5V XP?
2 1
3
See page 12
See page 11
MAINTENANCE
TROUBLESHOOTING FLOWCHART (LCD version)
Check Loop
Current at Terminal
Board
Loop Current
Above 23 mA?
Remove Electronic
Module
Loop Current
Above 1 mA?
Replace Terminal
Board
Replace Electronic
Module
Yes Yes
No
No
Failure to Operate
with Correct Loop
Inputs
Display
Working?
Yes
No
Retest Unit
Good
Display
Key Board
Responds?
Replace Electronic
Module
No
Check Loop
Current at Wiring
Board
Loop Current
22 - 4.0 mA?
Adjust 4 and 20 mA
Unit has
HART?
HART
Working?
Yes
Yes No
Yes
No
Address
Correct?
Correct Address
Replace Electronic
Module
No
Yes
Unit with Display
Communicates
No Yes
Reseat Boards
Display
Working?
Retest
No
Yes
1
2
4
See page 11
10
11
MAINTENANCE
TROUBLESHOOTING FLOWCHART (LCD version)
Unit with Display
Communicates
Error
Displayed?
"Open Probe?"
"Shorted Probe?"
"OSC Fail?" Yes
Check Probe and
Connectors
Check Analog
Parameters
Check Calibration
Parameters
Yes Yes
Yes
Corrupt Display
Text?
Replace Electronic
Module
No
Yes
Replace Electronic
Module
Same Error
Message?
Retest No
Yes
Active
HART
Analog Loop
Correct?
Trim 4-20mA
Check Offset and
4-20 mA Set Points
No
Yes
No
Call Factory
Display Reading
Correctly?
4
Yes
3
No
No
No
Call Factory
No
"Uncal?"
"Corrupt
Parameters?"
"Above Range?"
No
"Software Error?"
No
Yes
Yes
No
No
Yes
TRANSMITTER SPECIFICATIONS
12
Description Specication
Power (at terminals) General Purpose: 11 to 36 V DC
ATEX Intrinsically Safe: 11 to 28.6 V DC
Signal Output 4-20 mA or 4-20 mA with HART

3.8 to 20.5 mA useable (meets NAMUR NE 43)


Span minimum 5 pF - maximum 10.000 pF
Zero and Range 0 mm to 45 m (0' to 150')
Resolution Analog: 0.01 mA
Digital display: 0,1 cm (0.1")
Loop Resistance ATEX Intrinsically Safe/General Purpose: 650 @ 24 V DC
Damping Adjustable 1-45 s
Diagnostic Alarm Adjustable 3.6 mA, 22 mA, HOLD
(3.6 mA is not valid if unit includes HART

)
Digital Communication (HART

) compatible with software version 5.x


User Interface 3-button keypad and/or HART communicator
Display 2-line x 8-character LCD
Approvals ATEX II 1 G EEx ia IIC T4/T6 or FM/CSA intrinsically safe / non incendive
Electrical Data Ui = 28,6 V, li = 140 mA, Pi = 1 W
Equivalent Data Ci = 2,2 nF; Li = 0,037 mH
Menu Language English/Spanish/French or German
Housing Material Aluminium A356T6 (< 0.25% copper) or 316 SST (1.4401)/IP 65
Net and Gross Weight 2.70 kg net; 3.20 kg gross
Overall Dimensions H 214 mm (8.43") x W 111 mm (4.38") x D 188 mm (7.40")
FUNCTIONAL/PHYSICAL
Description Specication
Maximum Process Temperature 540 C @ 35 bar (1000 F @ 500 PSIG) - depending probe selection
Maximum Process Pressure 345 bar @ 40 C (5000 PSIG @ 100 F) - depending probe selection
Ambient temperature electronics -40 C to +80 C (-40 F to +175 F) blind transmitter
-20 C to +70 C (-5 F to +160 F) with LCD display and keypad
Storage temperature -40 C to +80 C (-40 F to +175 F)
Humidity 0-99 %, non-condensing
Electromagnetic Compatibility Meets CE requirements (EN-50081-2, EN 50082-2) / NAMUR NE 21 (EMV)
PROCESS CONDITIONS
Description Specication
Reference conditions 20 C (70 F)
Accuracy +/- 0.5% of span or 2.5 mm whichever is greater
Resolution 0.1 pF
Repeatability +/- 0.1% of span
Linearity +/- 0.25% of span
Response time less than 1 s (adjustable via damping)
Ambient temperature effect approximately +0.03% per C
Warm up time less than 5 s
PERFORMANCE
1200
1000
800
600
400
200
0
20 mA
23 mA
24 V DC
620
650
11

0 10 20 30 40 V DC
OUTPUT TABLE
13
DIMENSIONS in mm (inches)
CONNECTIONS
83
(3.28)
105
(4.12)
200
(7.88)
98
(3.85)
Mounting
Flange
2 cable
entries
Probe
Insertion
Length
45
214
(8.43)
126
(4.94)
111
(4.38)
45 View
Kotron 805 Housing
front View
Kotron 805 Housing
side view
Optional
Mounting
Flange
3/4" NPT
1" NPT
1G (1" BSP)
Optional
Mounting
Flange
Optional
Anchor
Assembly
Optional
Weight
13 (0.50) - bare probe
16 (0.625) - insulated probe
5 (0.1875)
6 (0.2500)
75
(2.95)
34
(1.32)
127
(5.00)
124
(4.87)
Insertion
Length
Rigid probe Flexible probe
220 (8.66) 220 (8.66)
3/4" NPT
Sanitary 3A Threaded
NPT
Threaded
1" BSP
Welded ange ANSI / DIN
Insertion
length
Insertion
length
Insertion
length
Insertion
length
14
IDENTIFICATION
0 None, for use with blind transmitter (requires HART

communication)
1 English for use with transmitter with LCD display and keypad
2 Spanish for use with transmitter with LCD display and keypad
3 French for use with transmitter with LCD display and keypad
4 German for use with transmitter with LCD display and keypad
0 Blind transmitter (requires HART

communication)
A Transmitter with 2 line x 8 character LCD display and keypad
0 4 - 20 mA analog output
1 4 - 20 mA analog output with HART

communication
8 0 5 Smart R.F. KOTRON

805 amplier
1 General Purpose (FM/CSA intrinsically safe)
A Intrinsically safe, ATEX II 1G EEx ia II C T6
A complete measuring system consists of a:
1. Smart R.F. KOTRON

805 amplier.
2. KOTRON

Probe; a full range of rigid and exible probes for conductive and non-conductive media is available
(see bulletin BE 50-125).
Rigid probes: from 150 mm (6") to 6000 mm (20') insertion length
Flexible probes: from 1 m (3,28') to 45 m (150') insertion length
3. OPTION: HART communicator
Magnetrol P/N : 089 - 5213 - 012 (Euro Plug) 089 -5213 - 013 (UK Plug)
BASIC MODEL NUMBER
1. Code for SMART R.F. KOTRON

805 amplier
TRANSMITTER TYPE
0 3/4" NPT (2 entries - one plugged)
1 M20 x 1.5 (2 entries - one plugged)
2 PG 13.5 (2 entries - one plugged)
CABLE ENTRY
SIGNAL OUTPUT
APPROVALS
MENU LANGUAGE
8 5 0 5
1 Cast aluminium, dual compartiment housing IP 65
2 Stainless steel, dual compartiment housing IP 65
HOUSING
complete code for SMART R.F. KOTRON

805 amplier
15
IMPORTANT
SERVICE POLICY
Owners of Magnetrol products may request the return of a control; or, any part of a control for complete rebuilding or
replacement. They will be rebuilt or replaced promptly. Magnetrol International will repair or replace the control, at no cost to
the purchaser, (or owner) other than transportation cost if:
a. Returned within the warranty period; and,
b. The factory inspection nds the cause of the malfunction to be defective material or workmanship.
If the trouble is the result of conditions beyond our control; or, is NOT covered by the warranty, there will be charges for labour
and the parts required to rebuild or replace the equipment.
In some cases, it may be expedient to ship replacement parts; or, in extreme cases a complete new control, to replace the
original equipment before it is returned. If this is desired, notify the factory of both the model and serial numbers of the
control to be replaced. In such cases, credit for the materials returned, will be determined on the basis of the applicability of
our warranty.
No claims for misapplication, labour, direct or consequential damage will be allowed.
RETURNED MATERIAL PROCEDURE
So that we may efciently process any materials that are returned, it is essential that a Return Material Authorisation (RMA)
form will be obtained from the factory. It is mandatory that this form will be attached to each material returned. This form is
available through Magnetrols local representative or by contacting the factory. Please supply the following information:
1. Purchaser Name
2. Description of Material
3. Serial Number and Ref Number
4. Desired Action
5. Reason for Return
6. Process details
All shipments returned to the factory must be by prepaid transportation. Magnetrol will not accept collect shipments.
All replacements will be shipped FOB factory.
BULLETIN N: BE 50-660.1
EFFECTIVE: APRIL 2002
SUPERSEDES: March 2000

UNDER RESERVE OF MODIFICATIONS


BENELUX Heikensstraat 6, 9240 Zele, Belgi
Tel. +32 (0)52.45.11.11 Fax. +32 (0)52.45.09.93 E-Mail: info@magnetrol.be
DEUTSCHLAND Schlostrae 76, D-51429 Bergisch Gladbach-Bensberg
Tel. 02204 / 9536-0 Fax. 02204 / 9536-53 E-Mail: vertrieb@magnetrol.de
FRANCE Le Vinci 6 - Parc dactivits de Mitry Compans, 1, rue Becquerel, 77290 Mitry Mory
Tl. 01.60.93.99.50 Fax. 01.60.93.99.51 E-Mail: magnetrolfrance@magnetrol.fr
ITALIA Via Arese 12, I-20159 Milano
Tel. (02) 607.22.98 (R.A.) Fax. (02) 668.66.52 E-Mail: mit.gen@magnetrol.it
UNITED Unit 1 Regent Business Centre, Jubilee Road Burgess Hill West Sussex RH 15 9TL
KINGDOM Tel. (01444) 871313 Fax (01444) 871317 E-Mail: sales@magnetrol.co.uk
INDIA B4/115 Safdurjung Enclave, New Delhi 110 029
Tel. 91 (11) 6186211 Fax 91 (11) 6186418 E-Mail: magnetrolindia@vsnl.com